LUMINAIRE POST METAL RAILINGS FIBER GLASS / FIBER GLASS COMPOSITE CONDUIT SLEEVE GRADE C A C ITS CONDUITS TO JB (TYP.) ITS CONDUITS TO JB (TYP.) 4’ MIN. RADIUS REQUIR. (TYP.) 4’ MIN. RADIUS REQUIR. (TYP.) A WINGWALL (TYP.) CONDUIT SUPPORT 3’ ON CENTER (TYP.) LUMINAIRE CONCRETE BASE FIBER GLASS / FIBER GLASS COMPOSITE CONDUIT SLEEVE (ALTERNATE MOUNTING) TYPICAL ELEVATION - CONDUIT INSTALLATION ON EXISTING BRIDGE / OVERPASS REFERENCE EXPANSION FITTING (TYP.) GALVANIZED C-CHANNEL STRUT, 12 GA. (INSTALL SUPPORT AND CLAMP AT 3’ O.C.) NOTES: CONCRETE SET BOLTS " X 3" (TYP.) GALVANIZED CONDUIT CLAMP WITH CUSHION, NUT & BOLT (VIBRATION DAMPING) (TYP.) 1. PROVIDE CONDUIT EXPANSION FITTINGS AT EXISTING STRUCTURE EXPANSION JOINTS. 2. ALTERNATE MOUNTING ON UNDERSIDE OF PARAPET MAY BE PERMITTED WHEN IT IS NECESSARY TO CORE DRILL THROUGH WING WALL IN LIEU OF ABUTMENT WALL. SEAL ALL WING WALL PENETRATIONS WITH EPOXY AROUND CONDUIT. 3. SURVEY EACH STRUCTURE AND SUBMIT SHOP DRAWINGS OF CONDUIT ATTACHMENT DETAILS ALONG WITH MANUFACTURERS RECOMMENDED EXPANSION FITTINGS FOR APPROVAL. 4. IF THERE IS AN EXISTING BRIDGE APPROACH SLAB IN THE SHOULDER AT THE LOCATION OF THE PROPOSED CONDUIT, INSTALL THE CONDUIT BENEATH THE APPROACH SLAB AFTER CORING THROUGH THE BACK WALL. ENSURE THE EXISTING APPROACH SLAB IS NOT DISTURBED. 5. ENSURE THE CONCRETE SET BOLT MATERIAL CONFORMS TO ASTM B-633 AND IS MADE OF ZINC PLATED STEEL. ENSURE THE SET BOLT CHARACTERISTICS CONFORMS TO GSA SPECIFICATION FF S-325, GROUP VII, TYPE 2. 6. WHEN ALTERNATE MOUNTING IS PROPOSED TO BE USED, ENSURE THAT EXISTING UNDER CLEARANCE IS MAINTAINED. CONCRETE WALL ITS CONDUITS(TYP.) PARAPET RAIL CONDUIT SLEEVE TRACER WIRE CONDUIT SLEEVE TRACER WIRE SECTION C-C pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE GALVANIZED CONDUIT CLAMP WITH CUSHION, NUT & BOLT (VIBRATION DAMPING) (TYP.) ITS CONDUITS (TYP.) B B GALVANIZED C-CHANNEL STRUT, 12 GA.(INSTALL SUPPORT AND CLAMP AT 3’ O.C.) (TYP.) CONDUIT SLEEVE GALVANIZED C-CHANNEL STRUT, 12 GA. (INSTALL SUPPORT AND CLAMP AT 3’ O.C.) CONCRETE PARAPET scale= 30.000000:1.00000 CONCRETE SET BOLTS " X 3" (TYP.) NOT TO SCALE ITS-704-01 CONCRETE SET BOLTS " X 3" (TYP.) NEW JERSEY DEPARTMENT OF TRANSPORTATION ALTERNATE MOUNTING BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:46 ITS CONDUITS(TYP.) GALVANIZED CONDUIT CLAMP WITH CUSHION, NUT & BOLT (VIBRATION DAMPING) (TYP) TRACER WIRE CONDUIT SLEEVE ITS DETAILS ITS CONDUITS (TYP.) GALVANIZED CONDUIT CLAMP WITH CUSHION, NUT & BOLT (VIBRATION DAMPING) (TYP.) SECTION B-B TYPICAL CONDUIT HANGER ATTACHMENTS SECTION A-A SHEET 1 OF 2 * * file= { EXISTING FASCIA GIRDER (TYP.) { BRGS. @ ABUT. CONDUIT HANGER ATTACHMENT @ 8’ C/C (MAX.) (TYP.) { BRGS. CONDUIT HANGER ATTACHMENT @ 8’ C/C (MAX.) (TYP.) { PIER SLEEVE { EXISTING FASCIA BEAM (TYP.) 1’-6" (MIN.) 1’-6" MIN. SLEEVE { EXISTING INTERIOR BEAM (TYP.) EXISTING DIAPHRAGM (TYP.) { EXISTING CONCRETE DIAPHRAGM (TYP.) { EXISTING INTERIOR GIRDER (TYP.) TYPICAL FRAMING PLAN STEEL STRUCTURE TYPICAL FRAMING PLAN PRESTRESSED CONCRETE STRUCTURE CONDUIT HANGER ATTACHMENT ON EXISTING STRUCTURE CONDUIT HANGER ATTACHMENT ON EXISTING STRUCTURE NOTES: 1. SURVEY EACH STRUCTURE AND SUBMIT SHOP DRAWINGS FOR CONDUIT ATTACHMENT DETAILS AND EXPANSION JOINT DETAILS AND LOCATIONS ALONG EACH STRUCTURE TO THE ENGINEER FOR APPROVAL PRIOR TO THE FABRICATION OF THE CONDUIT SUPPORTS. 2. ENSURE ALL STEEL SHAPES CONFORM TO ASTM A36, BOLTS ARE HIGH STRENGTH, HEX HEAD, CONFORMING TO ASTM A325 AND SUPPLIED WITH ONE NUT AND WASHER PER BOLT. HOT-DIP GALVANIZE STEEL PLATES IN ACCORDANCE WITH ASTM A123 AND ALL THREADED HANGER RODS, NUTS, WASHERS AND SPACER TUBES IN ACCORDANCE WITH ASTM A153. 3. ENSURE HANGER ATTACHMENTS, ARE CONCEALED BY THE FASCIA GIRDER AND THE PROPOSED CONDUIT AND SUPPORTS ARE POSITIONED SUCH THAT THE MINIMUM VERTICAL UNDER CLEARANCE IS NOT LESS THAN THE EXISTING CONDITION. 4. ENSURE STEEL PLATES AND HANGERS ARE CAPABLE OF SUPPORTING 1000 LBS. LOAD AND THE MAXIMUM HANGER SPACING IS 8FT. UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. 5. WELDING IS NOT PERMITTED. 6. PRIOR TO BOLTING PLATES OR ANGLES TO THE EXISTING GIRDER WEB, ENSURE THE CONNECTING AREA OF THE WEB IS THOROUGHLY CLEANED AND SPOT PAINTED AS PER STRUCTURAL REQUIREMENTS. 7. ENSURE CONDUIT LENGTHS ARE SELECTED SO THAT COUPLINGS DO NOT COINCIDE WITH HANGER LOCATIONS. 8. PROVIDE CONDUIT EXPANSION JOINTS NEAR EACH ABUTMENT AS SHOWN AND AT ALL PIER AND HINGE EXPANSION JOINTS. 9. PROVIDE A MINIMUM OF TWO EXPANSION JOINTS AT ALL BRIDGES. EXPANSION JOINT SPACING NOT TO EXCEED MANUFACTURER’S RECOMMENDATIONS. 10. ENSURE THE FINISH COAT PAINT COLOR MATCHES WITH THE PAINT COLOR ON THE EXISTING STRUCTURE. 11. IF THERE IS AN EXISTING BRIDGE APPROACH SLAB AND/OR TRANSITION SLAB IN THE SHOULDER AT THE LOCATION OF THE PROPOSED CONDUIT, INSTALL THE CONDUIT BENEATH THE APPROACH SLAB AND/OR TRANSITION SLAB AFTER CORING THROUGH THE ABUTMENT BACKWALL. ENSURE THE EXISTING APPROACH SLAB AND/OR TRANSITION SLAB IS NOT DISTURBED. 12. SUBMIT DETAIL OF SEAL BETWEEN PIPE SLEEVE AND CONDUIT TO THE ENGINEER FOR APPROVAL. 10’ MIN. ACTUAL LENGTH TO BE DETERMINED IN THE FIELD BY THE CONTRACTOR AS APPROVED BY THE ENGINEER TOP OF ROADWAY VARIES pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE APPROACH SLAB EXISTING CONCRETE BACKWALL VARIES GALV. PIPE SLEEVE EXISTING STEEL GIRDER EDGE OF CORE HOLE-SEAL GAP WITH NON-SHRINK GROUT FIBER GLASS SLEEVE A ITS CONDUITS scale= 30.000000:1.00000 NON-GASKETED EXPANSION JOINT TRACER WIRE 1’-0" MIN. EDGE OF CORE HOLE-SEAL GAP WITH NON-SHRINK GROUT 6"MIN. 5’-0" SEAL GAP BETWEEN FIBER GLASS SLEEVE AND ITS CONDUITS BEFORE INSTALLING EPOXY SEALANT NOT TO SCALE GALV. PIPE SLEEVE (TYP.) ITS-704-02 NEW JERSEY DEPARTMENT OF TRANSPORTATION A FIBER GLASS SLEEVE & ITS CONDUITS, UNDER EXISTING APPROACH SLAB AND TRANSITION SLAB BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 FIBER GLASS SLEEVE (TYP.) ITS DETAILS USE EPOXY SEALANT TO SEAL GAP BETWEEN ITS CONDUITS (TYP.) GALV. PIPE SLEEVE & FIBER GLASS SLEEVE SECTION THROUGH EXISTING ABUTMENT BACKWALL TYPICAL CONDUIT HANGER ATTACHMENTS SECTION A-A SHEET 2 OF 2 * * file= PAVEMENT EXISTING FROM TOP OF 12 IN. REQUIRED PAVEMENT FROM TOP OF EXISTING 36 IN. MIN. EXISTING PAVEMENT A ITS CONDUITS (TYP.) 4’ MIN. RADIUS 4’ MIN. RADIUS REQ. (TYP.) A TRACER WIRE REQ. (TYP.) 1 4 IN. MIN. (TYP.) 4’ MIN. RADIUS RMC SLEEVE 2 (TYP.) REQ. (TYP.) 4’ MIN. RADIUS EXISTING CULVERT ITS CONDUITS (TYP.) REQ. (TYP.) 12 IN. 60 IN. 60 IN. (TYP.) (TYP.) (TYP.) TOP OF EXIST. CRUSHED STONE LAYER, 2" THK. CULVERT BEDDING MATERIAL 6 IN. (TYP.) scale= 30.000000:1.00000 pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE SECTION A-A NOT TO SCALE NOTES: ITS-704-03 1. CONTRACTOR TO SURVEY THE STRUCTURE AND SUBMIT SHOP DRAWINGS FOR INSTALLATION DETAILS TO THE NEW JERSEY DEPARTMENT OF TRANSPORTATION ENGINEER FOR APPROVAL PRIOR TO SLEEVE BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 CONSTRUCTION. 2. SEAL ENDS OF RMC SLEEVE WITH OAKUM AND PACK WITH DUCT SEALANT. 3. INSTALL RMC SLEEVE ACCORDING TO MIN. TRENCH DEPTH FOR TYPICAL AREA. HOWEVER CONDUIT MAY NEED TO BE SET AT DEPTHS LESS THAN THOSE INDICATED IN ORDER TO CROSS THE STRUCTURE. 4. ITS DETAILS TYPICAL CONDUIT OVER CULVERT BEDDING MATERIAL IS REQUIRED AT LOCATIONS WHERE TYPICAL PLACEMENT DEPTH IS NOT POSSIBLE AND REQUIRES RMC SLEEVE TO BE PLACED AT SHALLOWER DEPTH ATOP EXISTING STRUCTURE. * * file= CURBLINE OR EDGE OF SHOULDER 80’-0" RADIUS (TYP.) 3’-0" RADIUS (MIN.) 5’-0" (TYP.) 4’-0" (TYP.) F ITS 50’ TRANSITION (TYP) GRADUAL TRANSITION TO EDGE OF PAVEMENT OR CURB LINE WITH NO CONDUIT BENDS 5’-0" TANGENT SECTION (TYP.) ITS GRADUAL TRANSITION FROM EDGE OF PAVEMENT OR CURB LINE WITH NO CONDUIT BENDS ITS CONDUITS SHOULDER ITS ITS 50’ TRANSITION (TYP) BERM JUNCTION BOX ITS TYPE A TYPICAL ITS CONDUIT HORIZONTAL TRANSITION GRADE JUNCTION BOX ITS TYPE A 1’-0" WARNING TAPE WARNING TAPE 3’-0" GRADUAL TRANSITION TO JB ENTRANCE WITH NO CONDUIT BENDS GRADUAL TRANSITION TO JB ENTRANCE WITH NO CONDUIT BENDS 4" MIN. 4" MIN. BOTTOM OF ITS CONDUITS BOTTOM OF ITS CONDUITS 10" 1’-2" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE SEE NOTES 1 & 2 TYPICAL ITS CONDUIT VERTICAL TRANSITION scale= 30.000000:1.00000 TYPICAL UNDERGROUND ITS CONDUIT TRANSITION AND LAYOUT NOT TO SCALE ITS-704-04 NEW JERSEY DEPARTMENT OF TRANSPORTATION BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 NOTES: 1. THE GRADUAL TRANSITION OF CONDUITS ENTERING THE JUNCTION BOX IS TO BE SUCH THAT THE CONDUIT ENDS REST ON THE STONES INSIDE THE JUNCTION BOX. ITS DETAILS 2. THE TRANSITION MUST PROVIDE FOR SUFFICIENT DRAINAGE TO ENSURE THAT WATER DOES NOT GET TRAPPED IN THE CONDUITS. 3. BACKFILL THE TRENCH WITHIN THE SAME DAY. 4. TYPICAL UNDERGROUND ITS CONDUIT TRANSITION AND LAYOUT TRANSITION LAYOUT FOR ITS CONDUITS LEADING TO JUNCTION BOXES ITS TYPE C AND D IS TO BE SIMILAR. * * file= BITUMINOUS CONCRETE SURFACE COARSE MIX I-4 (SEE NOTE 6) VARIABLE THICKNESS EXISTING PAVEMENT SURFACE VARIABLE VARIABLE THICKNESS 8" BASE OF NEW PAVEMENT INSTALL WARNING TAPE 18" BELOW FINISH GRADE INSTALL WARNING TAPE 18" BELOW FINISH GRADE 36" MIN. VARIABLE EXISTING PAVEMENT SURFACE NOTES: 36" MIN. 1. BACKFILL MATERIAL BEFORE BACKFILLING TRENCH, REMOVE ALL CUT DEBRIS FROM SITE. BACKFILL MATERIAL 2. PREPARE THE TRENCH BOTTOM FOR ITS CONDUITS TO ELIMINATE LUMPS, RIDGES, JAGGED EDGES AND HOLLOWS, UTILIZING CLASS C BEDDING MATERIALS. ITS CONDUITS (TYP.) ITS CONDUITS (TYP.) 3. CENTER THE ITS CONDUITS IN THE TRENCH AND HOLD FIRMLY IN PLACE WHILE THE TRENCH IS BACKFILLED. 1" MIN. 1" MIN. 1" MIN. TRACER WIRE (TYP.) 1" MIN. TRACER WIRE (TYP.) IN REHABILITATED/RECONSTRUCTED CONCRETE SHOULDER OR BITUMINOUS SHOULDER, TRAVELED WAY OR RAMP AREA IN BITUMINOUS SHOULDER, TRAVELED WAY OR RAMP AREA 4. ENSURE THE BACKFILL MATERIAL IS CLASS C BEDDING 2’ ABOVE THE TOP OF CONDUIT OR TO THE BOTTOM OF THE PAVEMENT BOX. 5. COMPACT THE BACKFILL MATERIAL IN EQUAL LIFTS TO A MAXIMUM OF 6" EACH WITH A MODIFIED VIBRATORY PLATE COMPACTOR. (MINIMUM THREE PASSES PER LIFT) 6. MOUND UP THE BITUMINOUS CONCRETE SURFACE COARSE MIX I-4 ABOVE THE EXISTING PAVEMENT SURFACE. AFTER THOROUGH COMPACTION ENSURE FINISH GRADE IS " ABOVE THE ADJACENT PAVEMENT SURFACE. COMPACT IN ACCORDANCE WITH SECTION 1003 (10 TON VIBRATORY ROLLER). 7. FOR WARNING TAPE DETAILS SEE FIBER OPTIC WARNING TAPE, MARKER & TAG DETAIL. 8. AFTER MATERIAL IS BACKFILLED, SEED AND MULCH IN ACCORDANCE WITH DIVISION 800. 36" MIN. SUITABLE GRANULAR MATERIAL FROM PROJECT OR COARSE AGGREGATE TO MEET EXISTING GRADE AS DIRECTED BY THE ENGINEER SEE NOTE 8 9. WHEN THERE IS A CONCRETE SHOULDER, SAW CUT AND REMOVE THE CONCRETE MATERIAL BACK TO THE CURB, UTILIZING A TRENCHING MACHINE TO MAKE THE TRENCH. ENSURE REPLACEMENT MATERIAL COMPLIES WITH NOTE 11. 10. WHEN THERE IS A CONCRETE SHOULDER WITH BITUMINOUS OVERLAY, REPLACE WITH 8" MINIMUM BITUMINOUS MATERIAL OR MATCH EXISTING SECTION. (SEE NOTE 6) 11. ENSURE QUICK SETTING CONCRETE IS TYPE 1A AND COMPLIES WITH SECTION 903.07. FOR CONCRETE REPLACEMENT ENSURE THE THICKNESS OF THE QUICK SETTING CONCRETE IS THE SAME AS THE EXISTING. REPLACE EXPANSION JOINTS AND DOWELS IN KIND AND INSTALL LONGITUDINAL JOINT TIES IN ACCORDANCE WITH THE STANDARD CONSTRUCTION DETAILS. CONTRACTOR IS TO SUPPLY THE ENGINEER WITH DETAILED DRAWINGS FOR APPROVAL PRIOR TO CONSTRUCTION. GUIDERAIL 12. INSTALL ONE #14 AWG CONDUCTOR TYPE THHW/THWN IN THE MIDDLE CONDUIT PER TRENCH. 13. UNLESS OTHERWISE SPECIFIED, EACH ITS CONDUIT IS 2" IN DIAMETER (I.D.) MEETING ALL CONDUIT REQUIREMENTS FOR FNMC (HDPE). INSTALL WARNING TAPE 18’ BELOW FINISH GRADE 36" MIN. CONDUIT TRENCH BACKFILL MATERIAL 14. PRIOR TO TERMINATION, ENSURE THE ITS CONDUITS NORMALIZES A MINIMUM OF 24 HOURS. ENSURE CONDUIT SLACK AND TERMINATIONS INSIDE THE JUNCTION BOX ARE IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATION FOR DISTANCES BETWEEN JUNCTION BOXES AND THE PROPER TEMPERATURE VARIATION TO ENSURE THE PROPER SLACK AND TERMINATION. 15. ENSURE THAT ONE OF ITS CONDUITS IS RED IN COLOR AND IS INSTALLED ON EITHER THE LEFT OR RIGHT SIDE OF THE TRENCH. THE REMAINING TWO ITS CONDUITS ARE TO BE ORANGE IN COLOR. ITS CONDUITS (TYP.) 1" MIN. 1" MIN. TRACER WIRE (TYP.) CONDUIT TRENCH OFFSET FROM EXISTING AND PROPOSED GUIDERAIL pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE IN GRASS AREA INSTALL WARNING TAPE 18" BELOW FINISH GRADE SEE NOTE 8 CURB SUITABLE GRANULAR MATERIAL FROM PROJECT OR COARSE AGGREGATE TO MEET EXISTING GRADE AS DIRECTED BY THE ENGINEER BACKFILL MATERIAL 36" MIN. scale= 30.000000:1.00000 CLASS "B" CONC. 1.5" MIN. ITS CONDUITS (TYP.) NOT TO SCALE 1" MIN. 1’-0" MIN. 2" MIN. ITS-704-05 2" MIN. TRACER WIRE (TYP.) BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS BEHIND THE CURB ITS CONDUIT TYPE A ITS CONDUIT, TYPE A * * file= VARIES ROADWAY R.O.W. 6" CAUTION: BURIED FIBER OPTIC CABLE BELOW CALL NJDOT TRAFFIC OPERATIONS NORTH 201-797-7314 OR SOUTH 856-486-6095 TYP. TOP CAP W C I A B B R E L N SEE DETAIL "A" TYP. BOTH SIDES F A R E O I P N T G I C For Mark Out Request-Go To http://www.state.nj.us/ transportation BEFORE EXCAVATING OR IN AN EMERGENCY CALL 1-800-272-1000 TOLL FREE WARNING TAPE SEE DETAIL "B" (TYP.) BOTH SIDES (BLACK LETTERS ON ORANGE BACKGROUND) 3’ CURB LINE WHITE POST 3" EXISTING GROUND NOTE: 1. 1’-6" PROVIDE WARNING TAPE TO BE ORANGE, 4 MIL. FLEXIBLE POLYETHYLENE FILM AND IS RESISTANT TO ACIDS, BASES, HYDROCARBONS AND WATER. SOIL ANCHOR FIBER OPTIC CABLE MARKER SPACE MARKERS 500’ APART BLACK LETTERS ON F C I A A B B R E L R E ORANGE DECAL W 7" MIN NJDOT " 4 8 C T R U N K R T 2 9 5 N B " N O I N BLACK LETTERS ON ORANGE DECAL P T UNDERGROUND CABLE IS OFFSET pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE I "X" G FEET FIBER COUNT FUNCTION ROUTE DIRECTION HORIZONTALLY & C "Y" FUNCTION FEET FOR MARK OUT REQUEST GO TO VERTICALLY http://www.state.nj.us/ transportation FROM THIS POINT OR IN AN EMERGENCY CALL 1-800-272-1000 (TOLL FREE) TRUNK, DISTC, TERMC CCTV WIM DMS TAG RD TRFSG WTHST scale= 30.000000:1.00000 DETAIL "B" DETAIL "A" NOT TO SCALE 3"x9" WARNING DECAL 3"x4" WARNING DECAL FIBER OPTIC CABLE TAG ITS-704-06 BDC07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS FIBER OPTIC WARNING TAPE, MARKER AND TAG FIBER OPTIC WARNING TAPE, MARKER AND TAG * * file= NOTES: 1. AS A MINIMUM, DESIGN THE BOX ASSEMBLY FOR TIER 22 LOADING AS SPECIFIED IN ANSI / SCTE 77 2002 "SPECIFICATION FOR UNDERGROUND ENCLOSURE INTEGRITY". SECTION "A-A" 1" T-SLOT 2. PROVIDE CERTIFICATION BY A PROFESSIONAL ENGINEER AND INCLUDE TEST RESULTS SHOWING THAT THE JUNCTION BOX AND COVER DESIGN MEETS THE LOADING REQUIREMENT. 3. DESIGN THE JUNCTION BOX WITH A MINIMUM SAFETY FACTOR OF 2.0 FOR WHEEL LOADS AND 2.0 FOR SOIL LOADS, SO THAT THE COVER DEFLECTION AT DESIGN LOADS DOES NOT EXCEED 0.5 INCHES AND SIDE WALL DEFLECTION DOES NOT EXCEEED 0.25 INCHES PER FOOT OF HEIGHT OF BOX. PERFORM TESTING ACCORDING TO CURRENT WESTERN UNDERGROUND COMMITTEE GUIDE NO. 3.6 NON-CONCRETE ENCLOSURE. 4. ENSURE ANY POINT ON THE COVER OR BOX WITHSTANDS A 70 FT. LBS. IMPACT ADMINISTERED WITH A C-TUP ACCORDING TO ASTM D-2444. 5. ENSURE THE MATERIALS UTILIZED IN THE MANUFACTURE OF JUNCTION BOXES AND COVERS ARE RESISTANT TO CHEMICALS COMMONLY FOUND IN THE SOIL OR IN THE OPERATING ENVIRONMENT, AND THEY ARE ALSO RESISTANT TO SUNLIGHT, UV AND ANY CLIMATIC "DIA. X 4" BOLT WITH HEX NUT. (2) BOLT DOWN PENTA BOLTS 1" " DIA. HOLE TAPERED SPRING " LONG " -13NC X 3" IN COVER (TYP.) "N.J.D.O.T. FIBER" LOGO 5" " THICK "A" "A" N.J. D.O.T. FIBER CONDITIONS IN ACCORDANCE WITH ASTM G53, -40^F TO +140^F. DETERMINE CHEMICAL RESISTANCE PROPERTIES USING ASTM D543 AND ASTM D570 FOR WATER ABSORPTION. "NYLOCK" STYLE LOCK NUT LIFTING EYES (6) CABLE BRACKETS (STAINLESS STEEL) POLYMER CONCRETE COVER 6. ENSURE THE MATERIALS ARE RESISTANT TO DIRECT FLAME AND HEAT IN ACCORDANCE WITH ASTM D635. 7. ENSURE ALL HARDWARE IS STAINLESS STEEL. 8. MOUNT THREE PAIRS OF CABLE BRACKETS AT 120 DEGREES APART. 9. FASTEN EACH CABLE BRACKET WITH A " DIA. X 1" LONG BOLT AND (1) HEX NUT, (2) FLAT WASHERS. 10. FACTORY ASSEMBLE THE JUNCTION BOX AND USE SILICON CAULKING FOR ALL FLANGE JOINTS. 11. ENSURE THE COVER SURFACE IS SKID RESISTANT WITH A COEFFICIENT OF FRICTION OF AT LEAST 0.5. 12. PERMANENTLY MOLD IDENTIFICATION OF THE COVER ON THE TOP SURFACE WITH "N.J.D.O.T. FIBER". 13. ENSURE THE COLOR OF THE COVER AND THE PART OF THE BOX THAT REMAINS VISIBLE AFTER INSTALLATION IS "CONCRETE GREY". 14. SET THE TOP OF THE POLYMER CONCRETE COVER FLUSH WITH THE TOP OF THE JUNCTION BOX AT GRADE. 15. PROVIDE AND INSTALL CONCRETE LOCK-IN FEATURE AROUND THE TOP OF THE BOX. 16. LIMIT THE GAP FROM THE EDGE OF THE COVER TO THE INSIDE EDGE OF THE BOX TO A MAXIMUM OF " +/- ". 17. AS AN ALTERNATE, A SINGLE SECTION OR TWO SECTION JUNCTION BOX MAY BE SUPPLIED. 18. VIBRATE AND COMPACT SOIL THOROUGHLY AROUND ENTIRE JB UP TO GRADE PER SECTION 203.03.02D OF NJDOT STANDARD SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION 2007. 19. TERMINATE RIGID NON-METALLIC CONDUITS WITH BELL END FLUSH WITH THE INSIDE WALL OF THE JUNCTION BOX. 20. TERMINATE FLEXIBLE NON-METALLIC CONDUIT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND MANUFACTURER’S REQUIREMENTS. LAY FNMC ON THE GRAVEL/BROKEN STONE IN JB. "A" EXTEND CONDUIT ENDS 4" PAST THE INSIDE WALL OF THE JB. 21. ENSURE CONDUITS ENTER INTO THE JUNCTION BOX PERPENDICULAR TO WALLS OR AS APPROVED BY THE RE. 1’-0" CLEAR OPENING TOP & BOTTOM 6" 22. CONCRETE 6" THICK. 3’-2" 1’-2" JUNCTION BOX MADE OF FIBERGLASS, PLASTIC COMPOSITE MATERIAL, RPM/ FRP COMBINATION OR POLYMER CONCRETE INSTALL A CONCRETE COLLAR AROUND THE TOP OF THE JUNCTION BOX OF CLASS "C" SEE BRACKET DETAIL 23. FIELD DRILL ALL CONDUIT ENTRANCES INTO THE JUNCTION BOX WITH A HOLE SAW, OR PUNCH OUT USING A HYDRAULIC HOLE PUNCH, UNLESS OTHERWISE DIRECTED BY THE RE. 24. SAND ALL CONDUIT OPENINGS. AFTER THE CONDUITS ARE INSTALLED, SEAL ALL CONDUIT ENTRANCES WITH AN EPOXY OR SILICON CAULK. 25. PROVIDE AND INSTALL PROTECTIVE COVER WITH THE BOLT ASSEMBLY. 26. PROVIDE AND INSTALL COMPACTED " GRAVEL OR BROKEN STONE. 27. PROVIDE AND INSTALL GROUNDING ROD (NOT SHOWN) AS PER NEC. pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 4" 2’-8" 4’-0" 4" 6" 4" 30.000000:1.00000 10" 1’-2" FILL WITH " GRAVEL scale= "A" ELEVATION SECTION "A-A" NOT TO SCALE ITS-704-07 BDC-07D-03- ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:47 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS JUNCTION BOX ITS, TYPE A JUNCTION BOX ITS TYPE A DO NOT INSTALL THIS BOX IN THE TRAVEL WAY AND SHOULDERS. * * file= C 1’-6" 1’-0" 1’-0" 1’-6" 4.5" 6" 1" KNOCK OUT WALL A A N.J. BOX WINDOWS 1" D.O.T. " FIBER 4’-0" 3’-0" 1" KNOCK OUT WALL dia. 3" x " x " HIGH NON - SKID LUGS CABLE RACK SUPPORTS (4) PICK HOLE MINIMUM WEIGHTS UNDERSIDE OF COVER SOLID LID 8" WEIGHT OF FRAME = 265# WEIGHT OF COVER = 175# NOTES: 4.5" " 3’- 2" C KNOCK-OUT WALL SECTION 2. PROVIDE SUFFICIENT STEEL REINFORCEMENT PER ASTM-A615 (GRADE 60) (FS) = 24,000 psi. TO MEET THE LOADING REQUIREMENTS. 3. CONCRETE DESIGN STRESSES: 1" 3’-0" 5’-0" CABLE RACK SUPPORTS (4) 1’-4" ENSURE THE ROADWAY JUNCTION BOX COMPLIES WITH AASHTO HS20-44 OR TANDEM 24 KIP AXLES AT 4 FOOT CENTERS, WHICHEVER GOVERNS, FOR LIVE LOADING. " TOP VIEW 1’-10" 1. 1’-10" 4’-0" 8" 1’-4" 1’-4" 1’-4" 2’-10" CABLE RACK SUPPORTS (4) 2" 3’-1" 3" b. CLASS DESIGN STRENGTH .....................................................4,600psi (IN ACCORDANCE WITH SECTION 914 OF THE SPECIFICATIONS) 3’-8" 1’-4" 1’-4" COVER THE STEEL REINFORCEMENT WITH A MINIMUM OF 1" OF CONCRETE. SECTION A-A RING AND COVER BOX WINDOW 6" 6" 4’-0" 6" CLASSA a. SPECIFIED DESIGN COMPRESSIVE STRENGTH (F’C)..............4,000psi 4’-0" 5. AFTER THE INSTALLATION OF CONDUIT, COMPLETELY SEAL ALL OPEN RECESSES WITH BRICK AND GROUT. 6. ENSURE THE RING AND COVER ARE MADE OF GRAY IRON, AND COMPLY WITH AASHTO M105, ASTM A-48, CLASS 30B, WITH A MIN. TENSILE STRENGTH OF 30,000 psi. 7. SET THE TOP OF THE RING AND COVER AT ROADWAY GRADE. BOX WINDOW 6" " BOX WINDOW 6" 6" BOX WINDOW 4’-0" NON-SKID LUG (TYP.) 1’-2" 6" TYP. B 1’-2" 8. 4.5" 9. B 1’-0" 6" TERMINATE RIGID NON-METALLIC CONDUITS WITH BELL END FLUSH WITH THE INSIDE WALL OF THE JUNCTION BOX. 6" 6" TYP. 6" TYP. TERMINATE FLEXIBLE NON METALLIC CONDUIT (FNMC) IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND MANUFACTURERS REQUIREMENTS. FNMC TO LAY ON THE GRAVEL/BROKEN STONE 6" IN JB. CONDUIT ENDS TO EXTEND 4" PAST THE INSIDE WALL OF JB. 8" 8" ~ 5" 10. BOX WINDOW (TYP.) MAINTAIN A 2" SEPARATION BETWEEN ADJACENT WALLS, CONDUITS AND CABLE RACKS. SIDE VIEW FRONT VIEW 2" CABLE RACK SUPPORTS (4) ENSURE CONDUITS ENTER INTO THE JUNCTION BOX PERPENDICULAR TO WALLS OR AS APPROVED BY THE ENGINEER. 4’-0" 11. PROVIDE 4 CABLE RACKS AS INDICATED. 12. PROVIDE CERTIFICATION BY A PROFESSIONAL ENGINEER FOR DESIGN CALCULATIONS SHOWING THE JUNCTION BOX MEETS 2’-8" BOX WINDOW ALL LOADING REQUIREMENTS. 13. PROVIDE 8" THK. LAYER OF COMPACTED " GRAVEL OR BROKEN STONE. 14. PERMANENTLY MOLD IDENTIFICATION OF THE COVER ON THE TOP SURFACE WITH "NJDOT FIBER". 15. PROVIDE AND INSTALL GROUND ROD AS PER NEC REQUIREMENTS. 2’-0" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 8" 1" DIA. GROUND ROD HOLES (4 HOLES REQUIRED) 2’-2" " GRAVEL OR BROKEN STONE INSTALL COPPER GROUND ROD - " DIA. X 12’ L 8" X 8" SQUARE HOLE. SECTION C-C 8" CABLE RACK PROVIDE GALVANIZED STEEL OR GLASS FILLED THERMOPLASTIC INSERTS AS REQUIRED. 30.000000:1.00000 1’-2" scale= 8" 3’-0" NOT TO SCALE 6"(TYP.) 4’-0" 6" ITS-704-08 6" BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:48 NEW JERSEY DEPARTMENT OF TRANSPORTATION SECTION B-B THREADED INSERT TAPPED FOR ITS DETAILS "~ BOLT N.C. CLASS 2 FREE FIT THREAD. FURNISH GALVANISHED BOLTS "~ N.C. CLASS 2 FREE FIT, THREAD 1" JUNCTION BOX ITS, TYPE B LONG AND FLAT WASHERS " I.D. X 1" O.D. JUNCTION BOX ITS TYPE B CABLE RACK SUPPORTS THIS JUNCTION BOX IS FOR INSTALLATION IN THE TRAVELWAY AND SHOULDER. file= * * NOTES: 35" 35" 1. A ENSURE THE COVER IS FASTENED TO THE BOX WITH TWO " -13NC STAINLESS STEEL HEX BOLTS, LOCATED AT OPPOSITE CORNERS OF THE COVER. BOLTS TO BE CAPTIVE TO LID. 2. ENSURE THE COVER SURFACE IS SKID RESISTANT WITH A COEFFICIENT OF FRICTION OF AT LEAST 0.5. 3. ENSURE THE DESIGN AND FABRICATION OF THE BOX AND COVER CONFORMS TO ALL ASPECTS OF ANSI/SCTE 77. ENSURE LOADING IS ENSURE THE LOADING TIER 15. 4. ENSURE THE JUNCTION BOX IS MADE OF FIBER POLYMER CONCRETE. ENSURE THE COVER IS MADE OF FIBER GLASS REINFORCED POLYMER CONCRETE. A 5. ENSURE THE COLOR OF THE COVER AND ANY PART OF THE BOX VISIBLE WHEN IT IS INSTALLED, IS "CONCRETE GREY." 6. ENSURE THE IDENTIFICATION OF THE COVER IS PERMANENTLY MOLDED ON THE TOP SURFACE WITH "NJDOT ITS". 7. UNLESS OTHERWISE DIRECTED BY THE ENGINEER ALL CONDUIT ENTRANCES INTO THE JUNCTION BOX ARE TO BE FIELD DRILLED WITH A HOLE SAW OR PUNCHED OUT USING A HYDRAULIC HOLE PUNCH. " x 4" LIFT 24" 24" NJDOT I.T.S. SLOT (2x) 8. ALL CONDUIT OPENINGS MUST BE SANDED. AFTER THE CONDUITS ARE INSTALLED, ALL CONDUIT ENTRANCES MUST BE SEALED WITH AN EPOXY PUTTY OR SILICON CAULK. 9. IN GRASS OR DIRT AREAS, A CONCRETE PAD, CLASS "C", MUST BE POURED AROUND THE TOP OF THE JUNCTION BOX. ELEC. 10. COMPACTED " GRAVEL OR BROKEN STONE IS REQUIRED BELOW THE BOX. SUPPLY AN ADDITIONAL SIX (6) INCHES OF TIGHTLY COMPACTED " CLEAN STONE PLACED IN BOTTOM OF BOX. 11. SKID RESISTANT COVER BOLT DOWN SURFACE (SEE DETAIL) PROVIDE A CONCRETE LOCK-IN FEATURE AT THE TOP OF THE BOX. ACTUAL DESIGN CAN VARY PER MANUFACTURER. 12. ENSURE THE GAP FROM THE EDGE OF THE COVER TO THE INSIDE EDGE OF THE BOX IS A MAXIMUM OF " +/- ". 13. ENSURE THE TOP OF THE POLYMER CONCRETE COVER IS SET FLUSH WITH THE TOP OF THE JUNCTION BOX. 14. PROVIDE EMBOSSED CERTIFICATION BY A PROFESSIONAL ENGINEER OF TEST RESULTS SHOWING THAT THE JUNCTION BOX AND COVER MEET THE DESIGN SPECIFIED LOADING REQUIREMENTS. 15. UTILIZE BOX EXTENSION TO PROVIDE REQUIRED DEPTH. 16. SUPPLY BOX WITH CABLE RACK SYSTEMS AFFIXED TO BOTH LONG SIDES OF THE BOX FOR STORAGE OF CABLE SLACK. 3" 17. THE BOX MUST MEET REQUIREMENTS OF NEC ARTICLE 314. 18. ALL EXPOSED HARDWARE TO BE STAINLESS STEEL. 19. DIMENSIONS ARE TYPICAL. ENSURE CUT SHEETS ARE SUBMITTED FOR APPROVAL FOR THE EXACT BOX TO BE UTILIZED. THE BOX IS TO HAVE AN OPEN BOTTOM. COVER TOP VIEW (COVER NOT SHOWN) BEARING LEDGE COVER 6" " - 13 NC X 2 S.S. HEX-HEAD CAPTIVE BOLT pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE BOX 39" 28" 6" ’ MIN. 3" SELF-CENTERING CORRISION RESISTANT NUT COVER BOLT DOWN DETAIL scale= 30.000000:1.00000 36" 12" NOT TO SCALE ITS-704-09 BDC-11D-03- ORIGINAL SHEET NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:48 NEW JERSEY DEPARTMENT OF TRANSPORTATION 42" ELEVATION ITS DETAILS 34" SIDE VIEW SECTION A-A JUNCTION BOX ITS TYPE C * * file= NOTES: 1. 74" COVER BOLT DOWN DEEP C’BORE 74" (SEE DETAIL) ENSURE THE COVER IS FASTENED TO THE BOX WITH TWO (2) " -13NC STAINLESS STEEL HEX BOLTS, LOCATED AT OPPOSITE CORNERS OF THE COVER. ENSURE BOLTS ARE CAPTIVE TO LID. " X 4" MIN PULL SLOT WITH " MIN CTR PIN 2. 4 PLACES 3. ENSURE THE COVER SURFACE IS SKID RESISTANT WITH A COEFFICIENT OF FRICTION OF AT LEAST 0.5. ENSURE THE DESIGN AND FABRICATION OF THE BOX AND COVER CONFORMS TO ALL ASPECTS OF ANSI/SCTE 77. ENSURE LOADING IS TIER 22. 4. ENSURE THE JUNCTION BOX IS PRECAST POLYMER CONCRETE. ENSURE THE COVER IS MADE OF FIBER GLASS REINFORCED POLYMER CONCRETE. 5. ENSURE THE COLOR OF THE COVER AND ANY PART OF THE BOX VISIBLE WHEN IT IS INSTALLED, IS "CONCRETE GREY." 6. ENSURE THE IDENTIFICATION OF THE COVER IS PERMANENTLY MOLDED ON THE TOP SURFACE WITH "NJDOT ITS". 7. UNLESS OTHERWISE DIRECTED BY THE ENGINEER ALL CONDUIT ENTRANCES INTO THE JUNCTION BOX ARE TO BE FIELD DRILLED WITH A HOLE SAW OR PUNCHED OUT USING A HYDRAULIC HOLE PUNCH. 8. " 39" ELEC NJDOT ITS NJDOT ITS COMM BE SEALED WITH AN EPOXY PUTTY OR SILICON CAULK. 9. 10. 39" ELECTRICAL POWER ALL CONDUIT OPENINGS MUST BE SANDED. AFTER THE CONDUITS ARE INSTALLED, ALL CONDUIT ENTRANCES MUST IN GRASS OR DIRT AREAS, A CONCRETE PAD, CLASS "C", MUST BE POURED AROUND THE TOP OF THE JUNCTION BOX. COMPACTED " GRAVEL OR BROKEN STONE IS REQUIRED BELOW THE BOX. SUPPLY AN ADDITIONAL SIX (6) INCHES OF TIGHTLY COMPACTED " CLEAN STONE PLACED IN BOTTOM OF BOX. COMMUNICATIONS 11. PROVIDE A CONCRETE LOCK-IN FEATURE AT THE TOP OF THE BOX. ACTUAL DESIGN CAN VARY PER MANUFACTURER. 12. ENSURE THE GAP FROM THE EDGE OF THE COVER TO THE INSIDE EDGE OF THE BOX IS A MAXIMUM OF " +/- ". 13. ENSURE THE TOP OF THE POLYMER CONCRETE COVER IS SET FLUSH WITH THE TOP OF THE JUNCTION BOX. 14. PROVIDE CERTIFICATION BY A PROFESSIONAL ENGINEER OF TEST RESULTS SHOWING THAT THE JUNCTION BOX AND COVER MEET THE DESIGN SPECIFIED LOADING REQUIREMENTS. SKID RESISTANT SURFACE 15. UTILIZE BOX EXTENSION TO PROVIDE REQUIRED DEPTH. 16. SUPPLY BOX WITH CABLE RACK SYSTEMS AFFIXED TO BOTH LONG SIDES OF THE BOX FOR STORAGE OF CABLE SLACK. 17. THE BOX MUST MEET REQUIREMENTS OF NEC ARTICLE 314. 18. ALL EXPOSED HARDWARE TO BE STAINLESS STEEL. 19. DIMENSIONS ARE TYPICAL. ENSURE CUT SHEETS ARE SUBMITTED FOR APPROVAL FOR THE EXACT BOX TO BE UTILIZED. 3" DIVIDER PANEL TOP VIEW (COVER NOT SHOWN) THE BOX IS TO HAVE AN OPEN BOTTOM. COVER BEARING LEDGE COVER 6" " - 13 NC X 2 S.S. HEX-HEAD CAPTIVE BOLT pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE BOX 78" 43" (4) -" DIA. BOLT TO RETAIN 6" " MIN. LIFT SLING SELF-CENTERING CORRISION RESISTANT NUT scale= 30.000000:1.00000 6" COVER BOLT DOWN DETAIL 48" NOT TO SCALE ITS-704-10 NEW JERSEY DEPARTMENT OF TRANSPORTATION BDC-11D-03 - ORIGINAL SHEET NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:48 6" ITS DETAILS 77" 42" JUNCTION BOX ITS TYPE D ELEVATION SIDE VIEW SECTION A-A * * file= DESIGN SPECIFICATIONS: UTILIZE 2009 AASHTO STANDARD SPECIFICATIONS FOR STRUCTURAL SUPPORT FOR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS WITH THE LATEST INTERIM. NO SPLICING ALLOWED. THE COMPOSITE COMMUNICATION CABLE TO BE PREWIRED WITH A CONTINUOUS RUN TO THE GROUND MOUNTED CONTROLLER. DESIGN WIND VELOCITY 80 M.P.H. (APPENDIX C) DESIGN ICE LOAD 3 P.S.F. FATIGUE CATEGORY 2 50 YEARS DESIGN LIFE TENON (8)" X 3" SLOTTED HOLES TENON ENSURE ALL LOADS APPLIED TO ALL MEMBERS HAVE BEEN TAKEN INTO ACCOUNT FOR STRENGTH DESIGN, AND ALL WELDED STRUCTURAL DETAILS HAVE BEEN ANALYZED 5" DIA. CENTER HOLE AGAINST FATIGUE. THE DESIGN ANALYSIS IS NOT LIMITED TO POLE, BUT OTHER COMPONENTS LIKE ACCESS DOOR, TENON, LOWERING DEVICE, WINCH ASSEMBLY, BASE PLATE, POLE-TO-BASE CONNECTION, ANCHOR BOLTS EMBEDMENT, ETC., MUST ALSO BE CONSIDERED. " 19" 17" ENSURE MAXIMUM HORIZONTAL DEFLECTION AT THE TOP OF THE POLE COMPLETELY ASSEMBLED WITH CCTV CAMERA AND ALL FIXTURES ATTACHED DOES NOT EXCEED 2 INCHES FROM THE CENTER LINE DUE TO A 40 MPH (GUST FACTOR 1.3) SEE TENON ASSEMBLY DETAIL AND POLE TOP PLATE DETAIL WIND SPEED (APPENDIX C WIND PRESSURE FORMULA) MINIMUM 60% PENETRATION WELD. A 100% FULL PENETRATION WELD AND GROUND SMOOTH IS REQUIRED FOR: 1. A DISTANCE OF 6" AT THE END OF THE BASE. 2. A DISTANCE OF 6" ON EACH SIDE OF FULL PENETRATION WELD JOINT. 3. A DISTANCE OF THE SLIP JOINT PLUS 6" AT THE FEMALE END. ROUND OR MINIMUM 18 SIDED STEEL TAPERED POLE. SUBMIT DETAIL PLANS AND DESIGN CALCULATIONS OF CAMERA STANDARD POLES WITH CAMERA SHOWING STRENGTH, FATIGUE AND DEFLECTION CHECKS. SHOW CAMERA ASSEMBLY WEIGHT, INCLUDING LOWERING DEVICE AND EFFECTIVE PROJECTED AREA (EPA). ENSURE THE DESIGN CALCULATIONS AND WORKING DRAWINGS ARE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER. 1" MATERIALS: ENSURE THE POLE MATERIAL CONFORMS TO ASTM SPECIFICATIONS A595,GRADE A (MIN. YIELD POINT 55 KSI) OR GRADE B (MIN YIELD POINT 60 KSI). TENON MATERIAL CONFIRMS TO ASTM A53, GRADE B (MIN. YIELD POINT 35 KSI). THE POLE TAPER TO BE 0.14 IN./FT. MAX. TWO SEGMENTS MUST BE THE SAME MATERIAL. AS AN ALTERNATE THE POLE (18 SIDED MIN.) AND TENON MAY BE FORMED FROM STEEL CONFORMING TO ASTM A572 GRADE 55 OR GRADE 60. ALL OTHER STEEL CONFORMS TO ASTM SPECIFICATION A709(AASTHO M270) GRADE 36 OR GRADE 50. ENSURE ALL POLES REGARDLESS OF THICKNESS AND ALL OTHER STEEL PLATES GREATER THAN " THICKNESS MEET THE AASHTO REQUIREMENTS FOR NOTCH TOUGHNESS (CHARPY TESTING) ZONE 2. GALVANIZE BOTH UNITS OF THE POLE AND TENON PER ASTM A123 AFTER FABRICATION. TENON PLATE VISUALLY INSPECT THE FINAL WELD INSIDE AND OUTSIDE. POLE SLIP JOINT DETAIL TYPICAL LONGITUDINAL SEAM WELD POLE TOP / TENON PLATES DETAIL 1. MIN. OVERLAP LENGTH 1.5 X THE INSIDE DIA. OF THE FEMALE SECTION. 2. SNUG FIT WITH MAX. DEVIATION OF " TOP DIA OF TUBE +" PROCURE BOLTS/ANCHOR BOLTS, NUTS AND WASHERS AS A PACKAGE FROM THE MANUFACTURER. ENSURE ANCHOR BOLT MATERIALS CONFORM TO ASTM F1554, GRADE 55. GALVANIZE THE ANCHOR BOLTS PER ASTM A153, CLASS C AFTER THREADING FOR THE FULL LENGTH OF THE BOLT, AS WELL AS NUTS AND WASHERS. (4)-2" DIA. HOLES HIGH STRENGTH BOLTS, NUTS AND WASHERS TO BE GALVANIZED PER ASTM A153 CLASS C. 30" DIA. BOLT CIRCLE PROVIDE STAINLESS STEEL FASTENERS (INCLUDING BOLTS, NUTS AND WASHERS) CONFORMING TO CURRENT ASTM A320, GRADE B8, CLASS 2 (AISI TYPE 304) AND STRAIN HARDENED. ALTERNATE MATERIALS PROPOSED TO BE USED FOR FASTNERS MUST BE PRE-APPROVED SEPERATELY PRIOR TO SUBMISSION OF WORKING DRAWINGS. 19" 17" 30" 3/16 " CONTINUOUS WELD 55’ (TYPE B) 75’ (TYPE A) M T UPPER ALL CONCRETE TO BE "CLASS B" AS DEFINED IN THE NJDOT STANDARD SPECIFICATIONS. CP NOTES: 30" " (8)" DIA. HOLES 1. 45^ 45^ " " X 1" BACKUP STRIP T LOWER POLE TOP PLATE SECTION A-A (BASE PLATE) (BOLTS NOT SHOWN) FULL PENETRATION DETAIL ENSURE STEEL POLE CONSISTS OF A MAXIMUM OF TWO STEEL SECTIONS.THE LOWER SECTION TO BE A MIN. OF 40 FT AND MAXIMUM OF 50’ LONG WITH A MIN. THICKNESS OF " WITH ONLY ONE LONGITUDINAL SEAM WELD. IF THE POLE DIA. IS GREATER THAN 24 INCHES, TWO LONGITUDINAL SEAM WELDS WILL BE PERMITTED. EITHER SLIP JOINTS OR FULL PENETRATION WELD JOINTS ARE ACCEPTABLE, SEE SLIP JOINT AND FULL PENETRATION DETAILS. LAMINATED TUBES ARE NOT PERMITTED. SEE TYPICAL LONGITUDINAL SEAM WELD DETAIL. 2. ENSURE THAT THE POLE DIAMETER IS SUFFICIENT TO ACCOMMODATE THE WINCH / MOTOR ASSEMBLY COMPLETELY INSIDE THE POLE. " DIA. ROD WITH 1" I.D. OPPOSITE SLOT FOR WIRE TIE-OFF (TYP.) (CABLE GUIDE) 6" O.D. X " WALL X 1’-0" LONG TENON 1" " 2 HOLD DOWN HEX NUTS AND 1 FLAT WASHER PER BOLT 1 LEVELING HEX NUT AND 1 FLAT WASHER PER BOLT WELD 5" X 1" SLOT CUT IN TENON WALL FOR CABLE AND PULLEY ACCESS BASE PLATE 6. DO NOT GROUT UNDER THE POLE . 2" 7. PROVIDE ONE (1) LEVELING HEX NUT, TWO (2) HOLD DOWN HEX NUTS AND TWO (2) FLAT WASHERS PER ANCHOR BOLT. (SEE SKETCH A) DETERMINE THE PROPER LENGTH OF THE ANCHOR BOLT FOR CJP pen table= FINISHED GRADE 1" MAX. FROM THE BOTTOM OF THE LEVELING NUT TO THE TOP OF THE CONCRETE FOUNDATION 1" MIN. FROM I.D. 8. ENSURE WELDING CONFORMS TO THE ANSI/AWS D1.1 STRUCTURAL WELDING CODE-STEEL, WITH NJDOT AMENDMENTS IN NJDOT STANDARD SPECIFICATIONS. ENSURE WELDING INSPECTION AND FULL PENETRATION WELD NONDESTRUCTIVE TESTING CONFORM TO AWS D1.1. UNLESS OTHERWISE SPECIFIED. 1" MIN. FROM I.D. GALVANIZED SCREEN 3" x " WITH STAINLESS STEEL BACK-UP RING NUT, BOLT & FLAT WASHER SKETCH "A" " THICK TENON PLATE WITH 5" DIA. CENTER HOLE " T = TUBE WALL THICKNESS 2" PROJECTION AND EMBEDMENT. THE CLEARANCE BETWEEN THE TOP OF THE FOUNDATION AND THE BOTTOM OF THE LEVELING NUT NOT TO EXCEED 1". THE PROJECTION LENGTH TO BE A MINIMUM OF 9". 7" 1" 45^ (T + 0.44) X T \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE " DIA. HOLE 0.25 TOP OF FOUNDATION 4. PROVIDE A GALVANIZED SCREEN, WRAPPED AROUND THE BASE OF POLE. 5. ENSURE THE GALVANIZED SCREEN HAS NO MORE THAN " OPENINGS AND IS HELD TOGETHER WITH STAINLESS STEEL NUT, BOLT AND FLAT WASHER. " DIA. HOLE CONTINUOUS 3. PROVIDE NEOPRENE DOOR GASKET CEMENTED TO DOOR. (4)" X 2" GALVANIZED A325 BOLT W/HEX NUT, (1) WASHER & (1) LOCK WASHER 1" THICK POLE TOP PLATE BASE PLATE TENON ASSEMBLY DETAIL SEE TYP. LONGITUDINAL SEAM WELD DETAIL 9. LOCATE TOP, CENTER AND BOTTOM ELECTRICAL CABLE GUIDES WITHIN THE POLE AND ALIGN WITH EACH OTHER. POSITION THE BOTTOM CABLE GUIDE 2 INCHES BELOW THE BOTTOM OF THE ACCESS DOOR AND THE TOP CABLE GUIDE 1 INCH DIRECTLY BELOW THE TOP OF TENON. POSITION TWO PARKING STANDS A MAXIMUM OF 2" INCHES BELOW THE TOP OF THE ACCESS DOOR AND LOCATED AT 90^ AND 270^ FROM THE ACCESS DOOR. ENSURE EACH CABLE GUIDE IS " WIRE EYE BOLT HAVING 1" INTERNAL DIA. FOR WIRE TIE OFF. 10. ENSURE THE TIGHTENING PROCEDURE FOR ANCHOR BOLTS CONFORMS WITH SECTION 6.9 OF THE 2005 FHWA " GUIDELINES FOR THE INSTALLATION, INSPECTION, MAINTENANCE AND REPAIR OF STRUCTURAL SUPPORTS FOR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS". OPENING FOR ACCESS DOOR scale= 30.000000:1.00000 (SEE ACCESS DOOR DETAIL, SHEET 2 OF 3) SEE SKETCH "A" NOT TO SCALE POLE A GROUND LUGS ( TO BE LOCATED FOR EASY ACCESS THRU ACCESS DOOR ) FINISHED GRADE A " NUT HOLDER 2 REQ. @ 180%%d " DIA. S.S.BOLTS WITH S.S. WASHERS & NUTS (4)- 1" DIA. GALVANIZED ANCHOR BOLTS BDC-07D-03- ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services 27-SEP-2011 08:48 date= TPOKEEG JUNCTION BOX LOCATION & SIZE AS SHOWN ON ELEVATION ID= 3 #8 IN 1" FLEXIBLE CONDUIT TO DISTRIBUTION PANEL DRILL " DIA. HOLE IN GROUND LUGS #1/0 BARE GROUND WIRE CONDUIT REDUCER GROUNDING CLAMP SCREEN NEW JERSEY DEPARTMENT OF TRANSPORTATION GROUNDING BUSHING #8 BARE GROUND BONDING WIRE PLAN SHEETS FINISHED GRADE ITS DETAILS 1" CAMERA STANDARD TYPE A, B SEE FOUNDATION CONCRETE FOUNDATION GROUNDING BUSHING TYPE CSS DETAIL 2’ MAX ANCHOR BOLT ASSEMBLY TWO #1/0 BARE WIRE EYES CHANNEL COUPLINGS 90^ 270^ ITS-704-11 DOWN CONDUCTORS L.D.ARM #1 PARK STAND NUMBER OF CONDUITS (2 MIN.) AND SIZE #8 GROUND WIRE SLOPE CAMERA SURVEILLANCE SYSTEM CAMERA STANDARD TYPE A & B AS SHOWN ON THE PLAN SHEET. 0^ DOWN CONDUCTOR #8 BARE GROUND BONDING WIRE ACCESS DOOR ORIENTATION VIEW file= " " X 12’ LONG GROUND ROD GROUND LUGS DETAIL LIGHTNING & BONDING DETAIL SHEET 1 OF 3 * * POLE / TUBE (TYP.) (4)-#10-32 (NF) X 1" LONG S.S. BOLTS WITH S.S. FLAT WASHERS AND S.S. HEX NUTS " DIA. ROD, PARK STANDS (TYP.) (INSIDE SHAFT WALL) FILLET WELD SIZE " MIN. IF THE WALL THICKNESS IS GREATER THAN ", WELD SIZE TO BE EQUAL TO WALL THICKNESS OF POLE. CABLE GUIDES (TYP.) " 1" 10" X 30" ACCESS DOOR HOLE FRAME (4" W X " THK.) MIN. THK. BAR (4) -" DIA. S.S. BOLT WITH S.S. HEX NUT GALVANIZED DOOR WITH NEOPRENE GASKET 2 " " " NEOPRENE GASKET GALVANIZED DOOR WITH NEOPRENE GASKET ONE PIECE CONTINUOUS PIANO STYLE S.S. PLAIN SURFACE HINGE W/ WELDED PIN (18" LONG) 10" " " W X" THK. X 1" LONG A36 GALVANIZED ANGLE NOTE: THE ANGLE IS TO BE WELDED PRIOR TO GALVANIZING THE POLE. PARK STAND (TYP.) ALL BRASS CCL LOCK #A15481RS-LS KEYED ALIKE FOR KEY #2, PROVIDED WITH DUST CAP. PROVIDE TWO KEYS WITH EACH POLE 2" SECTION Y-Y TYP. ACCESS DOOR FRAME (4" X" THK.) MIN. 30" STEEL POLE STEEL PLATE "Y" 10" "Y" RECTANGULAR STRUCTURAL TUBE CABLE GUIDE (TYP.) 2" (2) -" NUT HOLDER @ 180%%d WITH FASTENERS FOR GROUND LUGS pen table= 18" \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 6" (4)-" DIA. S.S. BOLT WITH S.S. HEX NUT (TYP.) ACCESS DOOR DETAIL scale= 30.000000:1.00000 (10" X 30" CLEAR OPENING) NOT TO SCALE ITS-704-12 BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:48 NEW JERSEY DEPARTMENT OF TRANSPORTATION ACCESS DOOR COVER DETAIL ITS DETAILS (FACTORY ASSEMBLED, TUBE & FRAME NOT SHOWN) CAMERA SURVEILLANCE SYSTEM CAMERA STANDARD TYPE A & B SHEET 2 OF 3 * * file= THE DIMENSIONS OF THE MOUNTING TUBE- PLATE ASSEMBLY AND WELD SIZE TO BE CONTINUOUS CJP DETERMINED BY THE MANUFACTURER TO 2" MIN. GAP ENSURE THE ASSEMBLY CAN WITHSTAND ALL LOADS FROM WINCH/CAMERA LOWERING 2’-6" ALUMINUM AIR TERMINAL " DIAMETER (BEVEL THE PLATE DEVICE SYSTEM. END IF NECESSARY) 8 GAUGE STAINLESS STEEL (4 PER CLAMP)-" DIA.- S.S. BOLTS WITH TWO S.S. WASHERS, ONE LOCK WASHER AND ONE NUT PER BOLT. WELD THE TWO PLATES OF THE ASSEMBLY INSIDE THE POLE PRIOR TO GALVANIZING. SECTION A-A ENSURE NO CRACKING AT WELDS. POSITION THE WINCH ASSEMBLY SO THAT 60" SLOT FOR CABLES AND LOWERING DEVICE WIRE THE WINCH SHAFT CAN ACCOMMODATE THE DRILL ADAPTER ASSEMBLY AND MANUAL HAND CRANK ASSEMBLY. WINCH MOUNTING HOLES TO BE PREDRILLED BY POLE MANUFACTURER. AIR TERMINAL OBTAIN THE WINCH MOUNTING HOLES TEMPLATE FROM LOWERING DEVICE MANUFACTURER. MAST ARM AIR TERMINAL CLAMPS (3 REQUIRED) CAMERA STANDARD MOUNTING TUBE-PLATE ASSEMBLY (WINCH NOT SHOWN) 6" A A 6" 2" 2" TO 6" MAX. AIR TERMINAL INTERNAL PERMANENT WINCH ASSEMBLY AIR TERMINAL CLAMP DETAIL ACCESS DOOR AREA NOTES: WINCH SHAFT 1. PROVIDE SEALED, SELF LUBRICATED BEARINGS, OIL TIGHT BRONZE BEARINGS OR SINTERED BRONZE BUSHINGS WITH ALL PULLEYS FOR THE CAMERA LOWERING DEVICE. GFI RECEPTACLE, CONDUITS AND WIRES TO BE PROVIDED AND INSTALLED FOR ELECTRICAL POWER TO OPERATE THE HEAVY DUTY DRILL SUPPLIED IN THE PROJECT. TENON CABLE GUIDE 6" HOT DIPPED GAL. STEEL MAST ARM PREWIRED POWER, VIDEO AND COMMUNICATIONS 10" COMPOSITE CABLE HOLLOW STRUCTURAL TUBE CABLE GUIDE 3. PROTECT ALL ELECTRICAL AND VIDEO COAXIAL CONNECTIONS BETWEEN THE FIXED AND LOWERABLE PORTION OF THE CONTACT BLOCK FROM EXPOSURE TO THE WEATHER WITH A WATERPROOF SEAL TO PREVENT DEGRADATION OF THE ELECTRICAL CONTACTS. PULLEY (TYP.) STEEL PLATE PERMANENT DIVIDER 1-1/4" CUSTOM GALVANIZED STEEL CONDUIT MOUNT ADAPTER 24" ALUMINUM OR STAINLESS CAMERA STANDARD STEEL DISCONNECT UNIT COVER, LOWERING DEVICE CABLE CONNECTORS CONCRETE FOUNDATION, CONTROL CABLE CONDUITS ARE NOT SHOWN CAMERA JUNCTION BOX PROVIDED WITH STAINLESS TRANSITION TO PVC CONDUIT STEEL QUICK DISCONNECT TOGGLE BOLTS ONE STAINLESS STEEL NUT, BOLT & FLATWASHER ANCHOR BOLT (TYP.) 2. ENSURE THE LOWERING CABLE HAS A MINIMUM OF " DIAMETER STAINLESS STEEL AIRCRAFT CABLE WITH A MINIMUM BREAKING STRENGTH OF 1740 POUNDS WITH (7) STRANDS OF 19 WIRE EACH. 4. DESIGN THE ELECTRICAL CONNECTIONS BETWEEN THE FIXED AND MOVABLE LOWERING DEVICE COMPONENTS TO CONDUCT HIGH FREQUENCY DATA BITS AND ONE (1) VOLT PEAK-TO-PEAK VIDEO SIGNALS AS WELL AS THE POWER REQUIREMENTS FOR OPERATION OF DOME ENVIRONMENTAL CONTROLS. 5. PROVIDE INTERFACE AND LOCKING COMPONENTS MADE OF STAINLESS STEEL. 6. ENSURE THE SUSPENSION CONTACT UNIT HAS LOAD CAPACITY OF 600 LBS. WITH A MINIMUM OF 4 TO 1 SAFETY FACTOR. 7. SUPPLY DRILL, ADAPTOR ASSEMBLY AND MANUAL HAND CRANK ASSEMBLY AS SHOWN. WEATHER DOME CAMERA HOUSING PVC CONDUIT CAMERA BOX SIDE VIEW FRONT VIEW (DOOR NOT SHOWN) (DOOR NOT SHOWN) 8. INCLUDE INTERNAL PERMANENT WINCH ASSEMBLY AND GFI RECEPTACLE BOX MOUNTING DETAILS, IN THE WORKING DRAWINGS FOR APPROVAL. 9. DURING THE INSTALLATION OF THE FIRST CAMERA SURVEILLANCE SYSTEM IN THE PROJECT PROCURE ASSISTANCE FROM THE LOWERING DEVICE MANUFACTURER. THE FACTORY REPRESENTATIVE OF THE LOWERING DEVICE MANUFACTURER IS DOME CAMERA AND LOWERING DEVICE ASSEMBLY WINCH ASSEMBLY MOUNTING DETAIL REQUIRED TO BE PRESENT DURING THE ASSEMBLY AND TESTING OF THE VERY FIRST LOWERING DEVICE AND WINCH ASSEMBLY ON THE CAMERA STANDARD. FOR SUBSEQUENT INSTALLATIONS WITHIN THE SAME PROJECT, IF A FACTORY REPRESENTATIVE OF THE LOWERING DEVICE MANUFACTURER IS NOT PROVIDED THEN A CERTIFICATION FROM THE LOWERING DEVICE MANUFACTURER WILL BE REQUIRED STATING THAT THE CONTRACTOR HAS BEEN INSTRUCTED AND TRAINED ON THE INSTALLATION, OPERATION AND SAFETY FEATURES OF THE LOWERING DEVICE AND WINCH ASSEMBLY. (LINE DIAGRAM) pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 10. ARRANGE FOR AND PROVIDE "ON SITE" OPERATIONAL INSTRUCTIONS AND TRAINING TO DOT-ITS MAINTENANCE PERSONNEL. BLACK OXIDE COATED STEEL 21" TO 27" AS NEEDED PART RELEASE ACCESS BLACK OXIDE scale= 30.000000:1.00000 COATED STEEL 304 STAINLESS " HEX ALUMINUM ROTATING HANDLE TO STEADY ASSEMBLY TORQUE LIMITER EXTENSION SHAFT 1 " HEX SOCKET NOT TO SCALE PHENOLIC PLASTIC WINCH HANDLE EXTENSION 1 " IMPACT SOCKET SHAFT 8" PART RELEASE ACCESS ITS-704-13 ZINC DICHROMATE COATED STEEL " DRILL CHUCK " DRIVE WINCH SHAFT NEW JERSEY DEPARTMENT OF TRANSPORTATION ADAPTER BDC-07D-03- ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:48 23" TO 30" AS NEEDED ITS DETAILS REVERSIBLE " HEAVY DUTY DRILL WITH TORQUE LIMITED CLUTCH EQUIPPED DRILL ADAPTER ASSEMBLY (LINE DIAGRAM) MANUAL HAND CRANK ASSEMBLY (LINE DIAGRAM) CAMERA SURVEILLANCE SYSTEM CAMERA STANDARD TYPE A & B SHEET 3 OF 3 * * file= DESIGN SPECIFICATIONS: BOLT CIRCLE (MUST MATCH MOUNTING FOOTPRINT FOR PAN AND TILT DRIVE) 180%%d " DRILL & TAP AS REQUIRED CONTINUOUS POLE TOP O.D. PLUS 2-1/2" MIN. WELD CJP 0.25 CAMERA MOUNTING TOP PLATE (SEE DETAIL B) (T + 0.44) X T 45^ T = TUBE WALL THICKNESS 2" 9" UTILIZE 2009 AASHTO STANDARD SPECIFICATIONS FOR STRUCTURAL SUPPORT FOR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS WITH THE LATEST INTERIM. DESIGN WIND VELOCITY DESIGN ICE LOAD FATIGUE CATEGORY DESIGN LIFE 1" DIA. HOLE (DEBURRED) ENSURE ALL LOADS APPLIED TO ALL MEMBERS HAVE BEEN TAKEN INTO ACCOUNT FOR STRENGTH DESIGN, AND ALL WELDED STRUCTURAL DETAILS HAVE BEEN ANALYZED 1" THK. CAMERA MOUNTING TOP PLATE AGAINST FATIGUE. THE DESIGN ANALYSIS IS NOT LIMITED TO POLE, BUT OTHER COMPONENTS LIKE ACCESS DOOR AND HANDHOLE OPENINGS/FRAMES, CAMERA MOUNTING TOP PLATE, CAMERA WEIGHT, AIR TERMINAL, BASE PLATE, POLE-TO-BASE CONNECTION, ANCHOR BOLTS EMBEDMENT, ETC., MUST ALSO BE CONSIDERED. 270%%d 90%%d 45%%d ENSURE MAXIMUM HORIZONTAL DEFLECTION AT THE TOP OF THE POLE COMPLETELY ASSEMBLED WITH CCTV CAMERA AND ALL FIXTURES ATTACHED DOES NOT EXCEED 2 INCHES FROM THE CENTER LINE DUE TO A 40 MPH (GUST FACTOR 1.3) WIND SPEED (APPENDIX C WIND PRESSURE FORMULA) 1" MIN. FROM I.D. 1" MIN. FROM I.D. 3" x " J HOOK 0%%d BACK-UP RING 3" X 5" HANDHOLE (CLEAR OPENING) WITH " THICK COVER ONE (1) - REQ’D. 80 M.P.H. (APPENDIX C) 3 P.S.F. 2 50 YEARS SUBMIT DETAIL PLANS AND DESIGN CALCULATIONS OF CAMERA STANDARD POLES WITH CAMERA SHOWING STRENGTH, FATIGUE AND DEFLECTION CHECKS. SHOW CAMERA ASSEMBLY WEIGHT, INCLUDING LOWERING DEVICE AND EFFECTIVE PROJECTED AREA (EPA). ENSURE THE DESIGN CALCULATIONS AND WORKING DRAWINGS ARE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER. BASE PLATE CAMERA MOUNTING TOP PLATE 1" MATERIALS: ENSURE THE POLE MATERIAL CONFORMS TO ASTM SPECIFICATIONS A595, GRADE A (MIN. YIELD POINT 55 KSI). AS AN ALTERNATE THE POLE (18 SIDED MIN.) MAY BE FORMED FROM STEEL CONFORMING TO ASTM A36 OR A572 GRADE 55. ALL OTHER STEEL CONFORMS TO ASTM SPECIFICATION A709 (AASTHO M270) GRADE 36 OR GRADE 50. ENSURE ALL POLES REGARDLESS OF THICKNESS AND ALL OTHER STEEL PLATES GREATER THAN " THICKNESS MEET THE AASHTO REQUIREMENTS FOR NOTCH TOUGHNESS (CHARPY TESTING) ZONE 2. GALVANIZE THE ENTIRE UNIT OF THE POLE PER ASTM A123 AFTER FABRICATION. POLE " 2 HOLD DOWN HEX NUTS AND 1 FLAT WASHER PER BOLT 1 LEVELING HEX NUT AND 1 FLAT WASHER PER BOLT CONTRACTOR IS RESPONSIBLE TO PROCURE BOLTS/ANCHOR BOLTS, NUTS AND WASHERS AS A PACKAGE FROM THE MANUFACTURER AND TO ENSURE SAFE INSTALLATION. DETAIL B BASE PLATE ENSURE ANCHOR BOLT MATERIALS CONFORM TO ASTM F1554, GRADE 55. GALVANIZE THE ANCHOR BOLTS PER ASTM A153, CLASS C AFTER THREADING FOR THE FULL LENGTH OF THE BOLT, AS WELL AS NUTS AND WASHERS. TOP OF FOUNDATION HIGH STRENGTH BOLTS, NUTS AND WASHERS TO BE GALVANIZED PER ASTM A153 CLASS C. FINISHED GRADE 40’ (TYPE C) PROVIDE STAINLESS STEEL FASTENERS (INCLUDING BOLTS, NUTS AND WASHERS) CONFORMING TO CURRENT ASTM A320, GRADE B8, CLASS 2 (AISI TYPE 304) AND STRAIN HARDENED. ALTERNATE MATERIALS PROPOSED TO BE USED FOR FASTNERS MUST BE PRE-APPROVED SEPERATELY PRIOR TO SUBMISSION OF WORKING DRAWINGS. 1" MAX. FROM THE BOTTOM GALVANIZED SCREEN OF THE LEVELING NUT TO THE TOP OF THE CONCRETE FOUNDATION WITH STAINLESS STEEL ROUND OR MIN. 18 SIDED STEEL TAPERED POLE ALL CONCRETE TO BE "CLASS B" AS DEFINED IN THE NJDOT STANDARD SPECIFICATIONS. NUT, BOLT & FLAT WASHER SKETCH "A" NOTES: 1. ENSURE STEEL POLE CONSISTS OF ONE STEEL SEGMENT AND CONTAINS ONLY ONE LONGITUDINAL SEAM WELD. LAMINATED TUBES ARE NOT PERMITTED. SEE TYPICAL LONGITUDINAL SEAM WELD DETAIL. 2. PROVIDE NEOPRENE DOOR GASKET CEMENTED TO DOOR. 3. PROVIDE A GALVANIZED SCREEN, WRAPPED AROUND THE BASE OF POLE. 4. ENSURE THE GALVANIZED SCREEN HAS NO MORE THAN " OPENINGS AND IS HELD TOGETHER WITH STAINLESS STEEL NUT, BOLT AND FLAT WASHER. (4)-2" DIA. HOLES 5. DO NOT GROUT UNDER THE POLE . 20" DIA. BOLT CIRCLE MINIMUM 60% PENETRATION WELD. A 100% FULL PENETRATION WELD AND GROUND SMOOTH IS REQUIRED FOR: 6. PROVIDE ONE (1) LEVELING HEX NUT, TWO (2) HOLD DOWN HEX NUTS AND TWO (2) FLAT WASHER PER ANCHOR BOLT.(SEE SKETCH A) DETERMINE THE PROPER LENGTH OF THE ANCHOR BOLT FOR 1. A DISTANCE OF 6" AT THE END OF THE BASE. 2. A DISTANCE OF THE SLIP JOINT PLUS 6" AT THE FEMALE END. 20" PROJECTION AND EMBEDMENT. THE CLEARANCE BETWEEN THE TOP OF THE FOUNDATION AND THE BOTTOM OF THE LEVELING NUT NOT TO EXCEED 1". THE PROJECTION LENGTH TO BE A MINIMUM OF 9". VISUALLY INSPECT THE FINAL WELD INSIDE AND OUTSIDE. pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 7. ENSURE WELDING CONFORMS TO THE ANSI/AWS D1.1 STRUCTURAL WELDING CODE-STEEL, WITH NJDOT AMENDMENTS IN NJDOT STANDARD SPECIFICATIONS. ENSURE WELDING INSPECTION AND FULL PENETRATION WELD NONDESTRUCTIVE TESTING CONFORM TO AWS D1.1, UNLESS OTHERWISE SPECIFIED. 20" 8. TYPICAL LONGITUDINAL SEAM WELD SECTION A-A (BASE PLATE) ENSURE THE TIGHTENING PROCEDURE FOR ANCHOR BOLTS CONFORMS WITH SECTION 6.9 OF THE 2005 FHWA " GUIDELINES FOR THE INSTALLATION, INSPECTION, MAINTENANCE AND REPAIR OF STRUCTURAL SUPPORTS FOR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS". (BOLTS NOT SHOWN) 4" X 6" ACCESS DOOR OPENING (SEE DETAIL ON SHEET 2 OF 2) scale= 30.000000:1.00000 J HOOK NOT TO SCALE POLE SEE SKETCH "A" GROUND LUGS ( TO BE LOCATED FOR EASY ACCESS THRU ACCESS DOOR ) 1’-3" " NUT HOLDER 2 REQ. @ 180%%d A " DIA. S.S.BOLTS WITH S.S. WASHERS & NUTS A 3 #8 IN 1" FLEXIBLE CONDUIT TO DISTRIBUTION PANEL JUNCTION BOX LOCATION & SIZE AS SHOWN ON BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 DRILL " DIA. HOLE IN GROUND LUGS ITS-704-14 #1/0 BARE GROUND WIRE CONDUIT REDUCER GROUNDING CLAMP SCREEN GROUNDING BUSHING NEW JERSEY DEPARTMENT OF TRANSPORTATION #8 BARE GROUND BONDING WIRE PLAN SHEETS FINISHED GRADE 1" SEE FOUNDATION (4)- 1" DIA. GALVANIZED ANCHOR BOLTS CONCRETE FOUNDATION GROUNDING BUSHING TYPE CCS DETAIL ITS DETAILS 2’ MAX ANCHOR BOLT ASSEMBLY TWO #1/0 BARE #8 GROUND WIRE DOWN CONDUCTORS NUMBER OF CONDUITS (2 MIN.) AND SIZE SLOPE CAMERA STANDARD TYPE C AS SHOWN ON THE PLAN SHEET. CAMERA SURVEILLANCE SYSTEM CAMERA STANDARD TYPE C DOWN CONDUCTOR " #8 BARE GROUND BONDING WIRE " X 12’ LONG GROUND ROD GROUND LUGS DETAIL LIGHTNING & BONDING DETAIL SHEET 1 OF 2 * * file= GALVANIZED DOOR WITH NEOPRENE GASKET AIR TERMINAL (SEE DETAIL) 4" PROVIDE A SINGLE CABLE WITH ENOUGH "SAG" FOR DRAINAGE OF WATER CAMERA HOUSING PARK STAND (TYP.) 1’-6" PAN AND TILT UNIT REPLACE THE EXISTING HANDHOLE COVER WITH ENCLOSURE AND UTILIZE EXISTING THREADED HOLES. PROVIDE AND INSTALL WATERTIGHT NEOPRENE GASKET BETWEEN HANDHOLE AND ENCLOSURE. TYP. "Y" "Y" CAMERA HOUSING CAMERA MOUNTING TOP PLATE ACCESS DOOR FRAME (2"W X " THK. BAR) MIN. 6" J-HOOK CURVATURE TO PROVIDE FREE MOVEMENT OF THE CAMERA STEEL POLE 5" WATERTIGHT NEMA 4X FIBERGLASS ENCLOSURE, 6" X 6" X 4" WITH LATCH PAN AND TILT UNIT HINGED COVER AND S.S. CONTINUOUS HINGE ALONG THE LENGTH OF THE COVER. FROM BOTTOM OF CAMERA MOUNTING TOP PLATE TO CENTER OF ENCLOSURE 1’-0" (2)-" DIA. X 1" S.S. BOLT WITH S.S. HEX NUT (TYP.) CABLE GUIDE (TYP.) 9" 2" SUPPORT GRIP (2) -" NUT HOLDER @ 180%%d WITH FASTENERS FOR GROUND LUGS FOR CABLE CAMERA STANDARD CGB FITTING(S) AND GROMMET (BOTTOM OF CLOSURE) POLE SINGLE COMPOSITE CABLE 6" ACCESS DOOR DETAIL ACCESS DOOR FRAME DETAIL (TO BE SHIPPED PRE-ASSEMBLED, POLE NOT SHOWN) (4" X 6" CLEAR OPENING) 6" CAMERA MOUNTING AND CABLE DETAILS POLE / TUBE (TYP.) 1’-0" FILLET WELD SIZE " MIN. IF THE WALL THICKNESS IS GREATER THAN ", WELD SIZE TO BE EQUAL TO WALL THICKNESS OF POLE. " W X" THK. X 1" LONG ACCESS DOOR HOLE FRAME (2" W X " THK. BAR) MIN. 8 GAUGE STAINLESS STEEL (4 PER CLAMP)-" DIA.- S.S. BOLTS A36 GALVANIZED ANGLE NOTE: WELD THE ANGLE ALUMINUM AIR TERMINAL PRIOR TO GALVANIZING THE POLE. " DIAMETER WITH TWO S.S. WASHERS, ONE LOCK WASHER AND ONE NUT PER BOLT. SECTION A-A " 1" (2)-" DIA. X 1" LONG S.S. BOLT WITH S.S. HEX NUT \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE " pen table= 45^ AIR TERMINAL 2 " SELECT ANGLE TO KEEP VERTICAL WHEN CLAMPED TO POLE " AIR TERMINAL CLAMPS (3 REQUIRED) GALVANIZED DOOR WITH NEOPRENE GASKET 8" BENDING RADIUS A A NEOPRENE 2" 2" TO 6" MAX. GASKET ONE PIECE CONTINUOUS 1’-3" PIANO STYLE S.S. PLAIN SURFACE HINGE W/ WELDED PIN (5" LONG) (4)-#10-32 (NF) X 1" LONG S.S. BOLTS WITH S.S. FLAT " scale= 30.000000:1.00000 WASHERS AND S.S. HEX NUTS AIR TERMINAL CLAMP DETAIL AIR TERMINAL DETAIL ALL BRASS CCL LOCK #A15481RS-LS KEYED ALIKE FOR KEY #2, WITH DUST CAP AND TWO KEYS PER LOCK. NOT TO SCALE SECTION Y-Y ITS-704-15 BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS NOTES: 1. INSTALL ALL WIRING INSIDE THE POLE AND PROVIDE STRAIN RELIEF FOR ALL CAMERA CABLES. 2. SUPPORT CAMERA CABLE WITH SEPARATE GRIP. CAMERA SURVEILLANCE SYSTEM CAMERA STANDARD TYPE C 3. PROVIDE AND INSTALL APPROVED INTERNAL TWISTLOCK CONNECTORS. 4. AIR TERMINAL POSITIONING NOT TO OBSTRUCT THE PREDETERMINED FIELD OF VIEW AND MUST PROVIDE CLEAR ACCESS TO NEMA ENCLOSURE COVER. file= SHEET 2 OF 2 * * FOUNDATION CSS NUMBER (2 MIN.), LOCATION & SIZE OF CONDUIT AS SHOWN ON PLAN SHEETS 4’-3" 3" COV. #13 BARS BOLT CIRCLE SEE TABLE ANCHOR BOLTS-(4) 1" X 90" WITH (12) HEX NUTS AND (8) FLAT WASHERS USE 20-#22 BARS 3" TYP. FINISHED GRADE PROJECTION LENGTH OF ANCHOR BOLTS AS RECOMMENDED BY MANUFACTURER WITH LEVELING NUT TYPE INSTALLATION 1’-6" LAP 1" CHAMFER (TYP.) 2" MAX. ANCHOR BOLTS #13 BARS @ 9" CENTER TO CENTER 10’ CIRCULAR FOOTING D= 4’-3" 6" HOOK (TYP.) CLASS B CONCRETE 4’-3" "BOLT CIRCLE TABLE" STANDARD TYPE POLE HEIGHT ANCHOR BOLT CIRCLE DIAMETER 75’ 30" B 55’ 30" C 40’ 20" scale= 30.000000:1.00000 pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE A NOT TO SCALE ITS-704-16 NOTES: HOT DIP GALVANIZE ANCHOR BOLTS PER ASTM A153 FOR THE FULL LENGTH OF THE BOLT AFTER THREADING. BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 1. NEW JERSEY DEPARTMENT OF TRANSPORTATION GENERAL DESIGN SPECIFICATIONS: 2. PROCURE ANCHOR BOLTS MEETING ASTM F 1554 GRADE 55 STEEL FROM THE MANUFACTURER OF CAMERA STANDARD. ANCHOR BOLTS EMBEDMENT LENGTH, THREADED LENGTH AND ITS DETAILS CONCRETE DESIGN STRESS: PROJECTION LENGTH ARE TO BE DETERMINED AND PROVIDED BY THE MANUFACTURER. SPECIFIED COMPRESSIVE STRENGTH (f’c) (CLASS B)..........................3,000 PSI EXTREME FIBER COMPRESSIVE STRESS (fc)...........................................1,200 PSI 3. LUBRICATE ANCHOR BOLT PROJECTION PORTION BEFORE MOUNTING THE POLE. REINFORCEMENT STEEL DESIGN STRESS: 4. FOR ANCHOR BOLT TIGHTENING PROCEDURE SEE NOTE 11 ON CSS CAMERA STANDARD TYPE A YIELD STRENGTH (fy) (A615, GRADE 60)....................................................60 KSI TENSILE STRENGTH (ts)...............................................................................90 KSI AND B DETAIL, SHEET 1 OF 3 OR NOTE 9 ON CSS CAMERA STANDARD TYPE C DETAIL, SHEET 1 OF 2. 5. CAMERA SURVEILLANCE SYSTEM FOUNDATION CSS ALL BAR SIZES ARE DESIGNATED IN SOFT METRIC SIZES. * * file= DOOR FRAME WITH CONTINUOUS NEOPRENE GASKET SECURED TO CIRCUIT # (TYP.) NEMA 3R CABINET DOOR TO INSURE DUST-TIGHT WEATHER-PROOF PROTECTION POWER, VIDEO AND COMMUNICATIONS ONE PIECE STN. STL. HINGE SECURED TO DOOR WITH 1/4" DIA. RIVETS AND TO CABINET WITH (8) 1/4" -20 NC X 1/2" LG. STN. STL. FL. HD. SCREWS METER FOR 100 AMP 120/240V SINGLE PHASE, 3 WIRE COMPOSITE CABLE TO CAMERA LOWERING DEVICE CONNECTOR THROUGH POLE & 5 5 MAST ARM FOR CAMERA STANDARDS TYPE LIGHT SWITCH WITH ENCLOSURE T12 LIGHT A & B OR TO CAMERA CONNECTOR FOR CAMERA CAMERA STANDARD TYPE C THERMOSTATICALLY CONTROLLED FAN 100 CFM S ELECTRONIC EQUIPMENT RECEPTACLES (TYP.) 24VAC/ 100VA " THICK ALUMINUM RAIN TIGHT DISCONNECT WHEN REQUIRED BY UTILITY CO. 24 AC IN POWER MOUNTED FULL WIDTH AND LENGTH OF CABINET (ONE COAT BLACK PAINT) WITH (4) 1/4" -20NC X 1 1/2" LG. STN. STL. FL. HD. SCREWS SUPPLY 3 VIDEO LAN COMMUNICATIONS EQUIPMENT COMMUNICATIONS EQUIPMENT 10/100 VIDEO ENCODER BASE T 24 AC DATA 3’-10" MIN. OUT DOOR SIZE 2’-3" X 3’-4" REMOTE SLIDE OUT DRAWER DATA (PTZ) VIDEO OUT DATA VIDEO IN PORT DATA IN " AIR SPACE 2 ADJUSTABLE TO COMMUNICATIONS 4 ALUMINUM SHELVES 2’-4"W X 1’-2"D ONE WITH A SLIDE OUT DRAWER NETWORK 24VAC 100VA VIDEO CODE CAMERA ENCODER SERVICE CONDUIT FOR SIZE SEE ITS PLANS DATA TRANSLATOR POWER LOUVERS REMOTE DATA PORT 3’-10" SUPPLY CODE DATA GFCI TRANSLATOR IN DATA OUT PROVIDE STN. STL. FASTENERS FOR GROUNDING 7 2’-4" MIN. 1’-4" MIN. PD FRONT ELEVATION SIDE ELEVATION 12-PORT FIBER OPTIC PATCH PANEL COMMUNICATIONS BLOCK DIAGRAM 120/240 POWER 8" CONVENIENCE RECEPTACLE DISTRIBUTION 6" 400 WATT PANEL 1’-8" MAX. 1’-4" MIN. 8 (GFCI) HEATER POWER DISTRIBUTION PANEL WITH BREAKER/CIRCUIT # (TYP.) THERMOSTAT 6" 2 POLE 8" MAIN BREAKER WITH NEMA 1 ENCLOSURE MB 1’-2" 1 GROUNDING BAR 2 1’-2" NO.8 GROUND WIRE ( TYP ) 3 4 5 6 7 8 2’-8" MAX. 2’-4" MIN. BOTTOM VIEW & ANCHOR BOLT LAYOUT CONDUITS TO ADJACENT JB SEE PLANS FOR NUMBER AND SIZE (MINIMUM 2-2") GROUND ROD," DIA. COPPER, 12’ LONG \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 2’-4" MIN. pen table= CABINET EQUIPMENT LAYOUT (TYP.) #6 THHW AWG. 600V WIRE PD NOTES: 1. ENSURE CABINET AND CABINET DOOR IS FABRICATED FROM SHEET ALUMINUM " THICK, 5052-H32 ALLOY, UNPAINTED. 2. SUPPLY WITH EACH CABINET (2) ANCHOR BOLTS "- 10NC X 15" LG. STL. WITH GALVANIZED 3" COUPLING (2) STAINLESS STEEL 1" O.D. X " THK. FLAT WASHERS AND (2)" - 10NC X 3" LG. STAINLESS STEEL CAP SCR. SECURE CABINET DOOR WITH A SUB-TREASURY LOCK NO. 0357S AND KEYPAD ALIKE FOR KEY NO. 5 AVAILABLE FROM THE AMERICAN HARDWARE CO. NEW BRITAIN, CONN., OR A TUMBLER LOCK NO. 15481 ARS AND KEYPAD ALIKE FOR NO. 2 AVAILABLE FROM CORBIN LOCK CO. NEW BRITAIN, CONN. scale= 30.000000:1.00000 3. 4. 5. SECURE CABINET LOCK TO THE DOOR WITH #10 - 24 X 1 " ROUND HEAD (STN. STL.) MACHINE SCREWS. 120V EXPOSED WIRING IS NOT PERMITTED. ENCASE WIRING TO ENCLOSURES AND OUTLETS IN LIQUID TIGHT FLEXIBLE CONDUIT AND FITTINGS INSIDE THE CABINET. 6. ENSURE ALL EQUIPMENT IS UL & NEMA LISTED FOR OUTDOOR INSTALLATION INSIDE NEMA 3R CABINET. 7. LABEL ALL ELECTRICAL RECEPTACLES EXCEPT GFCI AS "ELECTRONIC EQUIPMENT ONLY". LABEL GFCI RECEPTACLE AS "CONVENIENCE RECEPTACLE". 8. FOR BREAKER RATINGS, SEE TABLE A. 9. PROVIDE SURGE SUPPRESSION TO THE DATA LINES. 10. METER, RAIN TIGHT DISCONNECT SWITCH AND SERVICE CONDUIT ARE NOT REQUIRED IF ELECTRIC SERVICE IS CONNECTED TO ANOTHER LOAD CENTER AND NOT TO UTILITY COMPANY POWER SOURCE. TABLE A MB BREAKER RATING BREAKERS # FUNCTION TRIP RATING (AMPS) MB MAIN BREAKER 60 AMP 60 1 RECEPTACLE INSIDE CAMERA POLE BASE 15 2 SPARE 15 3 ELECTRONIC EQUIPMENT RECEPTACLE 15 4 ELECTRONIC EQUIPMENT RECEPTACLE 15 5 FAN & LIGHT 15 6 SPARE 15 7 CONVENIENCE RECEPTACLE (GFCI) 15 8 HEATER 20 METER TO BE PROVIDED BY UTILITY CO. SN #6 THHW AWG. 600V WIRE RAIN TIGHT DISCONNECT WHEN REQUIRED BY UTILITY CO. SERVICE 120/240V, 3 WIRE, 1-PHASE #2 AWG STANDARD 600V WIRE NOT TO SCALE POWER DISTRIBUTION DIAGRAM ITS-704-17 BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 NEW JERSEY DEPARTMENT OF TRANSPORTATION 11. WHERE REQUIRED, ENSURE METER PAN CONFORMS TO UTILITY COMPANY’S HEIGHT REQUIREMENTS. ITS DETAILS CAMERA SURVEILLANCE SYSTEM CONTROLLER CAMERA * * file= S.S. U-BOLTS (TYP.) 2" RMC SIGN PANEL 2" RMC (2)-" S.S. ’U’ BOLTS W/F.W., L.W. & NUTS SIGN STRUCTURE TRUSS CAP SIGN STRUCTURE TRUSS (TYP.) 8" READER ANTENNA 1" (2)-" S.S. BOLTS W/L.W. AS REQD. (2)-" S.S. ’U’ BOLTS W/F.W. , L.W. & NUTS 5^ TO 15^ H.D.G. STEEL BRACKET DETAIL "C" 1" NOTES: 1. APPROXIMATE LOCATIONS OF READER ANTENNA, CONDUIT, AND JUNCTION BOX ARE SHOWN ON THE PLAN SHEETS. THE EXACT PLACEMENT IN THE FIELD TO BE VERIFIED BY THE CONTRACTOR WITH TRANSCOM. 2. ENSURE ALL FASTENERS INCLUDING BOLTS, U-BOLTS, NUTS AND WASHERS ARE STAINLESS STEEL AND CONFORMS TO CURRENT ASTM SPECIFICATION A320, GRADE B8, CLASS 2 (ANSI TYPE 304) WITH NO. 4 FINISH AND STRAIN HARDENED. 3. SUBMIT DETAIL PLANS FOR MOUNTING ASSEMBLIES FOR REVIEW AND APPROVAL BY THE NJDOT. 4. CONDUIT ROUTING ON THE STRUCTURE, AND BETWEEN STRUCTURE OR POLE AND UTILITY POLE LOCATION MAY BE MODIFIED AS REQUIRED BY THE FIELD CONDITIONS SUBJECT TO THE APPROVAL OF THE NJDOT. 5. A SEPERATE GROUND IS REQUIRED FOR TTS EQUIPMENT. SEE READER CABINET DETAIL SHEET REGARDING GROUND REQUIRMENTS. 6. NO WELDING OR CUTTING OF EXISTING SIGN STRUCTURE WILL BE PERMITTED. SIGN STRUCTURE TRUSS 7. MAINTAIN THE MINIMUM BENDING RADIUS RECOMMENDED BY THE COAXIAL CABLE MANUFACTURER WHILE INSTALLING CONDUIT AND CABLE. 2" RMC 8. ENSURE CONDUIT PENETRATIONS FOR THE READER CABINETS ARE EXCLUSIVELY MADE THROUGH THE BOTTOM SURFACE OF THE CABINET TO PREVENT WATER AND MOISTURE FROM PENETRATING INTO ELECTRONIC EQUIPMENT. 9. WELDING IS NOT PERMITTED TO INSTALL THE TRANSMIT EQUIPMENT ON THE SIGN STRUCTURE. 10. MOUNT READER ANTENNAS WITH WEEP HOLE POSITIONED TO PERMIT CONTINUOUS MOISTURE DRAINAGE. 11. ONLY GALVANIZED RMC IS PERMITTED TO BE ATTACHED ON EXISTING STEEL STRUCTURES. DIRECTION OF TRAFFIC TYP. READER ANTENNA MOUNTING DETAIL "A" TOP VIEW (2)-3/8 " S.S. ’U’ BOLTS W/F.W., L.W. & NUTS SIGN STRUCTURE TRUSS SIGN STRUCTURE TRUSS (2)-" S.S. ’U’ BOLTS W/F.W., L.W. & NUTS S.S. U-BOLTS (TYP.) CAP SIGN PANEL AS REQD. H.D.G. STEEL BRACKET 5^ TO 15^ DETAIL "P" (2)-3/8 " S.S. BOLTS 2" RMC READER ANTENNA H.D.G. STEEL BRACKET DIRECTION OF TRAFFIC (2)-" S.S. BOLTS W/L.W. ELEVATION TYP. READER ANTENNA MOUNTING DETAIL "B" DETAIL "C" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 2" RMC REAR CENTER MEMBER TRI CHORD SIGN STRUCTURE " S.S. BANDS " S.S. BAND RMC CONDULET SEE READER ANTENNA MOUNTING DETAIL "B" " S.S. BANDS SEE READER ANTENNA MOUNTING DETAIL "A" 2" RMC REAR BOTTOM MEMBER RMC CONDULET " S.S. BANDS 30.000000:1.00000 2" RMC scale= (2)-1/2 " S.S. "U" BOLTS W/F.W., L.W. & NUTS 2" RMC READER CABINET READER CABINET BOTTOM OF SIGN HANGER ARMS " S.S. BAND ELECTRICAL CONDUITS NOT TO SCALE (2) -" S.S. "U" BOLTS " S.S. BANDS ITS-704-18 ELECTRICAL CONDUITS NEW JERSEY DEPARTMENT OF TRANSPORTATION BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 GROUND AT NEAREST JB GROUND AT NEAREST JB ITS DETAILS TRAVEL TIME SYSTEM TTS DETECTOR TYPE A TYP. ANTENNA INSTALLATION ON TRICHORD SIGN STRUCTURE TYP. ANTENNA INSTALLATION ON SIGN STRUCTURE SHEET 1 OF 2 * * file= STEEL BEAM WEB STEEL BEAM WEB 2" RMC (2)-HOLES FOR ’U’ BOLT 2" RMC 6" (2)-3/8 " S.S. BOLTS W/ F.W. & L.W. NOTES: 2" 3" (2) -" S.S. BOLTS W/ F.W. & L.W. 6" " S.S. ’U’ BOLT W/ F.W. & L.W. " S.S. ’U’ BOLT W/ F.W. & L.W. 4" 1. ENSURE ALL FASTENERS, INCLUDING BOLTS, U-BOLTS, NUTS AND WASHERS ARE STAINLESS STEEL AND CONFORMS TO ASTM SPECIFICATION A320, GRADE B8, CLASS 2 (ANSI TYPE 304) WITH NO. 4 FINISH, AND STRAIN HARDENED. 2. ENSURE ALL SUPPORT MEMBERS, PLATES AND SHAPES ARE GALVANIZED. AFTER COMPLETE FABRICATION, HOT-DIP GALVANIZE EACH STEEL SUPPORT ASSEMBLY CONFORMING TO THE REQUIREMENTS OF AASHTO M270 (ASTM A709) GRADE 50W. 3. WELDING IS NOT PERMITTED TO INSTALL THE TRANSMIT EQUIPMENT ON THE BRIDGE STRUCTURE. 4. THE DETAILS FOR CONDUIT SUPPORT BRACKET SHOWN ON THIS SHEET ARE CONCEPTUAL. SURVEY EACH TRANSMIT SITE AND SUBMIT SHOP 1" 2" " " THK. H.D.G. STEEL BRACKET STEEL STIFFENER " THK. H.D.G. STEEL BRACKET " THK. H.D.G. STEEL BRACKET DETAIL "D" DRAWINGS TO TRANSCOM FOR APPROVAL BEFORE SEEKING APPROVAL FROM SECTION "A-A" NJDOT. SECTION "B-B" { OF STEEL WEB UNDERSIDE OF STRUCTURE { OF STEEL WEB { OF STEEL WEB A (2) -" S.S. BOLTS W/F.W. & L.W. B (2) -" S.S. BOLTS W/F.W. & L.W. B 6" STEEL STIFFENER 2" RMC 4" ADJUST THE READER ANTENNA MOUNTINGS AND POSITION THE READER ANTENNAS SUCH THAT THE MINIMUM VERTICAL UNDER CLEARANCE IS NOT LESS THAN THE EXISTING CONDITIONS. NO CUT IN THE EXISTING STRUCTURE OR PAVEMENT IS ALLOWED TO AVOID REDUCING CLEARANCE. 7. MOUNT READER ANTENNAS WITH WEEP HOLE POSITIONED TO PERMIT CONTINUOUS MOISTURE DRAINAGE. 8. ENSURE MAXIMUM SPACING BETWEEN ADJACENT CONDUIT SUPPORTS IS 4 FEET UNLESS OTHERWISE APPROVED BY THE ENGINEER. 9. POSITION THE PROPOSED CONDUIT SUPPORTS SUCH THAT THE VERTICAL UNDER CLEARANCE IS NOT LESS THAN THE EXISTING CONDITION. 10. FURNISH AND INSTALL APPROVED EXPANSION JOINT FITTINGS ON BRIDGES AND OTHER STRUCTURES, AT LOCATIONS WHERE CONDUITS CROSS OVER EXPANSION JOINTS. FURNISH AND INSTALL EXPANSION FITTINGS AS RECOMMENDED BY THE MANUFACTURER. SUBMIT CONDUIT EXPANSION JOINT SPACING TO THE ENGINEER FOR APPROVAL. 11. LABEL ALL CONDUIT RUNS AND JUNCTION BOXES WITH WEATHERPROOF MARKER TAPE INDICATING THE PURPOSE AND VOLTAGE. LABEL CONDUIT RUNS EVERY 50’-0"AND AT WALL PENETRATIONS. 12. INSTALL ALL WIRING (POWER, AND COMMUNICATIONS, ETC.) IN GALVANIZED CONDUITS. CONDUIT SIZE AS INDICATED. 13. ENSURE ALL CONDUITS, EYS FITTINGS AND CONDULETS ARE GALVANIZED. 14. PLACE ALL U BOLTS SHOWN AS DRILL AND ANCHOR WITH ADHESIVE IN A CORE DRILLED HOLE WITH A DIA." WIDER THAN THE U-BOLT AND ANCHORED WITH APPROVED ADHESIVE ANCHOR SUCH AS "HILTI HVA ADHESIVE ANCHOR". 15. AVOID CONFLICTS WITH THE STRUCTURAL STEEL COMPONENTS OF THE BRIDGE, INCLUDING THE EXISTING ABUTMENT WALL REINFORCEMENTS WHEN DRILLING FOR PLACEMENT OF ANCHOR BOLTS. PRESERVE THE STRUCTURAL INTEGRITY OF THE BRIDGE COMPONENTS. H.D.G. STEEL BRACKET (TYP.) SEE DETAIL "D" 8" 8" 6. 2" RMC 5" 6" FIELD VERIFY EXISTING STRUCTURE CONDITIONS AND DIMENSIONS RELATIVE TO PROPOSED CONDUIT SUPPORT LOCATIONS PRIOR TO FABRICATION AND CONSTRUCTION. UNDERSIDE OF STRUCTURE UNDERSIDE OF STRUCTURE A (2) -" S.S. BOLTS W/F.W. & L.W. 5. 2" RMC H.D.G. STEEL BRACKET (TYP.) INTERIOR STEEL GIRDER (TYP.) " S.S. ’U’ BOLT W/F.W. & L.W. (TYP.) INTERIOR STEEL GIRDER (TYP.) " S.S. ’U’ BOLT W/F.W. & L.W. (TYP.) DETAIL "G" STEEL BEAM H.D.G. STEEL BRACKET (TYP.) DETAIL "I" DETAIL "H" SEE DETAIL "E" SEE DETAIL "F" INTERIOR STEEL GIRDER (TYP.) " S.S. ’U’ BOLT W/F.W. & L.W. (TYP.) STEEL BEAM H.D.G. STEEL BRACKET 2" RMC H.D.G. STEEL BRACKET 2" RMC (2)-2-HOLE S.S PIPE STRAPS 2’-6" DRILL THRU BEAM DRILL THRU BEAM 2’-6" ’U’ BOLT W/F.W., L.W. AND DOUBLE NUTS 6" 6" ’U’ BOLT W/F.W., L.W. AND DOUBLE NUTS 4" 2" RMC 4" 4" TOP OF ANTENNA 4" TOP OF ANTENNA 1’-0" READER ANTENNA (2) - " S.S. ’U’ BOLTS W/ F.W. & DOUBLE NUTS 1’-0" (2) -" SS BOLT, FW AND DOUBLE NUTS READER ANTENNA 5^ TO 15^ AS REQUIRED READER ANTENNA (2) -" SS BOLT, FW AND DOUBLE NUTS 5^ TO 15^ " S.S. SET SCREW W/ H.H. AS REQUIRED DETAIL "E" SHOWN DETAIL "F" OPPOSITE HAND DIRECTION OF TRAFFIC pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE DIRECTION OF TRAFFIC TYP. ANTENNA MOUNTING ON STEEL GIRDER (SEE DETAILS G, H AND I) FACE OF CONCRETE ABUTMENT WALL STEEL GIRDER 2" RMC WIRE OPENING RUBBER GROMMET scale= 30.000000:1.00000 6" RIGHT ANGLE CONDUIT, CONDULET AND EYS FITTINGS DRILL AND ANCHOR WITH ADHESIVE (TYP.) 2" RMC SEE DETAIL "J" " DIA. U-BOLT @ 4’-0" MAX. SPACINGS FACE OF CONCRETE ABUTMENT OR PARAPET BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:49 " THICK STEEL PLATE TYPICAL CONDUIT ATTACHMENT AT ABUTMENT JUNCTION BOX 2" RMC WITH " COAXIAL CABLES NOT TO SCALE WALL MOUNTED JUNCTION BOX 12" x 10" x 8" ITS-704-19 NEW JERSEY DEPARTMENT OF TRANSPORTATION ABUTMENT S.S. CLAMPS " S.S. BOLT W/L.W. (TYP.) TYPICAL JUNCTION BOX MOUNTING AT ABUTMENT TYPICAL OVERPASS/ BRIDGE INSTALLATION ITS DETAILS DETAIL "J" JUNCTION BOX TRAVEL TIME SYSTEM TTS DETECTOR TYPE A SHEET 2 OF 2 * * file= EXISTING SIGN POST EXISTING SIGN POST STRUCTURE STRUCTURE CONCRETE FOUNDATION NOTES: 2" 2’-10" 2" RMC TO READER 2" RMC TO READER ANTENNAS ANTENNAS 7.5" 1’-8" 2’-0" 7.5" 1. FABRICATE CABINET WITH 14 GAUGE TYPE 304 STAINLESS STEEL. 2. ENSURE DOOR IS NEMA TYPE 3R WITH CELLULAR NEOPRENE GASKET, AND HINGES ARE 14 GAUGE S.S., TYPE PIANO (CONTINUOUS). 3. PROVIDE CORBIN TYPE LOCK WITH 2 KEYS AND A THREE POINT LOCKING SYSTEM, THAT SECURES THE TOP, BOTTOM AND CENTER. 4. PROVIDE VENT HOLES ON THE UNDER SIDE OF THE COVER AND SLOTS ON THE DOOR TO CREATE A NATURAL FLOW OF AIR THAT HAS A COOLING EFFECT ON ELECTRICAL EQUIPMENT. COVER THE SLOTS WITH A FILTER ON THE INSIDE OF THE DOOR TO PREVENT DUST AND INSECTS FROM ENTERING THE CABINET. 5. PROVIDE COOLING FAN AND HEATER WITH ADEQUATE CAPABILITIES. 6. PROVIDE ONE REMOVABLE " ALLEN KEY. 7. ENSURE DOOR CATCH HOLDS THE DOOR OPEN AT 90^ AND 180^. 8. ENSURE CONTINUOUS HINGE LEAVES ARE NOT EXPOSED EXTERNALLY WHEN DOOR IS CLOSED. 9. FURNISH AND INSTALL GROUND RODS, GROUND WIRE AND FITTINGS IN ACCORDANCE WITH NEC AND STANDARD SPECIFICATIONS. 10. ENSURE RACK IS RS-310-C EIA STANDARD. 11. TERMINATE THE RG-58 RIGHT ANGLE CONNECTORS WITH 50 OHM TERMINATORS. 12. ENSURE CONDUIT PENETRATION FOR THE READER CABINET IS EXCLUSIVELY MADE THROUGH THE BOTTOM SURFACE OF THE CABINET TO PREVENT WATER AND MOISTURE FROM PENETRATING INTO ELECTRONIC EQUIPMENT. 13. NO OPENING IS PERMITTED IN THE CABINET FLOOR OTHER THAN SEALED CONDUIT ENTRIES. 14. INSTALL READER CABINET AND COORDINATE WITH TRANSCOM INC., FOR SETTING UP READER AND ANTENNA. 15. CAP 2" RMC, FOR FIBER CONNECTION 6" FROM THE FOUNDATION IF FIBER IS NOT INSTALLED. 16. PROVIDE AND INSTALL NO. 6 AWG GROUND WIRE AND GROUND ANCHOR BOLT 12" LONG " 10NC THD. FREE FIT MAT’L - STEEL PER ASTM A-576 (SEE NJDOT STANDARD DETAILS FOR ANCHOR BOLT ASSEMBLY) 2’-1" 2’-6" " S.S. BAND S.S. STUDDED NUT W/F.W & L.W. (TYP. OF 4) S.S. CHANNEL 1 - " S.S. ’U’ BOLT W/F.W & NUT SIZE AS REQUIRED 2’-6" CONCRETE PAD 1’-0" READER CABINET (SEE DETAILS) 1’-0" 4’-10" " S.S. " S.S. BAND BAND PLAN 1 - " S.S. ’U’ BOLT W/F.W & NUT SIZE AS REQUIRED TYP. DETAILS FOR GROUND MOUNTED READER CABINET ON FOUNDATION TTS, TYPE A 2" RMC CONDULET 2" RMC CONDULET " S.S. BANDS 2’-6" 2’-0" 2’-0" EXISTING SIGN STRUCTURE FOUNDATION READER CABINET (SEE DETAILS) 2-2" RMC WITH 1/C #6 AWG GROUND WIRE (ONE 2" RMC FOR POWER AND ONE FOUR (4) " 2" RMC FOR FIBER) CONCRETE ANCHOR BOLTS CONCRETE PAD 2" 4" 2’-0" CONCRETE CLASS B 2-2" RMC 1’-0" (ONE FOR POWER AND ONE FOR FIBER) 3’-0" " DIA. x 12’-0" LONG GROUND ROD SIDE VIEW 2" RMC TO READER ANTENNAS SEE ITS PLAN IN ACCORDANCE WITH NEC REQUIRMENTS. ELEVATION 17. 2’-10" PROVIDE AN ANTENNA EXTENSION TO OBTAIN MAXIMUM WIRELESS SIGNAL RECEPTION / TRANSMISSION. SUBMIT MOUNTING DETAILS. TYP. DETAILS FOR POST MOUNTED READER CABINET ON EXISTING SIGN STRUCTURE ELEVATION SWITCH PLATE CABINET ASSEMBLY EIA RAIL FAN PANEL GASKET SUPPORT TOP DOOR ASSEMBLY CONCRETE / BRICK WALL " CONCRETE ANCHOR LOCK BRACKET pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 1" SS CHANNEL CORBIN LOCK 1" SS CHANNEL READER CABINET 8-32 SCREW (SEE DETAILS) #8 LOCK WASHER #8 FLAT WASHER FILTER 3’-7" HINGE " CONCRETE ANCHOR S.S. STUDDED CHANNEL NUT 4-HOLES IN BACK OF READER CABINET FILTER SPRING CONDUIT STRAP AND BACK STRAP C C 2’-6" 2" RMC TO READER ANTENNAS 1’-8" 30.000000:1.00000 FILTER BRACKET scale= 2" RMC TO READER ANTENNAS DOOR HOOK ARM 4’-0" CONDULET SIDE VIEW 4’-0" 2-2" RMC NOT TO SCALE ELEVATION GROUND BRACKET ITS-704-20 UNISTRUT BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:50 NEW JERSEY DEPARTMENT OF TRANSPORTATION 2-2" RMC (ONE FOR POWER AND ONE FOR FIBER) AUTO DOOR CHANNEL EIA RAIL SUPPORT ELEVATION ITS DETAILS SIDE VIEW TYP. DETAILS FOR CONCRETE/BRICK WALL MOUNTED READER CABINET * TYP. READER CABINET DETAILS SECTION C-C file= TRAVEL TIME SYSTEM CONTROLLER TTS & FOUNDATION TTS TYPE A * DOOR FRAME WITH CONTINUOUS NEOPRENE GASKET SECURED TO DOOR TO INSURE DUST-TIGHT WEATHER-PROOF PROTECTION CIRCUIT # (TYP.) NEMA 3R CABINET ONE PIECE STN. STL. HINGE SECURED TO DOOR WITH 1/4" DIA. RIVETS AND TO CABINET WITH (8) 1/4" -20 NC X 1/2" LG. STN. STL. FL. HD. SCREWS METER FOR 100 AMP 120/240V SINGLE PHASE, 3 WIRE 7 7 LIGHT SWITCH WITH ENCLOSURE T12 LIGHT THERMOSTATICALLY CONTROLLED FAN 100 CFM 1 2 S ELECTRONIC EQUIPMENT RECEPTACLES (TYP.) RAIN TIGHT DISCONNECT WHEN REQUIRED BY UTILITY CO. SEE NOTE #10 BREAKER/CIRCUIT # (TYP.) POWER DISTRIBUTION PANEL 3 4 5 6 7 8 " THICK ALUMINUM MOUNTED FULL 1 WIDTH AND LENGTH OF CABINET WITH (4) 1/4" -20NC X 1 1/2" LG. STN. STL. FL. HD. SCREWS COMMUNICATIONS EQUIPMENT AS PER SPECIAL PROVISION #6 THHW AWG. 600V WIRE 3’-10" MIN. DOOR SIZE 27" X 40" SLIDE OUT DRAWER PD " AIR SPACE 2 ADJUSTABLE ALUMINUM SHELVES 2’-4"W X 1’-2"D, ONE WITH A SLIDE OUT DRAWER MB 2 ELECTRONICS EQUIPMENT AS PER SERVICE CONDUIT FOR SIZE SEE ITS PLANS SPECIAL PROVISION 3’-10" METER TO BE PROVIDED BY UTILITY CO. SN LOUVERS #6 THHW AWG. 600V WIRE GFCI PROVIDE STN. STL. FASTENERS FOR GROUNDING RAIN TIGHT DISCONNECT WHEN REQUIRED BY UTILITY CO. SERVICE 120/240V, 3 WIRE, 1-PHASE #2 AWG STANDARD 600V WIRE 3 2’-4" MIN. 1’-4" MIN. PD POWER DISTRIBUTION DIAGRAM FRONT ELEVATION SIDE ELEVATION 12-PORT FIBER OPTIC PATCH PANEL 8" 120/240 POWER DISTRIBUTION PANEL 14 CKTS. 6" 400 WATT 1’-8" MAX. 1’-4" MIN. 8 CONVENIENCE RECEPTACLE (GFCI) HEATER WITH THERMOSTAT 6" 2 POLE MAIN BREAKER WITH NEMA 1 ENCLOSURE 8" TABLE A MB GROUNDING BAR BREAKER RATING 1’-2" 1’-2" NO.8 GROUND WIRE (TYP.) BREAKERS # 2’-8" MAX. 2’-4" MIN. BOTTOM VIEW & ANCHOR BOLT LAYOUT CONDUITS TO ADJACENT JB SEE PLANS FOR NUMBER AND SIZE (MINIMUM 2-2") \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE CABINET TYPE "M" - FABRICATED GROUND ROD," DIA. COPPER, 12’ LONG TRIP RATING FUNCTION (AMPS) MB MAIN BREAKER 60 AMP 60 1 ELECTRONIC EQUIPMENT RECEPTACLE 15 2 ELECTRONIC EQUIPMENT RECEPTACLE 15 3 CONVENIENCE RECEPTACLE (GFCI) 15 4 SPARE 5 SPARE 15 6 SPARE 15 7 FAN & LIGHT 15 8 HEATER 20 15 pen table= 2’-4" MIN. CABINET EQUIPMENT LAYOUT (TYP.) NOTES: ENSURE CABINET AND CABINET DOOR IS FABRICATED FROM SHEET ALUMINUM " THICK, 5052-H32 ALLOY, UNPAINTED. 2. SUPPLY WITH EACH CABINET (2) ANCHOR BOLTS "- 10NC X 15" LG. STL. WITH GALVANIZED 3" COUPLING (2) STAINLESS STEEL 1" O.D. X " THK. FLAT WASHERS AND (2)" - 10NC X 3" LG. STAINLESS STEEL CAP SCR. 3. SECURE CABINET DOOR WITH A SUB-TREASURY LOCK NO. 0357S AND KEYPAD ALIKE FOR KEY NO. 5 AVAILABLE FROM THE AMERICAN HARDWARE CO. NEW BRITAIN, CONN., OR A TUMBLER LOCK NO, 15481 ARS AND KEYPAD ALIKE FOR NO. 2 AVAILABLE FROM CORBIN LOCK CO. NEW BRITAIN, CONN. 4. SECURE CABINET LOCK TO THE DOOR WITH #10 - 24 X 1 " ROUND HEAD (STN. STL.) MACHINE SCREWS. 5. 120V EXPOSED WIRING IS NOT PERMITTED. ENCASE WIRING TO ENCLOSURES AND OUTLETS IN LIQUID TIGHT FLEXIBLE CONDUIT AND FITTINGS INSIDE THE CABINET. BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NOT TO SCALE NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:50 scale= 30.000000:1.00000 1. 6. ENSURE ALL EQUIPMENT IS UL & NEMA LISTED FOR OUTDOOR INSTALLATION INSIDE NEMA 3R CABINET. 7. LABEL ALL ELECTRICAL RECEPTACLES EXCEPT GFCI AS "ELECTRONIC EQUIPMENT ONLY". AND GFCI RECEPTACLE AS "CONVENIENCE RECEPTACLE". 8. FOR BREAKER RATINGS, SEE TABLE A. 9. PROVIDE SURGE SUPPRESSION. 10. METER, RAIN TIGHT DISCONNECT SWITCH AND SERVICE CONDUIT ARE NOT REQUIRED IF ELECTRIC SERVICE IS CONNECTED TO ANOTHER LOAD CENTER AND NOT TO UTILITY COMPANY POWER SOURCE. ITS-704-21 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS ITS CONTROLLER 11. WHERE REQUIRED, ENSURE METER PAN CONFORMS TO UTILITY COMPANY’S HEIGHT REQUIREMENTS. * * file= 62" 50" 36" A FIBER CROSS CONNECT CABINET FIBER CROSS CONNECT CABINET (60"H X 50" L X 36"D) (60"H X 50" L X 36"D) QUAD NEMA 4X CABINET QUAD NEMA 4X CABINET 60" 60" CONDUITS STUBBED ABOVE CONDUITS STUBBED ABOVE CONCRETE SLAB CONCRETE SLAB FOUNDATION ITS TYPE A CONCRETE PAD 3’ X 5’2" X 4" THICK 6" 6" 6" 3’ . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . GROUND LEVEL GROUND LEVEL . GROUND LEVEL . 6" . . . . . .. . 3’ " DIA. X 12 FT. LONG CONCRETE PAD GROUND ROD 3’ X 5’2" X 4" THICK (SEE NOTES 4 & 5) FOUNDATION ITS TYPE A 2" RMC 2" RMC FIBER CROSS CONNECT CABINET INSTALLATION DETAIL (TYP.) SECTION A-A A 5’-2" 3’-10" 2’-7" 6" ANCHOR BOLT (TYP.) SEE DETAIL 2’-7" 3" 1" 6" " " " 1" " GENERAL DESIGN SPECIFICATIONS: 2’-0" 10" 1" " -10NC THD. FREE FIT .234" 2’-7" 4’-0" CONCRETE DESIGN STRESS: SPECIFIED COMPRESSIVE STRENGTH (f’c) (CLASS B)..........................3,000 PSI EXTREME FIBER COMPRESSIVE STRESS (f’c)...........................................1,200 PSI REINFORCEMENT STEEL DESIGN STRESS: 2’-0" COUPLING FLAT & LOCK WASHER MAT’L - STEEL, GALVANIZED AS PER ASTM A-153 MAT’L - STAINLESS STEEL pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE GROUND ROD SEE NOTE 1 YIELD STRENGTH (fy) (ASTM A615, GRADE 60).......................................60 KSI TENSILE STRENGTH (ts)...............................................................................24 KSI NOTES: SEE NOTE 2 1. " DIA. X 12 FT. LONG GROUND ROD. PROVIDE GROUNDING AND BONDING AS PER NEC. REQUIREMENTS. PLAN " -10NC THD. FREE FIT 1" 2. FOR NUMBER AND SIZE OF CONDUITS, SEE ITS PLANS. 3. COORDINATE THE LOCATION OF ANCHOR BOLTS WITH 1" THE MOUNTING HOLES OF THE CABINET SUPPLIED. 1" 5" FINISHED GRADE 1" MIN. 4. FINISHED GRADE 1" PROVIDE CONCRETE PAD ON THE FRONT AND BACK OF CABINET FOUNDATION. 5. PAYMENT FOR CONCRETE PAD TO BE INCLUDED UNDER PAY ITEM, FOUNDATION ITS, TYPE A. scale= 30.000000:1.00000 " 3’-0" ANCHOR BOLT 1’-0" NOT TO SCALE (TYP.) 4" ITS-704-22 3" NEW JERSEY DEPARTMENT OF TRANSPORTATION BDC-11D-03 - ORIGINAL SHEET NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:50 " "-10NC THD.FREE FIT APPROX. 62 CU. FT. CONCRETE CLASS ’B’ ITS DETAILS ELEVATION DIMENSIONS MAY VARY TO ACCOMMODATE THE METER CABINET SUPPLIED 1" CABINET FOUNDATION ANCHOR BOLT MAT’L -STEEL PER ASTM A-576 CAP SCREW GENERAL SYSTEMS FIBER CROSS CONNECT CABINET & FOUNDATION ITS TYPE A MAT’L- STAINLESS STEEL PER ASTM A-193 GRADE B-8 * FOUNDATION ITS TYPE A DETAIL (TYP.) file= * NOTES 1. CABINET CONSTRUCTED OF FORMED ALUMINUM ALLOY 5052-H32 0.125 INCH THICK WELDED WHERE SHOWN. 2" DIA. HOLE 45 45 2. CABINET IS NOT PAINTED. 3. ALL BOLTS TO BE VANDAL PROOF TYPE. 4. 8 HEAD OF BOLT FINISHED FLUSH " PLYWOOD (EXTERIOR GRADE) WITH OUTSIDE WALL 4 PLACES ANY VARIATIONS TO THE DIMENSIONS MUST BE APPROVED IN WRITING PAINTED BLACK BY THE N.J.D.O.T. ENGINEER BEFORE FABRICATION. " SPACER 5. NO CHANGES IN ANCHORAGE DIMENSIONS ARE PERMITTED. 6. IF METER IS NOT REQUIRED, INSTALL 1" I.D. SEALTITE FLEXIBLE CONDUIT X X 15" X X 7. X X X AND 1" I.D. NIPPLE FROM REDUCER COUPLING TO MAIN BREAKER PANEL. THE BASE OF THE CABINET TO BE " MINIMUM THICKNESS. X X X X X X X X X X (4)" DIA. HOLES 8. ON 4" DIA.BOLT CIRCLE X X X X AS AN ALTERNATE A STAINLESS STEEL PIANO TYPE HINGE X X MAY BE UTILIZED. IF REQUIRED BY UTILITY COMPANY, PROVIDE SERVICE DISCONNECT SWITCH STN. S.S. BOLTS, CKT.#7 CKT.#8 20A 20A CKT.#5 CKT.#6 20A 20A CKT.#3 CKT.#4 20A 20A CKT.#1 CKT.#2 40A 30A WASHERS & LOCKNUTS. X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X (LOCK TO BE SUPPLIED BY UTILITY COMPANY). SUBMIT WORKING DRAWINGS X X X TYP. WITH 240 VOLT, 100 A RATED, S/N, NEMA 3R ENCLOSURE AND PADLOCK PROVISIONS. X 9. (4)"-18 NC X 1" LG. " SHOWING SERVICE DISCONNECT SWITCH INSTALLATION FOR REVIEW AND APPROVAL. " 16" 10. PROVIDE S.S. FASTENERS " PROVIDE SCALED DRAWING TO VERIFY THAT PROPOSED COMPONENTS WILL FOR GROUNDING FIT IN THE CABINET. TOP VIEW 11. PROVIDE GROUNDING AND BONDING IN ACCORDANCE WITH NEC REQUIREMENTS. 12. SECURE CABINET DOOR WITH A CORBIN LOCK NO. 15481RS KEYED FOR #2 SERIES. PROVIDE TWO (2) COPIES OF THE KEY TO NJDOT AND ONE (1) COPY TO THE " ALUM. 5052-H32 ELECTRIC UTILITY. 6" x 6" X" THK. ALUM. 5052-H32 ALL WELDS SIZES ARE ". " 13. GFCI DUPLEX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1" X RECEPTACLE (3)"-20 NC X " LG. S.S. LOCKNUTS PER HINGE (TYP.) 6" CARRIAGE BOLTS, WASHERS & " X X X X X X X X X X X X X X X X X X X X X X X " 7 TYP. HINGE" S.S. WITH X A X X X X X X UTILIZING THREE POINT LATCHING DOOR" ALUM. (TOP, BOTTOM, & SIDE) DOOR GASKET - CLOSED CELL NEOPRENE (3)" DIA. RIVETS PER HINGE DOOR STIFFENER CORBIN LOCK NO. 15481RS 65 AMP SECTION A-A BLACK KEYED FOR #2 SERIES " AIR SPACE WHITE " PLYWOOD RED LOAD CENTER PANEL " STN. STL. PIN S.S. HANDLE & ASSEMBLY 54" A X X X X X 6 METER SOCKET 1" 0.234" " PROVIDE S.S. FASTENERS .125" FOR GROUNDING .750" 5" 3" 3" COUPLING SCHEMATIC WIRING DIAGRAM: 10" 1’-8" LEGEND " -10NC THD 1 " 6 MIN. 3 7 " 12" 1" 4" 5" WEATHERPROOF, 20AMP GFCI DUPLEX RECEPTACLE GROUND FAULT, IN 3" MALLEABLE IRON BOX. 13" RIGID METALLIC SERVICE CONDUIT. (SEE GENERAL 3 ANCHOR BOLT DETAIL AS SHOWN. 4 LOCATIONS FOR DISTRIBUTION CONDUITS - FOR NUMBER, DIMENSIONS MAY " 2 ITS-704-23 2’-6" " DIA. X 12 FT. LONG GROUND ROD. 2’-0" 5 1 . D Y A B R . D " 8 E S O 1 C A IR Y U R T O EQ I IL T BDC-11D-03 - ORIGINAL SHEET 8 + U NJDOT Design Services 3 2" 6" 11" 7" 30.000000:1.00000 scale= ONE (1) 2-POLE 30 AMP TWO (2) 2-POLE 20 AMP, AND FOUR (4) 1-POLE 20 AMP R 1" PROVIDE ONE (1) MAIN BREAKER 2-POLE 65 AMP; ONE (1) 2-POLE 40 AMP, NOT TO SCALE ITEM CONSTRUCTION PLANS FOR DIRECTION AND SIZE.) 27-SEP-2011 08:50 AND TO FEDERAL SPECIFICATION W-C-375B FOR CLASS 10A OR CLASS 10B. BREAKERS. 3 date= LOAD CENTER PANEL WITH ENCLOSURE- PROVIDE 125 AMP MAIN-RATED BUS, CIRCUIT BREAKERS THAT ARE UL LISTED, COMPLY WITH NEMA STANDARDS, PLAN 1 TPOKEEG AREA METER SOCKET IS TO BE INSTALLED AND FURNISHED BY CONTRACTOR). CONFORMING TO FEDERAL SPECIFICATION W-P-115C, TYPE 1, CLASS 1. PROVIDE 7" ID= METER SOCKET-INSTALLED BY CONTRACTOR-PROVIDED BY UTILITY COMPANY ON REQUEST. (IN JCP&L CO. 1" 1" FREE FIT 12" 5" 120/240 VOLT MAT’L - STEEL, GALVANIZED PER ASTM A-153 3" 4 MAT’L - STN. STL. 10" 6" 2" 2" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 6" 4 SEE ITS PLANS FREE FIT 3 4" 1 3 120/240V, 1 PHASE, 3 WIRE " -10NC THD 3" 2" 5" (MIN.) 5" ELECTRIC SERVICE 10" SIDE ELEVATION FRONT ELEVATION SECONDARY RACK FLAT & LOCK WASHER 2" POLE MOUNTED 1.250" 3" " 10" 4" TO UTILITY CO’S 1" 0.188" 1’-8" 3 3" VARY TO ACCOM- NEW JERSEY DEPARTMENT OF TRANSPORTATION MODATE THE METER 1" 2 CABINET SUPPLIED. "-10NC THD. FREE FIT ITS DETAILS SIZE AND POSITION SEE GENERAL PLANS. APPROX. 7 CU. FT. 11" 5 RADIUS - SUBJECT TO APPROVAL OF UTILITY COMPANY. CONCRETE ELEVATION BOTTOM VIEW ANCHOR BOLT MAT’L - STEEL PER ASTM A-576 CAP SCREW MAT’L - STN. STL. PER ASTM A-193 GRADE B-8 NOTE: ALL CONCRETE SHALL BE CLASS "B". FOUNDATION ITS TYPE MC 3 METER CABINET ITS & FOUNDATION ITS TYPE MC ANCHOR BOLT ASSEMBLY * * file= 5’-10" 4’-2" 9" 7 9 5 5 1’-4" 8 9" 2" 4 7 6" 5 2’-6" DIRECTONFA "A" 5 3 9" 4 1 4" 5" 6" 1’-4" 5 5 6" 10" 1’-8" 10" 3 "A" 5 1’-6" 6" 5 8 5 1 DIRECTONFA 1 " DIA. 2 3" DIA. RMC TERMINATED INTO JUNCTION BOX. 3 RMC (SERVICE CONDUIT). SEE GENERAL CONSTRUCTION X 12 FT. LONG GROUND ROD. PLANS FOR DIRECTION AND SIZE. IF NOT SPECIFIED, INSTALL 2" DIA. RMC. 4 2" DIA. RIGID METALLIC CONDUIT. (SERVICE CONDUIT) 5 ANCHOR BOLT (TYP. SEE "ANCHOR BOLT DETAIL"). 6 DRAIN - 1" DIA. RIGID METALLIC CONDUIT. (PITCH DOWN TO JUNCTION BOX.) 7 2" X 2" X 1" GALVANIZED TEE FITTING FOR DRAIN. 8 RMC (INTERCONNECT CONDUIT). SEE GENERAL PLAN FOR DIRECTION AND SIZE. IF NOT SPECIFIED INSTALL 2" DIA. RMC. 9 10 2" DIA RMC (INTERCONNECT CONDUIT) RADIUS - SUBJECT TO APPROVAL OF UTILITY COMPANY. 5 5 6 9" 5 5’-2" 3" 6" 6" 6" 3" 3" 6" 5" 2’-1" 9" 1’-4" 5" 1’-" 1’-4" 4" 10" 5’-2" 2’-6" 10" ITEM DESCRIPTION "A" "A" NOTES: 1. ALL CONDUITS WITH COUPLINGS ARE TO BE PLAN EMBEDDED, PLUMB AND FLUSH WITH TOP OF 1’-8" CONCRETE FOUNDATION. 1" 1" 2. INSERT J-BOLT 1" +/- 2" 5" 5 " 2" LEVEL 1 2 1" 5 5" 2 5 + 1" 1’-8" 1 5 1" PLAN 1’-8" 1’-8" 3. POUR MONOLITHIC FOUNDATIONS. 1" 4. ALL CONCRETE TO BE CLASS "B". 5. PLUG/CAP ALL CONDUIT ENDS. " R A D . E U A Q T S IL ’D IT B Y Y R R 4 M IN . 9 C O . 8 6. FOUNDATION AS REQUIRED BY THE UTILITY COMPANY. 18 " O R R 4 3 9 R A E Q S U Y IR C U E O T . IL D IT 8 Y B A D 2’-6" . 4" 3 O 10 2’-0" MIN. 18 2’-6" 2’-0" MIN. 2’-6" 10 " INTO 3" COUPLING ELEVATION ELEVATION FOUNDATION ITS TYPE "D" FOUNDATION ITS TYPE "D-MC" CLASS "B" CONCRETE 3’-6" 1’-8" 3’-6" "A" "A" SECTION A-A 5 5 1 7 1’-0" 5 5 DIRECTONFA 6" 5" 6" "A" 5 3 1 5 DIRECTONFA 2 OR 4-3/4 " DIA ANCHOR BOLTS WITH 1" OF THREAD. COUPLINGS, STN. STL. HEX HEAD CAP SCREWS 1" LG. ASTM A193, GRADE B8, STN. STL. LOCK WASHERS AND STN. STL. FLAT WASHERS. ALL THREAD STN. STL. LOCK WASHER TO BE " -10NC CL. STN. STL. FLAT WASHER 2 FIT. " I.D. X 1" O.D. 3" LG. GALV. COUPLING 12" 5" 5 6" 1’-2" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 2’-0" 6" 4 "A" 4" 2’-0" 5" 7" 5 1’-9" 1’-0" 3" 3" 3 6" 1’-0" 6" 5" 1’-0" 5" 6" 1’-9" 6" 10" 12" LG. HOOK BOLT WITH 1" OF THREAD. TOP 6" TO 6 PLAN 2 2 PLAN BE GALVANIZED PER ASTM A-153 1" BDC-11D-03 - ORIGINAL SHEET NJDOT Design Services 18 " R O A R D R . A E Q S B U Y IR C E O UT . IL D IT Y 3 4 3’-0" 2’-0" 10 1" 10 18 " O R A D A E . Q S B U Y I R C E O UT . IL D IT Y R R TYP. ANCHOR BOLT DETAIL NOT TO SCALE 3’-0" 2’-0" MIN. 30.000000:1.00000 scale= 27-SEP-2011 08:50 date= TPOKEEG ID= 1" 6 2" 5 5" 5 1" 1 1" 2" 5 5" 1 3 ITS-704-24 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS ELEVATION FOUNDATION ITS TYPE "C-MC" ELEVATION FOUNDATION ITS TYPE C, C-MC, D & D-MC FOUNDATION ITS TYPE "C" * * file= 11’-8" 10’-4" WOOD CURBING TIMBERS 8" X 8" NUMBER OF COMMUNICATIONS CONDUITS AS SHOWN IN THE FIBER OPTIC PLANS NUMBER AND SIZE OF ELECTRIC SERVICE CONDUITS AS SHOWN IN THE FIBER OPTIC PLANS 4’ TYP. HUB BUILDING 13’-8" 12’-4" COMMUNICATIONS CRUSHED STONE SEED AND FERTILIZER 3" 4" 4’-0" 3" 4" CONCRETE PLATFORM CONCRETE PLATFORM 4’-0" 6’-0" CONCRETE PLATFORM 5’-8" GROUNDING PLAN 4’ GATE LOCK CHAIN LINK FENCE PLAN VIEW PCH WALL PAVERS \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE PLAN VIEW pen table= CABLE LADDER METER PAN FOR 200A, 120V, 1 PHASE, 3 WIRE SERVICE 4.5" (IF RQUIRED) 5’-0" 1.5" 3" 12" 1.5" 3" RMC scale= 30.000000:1.00000 CONDUIT RISER 2’-6" MIN. BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 DENSE GRADED AGGREGATE FOUNDATION 2’-6" MIN. NOT TO SCALE ITS-704-25 10’-0" NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS COMMUNICATIONS CABLE ENTRANCE DETAIL NEW 3" RMC SERVICE ENTRANCE DETAIL COMMUNICATION HUB SHEET 1 OF 4 * * file= CONCRETE* HOLLOW METAL * LOUVER (TYP.) * FACIA (TYP.) DOOR AND FRAME TOP OF CONCRETE STRUCTURE LIGHT FIXTURE * 9’-0" FACE BRICK (TYP.) 3" RIGID GALVANIZED 11" STEEL CONDUIT RISER 4" CONCRETE INSIDE FLOOR 10^ 3" PLATFORM 6" (TYP.) TOP OF FOUNDATION 6" (TYP.) 3" WALLS 6" DENSE GRADED FRONT AGGREGATE BASE DETAIL "A" RIGHT SIDE COURSE (TYP.) 3" WALLS A/C (TYPICAL) A/C (TYPICAL) * * 5" LOUVER (TYP.) * ADDITIONAL MAT 4" x 4" - W4/W4 #13 BAR (18" LONG MIN.) DAYTON SUPERIOR INSERT F-64 91/2" x 6") SEE DETAIL "B" - ADDITIONAL REINFORCING DETAIL "A" EMERGENCY * " POWER INLET ELECTRIC * pen table= 5’-0" CONCRETE PLATFORM PLATFORM 12" CONCRETE 1-4" SCHEDULE 40 PVC 2’-6" DETAIL "B" 5" DETAIL "C" REF. 5" \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE DETAIL "C" SEE SEE " 8’-2" METER FAN 4’-0" SUMP FOR CONDENSATE 4x4 - W4/W3 WELDED WIRE MATS (2) MATS IN ROOF WITH ADDITIONAL #13 @ 15" INSIDE FACE (SHORT SPAN ONLY) scale= 30.000000:1.00000 (1) MAT IN WALLS (2) MATS IN FLOOR WITH ADDITIONAL #13 @ 8" EACH FACE (SHORT FACE ONLY) ADDITIONAL #13 BARS EACH FACE ALL SIDES OF OPEING NOT TO SCALE 2’-0" ITS-704-26 4’-0 5’-0" 4’-0 5’-0" " TO 1" GRADED STONE " BOLT @ 18" + - NEW JERSEY DEPARTMENT OF TRANSPORTATION 1-4" SCHEDULE 40 PVC BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 SUMP FOR CONDENSATE * MANUFACTURED AND DELIVERED TO ITS DETAILS " TO 1" GRADED STONE THE SITE PREASSEMBLED. ITEMS PROVIDED BY PREFAB BUILDING. 4’-0" 4’-0" COMMUNICATION HUB LEFT SIDE NOTE: 1. ALL BAR SIZES ARE DESIGNATED IN SOFT METRIC SIZES. BACK SHEET 2 OF 4 * * file= 1500W FA LOAD HEATER CENTERS MOTORIZED INTAKE LOUVER 3’-0" AC 2 23" EQUIPMENT RACK B M 200A T T 2’-0" T METER CHANNEL CABLE LADDERS ON RIGHT SIDE 20A WALL, ACROSS 240V WIDTH, AND ACROSS 100A 40W DEPTH OF BUILDING EMERGENCY FLOUR FIX 40W CONNECTION FLOUR FIX GENERATOR 19" EQUIPMENT RACK C AND D SHOP DESK 36W x 30D FS 40W AC FLOUR FIX 1 20A STORAGE FUTURE RACK 240V CABINET 36W x 18D 40W FLOUR FIX ST T F pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE SSS L 23" EQUIPMENT GRAVITY SHUTTER LOUVER WITH 650 CFM FAN scale= 30.000000:1.00000 RACK A NOT TO SCALE ITS-704-27 BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 NEW JERSEY DEPARTMENT OF TRANSPORTATION ELECTRIC WIRING PLAN RACK AND EQUIPMENT LOCATION PLAN ITS DETAILS COMMUNICATION HUB SHEET 3 OF 4 * * file= NON-EMERGENCY LOAD CENTER ELECTRIC UTILITY SYSTEM 100A 20A HEATER WH 20A RACK A POWER SYSTEMS AC 1, 240V 120 / 240VAC 20A 3W, 100A, 10 LIGHTING 60 HZ 20A OUTLETS 2-STAGE 20A TVSS OUTLETS 100A 5A SONET MUX PWR A 225A 5A SONET MUX PWR B A 5A T1 DATA MUX PWR A EMERGENCY 50A 50A RECT- RECT- -IFIER -IFIER V 5A T1 DATA MUX PWR B 10A LOAD CENTER 75A RACK FUSES PORTABLE EMERGENCY 100A 20A AC 2, 120V SWITCH 48V BATTERY 15A LIGHTING G SAFETY 2W 100A SWITCH 60 HZ 15A FAN 20A RACK OUTLETS 3 KVA MODULAR INVERTER DIST. MODULE 48 VDC POWER PLANT 1 KVA 30A 48V DC 30A 15A RACK B OUTLETS, 120VAC 30A 15A RACK C EQUIPMENT, 120VAC 15A RACK D EQUIPMENT, 120VAC scale= 30.000000:1.00000 pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE INVERTER BYPASS 120 VAC & BYPASS 120 VAC 70A @ 4 OR 10 HRS. OUTPUT 100A 1 KVA 100A 1 KVA TRANSFER GENERATOR ELECTRICAL SERVICE LOAD CENTERS NOT TO SCALE ITS-704-28 BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS COMMUNICATION HUB SHEET 4 OF 4 * * file= SHOULDER 6’ SHOULDER DIRECTION OF LOOP A TRAVEL B C D F E 3’ 3’ (TYP.) DIRECTION OF SHOULDER IDENTIFICATION OF TRAFFIC MONITORING LOOPS TRAVEL A C B 3’ TEMPERATURE SENSOR 1. 12’ AXLE SENSORS TO BE CENTERED IN THE LANE. 1" RMC (TYP.) FROM JUNCTION BOX 6’ JUNCTION BOX SHOULDER TAG THE LEADING LOOP AS LOOP "A" (FIRST LOOP IN THE DIRECTION OF TRAVEL OF THE RIGHT MOST LANE VARIOUSLY CALLED SLOW, SHOULDER, OR TRAVEL LANE), LOOP "B" AS THE TRAILING (SECOND) TO EXTEND 1’-6" INTO LOOP IDENTFY LOOPS WITH DURABLE IDENTIFICATION TAGS ON EACH LOOP LEAD PAIR. AFFIX LETTERS AS FOLLOWS: PAVED ROADWAY. LOOP IN THE SAME LANE AND LOOP "C" AS THE THIRD LOOP IN THE SAME LANE. 1 LANE TEMPERATURE SENSOR 3’ 12’ AXLE SENSORS TO BE CENTERED IN THE LANE. 3’ 2 LANE TO EXTEND 1’-6" INTO PAVED ROADWAY. 12’ (TYP.) LOOP SIMILARLY DESIGNATE LOOPS IN THE OPPOSITE DIRECTION BY LANE STARTING IN THE RIGHT MOST LANE, USING THE NEXT GROUP OF LETTERS, THEN ACROSS THE LANES TO THE DIVIDER OR MEDIAN. 1" RMC (TYP.) FROM JUNCTION BOX JUNCTION BOX 6’ IDENTIFY LOOPS IN GROUPS, WITH THE LEADING LOOP IN THE DIRECTION OF TRAVEL ALWAYS IDENTIFIED BY THE FIRST LETTER IN THE GROUP. ASSIGN THE GROUPS BY LANE ACROSS ROADWAY, TOWARD THE DIVIDER OR MEDIAN. JUNCTION BOX 1" RMC (TYP.) FROM JUNCTION BOX TO EXTEND 1’-6" INTO PAVED ROADWAY. (TWO) 3" RMC (TYP.) JUNCTION BOX NOTES: 1" RMC (TYP.) SHOULDER 6’ H G I FROM JUNCTION BOX (TWO) 3" RMC (TYP.) 1. CLEAN SLOTS FOR WEIGHT AXLE SENSOR, LOOPS AND LEAD-IN CABLES (PRESSURE WASHED WITH WATER) AND DRY PRIOR TO THE APPLICATION OF GROUT. 2. STAGGER ADJACENT LANE SENSORS. 3. WHERE CONCRETE ROADWAY EXISTS, INSTALL LOOPS IN CONCRETE SURFACE PRIOR TO RESURFACING. 4. WHERE REFLECTORS AND CASTINGS AND RUMBLE STRIPS ARE TO BE INSTALLED, ADJUST THE DEPTH OF THE LOOP LEADS AND AXLE SENSOR CABLES ACCORDINGLY TO AVOID DAMAGE. 5. ENSURE GROUT CURES AND IS CAPABLE OF SUPPORTING VEHICULAR TRAFFIC WITHIN A MAXIMUM OF 60 MINUTES FROM START OF INSTALLATION. 6. INSTALL LOOPS AFTER MILLING PROCESS, IF PERFORMED, AND PRIOR TO THE INSTALLATION OF THE FINAL OVERLAY. 7. SENSOR SPACING SHOWN IS TYPICAL SPACING REQUIREMENT. ACTUAL SENSOR SPACING MAY BE ALTERED TO SUIT SITE CONDTIONS AND MANUFACTURER’S RECOMMENDATION. 8. USE THIN WALLED PLASTIC TUBING TO CONTAIN THE SENSOR LEAD WIRE. INSTALL THE TUBING FROM THE END OF THE SENSOR SLOT TO A POINT 6-12 INCHES INSIDE THE JUNCTION BOX OR CONDUIT END. 9. INSTALL PIEZO SENSORS A MINIMUM OF 2 FEET FROM CRACKS, JOINTS, OR SAWCUTS WHEN POSSIBLE. 10. PROVIDE EACH SENSOR WITH A SUFFICIENT LENGTH OF SHIELDED LEAD CABLE FOR TERMINATION AT THE CONTROLLER IN THE CABINET WITHOUT SPLICING. 11. INSTALL TEMPERATURE SENSOR IN SHOULDER PER MANUFACTURER’S RECOMMENDATION. SUPPLY ONE TEMPERATURE SENSOR PER WIM COMPUTER. 12. WHEN ENCAPSULATION MATERIAL IS FULLY CURED, GRIND FLUSH WITH ROAD SURFACE USING AN ANGLE GRINDER OR BELT SANDER. TO EXTEND 1’-6" INTO PAVED ROADWAY. DIRECTION OF SHOULDER E TRAVEL D F J 3’ (TYP.) K L DIRECTION OF TRAVEL A SENSOR LAYOUT FOR WEIGH IN MOTION SITES B DIRECTION OF TRAVEL C H G I SHOULDER D E F 3’ (TYP.) TEMPERATURE SENSOR JUNCTION BOX 1" RMC (TYP.) FROM JUNCTION BOX TO EXTEND 1’-6" INTO PAVED ROADWAY. A B C 3 LANE SHOULDER TEMPERATURE SENSOR 1" RMC (TYP.) FROM JUNCTION BOX JUNCTION BOX TO EXTEND 1’-6" INTO PAVED ROADWAY. 4 LANE TYPICAL INSTALLATION - WIM ROADWAY DEVICES GROUT 6’-0" CLASS 1 SENSOR 1" MIN. C 6’-0" GAUGE WIRE. NUMBER OF TURNS 4 TRAFFIC LANE " MAX. 12’ ROADWAY 3 1/2" MIN. SINGLE PASS WET SAW CUT WITH CONCRETE BLADE. PRESSURE WASH SLOT WITH WATER AND BLOW DRY BEFORE SEALANT IS POURED. D D 1" RMC CONDUIT RUN BETWEEN J.B. AND EXTEND ENSURE SAW CUT WIDTH IS " WIDER THAN CABLE DIAMETER. B B 1. SECTION A-A THIN WALL," MIN. I.D., FLEX TUBING PVC OR POLYETHYLENE ROADSIDE JUNCTION BOX 3. \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 2" SHOULDER SURFACE 2. pen table= " MIN. 1’-6" INTO PAVED SHOULDER 5. LOOP SEALANT SENSOR LEAD A A C INDUCTIVE LOOP CONSISTS OF NO. 14 PIEZO TYPE AXLE SENSOR DETAILS 4. GROUT SENSOR LEAD 1" INDUCTIVE LOOP DETAILS SECTION D-D ROADWAY " 1" MIN. CLASS 1 PIEZO ELECTRIC SENSOR 2" MIN. 1" LEAD IN WIRES 1" EPOXY SLOT MADE BY SECTION B-B WET CUTTING 2 PASSES WITH CONCRETE SAW. SQUARE OUT BY CHISEL " 1" " scale= 30.000000:1.00000 " SECTION C-C SENSOR LEAD CABLE SEALED NOT TO SCALE INTO ROAD SURFACE LOOP CABLE SEALED INTO ROAD SURFACE SHOULDER ITS-704-29 TRAFFIC LANE SHOULDER TRAFFIC LANE EXCAVATE & FILL 1’-6" NOTES: NEW JERSEY DEPARTMENT OF TRANSPORTATION 1. LEAD WIRES TWISTED MINIMUM OF 3 TURNS PER FOOT. BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 1’-6" 2. DRILL HOLE 1’-6" FROM EDGE OF SHOULDER TO INSTALL RMC CONDUIT. ITS DETAILS JUNCTION BOX 3. 1" RMC CONDUIT RUN BETWEEN JUNCTION BOX AND SHOULDER SURFACE. 1" RMC CONDUIT RUN TO EXTEND 1’-6" INTO PAVED ROADWAY TO ROAD SIDE JUNCTION BOX JUNCTION BOX 4. INSTALL JUNCTION BOX AT ROAD EDGE FOR CONNECTIONS TO FEEDER CABLE. 5. MAKE ALL CONNECTIONS BETWEEN LEAD WIRES AND LOOP DETECTOR CABLE IN THE JUNCTION BOX. 1" RMC CONDUIT RUN TO EXTEND 1’-6" INTO PAVED ROADWAY TO ROAD SIDE JUNCTION BOX WEIGH IN MOTION SYSTEMS, ROADWAY DEVICES LOOP CABLE ROUTING DETAILS AXLE SENSOR CABLE ROUTING DETAILS * * file= SHOULDER 6’ SHOULDER DIRECTION OF LOOP A TRAVEL B C D 6’ 3’ (TYP.) DIRECTION OF SHOULDER IDENTIFICATION OF TVS ROADWAY LOOPS TRAVEL A B 6’ 1. LOOP 1" RMC (TYP.) FROM JUNCTION BOX JUNCTION BOX SHOULDER TAG THE LEADING LOOP AS LOOP "A" (FIRST LOOP IN THE DIRECTION OF TRAVEL OF THE RIGHT MOST LANE VARIOUSLY CALLED SLOW, SHOULDER, OR TRAVEL LANE), LOOP "B" AS THE TRAILING (SECOND) TO EXTEND 1’-6" INTO PAVED ROADWAY. 6’ IDENTFY LOOPS WITH DURABLE IDENTIFICATION TAGS ON EACH LOOP LEAD PAIR. AFFIX LETTERS AS FOLLOWS: LOOP IN THE SAME LANE AND LOOP "C" AS THE THIRD LOOP IN THE SAME LANE. 1 LANE JUNCTION BOX 1" RMC (TYP.) FROM JUNCTION BOX 2 LANE TO EXTEND 1’-6" INTO PAVED ROADWAY. SIMILARLY DESIGNATE LOOPS IN THE OPPOSITE DIRECTION BY LANE STARTING IN THE RIGHT MOST LANE, USING THE NEXT GROUP OF LETTERS, THEN ACROSS THE LANES TO THE DIVIDER OR MEDIAN. DIRECTION OF TRAVEL 1" RMC (TYP.) FROM JUNCTION BOX JUNCTION BOX LOOP LAYOUT FOR TRAFFIC VOLUME SYSTEM TO EXTEND 1’-6" INTO PAVED ROADWAY. 3" RMC SHOULDER IDENTIFY LOOPS IN GROUPS, WITH THE LEADING LOOP IN THE DIRECTION OF TRAVEL ALWAYS IDENTIFIED BY THE FIRST LETTER IN THE GROUP. ASSIGN THE GROUPS BY LANE ACROSS ROADWAY, TOWARD THE DIVIDER OR MEDIAN. JUNCTION BOX NOTES: 1" RMC (TYP.) E F FROM JUNCTION BOX 3" RMC (TYP.) 1. STAGGER ADJACENT LANE LOOPS. TO EXTEND 1’-6" INTO PAVED ROADWAY. 2. WHERE CONCRETE ROADWAY EXISTS, INSTALL LOOPS IN CONCRETE SURFACE PRIOR TO RESURFACING. SHOULDER DIRECTION OF TRAVEL 3. WHERE REFLECTORS AND CASTINGS AND RUMBLE STRIPS ARE TO BE INSTALLED, ADJUST THE DEPTH OF THE LOOP LEADS ACCORDINGLY TO AVOID DAMAGE. D C G 3’ (TYP.) A 4. INSTALL LOOPS AFTER MILLING PROCESS, IF PERFORMED, AND PRIOR TO THE INSTALLATION OF THE FINAL OVERLAY. DIRECTION OF TRAVEL B H E F 5. LEAD WIRES TWISTED MINIMUM OF 3 TURNS PER FOOT. 6. DRILL HOLE 1’-6" FROM EDGE OF SHOULDER TO INSTALL RMC CONCUIT. SHOULDER C D 7. 1" RMC CONDUIT RUN BETWEEN JUNCTION BOX AND SHOULDER SURFACE. 3’ (TYP.) JUNCTION BOX 1" RMC (TYP.) FROM JUNCTION BOX TO EXTEND 1’-6" INTO PAVED ROADWAY. 8. INSTALL JUNCTION BOX AT ROAD EDGE FOR CONNECTIONS TO FEEDER CABLE. A 9. MAKE ALL CONNECTIONS BETWEEN LEAD WIRES AND LOOP DETECTOR CABLE IN THE JUNCTION BOX. B 3 LANE SHOULDER 1" RMC (TYP.) FROM JUNCTION BOX JUNCTION BOX TO EXTEND 1’-6" INTO PAVED ROADWAY. 4 LANE TYPICAL INSTALLATION TVS ROADWAY LOOPS GROUT 6’-0" 1" MIN. 6’-0" INDUCTIVE LOOP CONSISTS OF NO. 14 GAUGE WIRE. NUMBER OF TURNS 4 TRAFFIC LANE A A 3 1/2" MIN. SINGLE PASS WET SAW CUT WITH CONCRETE BLADE. PRESSURE WASH SLOT WITH WATER AND BLOW DRY BEFORE SEALANT IS POURED. ENSURE SAW CUT WIDTH IS " WIDER THAN CABLE DIAMETER. B B 1. SECTION A-A SHOULDER 2. 3. pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 5. 4. GROUT INDUCTIVE LOOP DETAILS 1" MIN. 2" MIN. LEAD IN WIRES scale= 30.000000:1.00000 SECTION B-B NOT TO SCALE LOOP CABLE SEALED INTO ROAD SURFACE SHOULDER ITS-704-30 TRAFFIC LANE EXCAVATE & FILL BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 1’-6" NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS JUNCTION BOX 1" RMC CONDUIT RUN TO EXTEND 1’-6" INTO PAVED ROADWAY TO ROAD SIDE JUNCTION BOX TRAFFIC VOLUME SYSTEM (TVS), ROADWAY LOOPS LOOP CABLE ROUTING DETAILS * * file= SCREENED VENT SEE NOTE #9 1 CIR. 1 CIR. 5 DUPLEX 4 FAN 3 LIGHT RECEPTACLE 2 WIRING DIAGRAM ACCESSORIES: CIR. 6 CIR. 2 1. LOAD CENTER DISTRIBUTION PANEL BOARD. SPACE 2. DUPLEX RECEPTACLE. DUPLEX RECEPTACLE SPACE 3. CABINET LIGHT AND SWITCH. SPACE CIR. 3 SPACE T 4. THERMOSTATICALLY CONTROLLED FAN. SW CIR. 4 SEE NOTE #4 2 SPACE MINIMUM DIMENSIONS OF CABINET SN 3-#4 AWG STAINLESS STEEL HINGE & PIN SEE NOTE #5 SCHEMATIC WIRING DIAGRAM: 120/240 VOLT (100 AMPS) 4’-4" MIN. 3’-6" SEE NOTE #6 2’-2" MIN. SEE NOTE #3 VENTS FANS FAN THERMOSTAT CONTROL LIGHT DUPLEX RECEPTACLE NOTES: DUPLEX RECEPTACLE RJ-11 pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 1. 2. 3. 4. FABRICATE CABINET OF " THK. ALUM. (GRADE 50-52-H32) THE CABINET TO BE MOUNTED WITH THE ANCHOR BOLT CONFIGURATIONS SHOWN, IF REQUIRED USE" THK. ALUM. BASE ADAPTER PLATES AND CONSTRUCTED TO MEET THE MINIMUM CONDUIT ENTRANCE AREA. JACK(PHONE) ADJUSTABLE SHELVES WITH SURGE PROTECTION FIT EACH DOOR WITH A GASKET TO INSURE DUST TIGHT & WEATHERPROOF PROTECTION UNDER ALL WEATHER CONDITIONS. MANUAL CONTROL WEATHERPROOF MOMENTARY CONTACT SWITCH CONNECTED TO 6’-0" REINFORCED CORD STORED IN RECESS BEHIND SMALL DOOR IN LARGE DOOR. DISTRIBUTION PANEL ADJUSTABLE MOUNTING BRACKETS INSTALL TWO ADJUSTABLE SHELVES FOR TVS SYSTEM AND ONE ADJUSTABLE SHELVE FOR THE WIM SYSTEM. SECURE SMALL DOOR WITH A SUB-TREASURY LOCK #0357S AND KEYED ALIKE FOR #10 AS MANUFACTURED BY THE AMERICAN HARDWARE CO. NEW BRITIAN, CONN. 6. SECURE LARGE DOOR WITH A CCL LOCK #15481RS WITH A MATCH #2 KEY TO BE SUPPLIED TO NEW JERSEY DEPARTMENT OF TRANSPORTATION. FOR DOOR AND LOCK DETAILS, SEE DRAWING P-21 SHEET 2 OF 2, OF THE ELECTRICAL BUREAU SPECIFICATION EBM- TSC -ITB - 8. BDC-07D-03 - ORIGINAL SHEET BDC-11D-03 MISC. CHANGES 7. NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:51 scale= 30.000000:1.00000 5. WITH THE EXCEPTION OF LARGE DOOR LOCK DETAILS, ALL CABINET DIMENSIONS ARE APPROXIMATE. FRONT METER CABINET TYPE P-TMS NOT TO SCALE ( SHOWN WITH DOOR REMOVED ) 8. SECURE THE LARGE DOOR AT THE TOP AND BOTTOM OF THE CABINET BY A LOCKING BAR. ITS-704-31 9. INSTALL ALUMINUM VENT WITH SCREEN UNDER FRONT LIP ABOVE DOOR. NEW JERSEY DEPARTMENT OF TRANSPORTATION 10. THERMOSTAT TO BE INSTALLED IN TOP OF CABINET. 11. ENSURE THE MAIN DOOR HANDLE ROTATES INWARD. 12. MOUNT THE ELECTRIC SERVICE METER AND DISCONNECT PER METER CABINET ITS & FOUNDATION ITS TYPE MC DETAIL. 13. FOR FOUNDATION DETAILS SEE FOUNDATION, TYPE "D" OR TYPE "D-MC" ON THE FOUNDATION ITS TYPE C, C-MC, D & D-MC DETAIL. ITS DETAILS CONTROLLER CABINET TYPE P-TMS * * file= WIND SPEED / DIRECTION SENSOR CELLULAR ANTENNA GROUND RODS AT 10’ CAMERA PTZ TINNED GROUNDWIRE #3/0 AWG GROUND RODS AT 10’ STEEL TOWER WIVIS SENSOR AIR TEMPERATURE / RELATIVE HUMDITY TOWER / CABLE CLAMP SENSOR 3’-0" (TYP.) FLEXIBLE CONDUIT 10’-0" (TYP.) CABINET (SEE NOTE # 1) R P U SERVICE DISCONNECT SEE DETAIL "B" TOWER GROUNDING SEE DETAIL "A" SEE DETAIL "A" GROUND LEVEL EXISTING CHAIN LINK FENCE SEE PLANS GROUNDING GROUNDING CABLE TO SENSORS NON VEGETATIVE SURFACE FOUNDATION (FOR CONTROLLER TOWER DETAIL SEE ITS-704-19) TOWER RPU CONCRETE PAD 3’-0" 5’-0" pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE HEX HEAD SET SCREW TOWER LEG GATE GROUND LUG GROUND CABLE TO BUSSBAR CABINET FLOOR FLAT WASHER GROUND CABLE GATE, CHAIN LINK FENCE TO TOWER LEG SPLITE WASHER NUT GROUND LUG DETAIL "B" scale= 30.000000:1.00000 DETAIL "A" NOT TO SCALE ITS-704-32 BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:52 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS WEATHER STATION NOTE: ROADWAY WEATHER INFORMATION SYSTEM, WEATHER STATION INSTALL COPPER MESH OR STEEL WOOL IN ALL CONDUITS WITHIN THE RPU ENCLOSURE TO PREVENT RODENT INTRUSION. SHEET 1 OF 2 * * file= SEE DETAIL "A" 4" 9" " DIA. HOLES FOR " DIA. ANCHOR BOLTS (TYP.) 9" 3’-0" 1" THICK STEEL PLATE 2" 1’-0" 3" DIA. RIGID NON-METALLIC CONDUIT (TYP.) (TYP.) 3" DIA. RIGID NON-METALLIC CONDUIT 9" 4" C/C (TYP.) 4" 6" SQUARE 4" 9" 9" 9" RPU ENCLOSURE 4" DETAIL "A" 3’-0" SEE DETAIL "B" PLAN 2" X 2" X " STEEL. TUBE HORIZONAL LACING, 8 PIECES WELDED TO TOWER AND 4" X 4" X " TUBE STEEL TOWER " DIA. ANCHOR BOLT WITH NUTS & WASHERS FIXED POLE 4" X 4" X " 16 PIECES, LENGTH 1’ -10" (TYP. 4 PIECES NUTS FOR EACH BOLT) STEEL TUBE 1’-5" 3" 1’-3" 1" X " FLAT STOCK TOP 20’ NON-SHRINK GROUT (Fc = 5,000 PSI) 30’-0" #22 REBAR VERTICAL WITH 9" CC SPACING, 1" X " BOTTOM 10’ 6" X 6" X 1" STEEL PLATE 4" OF COVER 4 PIECES #13 REBAR HORIZONTAL WITH ALL SIDES HINGE POINT 1’-6" 4" C/C 4 MAIN ANGLE STEEL SPACING DETAIL "B" L 3" X 3" X " TOP 20’ pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE 4 MAIN ANGLE STEEL L 3" X 3" X " BOTTOM 10’ 2" X 2" X" 16 PIECES EMBEDED PLATE (TYP.) TRIANGULAR PLATE " THICK 2 PIECES WELDED TO 12" X 18" STEEL PLATE IN TRUSS 10’-0" FROM TOP OF 6" X 6" X 6" STEEL PLATE NOTES 1. ALL STEEL PLATES PER ASTM A36. 2. ALL STEEL TUBES PER ASTM A36 OR EQUAL. WINCH FOR GALVANIZED WIRE ROPE CABLE 6 X 19 IWRC " 3. ALL STEEL FLATE BAR PER ASTM A36. 4. ALL STEEL ANGLES PER ASTM A36. 5. ALL ANCHOR BOLTS PER ASTM A307 & GALVANIZED PER ASTM A153. 6. ALL ANCHOR BOLT NUTS PER ASTM A563 GRADE 1H OR ASTM 194 GRADE 2H. 6’-0" STEEL TOWER 7. ALL WELD FILLER MATERIAL PER ER70S-3, AWS 5.18. 5’-6" 8. ALL BOLTS PER ASTM A325 & GALVANIZED PER ASTM A153. 8" C/C 9. FABRICATE STRUCTURE TO SUPPORT THE DESIGN CRITERIA OF 2009 AASHTO STANDARD SPECIFICATIONS FOR STRUCTURE SUPPORTS. SPACING scale= 30.000000:1.00000 10. CONCRETE FOUNDATION PER ACI 301 & ACI 318 CONCRETE Fc = 3,000 PSI MIN. 11. REBAR Fy = 60,000 PSI MIN. 12. ALL WELDING PER AWS D1.1. NOT TO SCALE 13. ENTIRE STRUCTURE TO BE GALVANIZED PER ASTM A153 AFTER FABRICATION. SEE CONCRETE FOUNDATION DETAILS 14. ALL REBARS ARE DESIGNATED IN SOFT METRIC BAR SIZES. ITS-704-33 BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:52 NEW JERSEY DEPARTMENT OF TRANSPORTATION ITS DETAILS APPROX. 54 CU . FT. OF MIN. 3,000 PSI CONCRETE ROADWAY WEATHER INFORMATION SYSTEM, WEATHER STATION 4’-6" TOWER FOUNDATION SHEET 2 OF 2 * * file= SURFACE SENSOR " WIDE X 3" DEEP SAW KERF LINED UP WITH CENTER OF CAVITY WEATHERPROOF CONNECTOR LOCATE THE SURFACE SENSORS AN EQUAL DISTANCE BETWEEN THE CENTER LINE OF THE LANE AND THE CENTER LINE OF THE WHEEL TRACK. INSTALL SUB SURFAC TEMPERATURE PROBE IN ROADWAY SHOULDER. SENSOR CABLE CHISEL OUT TO FIT 2 LANE HIGHWAYS MULTI-LANE HIGHWAYS BRIDGE/ROADWAY AS SHOWN TRAFFIC FLOW TRAFFIC FLOW LEFT LANE TRACK RIGHT LANE TRACK CENTER OF LANE JUNCTION BOX RIGHT LANE TRACK BARRIER CURB EXPOSED RNMC AS SHOWN 1" FLEXIBLE RNMC LEFT LANE TRACK CENTER OF LANE RIGHT LANE TRACK CENTER OF LANE ROADWAY INSTALLATION TRAFFIC FLOW TRAFFIC FLOW SENSOR CABLE CONNECTOR LEFT LANE TRACK ON PLAN SENSOR CABLE GROUND WIRE BRIDGE ABUTMENT 6"X6"X4" JB 1" FLEXIBLE RNMC ANCHORED EVERY 5’ " SS ANCHOR, WASHERS, LOCK WASHERS AND SCREWS COVER 5" - 5" CORE HOLE " WIDE X 3" DEEP SAW CUT 1 " DIA. HOLE FOR SUBSURFACE LINED UP WITH CENTER OF CAVITY S TEMPERATURE PROBE CHISEL OUT TO FIT SENSOR CONNECTOR " TO 1" FEED THROUGH PROBE CABLE HOLE IN BRIDGE DECK pen table= \\Njdotprjws\v8system\NJDOTWS\Projects\NJDOTE (IF REQUIRED) BRIDGE INSTALLATION 1’-5" " WIDE X 3" DEEP SAW CUT SUBSURFACE TEMPERATURE PROBE SUBSURFACE TEMPERATURE PROBE INSTALLATION IN SHOULDER AREA 6-3/4" COREHOLE X 3-1/4" DEEP scale= 30.000000:1.00000 LINE UP WITH CENTER OF CAVITY TEMPERATURE SENSOR NOT TO SCALE ITS-704-34 NEW JERSEY DEPARTMENT OF TRANSPORTATION BDC-07D-03 - ORIGINAL SHEET MISC. CHANGES BDC-11D-03 NJDOT Design Services ID= TPOKEEG date= 27-SEP-2011 08:52 12" LONG X 1/2" WIDE X 3/4" DEEP SAW CUT ITS DETAILS WIRELESS INSTALLATION ROADWAY WEATHER INFORMATION SYSTEM, ROADWAY DEVICES * * file=