MODEL XR6 WIRING DIAGRAM Refer to the XR6 Installation Guide

advertisement
MODEL XR6 WIRING DIAGRAM
Refer to the XR6 Installation Guide (LT-0229) for a complete description of wiring connections.
Refer to the XR6 Programming Guide (LT-0230) for complete programming instructions.
NFPA 72
Household Fire Warning
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm
UL Recognized limited energy cable
Code, ANSI/NFPA 72-1996, (National Fire Protection Association, Batterymarch Park, Quincy, must be used for connection of all
MA 02269). Printed information describing proper installation, operation, testing, maintenance, initiating, indicating, and
evacuation planning, and repair service is to be provided with this equipment. Warning: Owner’s supplementary devices.
instruction notice, not to be removed by anyone except occupant.
Types of Service
J11
When used with the 350A
J16
1
Enclosure:
2
Command Processor Reset
RJ
Cable
Monitor
J7
3
suitable for Grade A Local and
Use DMP Model 306 Harness
4
Police Connect Mercantile
J7
Premises with basic line security,
AC wiring must be in conduit and exit
Grade A Local and Police Connect
out the left side of the panel enclosure.
J4
Mercantile Safe and Vault with
Wiring on
RJ SUP
terminals 5 - 26
basic line security, Grade B Central
must exit to the
Phone Jack Connector
Station and Grade A proprietary.
right and
maintain a 1/4”
See sections 17.3, 18.6, 19.2, and
separation from
U11
19.5 - 19.7.
the AC and
Household System
An alarm sounding device
must be installed indoors
so that it is clearly heard
in all sleeping areas.
Model 692
75mA @ 8 -16 VDC
Bell
GND Z4
Z5
Rear Tamper
Z6+ Z6-
1K W 1K W
1K W
Tamper protection
when required for
Model 350A Attack
Resistant Enclosure.
ZONE 6
ZONE 4
ZONE 3
ZONE 2
ZONE 1
22 GA. MIN BLACK
22 GA. MIN YELLOW
22 GA. MIN GREEN
Cold Water Pipe Earth Ground
22 GA. MIN RED
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 gauge wire: 40 feet
Bell
10.4 - 13.2 VDC
Total current:
1.5 Amps max. w/ 40 VA
600mA w/ 20 VA
Models 690, 790, 791,
793
100mA @ 8 - 16 VDC
Programmer Header J8
Use DMP Model 330 Harness
-B BELL GND RED YEL GRN BLK SMK Z1 GND Z2 Z3
16 - 18 gauge wire
Secondary Power
Supply
1.2 Amps max. charging
current. Use only 12 VDC
rechargeable batteries.
DMP Model 367. Replace
every 3 - 5 years.
Keypads
Models 670, 770, 771,
100mA @ 8 - 16 VDC
125mA with display lit
+B
Front Tamper
controlled
by switch.
RED
Model 324
16.5 VAC 20VA
Class 2 plug-in
PROG
AC
BLACK
Model 321
16.5 VAC 40VA
Class 2 plug-in
J8
AC
Output Header J11
All outputs must be
connected to devices
located within the same
room as the control
panel.
Use DMP Model 300
Harness.
EPROM
Socket
battery positive
wiring.
Suitable for Household Fire and
Grade A Household Burglary. Test
weekly.
DMP transformers:
Model 320
Plug into
120 VAC
16.5 VAC 40VA
outlet not
Class 2 wire-in
POWER LIMITED
All circuits on the Model
XR6 comply with the
requirements for inherent
power limitation and are
Class 2.
2-wire
smoke
detector
1K W
Smoke Output
100mA @ 10.4 - 13.2 VDC
Red
Terminal 11
Black
1K W
4-wire smoke detector
Up to 500mA auxiliary
current at 10.4 - 13.2
VDC from Terminal 7.
Power
Supervision
Relay
Smoke
Detector
+-
3.3k W
DMP Model 309
Zone 6 compatibility
identifier: A
Verification
Zone
6*
Control
Unit Delay
13.6 sec.
Maximum operating
range: 8.8 VDC 14.2 VDC.
See section 11.1 in the XR6
Installation Guide (LT-0229)
for a list of approved
2-wire smoke detectors.
Smoke
Model
Detector
Delay
______
_____ sec.
Heat detectors, manual pull stations, or any other
shorting device. Unlimited number of units.
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM
VERIFICATION FEATURE THAT RESULTS IN A DELAY OF
THE SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNITS PLUS
SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO OTHER SMOKE DETECTOR SHALL BE
CONNECTED TO THESE CIRCUITS UNLESS APPROVED
BY THE LOCAL AUTHORITY HAVING JURISDICTION.
LT-0445 (3/01)