University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Copper Hot Water Heating Boiler - 01/21/13 Section 235235 The manufacturer shall verify proper operation of the microprocessor control by electrically testing of all functions prior to shipping. A quality test report shall be shipped with each unit. Controller shall be Harmony Sequencer or approved equal by approved manufactures listed below. J. Boiler shall be RBI Futera III or approved equal by Patterson-Kelley or A.O. Smith Legend 2000. PART 3: EXECUTION 3.1 BOILER START-UP: Provide the services of a factory trained technician to place the boiler in operation and instruct the Owner's representative in operation and maintenance of the system. An operational test of the boiler performance shall be made at this time and the report submitted in triplicate to Architect. 3.2 GAS PIPING VENTS: Extend all gas regulator and switch vents to a point outside the building at least 10 feet above grade and 5 feet from any opening into the building. Terminate vent lines in a flash arrester. 3.3 BOILER COMBUSTION VENTS: Confirm boiler vent category and material system required for flue venting. Provide condensing trap loop for all condensing installations per boiler manufacturer’s instructions. 3.4 BOILER INSPECTION: A. Boiler shall be checked and piping inspected by the State Boiler Inspector prior to start-up. Contact the state Department of Labor office at 404-679-0687 regarding this inspection and pay all fees associated with the inspection. Contractor shall obtain boiler permit prior to final inspection. B. Submit report from inspector indicating that boiler installation has been inspected and accepted. 3.5 RELIEF VALVE: Extend relief valve discharge full size to floor drain. END OF SECTION 4 FMD NO. 1256976 100 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Air-Cooled Package Chiller - 01/21/13 Section 236428 SECTION 23 6428 AIR-COOLED PACKAGE CHILLER PART 1: GENERAL 1.1 DESCRIPTION: This section specifies the requirements for packaged air-cooled chillers. 1.2 RELATED SECTIONS: 1.3 1.4 A. Section 23 0010 General Provisions HVAC B. Section 23 0100 Operation and Maintenance of HVAC Systems C. Section 23 0500 Common Work Results for HVAC D. Section 23 0549 Vibration Isolation E. Section 23 0700 Mechanical Systems Insulation F. Section 23 2113 Hydronic Piping System G. Section 23 2500 Water Treatment System SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide data on unit performance including, but not limited to, entering water/air temperature, leaving water/air temperature, minimum capacity, total capacity, ARI part-load values, refrigerant pressures, EER, COP, maximum water flow, minimum water flow, nominal tonnage, ambient conditions, number of circuits, etc. C. Provide shop drawing showing chiller dimensions, weight, pressure rating, electrical requirements, service access requirements and pipe connection sizes and locations. D. A control diagram showing power and suggested interlock wiring, along with the necessary documentation of the interface and protocol utilized by the chiller control system shall be furnished by the manufacturer for use in incorporation into the control diagrams. E. Provide manufacturer’s instructions, indicate installation and support requirements. F. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. QUALITY ASSURANCE: Chiller capacity shall be rated in accordance with ARI 550/59098. 1 FMD NO. 1256976 101 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.5 STORAGE AND PROTECTION: protection of the chiller. Air-Cooled Package Chiller - 01/21/13 Section 236428 Contractor shall be responsible for storage and PART 2: PRODUCTS 2.1 AIR COOLED SCROLL CHILLER: A. The unit shall be a complete assembly consisting of condenser, cooler, scroll compressors, piping, controls, and weatherproof casing factory assembled, tested, packaged, and charged ready for operation. B. Chiller shall utilize R-22 or R-410a refrigerant. C. Compressors shall be hermetic scroll type with tip seals, suction cooled motor, vibration isolation mounts, and brazed connections. Compressor shall be provided with a five (5) year replacement warranty. Each compressor shall be provided with a completely independent refrigerant circuit. D. Provide hotgas bypass as required to achieve a minimum operating capacity of 20 tons. E. Cooler shall be accessible shell-in-tube type covered with 2" thick closed cell, foam plastic, vapor barrier insulation, protected against freeze-up by a thermostat controlled electric heater cable wrapped around the shell under the insulation. Fouling factor shall be 0.0005. Provide water nozzles with grooved mechanical couplings which will be field insulated. F. Refrigerant circuits shall include suction and discharge service valve, liquid line shutoff valve with charging port, removable core filter drier, moisture indicating sight glass, thermostatic expansion valves, low side pressure relief device and insulated suction line. G. Microprocessor controls shall be housed in a water tight enclosure, factory mounted and wired, providing all control functions including start up and shut down, leaving chilled water control, electronic expansion valve modulation, condenser fan sequencing, anti-recycle logic, automatic lead/lag starting and load limiting, and low ambient control to 0F. H. System Safeties: Shuts down compressor with manual reset required after the third trip in 90 minutes for high discharge pressure, low suction pressure, high pressure switch and motor protector. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings. I. Unit Safeties: Automatic reset type shutting down compressors on low ambient, low leaving chilled liquid temperature, under voltage and flow switch operation. Contractor shall provide flow switch and wiring per chiller manufacturer requirements. 2 FMD NO. 1256976 102 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Air-Cooled Package Chiller - 01/21/13 Section 236428 J. Alarm Contacts: Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (per compressor circuit) high discharge pressure, and low suction pressure. K. Capacity shall be as scheduled on the drawings. L. Chiller shall be wired for electrical service as scheduled. Electrical service enclosure and components shall have minimum short circuit withstand rating of 50,000 amps, RMS symmetrical. Unit shall have single point power disconnect switch, with the exception of the cooler heat trace circuit. M. Air cooled, electrically operated, chillers with condensers shall meet or exceed ASHRAE 90.1-2004 Performance Requirements: All capacities, Min Efficiency = 2.80 COP & 2.80 IPLV N. Chiller shall be Carrier 30RA, Trane CGA, or York YCAL. PART 3: EXECUTION 3.1 WINTERIZATION: All portions of exterior piping shall be heat taped before insulating, refer to Section 23 8237. 3.2 Contractor shall field sound attenuation kit. 3.3 Mount chiller on Type 3 neoprene pad isolators, refer to Section 23 0549. END OF SECTION 3 FMD NO. 1256976 103 BID NO. 36813636 FMD NO. 1256976 104 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Energy Recovery Unit - 01/21/13 Section 237200 SECTION 237200 ENERGY RECOVERY UNIT PART 1: GENERAL 1.1 DESCRIPTION: This section specifies requirements for both rooftop and indoor Energy Recovery Ventilator (ERV) units. 1.2 RELATED SECTIONS: 1.3 1.4 A. Section 23 0010 General Provisions HVAC B. Section 23 0100 Operation and Maintenance of HVAC Systems C. Section 23 3100 Ductwork SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide data on unit performance including, but not limited to, entering and leaving air temperatures, airflow and total static pressure, fan motor horsepower, total and sensible heat recovery. C. Provide shop drawing showing unit dimensions, weight, electrical requirements, service access requirements and duct connection sizes and locations. D. Provide manufacturer’s instructions, indicate installation and support requirements. E. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. QUALITY ASSURANCE: A. Unit shall be carry UL label of approval and bear AMCA certified rating seals for air performance. B. The ERV manufacturer shall provide a one-year warranty minimum on all parts. Enthalpy wheels shall carry a 5-year warranty. PART 2: PRODUCTS 2.1 ENERGY RECOVERY VENTILATORS: A. Energy Recovery Ventilators (ERV) shall be enthalpy-type, air to air heat exchangers utilizing desiccant-type heat wheels. Units shall include motorized heat wheel assemby, outside air supply fan, exhaust fan, supply filter, pre-wired single point electrical connection, motor starter with thermal overload protection, disconnect switch and 24 volt controls with dry contacts for interface with the building automation system. ERVs shall be rooftop mounted as scheduled on the Drawings. Minimum design efficiency shall be 95%. 1 FMD NO. 1256976 105 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Energy Recovery Unit - 01/21/13 Section 237200 B. Housing shall be heavy gage galvanized steel with 1" rigid board fiberglass insulation with foil facing. Maximum unit height shall not exceed 8’-6”. Hinged and gasketed access doors shall be provided for both supply and exhaust fan compartments. Heat wheel shall be easily accessible for inspection, removal and cleaning. Units scheduled for rooftop installation shall have weather resistant gasketing and seals and housing shall be suitable for outdoor installations. C. Provide motorized dampers on the unit’s outside air intake and the unit’s exhaust air discharge. Dampers shall be interlocked to open when fans run. Maximum damper leakage rate shall be 10 CFM/sq. ft. at 1.0 inch static pressure. D. Supply fan and exhaust fan shall be arranged for draw through configuration. Fans shall be forward curved type, statically and dynamically balanced at the factory prior to shipment. Adjustable sheaves shall be provided for independent balancing of supply and exhaust. E. Provide Economizer Control with Variable Frequency Drive on energy recovery wheel motor to allow modulating control of unit leaving air temperature. F. Motors shall be high-efficiency, heavy-duty type, furnished at specified voltage and phase. Bearings shall be selected for minimum (L10) life in excess 100,000 hours. G. Bearing Protection Ring: All motors being controlled by the use of a Variable Frequency Drive (VFD) shall be provided with a factory installed grounding ring to prevent fluting damage. Ring shall be continuous. Bearing Protection Ring shall be AEGIS model SGR. H. Airflow direction and inlet and outlet locations shall be as shown on Drawing. Rooftop ERVs shall include supply and exhaust weather hoods to prevent water entry. I. Filters shall be provided upstream of the supply fan and upstream of the exhaust side of the heat wheel. Filters shall be 6" thick UL listed Class 2 type with a minimum MERV 10 Rating (ASHRAE 52.2-1999) with not more than a 0.25" initial pressure loss at 500 FPM face velocity. Filters shall be Airguard, American Air Filter, Farr or equal. J. Rooftop ERVs shall include a full perimeter type roof curb supplied by unit manufacturer for field assembly. Curb shall be 12” high (minimum) insulated, with raised cant. K. Ventilator shall be Greenheck ERV, Venmar, Spinnaker RERV, or Penn Barry ERV. PART 3: EXECUTION 3.1 INSTALLATION: A. See drawings for scheduled capacities and requirements. B. Install ERV units per manufacturer’s installation instructions. END OF SECTION 2 FMD NO. 1256976 106 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Central Station Air Handlers - 01/21/13 Section 237300 SECTION 237300 CENTRAL STATION AIR HANDLERS PART 1: GENERAL 1.1 DESCRIPTION: This section specifies the interior modular type central station air handling unit requirements. 1.2 RELATED SECTIONS: 1.3 1.4 A. Section 23 0010 General Provisions HVAC B. Section 23 0100 Operation and Maintenance of HVAC Systems C. Section 23 0500 Common Work Results for HVAC D. Section 23 2113 Hydronic Piping E. Section 23 0514 Variable Frequency Drives F. Section 23 4100 Air Filters SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide data on unit performance including, but not limited to, entering and leaving air temperatures, fan airflow and associated total and external static pressure, fan motor horsepower, fan curves and coil capacity. C. Provide shop drawing showing unit dimensions, weight, electrical requirements, service access requirements and duct and piping connection sizes and locations. D. Provide manufacturer’s instructions, indicate installation and support requirements. E. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. F. Manufacturer shall ensure that submitted unit fits into allocated space with sufficient space for all coil pulls, filter pulls, and UV light pulls. QUALITY ASSURANCE: A. Fan performance shall be rated in accordance with AMCA 210. B. Coil performance shall be rated in accordance with ARI 410. C. Air handling unit shall be assembled in accordance with ARI 430 (when applicable). D. Sound performance data shall be rated per ARI 260. E. The AHU manufacturer shall provide a one-year warranty minimum on all parts and labor. 1 FMD NO. 1256976 107 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Central Station Air Handlers - 01/21/13 Section 237300 PART 2: PRODUCTS 2.1 CENTRAL STATION AIR HANDLING UNITS: A. Units shall be of the double wall type with arrangement and capacities as scheduled and shown on the drawings. All air-handling units shall be medium pressure type, rated for 6” positive static and 4” negative static pressure. B. Unit casing shall be constructed of removable, insulated double wall panels. Panels shall be gasketed where in contact with the unit frame. Maximum unit size shall not exceed dimensions shown on drawings. Module-to-module connections shall have gasketing between metal-to-metal surfaces. Outer wall shall be G90 galvanized steel, minimum 18 Ga. The inner wall shall be perforated galvanized steel upstream of the cooling coil and solid galvanized steel at and downstream of the cooling coil. Unit casing will be insulated with spray injected foam to achieve a minimum thermal resistance of R13hr-ft2-°F/BTU. C. Access doors, where shown or specified, shall be hinged, double wall type with full perimeter gasketing. Doors shall have quick operating latching handles on interior and exterior of unit. Insulation and thermal breaks shall be sufficient to prevent exterior unit casing condensation under all operating conditions. D. View Windows, where shown or specified, shall be provided in the access door of that section. E. Drain pans, where scheduled or specified shall be insulated double wall stainless steel construction. 1. Drain pans will be double sloped to a single drain connection (per pan) at least 1/8” per foot, and have no horizontal surfaces. 2. Drain connection material will be the same as the drain pan material. 3. Drain connections will be welded to the drain pans. 4. Drain pans will have at least 1” clearance between pan and associated coil supports. F. Provide a minimum of 6” galvanized steel base rail support frame to insure sufficient unit height for the condensate drain trap. G. Provide marine-type vapor-proof lights in the sections of the unit as shown on the drawings. Lights shall be factory wired in EMT conduit per NEC requirements to a single light switch with "ON" indicating pilot light located on the exterior of the unit and adjacent to the supply fan access door. H. Fan types shall be as specified on drawings. Fan Section shall include the belt driven fan and motor, all mounted on a spring-isolated (2” deflection) base with a flexible duct connection. Fan belts shall be synchronous type. Fan bearings shall be self-aligning with a L50 (minimum average life) of 200,000 hours. Fan bearing grease lines shall extend to the service access side of the fan for forward curved fans. Fan wheel and shaft shall not exce3ed 75% of their first critical speed at any cataloged fan speed. Fans shall provide operation down to 20% ofrated CFM. 2 FMD NO. 1256976 108 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Central Station Air Handlers - 01/21/13 Section 237300 Fan and drives shall be statically and dynamically balanced and run tested in the unit casing. Provide a man-sized access door into the fan section. 1. Plenum fans, when scheduled, shall be single width, single inlet, and Class II type, constructed of steel and painted with baked enamel. Blades shall be double thickness design. I. Fan motors shall be open drip proof high efficiency type as specified in Section 23 0500. J. Bearing Protection Ring: All motors being controlled by the use of a Variable Frequency Drive (VFD) shall be provided with a factory installed grounding ring to prevent fluting damage. Ring shall be continuous. Bearing Protection Ring shall be AEGIS model SGR. K. Coil Sections shall be provided to meet the scheduled capacities and air tested to 325 psig, minimum. Cooling coils shall be provided with a drain pan. If multiple cooling coils are stacked, an intermediate drain pan shall be provided with drop tubes down to the main drain pan. All piping connections shall extend through the casing with grommets, all headers shall be located inside the unit casing. 1. Chilled Water coils shall consist of 5/8" O.D. copper tubes with 0.02” wall thickness, aluminum fins, copper headers and 304 stainless steel casings with same end connections. Cooling coils shall be selected to eliminate any moisture carryover at face velocity scheduled. a. 2. Split Row Coils shall be constructed as one coil with continuous fins across the coil splits. The split coil shall be internally piped so that the bottom and top half of the coil shall each be capable of providing 50% capacity of the total capacity as scheduled. The split coil shall be externally piped to the exterior of the AHU casing to accommodate dedicated control valves to each section of the coil. Split row coils shall be provided as scheduled on drawings. Hot Water coils shall consist of 5/8" O.D. copper tubes with 0.02” wall thickness, aluminum fins, copper headers and 304 stainless steel casings with same end connections. L. Filter Section shall include the scheduled filters and associated racks, an access door and any blank-off required to prevent filter bypass. M. Blank Access Section shall include an access door. Section shall be as shown on drawings. N. Damper Section shall include the damper assembly for the specific application and an access door. Dampers shall be low leakage, type with double wall airfoil blades, jamb and edge seals, and opposed blade action. 3. Economizer Section shall include return air damper, outside air damper, and relief air damper. 4. Mixing Section shall include return air damper, outside air damper. O. UVC Emitters/Lamps 3 FMD NO. 1256976 109 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Central Station Air Handlers - 01/21/13 Section 237300 5. The UV dosage shall be calculated for probable rating of URV-13, 99% air disinfection (S.marcescens) at air velocity and temperature and shall be adequate to deactivate microbial growth on all exposed surfaces. Lamps shall be positioned for a 360 degree disinfection zone. the UV System shall be stainless steel and aluminum construction. Any exposed screws of fasteners shall be stainless steel. Lamp supports shall be stainless steel. The device submitted shall be UL Listed as an Air Duct Mounted Accessory and meet all applicable UL standards. Manufactures UL file number shall be permanently marked on the exterior of the product. The lamp shall be generic and available on the open market and not product specific. Lamps shall be by Phillips, GE, Sylvania, Ushio or owner preapproved equal. 6. UV Disinfection System shall be warranted to be free of defects in workmanship and material for a period of 5 years from date of shipment. 7. Lamp life shall be 9,000 hours minimum with no more than 20% loss of output after one year of continuous operation. 8. Safety interlocks/features shall be provided to limit hazard to operating staff. 9. Safety Design Guidance: a. In-duct systems should be fully enclosed to prevent leakage of UV radiation to unprotected persons or materials outside of the HVAC equipment. b. All access panels or doors to the lamp chamber and panels or doors to adjacent chambers where UV radiation may penetrate or be reflected should have warning labels in appropriate languages. Labels should be on the outside of each panel or door, in a prominent location visible to people accessing the system. c. Lamp chambers should have electrical disconnect devices. Positive disconnection devices are preferred over switches. Disconnection devices must be able to be locked or tagged out, and should be located outside the lamp chamber, next to the chamber’s primary access panel or door. Switches should be wired in series so that opening any access door deenergizes the system. On/off switches for UV lamps must not be located in the same location as general room lighting; instead, they must be in a location that only authorized persons can access, and should be locked to ensure that they are not accidentally turned on or off. d. The lamp chamber should have one or more viewports of UVC-absorbing materials. Viewports should be sized and located to allow an operating UV system to be viewed from outside of the HVAC equipment. e. Air Handling Units containing UV lighting systems systems should have on/off switches and an electrical disconnect device on the louvers. If UV radiation measurements at the time of initial installation exceed the recommended exposure limit, all highly UV-reflecting materials should be removed, replaced, or covered. UV-absorbing paints containing titanium oxide can be used on ceilings and walls to minimize reflectance in the occupied space. 4 FMD NO. 1256976 110 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) f. Central Station Air Handlers - 01/21/13 Section 237300 Warning labels must be posted on all upper-air UV fixtures to alert personnel of potential eye and skin hazards. Damaged or illegible labels must be replaced as a high priority. Warning labels must contain the following information: (1) Wall sign for Air Handling Units UVGI: Caution: Ultraviolet energy. Switch off lamps before entering area. (2) General warning posted near UVGI lamps: Caution: Ultraviolet energy. Protect eyes and skin. (3) Warning posted on the door of air handlers where UVGI is present in ductwork: Caution: Ultraviolet energy in duct. Do not switch off safety button or activate lamps with door open. 10. Personnel Safety Training a. Workers should be provided with as much training as necessary, including health and safety training, and some degree of training in handling lamps and materials. Workers should be made aware of hazards in the work area and trained in precautions to protect themselves. Training topics include (1) UV exposure hazards (2) Electrical safety (3) Lock-out/tag-out (4) Health hazards of mercury (5) Rotating machinery (6) Slippery condensate pans (7) Sharp unfinished edges (8) Confined-space entry (if applicable) (9) Emergency procedures b. Workers expected to clean up broken lamps should be trained in proper protection, cleanup, and disposal. c. No personnel should be subject to direct UV exposure, but if exposure is unavoidable, personnel should wear protective clothing (no exposed skin), protective eyewear, and gloves. Most eyewear, including prescription glasses, area sufficient to protect eyes from UV, but not all offer complete coverage; standard-issue protective goggles may be the best alternative. 5 FMD NO. 1256976 111 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 11. Central Station Air Handlers - 01/21/13 Section 237300 d. If individual lamp operating condition must be observed, this should preferably be done using the viewing window(s). e. Access to lamps should only be allowed when lamps are de-energized. The lamps should be turned off before air-handling unit (AHU) or fan shutdown to allow the lamps to cool and to purge any ozone in the lamp chamber (if ozone-producing lamps are used). If AHUs or fans are de-energized first, the lamp chamber should be opened and allowed to ventilate for several minutes. Workers should always wear protective eyewear and puncture-resistant gloves for protection in case a lamp breaks. f. Access to the lamp chamber should follow a site-specific lock-out/tag-out procedure. Do not rely on panel and door safety switches as the sole method to ensure lamp de-energizing. Doors may be inadvertently closed or switches may be inadvertently contacted, resulted in unexpected lamp activation. g. If workers will enter the condensate are of equipment, the condensate pan should be drained and any residual water removed. h. In general, avoid performance readings with the fan running and workers inside an AHU (e.g., to test for output reduction caused by air cooling). Tests of this nature should be instrumented and monitored from outside the equipment. During maintenance, renovation, or repair work in areas where UV systems are present, all UVGI systems must be deactivated before personnel enter the area. P. Shipping splits will be provided as necessary to fit the units into place. Lifting lugs will be provided where required for proper lifting. Shipping splits shall be coordinated with mechanical contractor prior to units being released for construction. Q. Air Handling Units shall conform to the following Acoustical Criteria at a minimum: Ducted Discharge 63 125 250 500 1000 2000 4000 8000 99 100 95 91 85 81 76 75 R. Air units shall be York Solution – High Performance, Trane Performance Climate Changer or approved equal by Temtrol. 2.2 WARRANTY: Manufacturer shall warranty unit for eighteen (18) months from date of shipment or twelve (12) months from date of start-up – whichever comes first. The warranty should included Parts and Labor. Warranty does not include parts associated with routine maintenance, such as belts, air filters, etc. Warranty does not extend to alterations, modifications, or external components installed after unit is shipped. PART 3: EXECUTION 3.1 Provide one set of spare drive belts for each fan. 6 FMD NO. 1256976 112 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Central Station Air Handlers - 01/21/13 Section 237300 3.2 Provide separate filter gauges to measure pressure drop across each filter bank. See Section 23 4100. 3.3 Adjust vibration isolators fan section after operation of equipment begins. Secure isolators to supports when finally set. 3.4 Bolt unit anchors to slab or pad at anchor points. 3.5 Provide airtight seal at each electrical connection to unit. 3.6 DELIVERY A. Unpainted units will be wrapped prior to shipment. B. Openings will be protected against damage from shipping C. Loose-shipped items will be packed, protected and secured with units. D. Largest Shipping split section shall not exceed 42” wide without prior approval from engineer. END OF SECTION 7 FMD NO. 1256976 113 BID NO. 36813636 FMD NO. 1256976 114 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Powered Induction Terminals - 01/21/13 Section 238226 SECTION 238226 POWERED INDUCTION TERMINALS PART 1: GENERAL 1.1 DESCRIPTION: This section specifies the requirements for fan powered induction units and accessories. 1.2 RELATED SECTIONS: A. Section 23 00 10 General Provisions HVAC B. Section 23 01 00 Operation and Maintenance of HVAC Systems C. Section 23 31 00 Ductwork 1.3 SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide data on unit performance including, but not limited to, entering and leaving air temperatures, heating coil capacity, airflow and total static pressure, and supply fan motor horsepower. C. Provide shop drawing showing unit dimensions, weight, electrical requirements, service access requirements and duct and piping connection sizes and locations. D. Provide manufacturer’s instructions, indicate installation and support requirements. E. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. 1.4 QUALITY ASSURANCE: Units shall be tested and rated in accordance with ADC 1062R4. PART 2: PRODUCTS 2.1 POWERED INDUCTION TERMINALS: A. Terminals shall be digital type. Casings shall be minimum 22 gauge, and shall be internally lined with a minimum ¾ inch thick, dual density fiberglass insulation with a solid sheet metal liner constructed from zinc-coated steel which complies with UL-181 and NFPA-90A. Any cut edges of fiberglass exposed to the airstream shall be coated with an NFPA-90A approved sealant. Liner surface shall have an EPA registered, anti-microbial agent coating to guard against potential growth of fungus and bacteria and have passed the testing of ASTM C 1138, G21 and G22 respectively Primary air valve shall be field adjustable pressure independent type with control to ±5% of rated flow at 4" inlet static pressure. Leakage rate shall not exceed 5% at 2" static pressure. B. Fan shall be forward curved type with resilient isolation and direct drive Electronically Commutated Motor (ECM), with brushless DC motor and integral inverter and microprocessor based motor controller. 1 FMD NO. 1256976 115 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Powered Induction Terminals - 01/21/13 Section 238226 Electronic speed controller switch shall be mounted on the side of the housing capable of resetting with a screwdriver. Electronic speed controller shall be capable of accepting 0-10VDC or 0-20 mA signal from the DDC system for remote adjustment. Fan shall be capable of gradual start when energized. Fan shall be provided with backdraft damper. Terminals shall be furnished with a side or bottom access filter rack at the air inlet with 1” throwaway filters. C. Hot water coils shall be copper tubes mechanically bonded to aluminum fins mounted in galvanized casings. Coils shall be one row where possible to meet capacities scheduled, rated for working pressure of 200 psi minimum with connections on same side. Coils shall be factory mounted on discharge of terminal units. D. Control manufactures digital control module shall be factory mounted on side of terminal. All sensors valves and actuators shall be factory mounted and wired. Supply voltage to controller shall be no more than 24 volts. E. Unit fan motors and duct heaters shall be wired for power as scheduled on drawings. F. Motors shall be wired for not less than 265 volts when service voltage is 277 or 480 volts and not less than 200 volts when service voltage is 208 volts. Power wiring for fan and heater shall be internally wired, fused and terminated in a junction box on the side of the unit to allow single point electrical service wiring. G. Unit sound power levels with fan operation on low or medium speed, or with fan off, shall not exceed the following at 1" differential pressure loss for nominal primary air size listed: Octave band Casing radiated noise Discharge noise: 1400 CFM unit 2000 CFM unit 1 72 2 70 3 61 4 60 5 57 6 56 7 66 8 65 80 83 69 72 58 62 55 57 53 55 50 53 48 52 50 50 H. Fan selection shall be based on low speed (two speed units), or medium speed (three speed units). I. All units scheduled to include a PIU manufacturer’s Discharge Attenuator section shall be provided with a 3 foot internally insulated attenuator that complies with UL 181 and NFPA 90A. Attenuator shall be rectangular opening with slip and drive cleat connection. J. Provide manufacturer’s field installed hanger brackets with spring isolators. K. Capacities shall be as scheduled on the drawings. L. Units shall be E.H. Price, Envirotech, Metal Aire, Titus, or Tuttle & Bailey. PART 3: EXECUTION 3.1 Hang units from the structure with threaded rods and manufacturer’s field installed hanger brackets with spring isolators. No hanger straps and screws shall be permitted. 2 FMD NO. 1256976 116 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Powered Induction Terminals - 01/21/13 Section 238226 3.2 Provide flex connectors on outlets of terminals, and maximum of 2' length of flexible duct inlet connection. 3.3 Coordinate exact unit locations to avoid light fixtures and walls to structure and to provide electrical panel access. END OF SECTION 3 FMD NO. 1256976 117 BID NO. 36813636 FMD NO. 1256976 118 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Electric Heaters - 01/21/13 Section 238237 SECTION 23 8237 MISCELLANEOUS ELECTRIC HEATERS PART 1: GENERAL 1.1 DESCRIPTION: This section specifies the requirements for electric heating equipment and heat tape. 1.2 RELATED SECTIONS: A. Section 23 0010 General Provisions HVAC B. Section 23 0100 Operation and Maintenance of HVAC Systems C. Section 23 0500 Common Work Results for HVAC 1.3 SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide data on heater performance including, but not limited to, entering and leaving air temperatures, capacity, and airflow. C. Provide shop drawing showing heater dimensions, weight, service access requirements and electrical requirements. D. Provide manufacturer’s instructions, indicate installation and support requirements. E. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. 1.4 QUALITY ASSURANCE: A. All electric heating equipment shall be U.L. listed and so labeled. B. Unit heaters, cabinet heaters and wall heaters shall be the products of one manufacturer. PART 2: PRODUCTS 2.1 ELECTRIC WALL HEATERS: A. Heaters shall be complete with fully enclosed permanently lubricated motor with fan, heating elements, inlet and outlet grilles, integral built-in tamper proof thermostat, automatic reset overheat protection, disconnect switch, wall box and cover. B. Cabinet design shall be of the surface mounted type providing an air seal to prevent dirt steaks and leaks along the wall surface. Inlet and outlet grilles shall be of 16 gauge steel, bar grille type to prevent insertion of objects into the fan or heating element. C. Heating elements shall consist of steel sheathed enclosed, finned tubular heaters. An integral two-pole terminal block shall be provided for wiring connections for each heater. 1 FMD NO. 1256976 119 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Electric Heaters - 01/21/13 Section 238237 D. The built-in thermostat shall be of the sensitive bulb and capillary type, fully enclosed, snap action to prevent radio and television interference. Thermostat adjustment shall be accessible only by using a narrow blade screwdriver inserted through the front grille. E. Heaters capacity shall be as scheduled on the drawings. F. Heaters shall be Q-Mark AWH-4000 or comparable by Berko, Markel or Raywall. 2.2 ELECTRIC HEAT TAPE: Heating tape shall be U.L. listed, 8 watts per foot (see requirements listed under Execution), covered with FEB Teflon jacket. Furnish junction box termination kit and thermostat for surface mounting to cycle heat off above 40F. ambient. Heat tape shall be Raychem XL-trace, Chromalox, or equivalent. PART 3: EXECUTION 3.1 Install heaters in accordance with manufacturer's U.L. listing for minimum clearance. 3.2 DUCT HEATERS: Connections to ductwork shall be air tight. Install heaters so that panel door will open fully. 3.3 UNIT HEATERS: Mount electric unit heaters as high as possible 3.4 HEAT TAPE: A. Install heat tape on all water piping located outside the building. Install heat tape prior to insulating pipe. B. Install heat tape in the watt density required to protect the insulated pipe from freezing with ambient temperatures down to -10ºF, as recommended by tape manufacturer. END OF SECTION 2 FMD NO. 1256976 120 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Grilles, Registers, & Diffusers- 01/21/13 Section 233713 SECTION 26 0000 ELECTRICAL GENERAL PROVISIONS PART 1: GENERAL 1.1 1.2 1.3 SCOPE A. This section applies to all Sections of Division 26 – Electrical. B. The general provisions of the contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this section and in all sections of this division. WORK INCLUDED A. Provide all labor, tools, and materials required for a complete and fully operational installation, as described on the drawings or in the specification. B. The work shall be installed in a neat and workmanlike manner. WORK NOT INCLUDED UNDER DIVISION 26 A. The following items of work are specified under other divisions of the specification: 1. 2. 3. 4. Temporary service for construction. Electric motors. Electric heaters unless otherwise noted on the drawings. Control and interlock wiring for work furnished under other divisions, except where specifically required under this division. 5. Access panels in walls or ceilings. 6. Field finish painting, except for field painting of electrical material with paint supplied by the manufacturer of the material. 7. Starters for certain items of equipment are furnished under other divisions for installation under this division. B. 1.4 Refer to other sections of this division for work required in connection with the above items. DEFINITIONS A. “Provide”: furnish and install, complete and ready for operation. B. “Install”: receive, mount, and connect, complete and ready for operation. C. “Wiring”: wires and cables installed with all required raceways, connectors, and fittings. D. “Concealed”: not exposed to view; embedded in masonry or other construction; in furred spaces or above suspended ceilings; below grade. 1 FMD NO. 1256976 121 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.5 E. “Exposed”: not concealed; not embedded or installed underground; under raised floors; inside trenches, tunnels, and basements, inside built-up HVAC equipment, crawl spaces, and accessible attics. F. “The Drawings”: that portion of the contract drawings annotated as electrical. G. “Furnish”: Supply, deliver to job site, protect and store. ABBREVIATIONS A. The abbreviations used on the drawings and in the specification are defined as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 1.6 Grilles, Registers, & Diffusers- 01/21/13 Section 233713 “AC”: Alternating Current “AFF”: Height above Finished Floor “AIC”: Ampere Interrupting Capacity “AICR”: Ampere Interrupting Current Rating “AHJ”: Authority Having Jurisdiction “NEC”: National Electrical Code “NIC”: Not in the Contract “NF”: or “N/F”: Non-fused “30A/2P”: Example of a circuit designation for a 30 Amp 2-Pole fused switch or a 30 Amp 2-Pole circuit breaker or device. “FBO”: Furnished by Others “EC”: Electrical Contractor “EX”: Existing to Remain “EXR”: Existing Relocated – new location indicated on the drawings. “HP”: Horsepower “kVA”: Kilovolt Ampere “kW”: Kilowatt “MCC”: Motor Control Center “MLO”: Main Lugs Only “NTS”: Not to Scale “WP”: Weatherproof CODES, RULES, AND REGULATIONS A. Comply with the following: 1. The edition of the National Electrical Code being enforced for this project by the local inspection authority. 2. All applicable laws and ordinances. 3. The rules and regulations of electric utility company serving the project applicable to the installation of service and metering equipment. 4. The rules and regulations of the telephone company serving the project applicable to the work required for routing telephone service into the facility. B. Give all necessary notices, obtain all required permits, and pay all inspection and other fees imposed by Authorities Having Jurisdiction over the work. 2 FMD NO. 1256976 122 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.7 STANDARDS A. The standards of the following organizations shall be applicable to the work: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. B. 1.8 1.9 Grilles, Registers, & Diffusers- 01/21/13 Section 233713 The National Fire Protection Association (NFPA) Underwriters Laboratories (U/L) National Electrical Manufacturers Association (NEMA) American National Standards Institute (ANSI) Institute of Electrical and Electronic Engineers (IEEE) Insulated Power Cable Engineers Association (IPECA) Illuminating Engineering Society of North America (IESNA) National Electrical Testing Association (NETA) National Electrical Contractors Association (NECA), Standard of Installation American Society for Testing and Materials (ASTM) Comply with the latest editions and Georgia Amendments of standards applicable to the work. MATERIALS A. All material shall be new, and shall comply with the indicated standards. B. All material shall be UL labeled or UL listed, except where the material is of a type not included in the UL listing service, in which case the material shall comply with other applicable industry standards and the contractor shall provide any examinations or certifications required by the local inspection authority in lieu of UL listing. C. All material shall be of a suitable type and rating for the intended use, and shall be installed in conformance with the instructions and recommendations of the manufacturer. DRAWINGS A. The drawings are schematic in nature and do not indicate all of the required details of the work. All materials customarily considered to be a part of the electrical work and normally required for a complete and operational installation, shall be provided without additional cost to the Owner. B. Refer also to the drawings of all other trades to coordinate the electrical installation. C. Equipment of other trades is shown schematically on the electrical drawings. Examine the drawings of the trade providing the equipment before roughing in the connections for it. Connect the equipment where actually installed, including wiring through any line voltage controllers, without any additional cost to the Owner. 3 FMD NO. 1256976 123 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.10 1.11 Grilles, Registers, & Diffusers- 01/21/13 Section 233713 D. Prior to roughing in circuits for equipment furnished by other trades, and prior to releasing for manufacture panelboards, starters or motor control centers feeding such equipment coordinate the electrical provisions being planned with the trade providing the equipment and submit any conflicts in writing. E. The Architect directs the location of any electrical outlet, or wall switch, or luminaries, or other equipment, to a location within 10 feet of the location shown on the drawings at no additional cost to the Owner provided such relocation is made prior to the installation of the equipment being relocated. SUBMITTALS A. Submit shop drawings in the manner and form described elsewhere in the contract requirements. B. Submittals are required for material as noted in other sections of this division. C. Check shop drawings prior to submission and provide date and signature of checker on each item. Note all corrections. Note any requested deviation from the drawings or specification, or if none, then so indicate. The Architect shall return documents without review where submitted without prior review by the contractor. D. Review of submittals will be only for general conformance with the design concept indicated on the drawings and in the specification and general compliance with the information given in the Contract Documents. Review will be made only of information clearly and specifically indicated in the submittal, and does not imply the acceptability of details, which are not so described in the submittal. Approval of a specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the Work of all trades; and performing all work in a satisfactory manner. E. Review of the submittal documents by the Architect does not relieve the contractor of the responsibility to comply with all requirements of the Contract Documents. PROJECT CLOSEOUT A. Furnish closeout documents in the manner and form described elsewhere in the Contract Documents. B. Closeout documents shall include the following: 1. Final shop drawings. 2. As-built drawings including as-built field layout drawings. 3. Operation and maintenance manuals. 4 FMD NO. 1256976 124 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Grilles, Registers, & Diffusers- 01/21/13 Section 233713 4. Receipts from the Owner stating that he has received satisfactory operational demonstrations and instruction for electrical systems. 5. Signed receipts from the Owner for spare parts and materials that are specified to be furnished. 6. Written guarantee. 7. All required certifications, including certificate of inspection approval of the code-enforcing authority. 8. All required test reports (include in operations and maintenance manual). 1.12 1.13 Record DRAWINGS and specifications A. Provide record drawings and specifications in the manner and form described elsewhere in the Contract Documents. B. Record drawings shall be maintained at the jobsite, and shall be available for review during construction. C. Record the final arrangement of the work and exact locations of the work as installed. Provide photographs of buried grounding work prior to backfill of trenches. D. Record drawings and specifications shall be kept current during the course of construction of the work. OPERATION AND MAINTENCE MANUALS A. Provide minimum of (3) copies of operation and maintenance manuals in the manner and form described elsewhere in the contract requirements. Manuals shall be typewritten, indexed, tabbed, and loose leaf bound in heavy duty 3-ring binders. B. Manuals shall include the following: 1. 2. 3. 4. 5. Operating instructions customized to this specific project Maintenance instructions Parts list Descriptive literature Location, telephone number and contact information of contractors, distributors, dealers and authorized service agents. 6. Test reports and certifications. 7. Record copies of all shop or submittal drawings and data 8. Copies of all software on diskette or compact disk, licensed to the Owner. C. Maintenance instructions and parts lists shall include the most detailed and advanced publications available from the equipment manufacturer. D. Demonstrate the operation of the equipment to the Owner, including instruction in its use and operation. Provide instruction by manufacturers representatives where specified. 5 FMD NO. 1256976 125 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) E. 1.14 1.15 Grilles, Registers, & Diffusers- 01/21/13 Section 233713 Provide operation and maintenance manuals for equipment and systems as specifically by the sections in Division 26. SPARE PARTS A. Furnish spare parts as specified by the sections in Division 26. B. Turn over spare parts to Owners representative. Store on site as directed by the Owner. Obtain written receipt detailing specific spare parts turned over and submit with close-out documents. C. Replace at no cost to the Owner any spare parts used from the Owners stock prior to substantial completion or for warranty related repairs. GENERAL TESTING A. Test all parts of the work to verify compliance with the drawings and specification. B. Verify tightness of all mechanical and electrical connections. C. Verify integrity of all wiring systems to assure continuity, absence of unintentional grounds, and integrity of required grounds. D. Perform any required special factory or field testing as specified in the other sections of this division. Provide all wiring, instruments, and personnel required to complete these tests. E. Where other requirements of this division require testing in the presence of the Architect, provide at least seven (7) business days advance written notice of such testing to the Architect. F. Where other requirements of this division require submission of written records of tests and test results, accumulate and submit all such reports and include as a separate section in the operations and maintenance manuals described elsewhere in this section. END OF SECTION 26 0000 6 FMD NO. 1256976 126 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Duct-Mounted Humidifier - 01/21/13 Section 238413 SECTION 23 8413 DUCT-MOUNTED HUMIDIFIER PART 1: GENERAL 1.1 DESCRIPTION: This section specifies the requirements for electric heating equipment and heat tape. 1.2 RELATED SECTIONS: A. Section 23 0010 General Provisions HVAC B. Section 23 0100 Operation and Maintenance of HVAC Systems C. Section 23 0500 Common Work Results for HVAC 1.3 SUBMITTALS: A. See General Conditions for submittal procedure. B. Provide product data including, but not limited to, capacity, entering and leaving air conditions and absorption requirements. C. Provide shop drawing showing unit dimensions, construction and fabrication, weight, electrical requirements, service access requirements and accessories. D. Provide manufacturer’s instructions, indicate installation and support requirements. E. Provide operation and maintenance procedures; include start-up instructions, assembly drawings and parts list. 1.4 QUALITY ASSURANCE: A. Humidifiers shall be U.L. or E.T.L. listed. B. Product shall be provided with a two-year warranty. PART 2: PRODUCTS 2.1 DUCT HUMIDIFIER SYSTEM A. Duct Humidifier system shall be a complete duct humidifying system, including but not limited to, steam generator, controls, drain cooler, duct mounted steam dispersion device, steam and condensate return hoses/pipes. Duct humidifier system shall use potable water and require no filtration or water treatment prior to entering the steam generator. B. Enclosure shall be an 18-gauge steel frame including a drip pan with threaded drain connection. If controls are housed in same enclosure as steam generator, all electrical devices shall be housed in a separated compartment. Frame shall have pre-punched mounting holes for wall mounting. All plumbing and electrical components shall be fully assembled and prewired. 1 FMD NO. 1256976 127 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Duct-Mounted Humidifier - 01/21/13 Section 238413 C. Steam generator shall have a cleanable stainless steel vaporizing chamber with welded seams. Electrical, water supply and drain connections shall have unions and plugs to allow convenient removal of the evaporating chamber for cleaning. D. Humidifier shall be provided with an automatic electronic drain valve, a duct mounted humidity sensor and a drain cooling system to reduce the drain output temperature to a maximum of 140F. E. Controls shall operate the system with a modulating signal input demand from the BAS, provide control over automatic refill, low water cutoff, drain/bleed control and automatic drain-down, and shall include a make-up water switch, low water safety shut-off, keypad capable of monitoring and controlling relative humidity setpoint and actual conditions in the duct, system demand and output, drain/flush frequency, system alarms, fault messages and humidifier functions. Controls shall have output signals to the BAS consisting of alarm status, duct RH level and setpoint, steam production in lbs/hr, and mode status. F. Duct mounted steam dispersion device shall include a steam supply/distribution tubes and condensate collection. The dispersion device shall be designed to be installed into the vertical AHU discharge and have a design absorption distance of 12 inches. Tubes and headers shall be stainless steel. Airflow pressure drop across the dispersion device at 14,000 cfm shall not exceed 0.15” H20. G. Steam and condensate return hoses/pipes shall be of the type recommended by the manufacturer to carry steam or condensate between the humidifier, steam dispersion device and the drain cooler. H. Duct Humidifier System shall have the capacities scheduled on the drawings. I. Duct Humidifier System shall be Dri-Steem Vapormist with Ultra-Sorb LH, or equivalent by Nortec, Armstrong or other pre-approved manufacturer. PART 3: EXECUTION 3.1 INSTALLATION: A. Humidifier system including steam generator, enclosure, dispersion device, drain cooler and all hoses/piping between shall be installed per the manufacturer’s instructions. B. Seal all hose/pipe connections and penetrations through structure and or ducts. C. Install with required clearance for service and maintenance. END OF SECTION 2 FMD NO. 1256976 128 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Electrical General Provisions - 01/21/13 Section 260000 SECTION 26 0000 ELECTRICAL GENERAL PROVISIONS PART 1: GENERAL 1.1 1.2 1.3 SCOPE A. This section applies to all Sections of Division 26 – Electrical. B. The general provisions of the contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this section and in all sections of this division. WORK INCLUDED A. Provide all labor, tools, and materials required for a complete and fully operational installation, as described on the drawings or in the specification. B. The work shall be installed in a neat and workmanlike manner. WORK NOT INCLUDED UNDER DIVISION 26 A. The following items of work are specified under other divisions of the specification: 1. 2. 3. 4. Temporary service for construction. Electric motors. Electric heaters unless otherwise noted on the drawings. Control and interlock wiring for work furnished under other divisions, except where specifically required under this division. 5. Access panels in walls or ceilings. 6. Field finish painting, except for field painting of electrical material with paint supplied by the manufacturer of the material. 7. Starters for certain items of equipment are furnished under other divisions for installation under this division. B. 1.4 Refer to other sections of this division for work required in connection with the above items. DEFINITIONS A. “Provide”: furnish and install, complete and ready for operation. B. “Install”: receive, mount, and connect, complete and ready for operation. C. “Wiring”: wires and cables installed with all required raceways, connectors, and fittings. D. “Concealed”: not exposed to view; embedded in masonry or other construction; in furred spaces or above suspended ceilings; below grade. 1 FMD NO. 1256976 129 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.5 E. “Exposed”: not concealed; not embedded or installed underground; under raised floors; inside trenches, tunnels, and basements, inside built-up HVAC equipment, crawl spaces, and accessible attics. F. “The Drawings”: that portion of the contract drawings annotated as electrical. G. “Furnish”: Supply, deliver to job site, protect and store. ABBREVIATIONS A. The abbreviations used on the drawings and in the specification are defined as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 1.6 Electrical General Provisions - 01/21/13 Section 260000 “AC”: Alternating Current “AFF”: Height above Finished Floor “AIC”: Ampere Interrupting Capacity “AICR”: Ampere Interrupting Current Rating “AHJ”: Authority Having Jurisdiction “NEC”: National Electrical Code “NIC”: Not in the Contract “NF”: or “N/F”: Non-fused “30A/2P”: Example of a circuit designation for a 30 Amp 2-Pole fused switch or a 30 Amp 2-Pole circuit breaker or device. “FBO”: Furnished by Others “EC”: Electrical Contractor “EX”: Existing to Remain “EXR”: Existing Relocated – new location indicated on the drawings. “HP”: Horsepower “kVA”: Kilovolt Ampere “kW”: Kilowatt “MCC”: Motor Control Center “MLO”: Main Lugs Only “NTS”: Not to Scale “WP”: Weatherproof CODES, RULES, AND REGULATIONS A. Comply with the following: 1. The edition of the National Electrical Code being enforced for this project by the local inspection authority. 2. All applicable laws and ordinances. 3. The rules and regulations of electric utility company serving the project applicable to the installation of service and metering equipment. 4. The rules and regulations of the telephone company serving the project applicable to the work required for routing telephone service into the facility. B. Give all necessary notices, obtain all required permits, and pay all inspection and other fees imposed by Authorities Having Jurisdiction over the work. 2 FMD NO. 1256976 130 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.7 STANDARDS A. The standards of the following organizations shall be applicable to the work: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. B. 1.8 1.9 Electrical General Provisions - 01/21/13 Section 260000 The National Fire Protection Association (NFPA) Underwriters Laboratories (U/L) National Electrical Manufacturers Association (NEMA) American National Standards Institute (ANSI) Institute of Electrical and Electronic Engineers (IEEE) Insulated Power Cable Engineers Association (IPECA) Illuminating Engineering Society of North America (IESNA) National Electrical Testing Association (NETA) National Electrical Contractors Association (NECA), Standard of Installation American Society for Testing and Materials (ASTM) Comply with the latest editions and Georgia Amendments of standards applicable to the work. MATERIALS A. All material shall be new, and shall comply with the indicated standards. B. All material shall be UL labeled or UL listed, except where the material is of a type not included in the UL listing service, in which case the material shall comply with other applicable industry standards and the contractor shall provide any examinations or certifications required by the local inspection authority in lieu of UL listing. C. All material shall be of a suitable type and rating for the intended use, and shall be installed in conformance with the instructions and recommendations of the manufacturer. DRAWINGS A. The drawings are schematic in nature and do not indicate all of the required details of the work. All materials customarily considered to be a part of the electrical work and normally required for a complete and operational installation, shall be provided without additional cost to the Owner. B. Refer also to the drawings of all other trades to coordinate the electrical installation. C. Equipment of other trades is shown schematically on the electrical drawings. Examine the drawings of the trade providing the equipment before roughing in the connections for it. Connect the equipment where actually installed, including wiring through any line voltage controllers, without any additional cost to the Owner. 3 FMD NO. 1256976 131 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.10 1.11 Electrical General Provisions - 01/21/13 Section 260000 D. Prior to roughing in circuits for equipment furnished by other trades, and prior to releasing for manufacture panelboards, starters or motor control centers feeding such equipment coordinate the electrical provisions being planned with the trade providing the equipment and submit any conflicts in writing. E. The Architect directs the location of any electrical outlet, or wall switch, or luminaries, or other equipment, to a location within 10 feet of the location shown on the drawings at no additional cost to the Owner provided such relocation is made prior to the installation of the equipment being relocated. SUBMITTALS A. Submit shop drawings in the manner and form described elsewhere in the contract requirements. B. Submittals are required for material as noted in other sections of this division. C. Check shop drawings prior to submission and provide date and signature of checker on each item. Note all corrections. Note any requested deviation from the drawings or specification, or if none, then so indicate. The Architect shall return documents without review where submitted without prior review by the contractor. D. Review of submittals will be only for general conformance with the design concept indicated on the drawings and in the specification and general compliance with the information given in the Contract Documents. Review will be made only of information clearly and specifically indicated in the submittal, and does not imply the acceptability of details, which are not so described in the submittal. Approval of a specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the Work of all trades; and performing all work in a satisfactory manner. E. Review of the submittal documents by the Architect does not relieve the contractor of the responsibility to comply with all requirements of the Contract Documents. PROJECT CLOSEOUT A. Furnish closeout documents in the manner and form described elsewhere in the Contract Documents. B. Closeout documents shall include the following: 1. Final shop drawings. 2. As-built drawings including as-built field layout drawings. 3. Operation and maintenance manuals. 4 FMD NO. 1256976 132 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Electrical General Provisions - 01/21/13 Section 260000 4. Receipts from the Owner stating that he has received satisfactory operational demonstrations and instruction for electrical systems. 5. Signed receipts from the Owner for spare parts and materials that are specified to be furnished. 6. Written guarantee. 7. All required certifications, including certificate of inspection approval of the code-enforcing authority. 8. All required test reports (include in operations and maintenance manual). 1.12 1.13 Record DRAWINGS and specifications A. Provide record drawings and specifications in the manner and form described elsewhere in the Contract Documents. B. Record drawings shall be maintained at the jobsite, and shall be available for review during construction. C. Record the final arrangement of the work and exact locations of the work as installed. Provide photographs of buried grounding work prior to backfill of trenches. D. Record drawings and specifications shall be kept current during the course of construction of the work. OPERATION AND MAINTENCE MANUALS A. Provide minimum of (3) copies of operation and maintenance manuals in the manner and form described elsewhere in the contract requirements. Manuals shall be typewritten, indexed, tabbed, and loose leaf bound in heavy duty 3-ring binders. B. Manuals shall include the following: 1. 2. 3. 4. 5. Operating instructions customized to this specific project Maintenance instructions Parts list Descriptive literature Location, telephone number and contact information of contractors, distributors, dealers and authorized service agents. 6. Test reports and certifications. 7. Record copies of all shop or submittal drawings and data 8. Copies of all software on diskette or compact disk, licensed to the Owner. C. Maintenance instructions and parts lists shall include the most detailed and advanced publications available from the equipment manufacturer. D. Demonstrate the operation of the equipment to the Owner, including instruction in its use and operation. Provide instruction by manufacturers representatives where specified. 5 FMD NO. 1256976 133 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) E. 1.14 1.15 Electrical General Provisions - 01/21/13 Section 260000 Provide operation and maintenance manuals for equipment and systems as specifically by the sections in Division 26. SPARE PARTS A. Furnish spare parts as specified by the sections in Division 26. B. Turn over spare parts to Owners representative. Store on site as directed by the Owner. Obtain written receipt detailing specific spare parts turned over and submit with close-out documents. C. Replace at no cost to the Owner any spare parts used from the Owners stock prior to substantial completion or for warranty related repairs. GENERAL TESTING A. Test all parts of the work to verify compliance with the drawings and specification. B. Verify tightness of all mechanical and electrical connections. C. Verify integrity of all wiring systems to assure continuity, absence of unintentional grounds, and integrity of required grounds. D. Perform any required special factory or field testing as specified in the other sections of this division. Provide all wiring, instruments, and personnel required to complete these tests. E. Where other requirements of this division require testing in the presence of the Architect, provide at least seven (7) business days advance written notice of such testing to the Architect. F. Where other requirements of this division require submission of written records of tests and test results, accumulate and submit all such reports and include as a separate section in the operations and maintenance manuals described elsewhere in this section. END OF SECTION 26 0000 6 FMD NO. 1256976 134 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Basic Materials & Methods- 01/21/13 Section 260500 SECTION 26 0500 BASIC MATERIALS AND METHODS PART 1: GENERAL 1.1 GENERAL A. This section covers items of work required by more than one section of Division 26 – Electrical. B. Refer to other Divisions for requirements pertaining to: 1. 2. 3. 4. 5. 1.2 Cutting and repairing Excavation and backfilling Concrete Field painting Equipment furnished under other Divisions and installed under this Division SUBMITTAL DOCUMENTS A. Required for fireproofing system materials and. B. Provide manufacturer’s data sheets with complete description of all components, catalog numbers, specific details of applicable UL listings, and detailed line drawings of fireproofing methodology to be used for each type of penetration. PART 2: PRODUCTS 2.1 2.2 2.3 MANUFACTURE A. Concrete Inserts: Grinnell, Kindorf, Unistrut, B-Line or Hohmann & Barnard. B. Drilled Anchors: All metal; heavy duty, non-caulking, expansion bolt anchor. Minimum size used shall be ¼” machine thread. C. Metal Framing Channel: 1-5/8” x 1-5/8”, 12 Gauge. Use appropriate fittings of same manufacture. WOOD BACKBOARDS A. Wood backboards shall be ¾” thick, grade B-C, plywood. Paint with gray color fire-retardant paint. B. Use backboards only in interior spaces and sized as indicated on the drawings. NAMEPLATES A. Provide engraved plastic equipment nameplates for all switchboards, panelboards, motor control centers, starters, disconnects, primary selector switches, time clock controls, contactors, and transformers. 1 FMD NO. 1256976 135 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 2.4 Basic Materials & Methods- 01/21/13 Section 260500 B. A circuit nameplate indicating circuit number and the equipment served shall be provided for each feeder in service switchboard, and each branch device in power distribution panels, and motor control centers. C. Distribution equipment nameplates shall state equipment designation, ampere rating, voltage and phase, and “fed from (name)”. D. Nameplates for individually mounted starters, safety switches, etc., shall state load served, circuit number, voltage and phase. E. Refer also to Section 16140 for additional requirements pertaining to device labeling. F. Refer also to Section 16195 for additional electrical identification requirements. FIREPROOFING A. All fireproofing materials shall be the product of one manufacturer and shall be U.L. listed for the type of application where applied. B. Provide caulk, expanding foam, putty, rigid boards, tape and packing as required by the U.L. listing for the type of penetration being fireproofed. C. Fireproofing of sleeves, cable trays, troughs, and nipples to be used for low voltage cables shall be indefinitely non-hardening and removable with common hand tools. D. Fireproofing for penetrations of floor slabs shall also be waterproof for standing water in a non-fire condition. E. Acceptable Manufacturers: 1. 2. 3. 4. 5. Dow Corning Hilti Nelson 3-M Other manufacturers as determined acceptable by the Architect. PART 3: EXECUTION 3.1 SUPPORTS A. All work shall be supported from structural elements of the building, except ceiling mounted equipment such as light fixtures, detectors, remote lamps, which shall be supported from ceiling support members independent of ceiling tiles. B. Size and spacing of supports shall be determined by the load to be supported such that the working load of supports will not exceed a safety factor of 4:1. 2 FMD NO. 1256976 136 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.2 Basic Materials & Methods- 01/21/13 Section 260500 C. Spacing intervals of supports shall in no case exceed intervals required by applicable codes. D. Plastic anchors, non-removable drive-in type expansion anchors are not acceptable. E. Work under this division shall not be supported from piping, ducts, or work of other trades, unless specifically noted on the drawings or with the written permission of the architect. F. Drilled anchors in sides of concrete joists shall be at least 3” from bottom of joist in the vertical plane. G. Provide drilled expansion bolt anchors to support all material mounted on masonry construction. H. All hardware, nuts, bolts, channel, braces, etc., used on exterior of building shall be galvanized. I. Rod supports shall be constructed of minimum 1/4” nominal continuously threaded rod of a continuous length. Use of rod couplings to extend the length of hanger rod shall not be allowed. J. Work installed under Division 26 supported from or attached to structural steel members shall not be welded to steel member but shall be attached by clamping a device manufactured specifically for this purpose. K. Floor mounted equipment shall be anchored to supporting concrete pad with expansion anchors, minimum ½” nominal stud size. L. Framework required to support electrical equipment shall be constructed of 1 ½” x 1 ½” steel framing channel bolted together with fittings provided by the framing channel manufacturer. PAINTING A. Provide the following painting under Division 26 in accordance with the requirements of the specification section describing Finish Painting. 1. Plywood backboards – wood primer and finish coat of ASA 61 gray fire retardant paint. 2. Panelboards, transformers, disconnect switches and exposed conduits that are a part of the life safety distribution system – primer (on conduits only) and one coat of red enamel. 3. Color of all field paint shall be as directed by Architect. B. 3.3 The vendor for painting furnished under Division 26 shall be primary painting subcontractor being utilized by the general contractor. WOOD BACKBOARDS 3 FMD NO. 1256976 137 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.4 3.5 3.6 3.7 Basic Materials & Methods- 01/21/13 Section 260500 A. Unless otherwise noted on the drawings, backboards shall be 8’-0” high by the width shown on the drawings. B. Backboards shall be attached to supporting structure with 3/8” expansion anchors or toggle bolts with fender washers placed a maximum of 48” on center on all sides of backboard. CONCRETE A. Provide 3000 PSI concrete where concrete work is required to support equipment furnished under Division 26, such as for equipment pads, lighting standard bases, and concrete-encased duct banks. Refer to drawings and other sections for locations where concrete is required. B. Exposed surfaces of concrete placed under this section shall be hand rubbed and all edges shall have 1” chamfer. EQUIPMENT PADS A. Provide 4” high concrete pads for all floor mounted electrical distribution equipment, including switchboards, and elsewhere as specifically noted on the drawings. B. Concrete pads for switchgear, switchboard motor control centers and UPS equipment shall be level to with 1/8” from front to back and from side to side. Provide (2) embedded steel “U” channels; 4”W X 1 ½” H x 0.25” T, inverted and flush with the top of the pad. Channels shall be at the front and back of the pad located as directed by the equipment manufacturer, to provide a level base for the equipment. C. Anchor equipment in accordance with seismic study. EQUIPMENT OF OTHER TRADES A. Motors, heaters, and other utilization apparatus shall be mounted by the trade which furnished the apparatus. B. Provide all power wiring and connections for all electrically operated equipment. Power wiring includes wiring through any line voltage control devices, such as thermostats and manual starters. C. Phase connections of motors shall provide proper motor shaft rotation. D. Starters and contactors furnished under other divisions, except those furnished as an integral part of the equipment, shall be installed under this division. EQUIPMENT CONNECTIONS A. Connections to motors, transformers, duct heaters and other vibrating equipment shall be made with a short length of liquidtight flexible conduit, minimum 18”, installed in a manner to permit movement of equipment. 4 FMD NO. 1256976 138 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) B. 3.8 3.9 Basic Materials & Methods- 01/21/13 Section 260500 For floor-mounted equipment, which is fed overhead and not located adjacent to a wall or column, provide a rigid conduit standpipe from floor to ceiling with a floor flange. Provide appropriate cast conduit “tee” fitting in standpipe for connection of equipment. MISCELLANEOUS WORK A. Perform all excavating, backfilling, cutting and repairing required for work included in this division. B. Protect all work from damage and from entry of concrete, moisture, and other foreign material. FIREPROOFING A. All penetrations of fire rated walls, slabs, partitions, and ceilings shall be fireproofed with a U.L. listed system that will maintain the original fire rating of the penetrated structure. B. Initial fireproofing of sleeves, cable trays and wireways for low voltage cable shall not be installed until cables are installed or until required for issuance of certificate of final inspection, whichever is earlier. 3.10 Multi-wire branch circuits A. Each multi-wire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. B. Combining of circuits into a multi-wire branch circuit is not permissible except where specifically indicated on the drawings. END OF SECTION 26 0500 5 FMD NO. 1256976 139 BID NO. 36813636 FMD NO. 1256976 140 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Grounding System - 1/21/13 Section 260526 SECTION 26 0526 GROUNDING SYSTEM PART 1: GENERAL 1.1 1.2 DESCRIPTION A. Grounding System: Grounding of all electrical equipment and raceways. B. Buried Grounds: Buried ground radials and driven ground rods as indicated on the Drawings. C. Miscellaneous grounding, installation of separate ground bus bars and miscellaneous bonding. D. Provide all grounding and bonding described herein and as detailed on the drawings. E. Provide the services of an approved testing contractor to perform a ground resistance test of the completed grounding system. F. The completed grounding system installation is subject to review and acceptance by the Consultant. SUBMITTALS A. Required for materials and fittings for exterior grounding work. B. Documents: 1. Manufacturers data sheets describing each component of the system; 2. Qualifications of the proposed testing contractor. PART 2: PRODUCTS 2.1 BUILDING GROUNDING SYSTEM A. Raceways for separate ground conductors: Type RNC, Schedule 40 conduit. B. Conductors: 1. 98% conductivity copper, solid or stranded, sizes and types as indicated on the drawings. 2. In general, main buried ground conductors shall be bare copper, AWG 3/0, seven-strand. C. Connections: 1. Underground or exterior connections shall be exothermic weld between conductors, and between conductors and ground rods. 1 FMD NO. 1256976 141 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Grounding System - 1/21/13 Section 260526 2. In locations where conductor connects to main structural steel components, exothermic welds shall be used. For connections to light-gauge metals or in other locations where a lug must be used, a 2-hole lug shall be exothermic welded to the grounding conductor. 3. Lugs shall be 2-bolt tongue, compression type. 4. Compression Splices and Taps: Tin plated copper. 5. Water pipe clamps, fence posts, test ground rod: T&B 3900 series or Burndy Type “GAR” Series, cast bronze. 6. Exothermic welds: Cadweld, Thermaweld or Ultraweld. 7. Solid conductor to equipment or bus: Exothermic weld lug bolted to equipment. 8. Flexible copper grounding and bonding jumpers: 0-Z/Gedney Type “FB” series, or Burndy Type “B” Series, rated 190 AMPS, length as required for each application. 9. Ground Rods: “Copperweld”, copper clad steel, ¾ “ diameter, 10’ length. Provide sectional rods of same construction where lengths greater than 10 feet are required to be used. D. Non-Oxide Compound: 1. “NO OXID A” compound as manufactured by Sanchem Chemical Company, Chicago Illinois. PART 3: EXECUTION 3.1 3.2 BURIED GROUNDS A. Unless otherwise indicated, ground rods shall be driven into undisturbed earth. B. Tops of rods and all horizontal buried conductors shall be minimum 30” below finished grade. C. Minimum lateral distance from building footings shall be 24”. D. Installed grounding work below grade shall not be covered until reviewed by the testing contractor. EQUIPMENT GROUNDING CONDUCTORS A. Separate Grounding Conductor: All branch circuits and feeders operating at higher than 50 volts to ground shall have an insulated equipment ground conductor, green color, sized in accordance with the National Electrical Code. B. Raceway Grounds: Other circuits shall utilize the raceway as the equipment ground conductor except where noted otherwise. C. Single grounding conductors, or RNC conduits containing single ground conductors, shall not be totally encircled by ferrous metal. Use nylon bolts in pipe hangers or in Unistrut conduit straps. 2 FMD NO. 1256976 142 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.3 Grounding System - 1/21/13 Section 260526 D. All grounding connections shall be subject to inspection and review by the testing contractor and the Consultant. Provide 72 hours advance notice for scheduling review. E. Provide specified “non-oxide” compound between mating surfaces on all equipment bonding connections where mechanical connections are utilized in lieu of exothermic welds. F. Ground conductors shall be installed using long radius bends, minimum 12” radius, and shall maintain a downward or horizontal direction. U-bends or tight radius bends less than 90 degrees are not acceptable. G. All connections to the buried ground ring conductor shall be exothermic welded including connections to ground rods. H. Bond connections to equipment shall utilize exothermic weld lugs, 2-bolt tongue type, attached using machine screw thread type bolts where exothermic welds cannot, or should not, be utilized. I. Provide combination “Do Not Disconnect” and “Destination” tags at all interior bonding and grounding connections. Tags shall be green plastic laminate with white letters. Letters shall be minimum ¼” high. Attach all tags using Nylon cable Ty-raps. GROUND TESTING A. Testing of grounding systems and made ground electrodes shall be performed by an approved testing company. B. Measurements shall include the earth resistivity and resistance of the grounding electrode system. C. Record ambient temperature; date; time; condition of soil (wet or dry). Where available, record approximate water table level (as obtained from local geologists, special core drilling is not required); type of earth materials; earth resistivity. D. Provide written record of resistance readings and all other information listed above. Include on “Record Drawings”. E. Notify Owner if ground resistance is above 25 ohms. END OF SECTION 26 0526 3 FMD NO. 1256976 143 BID NO. 36813636 FMD NO. 1256976 144 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Conduit- 1/21/13 Section 260533 SECTION 26 0533 CONDUIT PART 1: GENERAL 1.1 1.2 1.3 1.4 1.5 GENERAL A. This section describes conduit and related fittings. Other raceway types are specified in other sections. B. Boxes and other raceway accessories are specified in other sections. SIZE A. Minimum conduit size shall be ½”; Exception: 3/8” flexible metal conduit or Type AC or MC is permitted for flexible connections to lighting fixtures and fire alarm devices. B. Conduit size may be increased to facilitate pulling of conductors. COORDINATION WITH WORK OF OTHER TRADES A. Coordinate the conduit layout with the work of other trades. Conduits shall be located to avoid interference with equipment that requires access, maintenance, adjustment, or repair. Conduits shall not restrict the required working clearance around such equipment. B. Conduits feeding, or connecting to, equipment provided by other trades shall not be installed until such equipment is installed or until the trade providing the equipment furnishes specific rough-in instructions. C. Conduits shall be concealed, unless otherwise indicated. SCOPE OF CONDUIT WORK SHOWN ON THE DRAWINGS A. The conduit layout indicated on the drawings is schematic and is not intended to show the exact location of conduits unless specifically dimensioned. Locate conduit as required by the architectural and structural details of construction and by the coordination with the work of other trades. B. Provide all fittings, offsets, supports, pullboxes and other components of the conduit system as required for a complete raceway system. QUALITY ASSURANCE A. The conduit shall be new, of uniform quality and appearance, and marked with U.L. listing and name of manufacturer. B. All seams shall be smooth, without splits, clean, and with threads protected when delivered to or stored on site. 1 FMD NO. 1256976 145 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 1.6 Conduit- 1/21/13 Section 260533 C. Provide fittings designed and U.L. listed for use with the specific wiring method used. D. Set-screw fittings are NOT allowed. SUBMITTAL DOCUMENTS A. Provide submittal documents for the following: 1. 2. 3. 4. PVC raceways and fittings EMT fittings Conduit bushings Flexible conduit and fittings PART 2: PRODUCTS 2.1 RIGID METAL CONDUIT (TYPE RMC) A. Manufacturers: 1. 2. 3. 4. 5. 6. 7. 8. 9. Allied Tube & Conduit Corp. Jones & Laughlin Pittsburgh-Standard Republic Triangle Wire & Cable, Inc. Wheatland Tube Co. Youngstown ETP Robroy Industries, Inc. B. Material: Full weight, steel, standard size, hot dipped galvanized outside, galvanized or coated inside, threaded ends. C. Fittings: 1. Couplings: Continuous threaded, furnished by the manufacturer with conduit. For IMC, ETP “Uni-Swivel” couplings are acceptable. 2. Threaded joint compound: Fel-Pro C5A. 3. Terminations (dry locations): Double locknuts with insulated throat, metallic grounding bushing, 0-Z/Gedney type “BLG”. 4. Terminations (wet locations): Watertight hubs, 0-Z/Gedney Type “CHM”, or conduit hubs integral with equipment. 2.2 INTERMEDIATE METAL CONDUIT (TYPE IMC) A. Manufacturers: same as for RMC B. Material: Lightweight steel, standard size, hot dipped or electro-galvanized zinc outside and galvanized or enamel coated inside, threaded ends. C. Fittings: same as for RMC 2 FMD NO. 1256976 146 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 2.3 RIGID NON-METALLIC CONDUIT (TYPE RNC) A. Manufacturer: 1. 2. 3. 4. 5. 2.4 Conduit- 1/21/13 Section 260533 Carlon, Division of Lamson & Sessions Co. Sedco Centex, Inc. Heritage Plastics Certainteed Corp. B. Material: PVC Schedule 40, unless otherwise indicated, rated for use with 90ºC conductors. C. Where PVC being run under slabs, or grade, turns up through the slab, or above grade, the elbow and vertical section of conduit from the elbow to the termination of the conduit shall be RMC, or IMC, as protection against the exposed conduit being damaged. D. Accessories: Fittings, couplings, cement, and other accessories shall be of the same manufacture as the PVC conduit that they are used with. ELECTRICAL METALLIC TUBING (TYPE EMT) A. Manufacture: same as for RMC. B. Material: Thin-wall steel, galvanized outside, coated inside, threadless. C. Fittings: 1. For EMT (Sizes 1.25” and smaller): a. Couplings: All steel, compression style, concrete tight where installed in concrete, Raco, T&B, Midwest, or Steel City, O-Z/Gedney b. Connectors: All steel, compression style, with nylon throat; Raco, T&B, Midwest, or Steel City. 2. For EMT (Sizes 1.50” and larger): a. Couplings: All steel, compression style, of same manufacture. b. Connectors: All steel, compression style, of same manufacture, and insulated throat, metallic grounding bushing, 0-Z/Gedney Type “BLG”. 2.5 FLEXIBLE METAL CONDUIT (TYPE FMC) A. Manufacture: 1. 2. 3. 4. AFC Cable Systems, Inc. Alflex Electri-Flex Co. Steelflex Electro Corp. B. Material: galvanized steel, Continuous single interlocking strip. C. Fittings: T&B “Tite-Bite” series, Midwest Fittings. 3 FMD NO. 1256976 147 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 2.6 Conduit- 1/21/13 Section 260533 LIQUIDTIGHT FLEXIBLE METAL CONDUIT (TYPE LFMC) A. Manufacture: same as for FMC. B. Material: Flexible metallic conduit with PVC jacket, type “UA”, with integral copper grounding conductor suitable for use as equipment grounding conductor. C. Fittings: 1. Material: Steel, or malleable iron, liquid-tight connector with insulating throat liner (use bushing above 1.25”). 2. Manufacture: T&B, Midwest Fittings, O-Z/Gedney. 2.7 EXPANSION FITTINGS AND ACCESSORIES A. Expansion fittings: 1. For conduit not embedded in concrete while passing across building expansion joint, provide 0-Z/Gedney type AX for GRC and IMC or type TX for EMT. Provide bonding jumper. 2. For conduit embedded in concrete while passing across building expansion joint, provide 0-Z/Gedney type DX expansion joint or type AXDX if required by the degree of expansion possible. B. Seals for exterior wall below grade penetrations: 1. Cast-in-place type: 0-Z/Gedney Type “WSK”. 2. Cored openings: 0-Z/Gedney Type “CSMI” and Type “CSMC”. 3. Non-shrink grout where indicated on the drawings and where acceptable to the Architect. C. Conduit bodies: 1. Used for pulling conductors: Crouse-Hinds LBD series through 2.00” and LBNEC Series 2.50” and above. 2. Used for motor connection: Crouse-Hinds condulet “T” series. D. Pull strings for empty conduits shall be equal to Greenlee 430 poly pull line. PART 3: EXECUTION 3.1 GENERAL A. Conduit supports and seismic bracing is specified in other sections. B. Run exposed conduits parallel or perpendicular to structural elements. C. Two or more raceways run together shall be installed on trapeze type gang hangers. Such raceways assemblies shall be run parallel or perpendicular to structural elements. 4 FMD NO. 1256976 148 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.2 Conduit- 1/21/13 Section 260533 D. Where bends are made in a rack of exposed conduits, field bent concentric elbows shall be used. E. All wiring shall be installed in conduit, unless plenum rated cable is specified in other sections to be installed without conduit or, unless the wiring is shown to be in a wireway or cable tray. F. Unless specifically noted on the drawings all raceways shall be concealed in walls, floor slabs, topping slab on floor, or in ceiling plenums. G. Apply threaded joint compound on all Type RMC and Type IMC threaded joint connections. SCHEDULE A. Unless otherwise required, provide RMC or IMC for the following applications: 1. Where subject to damage. 2. Exposed on exterior of building. 3. Exterior circuits under roadways. B. Provide EMT in dry locations only for the following applications: 1. 2. 3. Concealed work in walls, and ceiling plenums. Branch circuit feeder wiring not otherwise required to be run in RMC or IMC. Signal or communication raceways (other than underground) C. Provide RNC PVC for the following applications: 1. Concrete encased duct banks where specifically indicated. 2. Single grounding conductors as indicated and where not run in plenum spaces. 3. Concealed work in slabs. 3.3 D. Flexible conduit is permitted only where concealed above suspended ceilings for connections of light fixtures, tele-power poles, and similar equipment and shall not exceed 3’-0” length. Light fixture whips may be 6’0” in length. E. Liquid-tight flexible metal conduit (LFMC) shall be used for all connections to vibrating equipment, such as motors and transformers, and where flexible conduit is indicated on the drawings, except as noted above. Use Type FMC in plenum spaces. INSTALLATION A. Conduits embedded in slabs shall have a minimum of 1” cover of concrete on all sides. Outside diameter of conduit shall not exceed 1/3 of the slab thickness and shall not be larger than 1.25”. B. All threaded conduits shall be terminated with specified bushings. 5 FMD NO. 1256976 149 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) C. Paint all underground steel conduits with one coat of Rustoleum 5269 primer and one coat of Rustoleum 5282 acrylic industrial enamel. Touch up all wrench marks and other defects. D. Underground conduits shall be a minimum of 24” below final grade. E. Conduit joints: 1. 2. 3. 4. 3.4 Conduit- 1/21/13 Section 260533 Ream end of conduit smooth. Conduit ends shall meet in coupling. Provide unions where required, of the Erickson Type. Provide joint compound on the male threads of RMC and IMC conduit. F. Use double locknuts at threaded conduit terminations. G. The conduit system shall be left free of all debris, water and foreign material. Plug or cap all conduits with exposed ends to prevent entrance of concrete or other foreign material. Pull a cleaning swab through all conduits prior to pulling conductors. H. Conduits run parallel to, or crossing hot pipes, shall not be closer than 0’-6” to hot pipe. I. Anchors or supports in waterproof walls shall be of the type and methodology directed by the architect. J. Empty EMT raceways shall be terminated with connectors, and if over 1.25”, specified bushings. K. Raceways in accessible ceiling plenums shall not be installed closer than 8” to ceiling. L. Groups of two or more conduits turned out of a slab shall be neatly arranged parallel to the adjacent wall and evenly spaced with at least (1) inch separation. M. Conduit passing through walls below grade shall be run through specified fittings in the wall and shall be sealed to be waterproof. N. All threaded joints in rigid conduit shall have pipe compound applied to the male thread only, to be watertight where buried below grade and not encased in concrete. ACCESSORIES A. Pull wires: provide nylon pull wire in all empty conduits and at all data and telephone outlet locations. B. Expansion fittings: provide at all building expansion joints. C. Fire seals: provide where conduit passes through a floor slab (other than slab on grade) and where conduit passes through fire-rated masonry walls, unless cast in place. 6 FMD NO. 1256976 150 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) D. 3.5 Conduit- 1/21/13 Section 260533 Install specified seals for exterior wall below grade for penetrations of conduits. IDENTIFICATION A. All exposed conduits 2 inches and larger shall be identified with markers 20 feet on center. Also refer to Section 260553 – Electrical Identification. B. Markers shall be permanent, plastic-sheet conduit markers extending 360 degrees around conduit. C. Marker shall identify voltage and function of conductors in conduit and be minimum length of 8 inches. END OF SECTION 26 0533 7 FMD NO. 1256976 151 BID NO. 36813636 FMD NO. 1256976 152 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Boxes- 1/21/13 Section 260534 SECTION 26 0534 BOXES PART 1: GENERAL 1.1 1.2 SCOPE A. This section covers pull boxes, outlet boxes, and junction boxes. B. Refer to Section 262726, WIRING DEVICES for additional requirements for outlet boxes for wiring devices. APPLICATIONS A. All splices, pull boxes, taps, connections, devices, etc., shall be installed using boxes of the appropriate type, designed and approved for the intended purpose. PART 2: PRODUCTS 2.1 2.2 2.3 GENERAL A. Box sizes specified are minimums, and shall be increased where required by code due to the number of conduit entries, conductors, devices, or taps in the box. B. All boxes shall be made of galvanized sheet steel, of code gauge thickness, but no less than 1/16” thick or 14 Gauge. C. Outlet box covers shall be attached by means of machine screws. Self-tapping sheet metal screws are not acceptable. MANUFACTURE A. Outlet boxes: Steel City, Appleton, Raco B. Cast boxes: Crouse-Hinds, Appleton SCHEDULE A. Schedule indicates box type; select actual box and plaster ring to suit actual conditions: 1 FMD NO. 1256976 153 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Boxes- 1/21/13 Section 260534 USE Recessed device outlet Recessed tele/data outlet Recessed wall mounted fixture Flush concrete outlet Flush concrete junction Junction box above ceiling Exposed device outlet Exposed fixture outlet Flush ceiling fixture 2.4 2.5 BOX RACO 683 RACO 683 RACO 683 RACO 272 RACO 272 RACO 257 C/H “FS” C/H “GRFX” RACO 683 COVER RACO 770 RACO 770 RACO 767 RACO 893 RACO 892 RACO 832 C/H DS32 --------RACO 767 SPECIALTIES A. Boxes installed in concrete shall be UL listed for such use. B. Through-wall boxes are not acceptable. C. Provide 3/8-fixture stud and box supported from structure when required by weight of fixture being supported. D. Junction boxes installed above ceilings shall be plenum type. PULL BOXES AND JUNCTION BOXES A. In dry locations, boxes shall be galvanized sheet steel, minimum 12 gauge, with machine screw covers, and welded construction. Welds shall be slag-free and cold galvanized. B. In damp locations or outdoors, unless otherwise shown on the drawings, boxes in steel raceway runs shall be galvanized cast iron, with gasketed covers and conduit hubs, or drilled and tapped. Boxes in Type RNC PVC raceway runs shall be PVC with gasketed cover. C. All boxes shall be rated for their application, such as sidewalk, or light vehicle traffic. D. Provide insulated cable support racks in feeder pull boxes where conductor length exceeds 48” inside pullbox. PART 3: EXECUTION 3.1 GENERAL A. Refer to other sections for mounting heights of boxes for devices and equipment. B. Boxes shall be located clear of other trades, and shall be accessible. C. Coordinate the exact location of ceiling outlet boxes and boxes concealed above ceilings, with ductwork and piping so that the box will be accessible. 2 FMD NO. 1256976 154 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.2 Boxes- 1/21/13 Section 260534 D. All required pull boxes are not indicated on the drawings. Provided boxes as determined by actual field installation and as required for a complete installation. E. Using a permanent, waterproof, wide black marker, clearly label covers of all branch circuit junction boxes, and smaller pull boxes, with panel and circuit number of circuits contained in, or passing through, the box. F. Branch circuit and feeder junction and pull boxes used with emergency lifesafety feeders and circuits shall be painted red. G. Provide engraved “lamicore” nameplate on cover of each major feeder pull, or junction, box as specified under Section 260553 - “Electrical Identification”. INSTALLATION A. Boxes shall be securely anchored in place, and shall be supported independent of the raceway system. B. Boxes installed in poured concrete shall be anchored to the formwork and protected against entry of any concrete. C. Boxes shall be set square and plumb with building elements. D. Outlets for ceiling mount fixtures shall be rigidly supported from the grid or structure with an assembly manufactured for this purpose. END OF SECTION 26 0534 3 FMD NO. 1256976 155 BID NO. 36813636 FMD NO. 1256976 156 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Seismic Restraints- 1/21/13 Section 260548 SECTION 26 0548 SEISMIC RESTRAINTS PART 1: GENERAL 1.1 DESCRIPTION A. 1.2 1.3 This section outlines requirements for seismic restraints for electrical conduit and equipment. STANDARDS A. International Building Code (IBC), 2000 Edition. B. Refer to SMACNA/ASHRAE "Seismic Restraint Applications", First Edition, 2002. C. UL 1570 - Fluorescent Lighting Fixtures. D. ASTM E 580 - Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Moderate Seismic Restraint. SEISMIC DESIGN COMPLIANCE A. Electrical work shall meet the seismic requirements of the International Building Code with local building code amendments. B. Provide seismic bracing details for panels, miscellaneous equipment, conduits and cable trays. Analysis shall be performed by a firm or manufacturer regularly engaged in seismic analysis. C. Seismic restraint layouts and bracings shall be stamped by a registered design professional/qualified structural engineer licensed to practice in the State of Georgia. D. Occupancy Category = III. E. Seismic Design Category = B. F. Design Spectral Response Acceleration: SDS=0.228. G. Component Importance Factor – Other Equipment: IP= 1.0 H. Loading of cable trays and ladders shall be assumed to be 90% of the maximum rated load. I. Refer to structural drawings and structural general notes to reference code/design information. PART 2: PRODUCTS 2.1 MATERIALS 1 FMD NO. 1256976 157 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Seismic Restraints- 1/21/13 Section 260548 A. Hangers shall be as specified in Section 260500, Basic Materials and Methods. B. Obtain materials from an approved manufacturer of seismic restraint equipment. C. Lighting fixtures and supports shall conform to UL 1570 or UL 1571 as applicable. PART 3: EXECUTION 3.1 ELECTRICAL EQUIPMENT REQUIRING RESTRAINTS A. All the following equipment and raceways located inside the building shall be provided with restraints: 1. Recessed fluorescent lighting fixtures. 2. Raceways 2½” and larger which are independently supported from the structure. B. 3.2 Raceways listed above are not required to be restrained if the hangers are 12” or less in length as measured from the top of the conduit to the bottom of the hanger support. SUPPORT REQUIREMENTS A. Seismic support shall be provided for both transverse and longitudinal restraint. B. Restraints shall be as supplied by the restraint equipment manufacturer for the specific jobsite condition, installed in accordance with manufacturer’s instructions. END OF SECTION 26 0548 2 FMD NO. 1256976 158 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Electrical Identification- 1/21/13 Section 260553 SECTION 26 0553 ELECTRICAL IDENTIFICATION PART 1: GENERAL 1.1 1.2 SCOPE A. Identification nameplates and labels B. Wire and cable identification markers C. Conduit identification markers SUBMITTALS A. Product Data: Provide catalog data for nameplates, labels, and markers. B. Manufacturer’s application conditions and limitations of use including, instructions for storage, handling, protection, examination, preparation, and installation of product. PART 2: PRODUCTS 2.1 NAMEPLATES AND LABELS A. Engraved three-layer laminated plastic nameplate with minimum 1/4” height letters. B. Equipment connected to non-essential supply (commercial power only) commercial source: Black letters on white background. C. Equipment connected to the essential supply (commercial power or generator power via transfer breakers or a transfer switch): White letters on red background. D. Locations: 1. Main Service and Distribution equipment enclosures and over-current devices. 2. Electrical distribution equipment enclosures. 3. Transformers 4. Motor Control Devices and Contactors. 5. Disconnect switches. 6. Communication cabinets. E. Labels: 1. Locations required: a. All motors. b. All field equipment fed from 120/208 V power source. c. All field equipment such as motors, control stations, etc. 1 FMD NO. 1256976 159 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Electrical Identification- 1/21/13 Section 260553 d. All lighting switches and receptacles in unfinished areas. F. Provide engraved plastic equipment nameplates for all switchboards, panelboards, motor control centers, starters, disconnects, primary selector switches, time clock controls, contactors, and transformers. G. Nameplate wording shall be coordinated with final equipment identification nomenclature and approved by the owners’ designated representative prior to installation. H. Letter Size: 1. 1/4 inch letters: Identify individual equipment, and loads. 2. 1/2 inch letters: Identify major electrical equipment and panelboards. 2.2 WIRE and CABLE MARKERS A. Description: Non-ferrous identify tag or shrink type label. B. Locations: Each cable feeder, power circuit, and conductor in vaults, manholes, gutters, pull boxes, starters, outlet and junction boxes, control panels, panelboards, switchboards, etc., and each load connection. C. Legend: Each tag or label shall be typewritten with description listed below. 1. Power and Lighting Circuits: Branch circuit or feeder number indicated on drawings. 2. Control Circuits: Control wire number indicated on schematic and interconnection diagrams. 2.3 CONDUIT MARKERS A. Location: Furnish vinyl markers for each exposed 2.00” or larger conduit longer than 6 feet for power circuits or exposed Type MC Cable with 3/0 or larger conductors longer than 6 feet. B. Spacing: Adjacent to each termination at equipment and pull boxes and intermittently at 20 feet on center. C. Color: Match existing color-coding scheme in the facility. Where color-coding does not already exist; then use the following color-coding on new work: 1. 480 volt system: Orange color and black stencil, voltage in 1/2” black letters. At the source end, also indicate the load served in 1/2” black letters. At the load end, also indicate the circuit source identification in 1/2” black letters. At intermediate points, also identify both the circuit identification and load in 1/2” black letters. 2. 208 volt system: White color and black stencil, voltage in 1/2” black letters. At the source end, also indicate the load served in 1/2” black letters. At the load end, also indicate the circuit identification in 1/2” black letters. 2 FMD NO. 1256976 160 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Electrical Identification- 1/21/13 Section 260553 At intermediate points, also identify both the circuit identification and load in 1/2” black letters. 2.4 UNDERGROUND WARNING TAPE A. Description: 4 inch wide plastic tape, detectable type, colored red with suitable warning legend describing buried electrical lines. B. Location: Along length of each underground conduit or direct buried cable or duct bank. PART 3: EXECUTION 3.1 PREPARATION A. 3.2 Degrease and clean surfaces to receive nameplates and labels. INSTALLATION A. Install nameplate and label parallel to equipment lines. B. Secure nameplate to equipment front using screws. C. Secure nameplate to inside surface of door on panelboards that are recessed in finished wall locations. D. Install conduit markers per Article 2.3. E. Stencil conduit markers or use adhesive letters or order pre-labeled. Handwritten entries that are neat and legible and not smeared are acceptable. Any conduit markers that that are determined not to be neat, legible, and free from smears shall be replaced to the satisfaction of the Architect. F. Identify underground conduits and direct buried cables using underground warning tape. Install one tape per trench at 3 inches below finished grade and at 12 inches above top of conduits. G. Use Scotch +35 marking tape to color-code the phase conductors equal and larger than AWG #6. H. In a high delta service, the phase with the highest voltage to ground shall be orange. I. For other conductor color-coding, see Section 260519 - Building Wire and Cable. END OF SECTION 26 0553 3 FMD NO. 1256976 161 BID NO. 36813636 FMD NO. 1256976 162 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Protective Device Coordination Study- 1/21/13 Section 260573 SECTION 26 0573 PROTECTIVE DEVICE COORDINATION STUDY PART 1: GENERAL 1.1 1.2 1.3 SCOPE A. Provide a protective device Time-Current Coordination (TCC) Study in a computergenerated format. B. From the utility connection down through the last branch circuit breaker. C. Compute short-circuit currents as needed for use in the TCC study. QUALITY ASSURANCE A. The Study shall be prepared by a Registered Professional Electrical Engineer experienced in studies of this type and shall bear the PE’s seal and signature. B. Study shall conform to current ANSI/IEEE standards. SUBMITTALS A. Submit prior to equipment delivery. B. Description and version of software program used, including database type libraries. C. One Line Diagram identifying equipment, busses, and protective devices. D. Textual description of coordination obtained and compromises selected. E. Tabulation of all adjustable device settings. F. Time-current curve plots graphically illustrating protective device ratings and characteristics including: 1. Utility protective device. 2. Secondary main protective device. 3. Each device through, and including, the main and largest branch circuit device in the most downstream panel. 4. Transformer inrush and damage limits. 5. Device long-time pick-up and delay, short-time pick-up and delay, instantaneous, ground fault pick-up and delay. 6. Motor-starting curve. G. Submit final As-Built version of Study minimum 60 days prior to final review of electrical system. END OF SECTION 26 0573 1 FMD NO. 1256976 163 BID NO. 36813636 FMD NO. 1256976 164 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Service & Distribution Equipment- 1/21/13 Section 262000 SECTION 26 2000 SERVICE AND DISTRIBUTION EQUIPMENT PART 1: GENERAL 1.1 SCOPE A. Specification Sections 262001 through 262419 describe low voltage electrical distribution equipment such as switchboards, panelboards, motor control, transformers, and similar equipment. This section describes general requirements pertaining to the distribution system and all equipment specified in Sections 262001 through 262419. B. Fuses, safety switches, and individually enclosed circuit breakers are specified in other Sections. 1.2 UNIFORMITY A. All switchboards, motor control centers, circuit breakers, panelboards, and other items of distribution equipment furnished under this specification shall be of the same manufacture except as otherwise noted. 1.3 STANDARDS A. All material shall be listed and labeled by Underwriters Laboratories, Inc., where such listing is available for that class of equipment. 1.4 LOCKS A. All locks for switchboards, power panels, branch circuit panels, and other distribution equipment doors shall be keyed identical. 1.5 SYSTEM CHARACTERISTICS A. The service voltage is 120/208 volts, 3–phase, 4–wire, wye, with grounded neutral. 1.6 POWER COMPANY COORDINATION AND SCHEDULING A. Field coordinate any required utility outages with UGA Facilities Management Department. 1.7 FAULT CURRENT A. Equipment fault current ratings (SCCR) indicated on the drawings, or specified herein, shall be the minimum rating of the equipment, including device interrupting ratings and bracing. PART 2: PRODUCTS 2.1 MANUFACTURERS: A. Acceptable equipment manufacturers are listed within sections 262001 through 262419. PART 3: EXECUTION (Not Used) END OF SECTION 26 2000 1 FMD NO. 1256976 165 BID NO. 36813636 FMD NO. 1256976 166 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Distribution Equipment Testing- 1/21/13 Section 262001 SECTION 26 2001 DISTRIBUTION EQUIPMENT TESTING PART 1: GENERAL 1.1 DISTRIBUTION EQUIPMENT TESTING A. All costs incurred for testing shall be included under Division 26. B. Description of Tests: 1. Preliminary Inspections and Tests: Visual inspections of electrical equipment, wire checks of factory wiring and any other preliminary work required to prevent delays during performance of electrical acceptance tests. 2. Electrical Acceptance Tests: Those inspections and tests required to show that the workmanship, methods, inspections, and materials used in erection and installation of the electrical equipment conforms to accepted engineering practices, IEEE, ICEA and NEMA Standards, the National Electrical Code, InterNational Electric Testing Association (NETA) specifications, and manufacturer’s instructions, and to determine that the equipment involved may be energized for operational use. 3. Operating Tests: Tests performed on electrical equipment, installed under other sections, to show that the electrical equipment will perform the functions for which it was designed. 4. Final Acceptance: Final acceptance of electrical equipment will depend on equipment integrity as determined by the electrical acceptance test, and also depend on complete operational tests. C. Test and calibrate all new circuit breakers furnished under this contract and “spare” breakers scheduled to be placed into service, prior to acceptance of the building. This requirement shall apply to breakers rated 100 amp and larger. D. Tests shall be conducted by a NETA certified and approved independent testing company per NETA recommendations and in accordance with NETA Standard Practices E. In general, tests shall include the following: 1. 2. 3. 4. Determine proper operation of circuit breaker trip devices. Determine trip ratings or settings are correctly adjusted Determine control and interlock devices perform as specified. Determine electrical resistance across contact surfaces in switches, circuit breakers and bus way is acceptable. 5. Torque all bolted connections 6. Determine bus bars are properly braced as specified. F. Contractor shall advise in writing as to when the distribution equipment will be tested so that the Owner’s representative may be present to witness this test. At least one week’s notice of this test shall be given. G. At the contractor’s option, a representative of the distribution equipment manufacturer may be present to witness the test and verify the results. 1 FMD NO. 1256976 167 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Distribution Equipment Testing- 1/21/13 Section 262001 H. These tests shall not alter the contractor’s guarantee of the equipment. All work and materials found to be in non-compliance shall be replaced and re-tested by the contractor without additional cost to the Owner. I. Provide (3) copies of bound test reports, bound and included in the closeout documentation. PART 2 – PRODUCTS (Not Used) PART 3 – EXECUTION (Not Used) END OF SECTION 26 2001 2 FMD NO. 1256976 168 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Distribution Switchboards- 1/21/13 Section 262413 SECTION 26 2413 DISTRIBUTION SWITCHBOARDS PART 1: GENERAL 1.1 SCOPE A. This section describes service entrance and distribution switchboard equipment. 1.2 STANDARDS AND CERTIFICATION: A. The switchboard shall be designed, assembled, and tested in accordance with the applicable standards of ANSI, IEEE, and NEMA. B. The switchboard shall be listed under UL 891. 1.3 SUBMITTAL DOCUMENTS: A. For switchboard: 1. 2. 3. 4. 5. 6. 7. 8. 1.4 Physical dimensions of the equipment. Bussing diagrams, including bus sizes. Minimum device interrupting capacity Bus bracing. Device locations and height of all circuit breaker operating handles. Breaker descriptions. Mimic bus diagram and nameplates. Elevation view drawings. OPERATION AND MAINTENANCE MANUALS: A. Provide two copies of operation and maintenance manuals, assembled in binders and indexed, for a complete operation and maintenance manual. B. Include maintenance instructions, detailed drawings, and parts list for circuit breakers. C. Include record copy of submittal documents D. Include manufacturer’s published recommended procedures for preventative maintenance, repair, and normal operation of the switchboard, and all components. E. Include all required literature as a separate section within primary Division 16 Operation & Maintenance (O&M) Manual(s) for equipment specified in Sections 262000 through 262419. 1.5 TRAINING: A. Training for equipment furnished under this section shall be included. B. Training shall be scheduled at the convenience of the Owner. 1.6 PRODUCT DESCRIPTIONS: 1 FMD NO. 1256976 169 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Distribution Switchboards- 1/21/13 Section 262413 A. Where reference is made in this Specification to a specific manufacturer, model number, or series, the equipment being specified by this reference shall be complete with, as a minimum, all standard features, accessories, ancillary device, controls, operational sequences and other characteristics shown in the manufacturer’s published technical and sales data that describes the model or series referenced. Where higher standards, additional, optional features, or more stringent requirements are stated elsewhere in the Specification, the Specification shall govern. PART 2: PRODUCTS 2.1 MANUFACTURERS: A. Square D: “I-Line” construction. B. GE: “Spectra” C. Cutler Hammer: “Pow-R-Line C” D. Siemens: “SB1” 2.2 CONSTRUCTION: A. Freestanding, front connected, metal-enclosed with individually mounted breakers. enclosure shall not require rear access. The B. Dimensions shall not exceed those shown on the drawings or specified. Maximum depth shall be 2’-1”. C. Construction shall allow for cable entry from top and bottom into cable compartments. D. The minimum short circuit interrupting and withstand rating of equipment shall be as indicated on the drawings. E. Each section of multi-section switchboards shall be equipped with barriers constructed of grounded metal or 0.25” thick (minimum) rigid glass polyester insulating board. F. Main breaker compartment shall be barriered. G. Shipping split locations shall be field coordinated with the installing Contractor. 2.3 BUS: A. All bus shall be plated copper, with joints bolted by high strength grade 5 bolts and Belleville spring type washers. B. Provide ground bus, ¼” thick, minimum 40% rated, bolted to frame full length of switchboard. Provide lugs on ground bus for incoming and outgoing feeder ground conductors. Ground bus shall be continuous throughout. C. Neutral bus shall be isolated and shall be 100 percent rated continuous through-out the entire board. 2 FMD NO. 1256976 170 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Distribution Switchboards- 1/21/13 Section 262413 D. Bus ratings: 1. Main Bus: full size as indicated on the drawings, entire length of switchboard. Current density shall be 1000 amps per square inch. 2. Section Bus: equal to the sum of branch device frame sizes (up to size of main bus). 3. Device Bus: equal to device rating as a minimum. 4. Provide bus equipped with breaker stabs, quantity and rating as indicated on the drawings, where “provisions” or “spaces” are noted. 5. All bus shall be factory drilled, or punched, with copper, two-hole tongue, compression lugs bolted to bus. Coordinate lug size requirements with feeder schedule. 2.4 DISTRIBUTION CIRCUIT BREAKERS: A. Molded case circuit breakers manually operated. B. Trip units shall be thermal-magnetic, or Solid State electronic type with field interchangeable rating plugs, with adjustable long time pickup and delay, adjustable short time pickup and delay, adjustable instantaneous. C. Circuit breaker handles shall be accessible and visible without special detachable operating handles. 2.5 SWITCHBOARD ACCESSORIES: A. Provide all required breaker accessories. B. Provide engraved plastic laminated nameplates for each device, displaying circuit number and load served as scheduled, white color with black letters. PART 3: EXECUTION 3.1 EXECUTION A. Install the equipment in accordance with the manufacturer’s recommendations and instructions, mounted on 4” high concrete housecleaning pad. B. Protect the equipment from moisture and contamination during shipping. C. Tighten all bus joints and connections to manufacturer’s recommended torque settings prior to energizing. D. Provide a Megger test of the bussing prior to energizing. Protect switchboard electronic metering and equipment E. Lace up all wiring using nylon ties. Secure cable bundles to insulated conductor bracing. Provide additional insulation material where required to protect cables from sharp edges inside cubicles. END OF SECTION 26 2413 3 FMD NO. 1256976 171 BID NO. 36813636 FMD NO. 1256976 172 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Branch Circuit Panelboards- 1/21/13 Section 262416 SECTION 26 2416 BRANCH CIRCUIT PANELBOARDS PART 1: GENERAL 1.1 DESCRIPTION A. This section describes panelboards as scheduled on the drawings as “Panelboards” and also referred to on the drawings and in the specification as “panel”. B. Definition: As defined in the National Electrical Code. 1.2 SUBMITTAL DOCUMENTS A. Provide a schedule of each panelboard demonstrating placement of branch breakers in accordance with the schedules on the drawings. Circuit numbering shall be indicated and configured as scheduled. B. Dimensioned drawings of panel can and panel cover detailing construction of hinged front cover. Gutter sizes shall be indicated. C. Provide ratings of each main and branch device, panelboard electrical characteristics, and assembly fault current rating. 1.3 OPERATION AND MAINTENCE MANUALS A. Provide record copy of submittal documents. B. Provide maintenance instructions, detailed drawings, and parts lists. C. Provide manufacturers published recommended procedures for preventative maintenance, repair, and normal operation of the panelboards and all components. PART 2: PRODUCTS 2.1 CONSTRUCTION A. Lighting and branch circuit panels shall be factory assembled with bolt-on breakers. B. Bus shall be plated copper. C. Construction shall be dead front with separately mounted interior trim. D. Branch breakers shall be arranged as scheduled on the drawings. E. Multi-pole breakers shall be common trip. Tandem breakers shall not be furnished. F. Enclosure shall be galvanized sheet steel. End panelboards shall be blank without knockouts. G. All panels shall have finished door cover trim “hinge-mounted” to box on surface mounted panelboards. Factory paint cover with two coats of standard gray color enamel. 1 FMD NO. 1256976 173 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Branch Circuit Panelboards- 1/21/13 Section 262416 H. Provide flush lock and catch. Lock mechanism shall be metal construction. I. Gutter sizes: 1. Manufacturers standard, unless otherwise required. 2. Provide additional 8” gutter width with sheet metal barrier where feeder passes through panel can or is tapped in gutter. J. Provide ground bus bonded to enclosure. K. Where a panelboard is shown to be fed by more than one conductor per phase, an individual lug shall be provided for each conductor. L. Provide circuit breaker mounting hardware where a “space” is scheduled. M. Minimum interrupting rating of main and all breakers shall be the minimum assembly rating as scheduled on the drawings. PART 3: EXECUTION 3.1 GENERAL A. For all flush mounted panelboards provide (6) six ¾” empty conduits stubbed out at top of wall from panel. B. Branch circuit conductors shall be run at right angles to enclosure sides, bundled neatly and laced with nylon Ty-Raps. C. Provide typewritten panel directories indicating location and type of load served by each branch circuit. D. Conductors shall not be spliced within the panelboard enclosure. Branch circuit conductors not long enough to reach the scheduled branch circuit breaker shall be replaced. E. Tighten all factory connections, including breaker mounting hardware prior to energizing panelboard. F. All unused breaker mounting spaces shall be covered or blanked. G. Provide specified nameplate on panel front cover. 3.2 MOUNTING A. Surface mount or flush mount, at locations as indicated on the drawings, at same height to top of trim, generally 6’-6”, unless otherwise required by specific site conditions. END OF SECTION 26 2416 2 FMD NO. 1256976 174 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Distribution Equipment- 1/21/13 Section 262700 SECTION 26 2700 MISCELLANEOUS DISTRIBUTION EQUIPMENT PART 1: GENERAL 1.1 DESCRIPTION A. This section describes disconnect switches, separate individually-enclosed circuit breakers, electronic time clocks, lighting contactors, photoelectric control devices, and fuses for other than devices furnished with integral current-limiting fuses, such as fused circuit breakers and motor circuit protectors. B. Spare fuses of all types are included in this section. C. Provide required fuses, including spare fuses, for all fusible equipment furnished under this division. 1.2 NAMEPLATES A. Provide engraved “lamicore” nameplates for all disconnect switches, time clocks, contactors, and individually enclosed circuit breakers, indicating the equipment served. Refer also to Section 260553, Electrical Identification. 1.3 SPARE FUSES A. Provide (3) three spare fuses of each type and rating for all power and control fuses, including current-limiting fuses furnished as an integral part of fused circuit breakers or motor circuit protectors. 1.4 SUBMITTAL DOCUMENTS A. Required for all equipment specified by this section. B. Circuit breaker submittal shall indicate device ratings, including interrupting capacity, dimensions of enclosure, and wire bending space. 1.5 OPERATION AND MAINTENCE MANUALS A. Provide record copy of all submittal documents and assemble as identified in another section. B. Provide two (2) copies of any software required to configure the lighting control system(s). PART 2: PRODUCTS 2.1 GENERAL A. All devices shall be UL labeled. 2.2 FUSES A. Manufacturer: 1. Bussman 1 FMD NO. 1256976 175 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Distribution Equipment- 1/21/13 Section 262700 2. Ferraz-Shawmut 3. Little-Fuse B. Fuses applied on circuits operating at 250 Volts or less shall be 250 Volt rated. C. Fuses applied on circuits operating at less than 600 Volts and more than 250 Volts shall be 600 Volt rated. D. All fuses shall have an interrupting capacity of 200,000 amps, RMS symmetrical, at rated voltage. E. Fuses for transformer feeders and motor branch circuits shall be dual-element time delay, current-limiting, Class J for 600 Amp and smaller, Class L for larger than 600 Amp. F. Fuses for feeders, control circuits, and other loads shall be fast acting, current limiting, Class J for 600 Amp and smaller, Class L. for larger than 600 Amp. 2.3 DISCONNECT SWITCH (SAFETY SWITCH) A. Manufacturer: 1. Cutler-Hammer 2. General Electric 3. Siemens 4. Square D B. Shall be of the fusible or non-fusible type, as indicated on the drawings. C. Shall be heavy duty, quick-make, quick-break, HP rated, hinged cover dual interlocked with switch handle and with external interlock defeat mechanism, with provision for handle and door padlocking. D. In dry locations shall be Type NEMA 1 enclosed. E. In damp locations, or outdoors, shall be Type NEMA-3R, enclosed, except where the applied use requires an alternate Type NEMA enclosure rating. 2.4 DOUBLE-THROW DISCONNECT SWITCH A. Manufacturer: 1. Cutler-Hammer 2. Siemens 3. Square D B. Shall be of the fusible or non-fusible type as indicated on the drawings. C. Shall be heavy duty, quick-make/quick-break, load-make/load-break rated, HP rated, hinged cover dual interlocked with switch handle and with external interlock defeat mechanism, with provision for handle and door padlocking. D. Switch handle shall have padlocking provisions in all (3) three switch positions and external interlock defeat mechanism. 2 FMD NO. 1256976 176 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Distribution Equipment- 1/21/13 Section 262700 E. Installed in dry locations: Type NEMA-1 enclosed. F. Installed in damp locations or outdoors: Type NEMA-3R enclosed, except where the applied use requires an alternate Type NEMA enclosure rating. G. Provide separate ground bus. Provide insulated neutral bus where the scheduled feeder contains a neutral conductor. H. Provide lugs sized for actual feeder conductors where standard factory lugs are not suitable. 2.5 INDIVIDUALLY ENCLOSED CIRCUIT BREAKERS A. Manufacturer: 1. 2. 3. 4. Cutler-Hammer General Electric Siemens Square-D Company B. Breakers shall be of appropriate frame size for the indicated trip setting, and rated for the applied circuit voltage. Fault current interrupting rating of each breaker shall be as noted on the drawings, minimum 42,000 A.I.C.R. C. Installed in dry locations: NEMA-1, enclosed. D. Installed in damp locations or outdoors: NEMA-3R enclosed, except where the applied use requires an alternate rating. 2.6 COMBINATION TIME SWITCH/PHOTOCONTROL A. Two-channel digital time switch with 30A SPDT contacts, capable of 20 set points, automatic Daylight Savings Time and Leap Year compensation, and LCD display. B. Unit shall have astronomic option with offset up to 4 hours and 59 minutes, before or after sunrise. C. Real time clock shall be retained by super capacitor for 100 hours. D. Unit shall be capable of manual override ON or OFF either to next scheduled event or permanently. E. Provide electronic light sensor which can be mounted up to 1000 feet from the controller. 2.7 TIME SWITCH A. Two-channel digital time switch with 30A SPDT contacts, capable of 20 set points, automatic Daylight Savings Time and Leap Year compensation, and LCD display. B. Unit shall have astronomic option with offset up to 4 hours and 59 minutes, before or after sunrise. C. Real time clock shall be retained by super capacitor for 100 hours. 3 FMD NO. 1256976 177 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Miscellaneous Distribution Equipment- 1/21/13 Section 262700 D. Unit shall be capable of manual override ON or OFF either to next scheduled event or permanently. 2.8 LIGHTING CONTACTORS A. Mechanically held, multi-pole, minimum of (1) one spare pole space. Contacts shall be field convertible with N.O. and N.C. indicators. B. Ratings: 30 Amp fluorescent lighting; 20 Amp tungsten lighting. C. Enclosure: Type NEMA 1, except where the applied use requires an alternate rating. PART 3: EXECUTION 3.1 INSTALLATION A. Mount disconnects on building structural elements, or on auxiliary framing, with top at 6’-0” A.F.F. where allowed by surrounding conditions. B. Devices shall not be supported from, or mounted to, equipment of other trades unless approved in writing by the manufacturer of that equipment. C. Raceways connecting NEMA-3R enclosed devices shall be installed in such a manner as to prevent the entry of water. Raceways shall enter only the bottom of the enclosure. D. Provide engraved lamicore nameplate for each disconnect and separately enclosed breaker. Nameplates shall state source of circuit, load served, circuit number, voltage, and phase. Refer to Section 26 05 53, Electrical Identification. E. Provide disconnect switches for all motors, HVAC, plumbing equipment, and other electrically operated equipment where not connected by cord and plug, unless fed from a motor control center located in the immediate area of the motor. Disconnect switches shall be fused where equipment manufacturers electrical data label plate states “Maximum Fuse Size”, or similar wording. F. Mount individual line voltage photoelectric controls on suitable weatherproof box, or suitable cast conduit fitting, in the directional orientation as recommended by the manufacturer. Adjust sensor window for suitable operation at dusk and at dawn END OF SECTION 26 2700 4 FMD NO. 1256976 178 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Wiring Devices - 1/21/13 Section 262726 SECTION 26 2726 WIRING DEVICES PART 1: GENERAL 1.1 SCOPE A. This section describes wall switches, occupancy sensors, receptacles, faceplates, and other wiring devices. B. Outlet boxes are specified in another section. 1.2 STANDARDS A. All devices shall be UL labeled. B. All devices shall meet applicable NEMA wiring device standards. C. All special-purpose receptacles shall be NEMA Standard configuration. 1.3 SUBMITTAL DOCUMENTS A. Submit manufacturer catalog cut sheets of wiring devices specified in this section. 1.4 OPERATION AND MAINTENANCE MANUAL A. Provide record copy of device submittal incorporated into the project O&M Manuals. PART 2: PRODUCTS 2.1 MANUFACTURE A. Switches, receptacles, plates: 1. 2. 3. 4. Arrow-Hart Bryant Hubbell P&S/Legrand B. Occupancy Sensors: 1. Wall Mounted: passive dual technology type sensor, suitable for single or multi-gang mounting in standard depth wall box. 2. Ceiling Mounted: passive dual technology type sensor, suitable for mounting at ceiling height in suitable outlet box. 3. Manufacturer: a. Sensor Switch b. Watt Stopper c. Hubbell 4. Device types and manufacturer series numbers on the drawings are based on Sensor Switch. 1 FMD NO. 1256976 179 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 2.2 Wiring Devices - 1/21/13 Section 262726 DESCRIPTION A. The color of all devices mounted in finished interior spaces shall be as selected by the Architect. B. Switches, receptacles: 1. Standard wall toggle switches for lighting circuits shall be heavy-duty, 277 Volt, 20 Amp, AC only, nylon, quiet type, with ground bonding screw terminal, Hubbell #HBL1221 Series, back wired using screw and clamp. 2. Special purpose switches, such as 3-way, double-pole, and 4-way switches shall be similar construction. 3. Duplex receptacles shall be heavy-duty, 125 volt, 15 Amp, 3-wire grounding, nylon face, with self-grounding attachment, with ground bonding screw terminal, Hubbell #HBL5362 Series, back wired using screw and clamp. 4. Individual duplex receptacles on separate 20 Amp circuits shall be rated 20 Amp. 5. Special purpose receptacles shall be of NEMA type indicated, heavy-duty, with nylon face where available. 6. Wall toggle switches mounted adjacent to wall box dimmers shall be of the same manufacture and appearance as the wall box dimmer. 7. G.F.C.I. Type receptacles shall be rated 20 Amp, Hubbell #GF5362 Series. 8. All 15- and 20-ampere, 125- and 250-volt nonlocking receptacles installed in a wet location shall be listed weather-resistant type. 9. Remote switch with local override: a. 5A, SPST (single pole) – Sentry Switch SS05277, Lithonia SSPL5277, Cooper G5-W b. 5A, SPDT (three-way) – Sentry Switch SS053277, Lithonia SSPL53277, Cooper G5T-W c. 20A, SPST (single pole) – Sentry Switch SS20277, Lithonia SSPL20277, Cooper G20-W d. 20A, SPDT (three-way) – Sentry Switch SS23277, Lithonia SSPL23277, Cooper G20T-W C. Device plates/covers for interior application: 1. Finished Room Areas: As selected by Architect. 2. Utility and Mechanical Room Areas: Nylon cover, color to match devices. D. Device plates/covers for exterior exposed outlets: 1. Weatherproof, heavy-duty cast aluminum, “in-use” type where required by the location to be applied, Hubbell #WPxxx Series, or cast iron for FS/FD box mounting. 2. Weatherproof receptacle covers shall be suitable for the specific application. a. 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug is inserted. PART 3: EXECUTION 3.1 GENERAL A. Refer to Section 260534, BOXES, for outlet box requirements. 2 FMD NO. 1256976 180 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Wiring Devices - 1/21/13 Section 262726 B. All devices shall be installed in appropriate boxes designed for the purpose, in accordance with manufacturer’s directions. C. Adjacent outlets of any type, including dimmers and fan speed controls, shall be installed in multi-gang boxes with a single multi-gang faceplate. 3.2 INSTALLATION A. Locations, unless otherwise required by local codes or noted on the drawings (dimensions in center): 1. Switches: 48 in. above finished floor, 4 in. from doorjamb on strike side of door. 2. Receptacles: 1 ft. 6 in. above finished floor, except where indicated above a countertop. 3. Telephone and data outlets: 1 ft. 6 in. above finished floor, except where indicated above a countertop. B. Grounding: Provide AWG 12, green color, insulated copper ground bonding jumpers for all switches and receptacles, bonded to the grounding screw provision within the box with separate grounding screw or lug. C. Device Labeling (applies to branch circuit devices wiring outlets under this section): 1. Provide adhesive backed label on each wall switch and receptacle device outlet coverplate indicating panelboard served from and circuit number (i.e.: LPA-6). 2. Labels shall be made on 3/8” or ½” inch stock, black color letters with clear background. 3. Label system shall be Brother “P-Touch” System or equivalent. 4. Labels shall not be applied until final touch-up painting is complete and covers are permanently mounted. END OF SECTION 26 2726 3 FMD NO. 1256976 181 BID NO. 36813636 FMD NO. 1256976 182 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Motor Control - 1/21/13 Section 262900 SECTION 26 2900 MOTOR CONTROL PART 1: GENERAL 1.1 SCOPE A. This section describes motor control centers and separately mounted starters that are furnished under this division. B. Certain starters and contactors are provided under other divisions, either separately mounted or integral with the equipment, and shall be installed and connected under Division 26. 1.2 SUBMITTAL DOCUMENTS A. Technical data and catalog sheets completely describing physical and electrical characteristics of all unit-mounted and individually mounted starters. B. Manufacturers published illustrative literature providing details of equipment construction and appearance. 1.3 OPERATION AND MAINTENANCE MANUALS A. Provide (3) three copies of operation and maintenance manuals, assembled in binders and indexed, for a complete operation and maintenance manual. B. Include record copy of submittal documents C. Provide manufacturers published recommended procedures for preventative maintenance and repair. D. Included all required literature as a separate section within the primary Division 26 Operations & Maintenance (O&M) Manuals(s) for equipment specified in Sections 262000 through 262419. 1.4 COORDINATION WITH THE WORK OF OTHERS A. Coordinate with each trade furnishing equipment requiring electrical service to verify and determine that the characteristics shown on the electrical drawings for the circuit serving the equipment are compatible with the requirements of the equipment being furnished. Provide written notice of any discrepancies. PART 2: PRODUCTS 2.1 MANUFACTURERS: A. Allen-Bradley B. General Electric 1 FMD NO. 1256976 183 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Motor Control - 1/21/13 Section 262900 C. Cutler-Hammer D. Siemens E. Square-D 2.2 STARTERS: Unless otherwise indicated, starters shall be: A. NEMA sized, magnetic, full-voltage, non-reversing, single-speed (FVNR); B. Where specifically indicated on the drawings provide magnetic starters of other types, such as reversing or reduced-voltage C. Provide variable frequency AC motor drives where noted on the drawings as “VFD” type control. D. With “hand-off-automatic” switch. Provide (2) SPDT additional contacts on switch for use by DDC Controls Vendor to monitor position of switch. E. With 120 volt control power transformer, with fused primary and grounded fused secondary F. Red and green “LED” type pilot lights to indicate “RUN” or “OFF” G. With two additional spare single-pole double-throw (SPDT) contacts. H. With electronic solid-state type overloads sized on the basis of the actual full load running current of the motors furnished; overloads in all three phases. I. With reset button in cover J. Combination starters shall incorporate an adjustable, magnetic-only, motor circuit protector (MCP) type circuit breaker. MCP’s with current limiters shall be provided where required by the available fault current. The MCP rating shall be selected on the basis of the horsepower of the actual motor installed. K. Starter doors shall be interlocked to prevent opening of the door with disconnect in the “on” position, with approved voidable feature. L. Disconnect handle shall have padlocking provisions. M. Provide engraved plastic nameplate for each starter with description of equipment served. Refer to Section 260553, Electrical Identification. PART 3: EXECUTION 3.1 SEPARATELY-MOUNTED INDIVIDUAL STARTERS A. Mount individual starters directly on wall, or on structure, or on auxiliary Unistrut framing where other suitable mounting surface is not available. B. For gypsum board wall mounting, group and mount starters on suitably painted, fire-retardant wood backboards. 2 FMD NO. 1256976 184 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 3.2 Motor Control - 1/21/13 Section 262900 OVERLOAD ELEMENTS A. Adjust and set solid-state overload elements based on actual motor nameplate data, motor ambient temperature, and starter ambient temperature, where different from motor. B. Provide a tabulation of all motors, indicating motor designation, nameplate full-load current, ambient temperatures, and overload type provided. 3.3 FIELD COORDINATION A. Coordinate with the manufacturer’s start-up representative and assist with their field personnel as required to allow timely completion of factory required services. Place each variable frequency drive in service after all adjustments. Submit report of final settings for each control point. END OF SECTION 26 2900 3 FMD NO. 1256976 185 BID NO. 36813636 FMD NO. 1256976 186 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Luminaires - 1/21/13 Section 265000 SECTION 26 5000 LUMINAIRES PART 1: GENERAL 1.1 SCOPE A. Lighting fixtures, lamps, ballasts, bases, and associated equipment. 1.2 STANDARDS A. All material shall bear the label of the Underwriters Laboratories, Inc. 1.3 VOLTAGE A. Fixture voltage is indicated by circuit in which it is connected. Contractor shall determine fixture voltage from drawings. 1.4 CEILING INTERFACE A. Specific catalog numbers shown for fixtures do not necessarily describe all mounting hardware or accessories required for a particular installation. Determine ceiling types from the finish schedule specified under another division, and furnish all required materials for a complete and proper installation. Provide plaster frames for wet plaster or stucco ceilings. 1.5 COORDINATION A. Provide other trades with a schedule of the outside dimensions of each type of recessed fixture when submittal documents have been approved. Examine applicable plans and shop drawings describing the work of other trades for possible conflicts in the clearances required for installation. The architect shall be notified prior to fabrication of any material of any conflict that cannot be resolved at no cost to the Owner by normal jobsite coordination between trades. 1.6 SUBMITTAL A. Furnish a bill of material cover sheet and original data sheet, combined into binder, describing each fixture type. If a catalog page describes more than one fixture, the page shall be appropriately marked identifying the exact item being submitted. Photometric data shall be submitted for each fixture type that has a reflector or lens for directing the light output. Drawings larger than 8 ½ x 14 shall be submitted in 8 ½ x 11 envelopes bound into the submittal brochure. B. Copy of Solid State Ballast warranty. C. Point by point plot on a scaled drawing to indicate the foot-candle performance of all exterior fixtures. D. A tabulation of all lamps to be utilized in each fixture. 1 FMD NO. 1256976 187 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Luminaires - 1/21/13 Section 265000 E. Where equivalent manufacturers for lighting fixtures are not indicated or scheduled, one manufacturer and model number is listed as “Design Standard” on the fixture schedule. The intent is to define the appearance, style, function, performance, and level of quality deemed necessary by the architect as well as to define the standard used by the architect as the basis of the design described by the drawings and specifications. Light fixtures equal in the appearance, style, function, performance, and level of quality as manufactured by other than the “Design Standard” manufacturer may be proposed by the Contractor at or before submittal. The proposed material will be evaluated by the Design Professional and determination of equality with the “Design Standard” will not be unreasonably withheld. To assist in this determination, the Contractor shall submit detailed photometric and power density calculations for each space that the proposed alternate fixture will be utilized. If the alternate manufacturer or model is determined by the Design Professional to not be equal to the “Design Standard” in a parameter whose acceptance would not be in the best interest of the Owner, the alternate fixture will be rejected. The Contractor may then submit, at no additional cost to the owner, another alternate fixture or the fixture scheduled as the “Design Standard” for review by the Design Professional. Alternate material furnished shall comply with all requirements of the material specification, shall be, as determined by the Design Professional, equal in form and performance to the “Design Standard” and shall be dimensionally identical to the design standard where features are visible or where the work of other trades is affected. Determination of equally shall remain solely with the architect and his decision shall be final. 1.7 OPERATING and MAINTENANCE MANUAL A. Provide record copy of submittal documents. B. Provide tabulation of lamp type furnished for each fixture type. C. Bind all information together with other Division 26 manuals. PART 2: PRODUCTS 2.1 BALLASTS A. Fluorescent – T8 and Compact Fluorescent Lamps: 1. Solid state, 20 to 35 KHz lamp operation, total harmonic distortion on input current shall not exceed 10%. 2. Efficiency: 31 watts maximum input wattage per FO32T8 lamp connected to the ballast. Ballasts shall operate installed lamps at full output, parallel lamp operation. 3. UL, CBM, & ETL listed. 4. Suitable for continuous operation in fixtures where used. 5. Sound rating “A”. 6. Single ballast per fixture except where multi-level switching is shown on the drawings. 7. Warranty by ballast manufacturer to fixture end user: minimum 2 years non-prorated. 8. Ballast shall have an RFI filter on line input and shall comply with FCC Part 18 and NEMA requirements limiting EMI and RFI and shall not interfere with the operation of other normal electrical equipment. 9. Ballast shall comply with ANSI standards for surge protection. 2 FMD NO. 1256976 188 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 10. Design standard: Triad Ballastar. 11. Acceptable Manufacturers: Electric/Motorola. Luminaires - 1/21/13 Section 265000 Advance, Valmont, Osram/Sylvania, General B. HID 1. 2. 3. 4. UL listed. Type as noted by fixture type. Rated to operate at voltages within 10% of nominal. Provide with individual fuse for each ungrounded input conductor. Fuse size as recommended by ballast manufacturer. 5. Rated for operation to -20ºF for exterior fixtures. 2.2 LAMPS A. All lamps of any one type shall be of the same manufacturer. B. Incandescent: 1. 130 Volt rating if a standard catalogued item unless lamp is used in low voltage fixture 2. Wattage as scheduled 3. Type as required for specific fixture. C. Fluorescent: 1. 2. 3. 4. T8 triphosphor as scheduled Full output unless scheduled otherwise 3500 Kelvin Lamp color. Install clear lamp protection sleeves on linear T8 fluorescent lamps mounted in turret type industrial fixtures. 5. T5 triphosphor as scheduled D. HID: Super Metal Halide, or high-pressure sodium, as scheduled. E. Compact Fluorescent: 1. 3500 Kelvin F. Acceptable Manufacturers: 1. GE 2. Osram/Sylvania 3. Philips 2.3 TROFFERS A. Housing: 1. All steel parts shall be painted after fabrication with a minimum 90% reflective paint. 2. The housing for a fixture with parabolic louvers shall be a minimum of 5½” deep. 3. The housing for a fixture with lens shall be a minimum of 4½” deep. 3 FMD NO. 1256976 189 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Luminaires - 1/21/13 Section 265000 4. 3-lamp fixtures with 18-cell parabolic louver shall have two ballast covers for use with multi-level switch control of the inner lamps separate from the outer lamps. B. Parabolic Louvers: 1. The finish shall be silver, semi-specular, and low-iridescent. 2. The louver shall be a minimum 3” deep. 3. The louver shall be hinged and secured to the housing with reversible cam-action latches. C. Lens: 1. The lens shall be a minimum of 1/8” thick, and shall be pattern A-12. 2. The lens frame shall be regressed aluminum, hinged and secured to the housing with reversible cam-action latches. 3. Submit a 4” x 4” sample of lens with submittals. 2.4 RECESSED DOWN LIGHTS A. Reflector cones shall be one-piece, self-flanged. 2.5 POLES, POLE MOUNTED FIXTURES, BOLLARDS, WALL MOUNTED AREA LIGHTS A. Fixture and Bollard Finish: 1. Powder coating, 5mil minimum thickness 2. Color as selected by architect B. Area Lighting Poles: 1. 2. 3. 4. 5. 6. Aluminum square non-tapered pole with finish as scheduled. Constructed of seamless 6063 alloy aluminum tubing with internal vibration damper. With galvanized anchor bolts and hardware. With handhole at base and ground lug accessible through handhole. With anchor bolt cover with finish on all surfaces identical to pole finish. Wind rating: 100 MPH when supporting scheduled fixtures. C. Provide in-line, waterproof disconnecting fuse holders at each pole at handhole with fuses sized at 300% of ballast line amps. 2.6 FIXTURES SUSPENDED WITH AIRCRAFT CABLE A. The fixture manufacturer shall provide the field adjustable, 1/16”, galvanized, steel aircraft cable. B. Provide cable length as required to mount the fixture at the height shown on the drawings measured to the top of the fixture. C. In areas with finished ceiling, the aircraft cable shall be supported with a ¼ - 20 threaded rod anchored in/to the structure and extended ¾” below the finished ceiling. D. The fixtures shall be supported at a maximum of 8’-0” centers. 4 FMD NO. 1256976 190 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) 2.7 Luminaires - 1/21/13 Section 265000 FIXTURE TYPES: A. As scheduled on the drawings. B. All downlights shall be by the same manufacturer. C. All parabolic fluorescent troffers shall be by the same manufacturer. D. All direct/indirect and indirect suspended fixtures shall be by the same manufacturer. 2.8 Fixture types with an emergency ballast: A. Emergency lighting shall be provided by using a standard fluorescent fixture equipped with emergency ballast. This emergency ballast shall consist of a field-replaceable, hightemperature, maintenance-free nickel-cadmium battery, charger and electronic circuitry contained in one metal case with a 2’ length of flexible conduit. B. A solid-state charging indicator light to monitor the charger and battery, a single-pole test switch and installation hardware shall be provided. C. The emergency ballast shall be capable of operating all fluorescent lamps within the fixture at the minimum lumens initial output listed below for a minimum of 90 minutes: 1. 2. 3. 4. 5. 1 Linear fluorescent lamp a minimum of 2250 to 3000 lumens. 2 Linear fluorescent lamps a minimum of 1375 to 1500 lumens per lamp. 3 Linear fluorescent lamps a minimum of 1083 to 1133 lumens per lamp. 1 Compact fluorescent lamp a minimum of 350 to 750 lumens. 2 Compact fluorescent lamps a minimum of 212 lumens to 375 lumens per lamp. D. The emergency ballast shall be suitable for indoor locations. E. The emergency ballast shall have 8 Watts maximum of input power and a 57.6 Watt-hour battery capacity and shall exceed emergency standards set forth by the current NEC. F. The emergency ballast shall be U.L. listed for installation on top of or remote from the fixture and shall be warranted for a full five years from date of purchase. PART 3: EXECUTION 3.1 LOCATION A. The exact location of all fixtures in finished areas shall be as shown on the reflected ceiling plans. If the location shown on the reflected ceiling plan for a fixture differs from the location shown on the electrical plans, the fixture shall be installed as shown on the reflected ceiling plan. In utility and mechanical rooms the contractor shall adjust the location and mounting height of the indicated fixtures for best coordination with the work of other trades. 3.2 INSTALLATION A. Fluorescent fixtures with steel housings shall not be installed in direct contact with concrete structure, but shall be held off of the structure at least ½ inch with approved spacers. 5 FMD NO. 1256976 191 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building (Bldg. No. 2130) Luminaires - 1/21/13 Section 265000 B. All wire run into fluorescent or HID fixture housings or raceway shall be minimum 90ºC rated, Type THHN/THWN. Wiring run into incandescent fixture housings shall be 150ºC rated, Type SFF, or better. C. Flexible conduit connections to recessed fixtures shall be (6) ft. lengths of 3/8-inch steel flex with flex connectors as specified in the “Basic Materials and Methods” section. The flexible connections shall contain stranded conductors, AWG #14 minimum, Type THWN, with a separate grounding conductor bonded securely to the fixture housing. D. Flexible conduit connections to recessed fixtures located in accessible ceilings shall be installed such that each fixture can be relocated (1) ceiling tile space in any direction. 3.3 SUPPORTS AND ANCHORS A. Refer to Section 260548 - Seismic Restraints, for additional support and anchor requirements. B. Fixtures shall not be supported from ducts or piping of other trades without the approval of the Architect. C. Recessed fixtures not designed to lay-in a ceiling grid, and suspended fixtures, shall be supported by a threaded rod dropped from approved channels or brackets transmitting the fixture weight to the building structure. If the fixture is outlet box mounted, the box shall be supported in the same manner. D. Provide (4) clips with each lay-in type fixture anchoring the fixture to its supporting grid members. E. Hardware and unpainted metal used for mounting of exterior fixtures shall electrogalvanized. 3.4 ACCEPTANCE A. Incandescent fixtures used for construction lighting shall be provided with new lamps prior to final acceptance. B. Adjust locations of fixtures shown in mechanical equipment rooms to best suit the actual conditions based on final placement of equipment of other trades. Install in a manner and location to obtain optimum illumination. C. Target and focus adjustable fixtures in the presence of the Consultant. D. Noisy ballasts shall be considered defective and shall be replaced. E. All fixtures trims shall be free of light leaks as viewed from the occupied space. Suitably seal around trims to eliminate any light leakage around downlight trims and fluorescent fixtures. Louvers and lens shall be clean and free from fingerprints, dust, and physical damage. END OF SECTION 26 5000 6 FMD NO. 1256976 192 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building Fire Alarm System - 1/21/13 (Bldg. No. 2130) Section 283100 SECTION 28 3100 FIRE ALARM SYSTEM PART 1: GENERAL 1.1 DESCRIPTION A. 1.2 1.3 1.4 All components provided for modification of the existing system shall be compatible with and designed for use with the existing system. SCOPE A. All of the products described by this section shall be manufactured by a single U.S. manufacturer and furnished by the manufacturer or authorized representative. B. The installing company shall employ NICET (minimum Level II Fire Alarm Technology) technicians on site to guide the final checkout and to ensure the system integrity. C. The drawings are schematic in nature. The manufacturer’s listed device spacing requirements and applicable code requirements shall be maintained at all times. CODES AND STANDARDS A. The fire alarm system specified in this section shall be in accordance with the National Fire alarm Code (NFPA 72), the National Electrical Code (NFPA 70) and the Life Safety Code (NFPA 101). B. The fire alarm system and installation shall comply with provisions of UL safety standards pertaining to fire alarm systems. All products and components shall be UL listed and/or labeled. SUBMITTALS A. Submittals shall be prepared by the system manufacturer or authorized representative. Six copies of all submittals shall be submitted to the Engineer for review. B. Submittals should include technical product data including specifications and installation instructions for each type of component, control panel elevations, system point-to-point wiring diagrams, termination details, and battery capacity calculations. C. Submittals shall include sufficient information to determine compliance with drawings and specifications. D. All substitute equipment proposed as equal to the equipment specified herein, shall meet or exceed the following standards. For equipment other than that specified, the contractor shall supply proof that substitute equipment equals or exceeds the standards of the specified equipment. 1 FMD NO. 1256976 193 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building Fire Alarm System - 1/21/13 (Bldg. No. 2130) Section 283100 E. 1.5 1.6 1.7 1.8 Submit a software copy of all point-to-point wiring diagrams on a CD in ‘DXF’ or latest AutoCAD version format. MANUALS A. Complete operating and maintenance manuals shall be submitted with the shop drawings. B. Manuals shall include wiring diagrams indicating internal wiring for each component and the interconnections between components. DELIVERY, STORAGE AND HANDLING A. Handle fire alarm equipment carefully to prevent damage, breaking, and scoring. Do not install damaged equipment or components. B. Store fire alarm equipment in a clean, dry place. Protect from weather, dirt, water, construction debris, and physical damage. QUALITY ASSURANCE A. The vendor of the system shall currently maintain a locally run business for a minimum of five years and shall be an authorized distributor of the supplied equipment with full warranty privileges. B. The vendor shall maintain at his facility the necessary spare parts in the proper proportion as recommended by the equipment manufacturer to maintain and service the equipment being supplied. This facility shall be available for inspection by the engineer. C. The supplying vendor shall have attended the manufacturer's installation and service school. D. The vendor shall furnish manufacturer's manuals of the completed system including individual specification sheets, schematics, inter-panel and intra-panel wiring diagrams. In addition, all information necessary for the proper operation of the system must be included. Any bidder using other than the specified equipment must provide this information prior to bidding. E. As built drawings that include any changes to wiring, wiring designations, junction box labeling and any other pertinent information shall be supplied upon completion of project. SOFTWARE MODIFICATIONS A. All system modifications, changes, or upgrades shall be performed by a factory trained and certified technician. 2 FMD NO. 1256976 194 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building Fire Alarm System - 1/21/13 (Bldg. No. 2130) Section 283100 B. All hardware, software, tools and documentation necessary to modify the fire alarm system on site shall be provided as part of this contract. Modification of software shall not require power-down of the system or loss of facility fire protection while modifications are being made. PART 2: PRODUCTS 2.1 2.2 EQUIPMENT AND MATERIAL – GENERAL A. All equipment and components shall be new and the manufacturer’s current model. The devices, components, appliances and equipment shall be tested and listed by a nationally recognized approval agency for use as part of a protected premise protective signaling system. B. All equipment and components shall be installed in accordance with the manufacturer’s recommendations. CONDUIT AND WIRE A. Conduit: 1. Conduit shall be installed and sized in accordance with the National Electrical Code (NEC), state and local requirements. 2. All wiring shall be installed in conduit or raceway 3. Conduit shall be ½” minimum. B. Wire: 1. All fire alarm system wiring shall be new. 2. Wiring shall be in accordance with the NEC, state and local codes and as recommended by the fire alarm system manufacturer. Number and size of conductors shall be as recommended by the system manufacturer, but shall not be less than 18 AWG for initiating device circuits and signaling line circuits, and 14 AWG for notification appliance circuits. 3. All wire and cable shall be listed and approved by a recognized testing agency for use with a protective signaling system. 4. Wire and cable not installed in conduit shall have a fire resistance rating suitable for the installation as indicated in the NEC. 2.3 SECONDARY POWER SUPPLY A. Batteries shall be 12 volt, Gel-Cell type. B. Batteries shall have sufficient capacity to power the fire alarm system for not less than 24 hours of standby plus 10 minutes of alarm upon a normal AC power failure. C. Batteries shall have a 25% capacity safety factor. 3 FMD NO. 1256976 195 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building Fire Alarm System - 1/21/13 (Bldg. No. 2130) Section 283100 D. 2.4 Batteries are to be completely maintenance free. SYSTEM COMPONENTS A. Duct Smoke Detectors: 1. The in-duct smoke detector housing shall accommodate an intelligent photoelectric detector with integral auxiliary contacts. 2. Each in-duct smoke detector shall include air-sampling tubes installed per manufacturer’s recommendations and NFPA 72. B. Control Module (ADDRESSABLE OUTPUT DEVICE): 1. Addressable Control Modules shall be provided to supervise and control the operation of the fire/smoke dampers upon alarm. 2. The Control Module shall mount in a standard 4-inch square, 2-1/8" deep electrical box, or to a surface mounted backbox, or directly in the Fire Alarm Control Panel. 3. The Control Module shall provide address-setting means using rotary decimal switches or binary dip switches and shall also store an internal identifying code, which the Control Panel shall use to identify the type of device. An LED shall be provided which shall flash under normal conditions, indicating that the Control Module is operational and is in regular communication with the Control Panel. 2.5 ACCEPTABLE SYSTEM MANUFACTURER A. Match Existing PART 3: EXECUTION 3.1 INSTALLATION A. Installation shall be in accordance with the NEC, NFPA 72, state and local codes, as shown on the drawings and as recommended by the equipment manufacturer. B. All conduit, junction boxes, conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas. Smoke detectors shall not be installed prior to the system programming and test period. If construction is ongoing during this period, measures shall be taken to protect smoke detectors from contamination and physical damage. C. All fire detection and alarm system devices, control panels and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas. D. The system shall be equipped with the following protective devices to prevent damage or nuisance alarms by nearby lightning strikes, stray currents, or voltage transients. 4 FMD NO. 1256976 196 BID NO. 36813636 University Of Georgia HVAC Renovations for the University Print Building Fire Alarm System - 1/21/13 (Bldg. No. 2130) Section 283100 1. On AC input: Ditek DTK-120HW or DTK 120/240CM, EFI HWM-120, Leviton OEM120EFI, Northern Technologies TCS-HW, Transtector ACP100BWN3, or equal UL listed device. Install device at the electrical panelboard and trim excess lead lengths. Wind small coil in the branch circuit conductor just downstream of the suppressor connection. Coil shall be 5 to 10 turns of about 1” diameter and tiewrapped. 2. On DC circuits extending outside building: Near the point of entry to the building, provide suppressors equal to Simplex 2081-9027 and 2081-9028, Transtector TSP8601, Ditek DTKxLVL series, Citel America B280-24V, Northern Technologies DLP-42. 3.2 E. Monitor, control, isolation, and other auxiliary control devices shall be located at a height not to exceed 6’ above finished floor where possible. F. All addressable loop circuits shall have a minimum of 20% spare capacity for future use. G. There shall be no splices in the system other than at terminal blocks. Wire nuts and crimp splices are not acceptable. H. All devices and appliances shall be clearly identified by addressable loop name, floor, device type and device number as shown on drawings. I. High-powered audible devices shall be installed in mechanical equipment rooms and other areas with high ambient noise levels. ACCEPTANCE TESTS A. Provide the service of a competent, factory-trained engineer or technician authorized by the system manufacturer to technically supervise and participate during all of the adjustments and tests of the system. 1. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation. 2. Close each sprinkler system flow valve and verify proper supervisory alarm at the FACP. 3. Verify activation of all flow switches. 4. Open initiating device circuits, signaling line circuits, and notification appliance circuits to verify that the trouble signal activates. 5. Ground initiating device circuits, signaling line circuits, and notification appliance circuits to verify response of trouble signals. 6. Check alert tone to all alarm notification appliances. 7. Check installation, supervision, and operation of all intelligent smoke detectors during a walk test. 8. Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points. END OF SECTION 28 3100 5 FMD NO. 1256976 197 BID NO. 36813636 FMD NO. 1256976 198 BID NO. 36813636