IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 495 An Improved Control Algorithm of Shunt Active Filter for Voltage Regulation, Harmonic Elimination, Power-Factor Correction, and Balancing of Nonlinear Loads Ambrish Chandra, Senior Member, IEEE, Bhim Singh, B. N. Singh, Member, IEEE, and Kamal Al-Haddad, Senior Member, IEEE Abstract—This paper deals with an implementation of a new control algorithm for a three-phase shunt active filter to regulate load terminal voltage, eliminate harmonics, correct supply power-factor, and balance the nonlinear unbalanced loads. A three-phase insulated gate bipolar transistor (IGBT) based current controlled voltage source inverter (CC-VSI) with a dc bus capacitor is used as an active filter (AF). The control algorithm of the AF uses two closed loop PI controllers. The dc bus voltage of the AF and three-phase supply voltages are used as feed back signals in the PI controllers. The control algorithm of the AF provides three-phase reference supply currents. A carrier wave pulse width modulation (PWM) current controller is employed over the reference and sensed supply currents to generate gating pulses of IGBT’s of the AF. Test results are presented and discussed to demonstrate the voltage regulation, harmonic elimination, power-factor correction and load balancing capabilities of the AF system. Fig. 1. Fundamental building block of the active filter. Index Terms—Active filter, harmonic compensation, load balancing, power-factor correction, voltage regulation. I. INTRODUCTION S OLID state control of ac power using thyristors and other semiconductor devices is in an extensive use in a number of applications such as adjustable speed drives (ASD’s), furnaces, computers power supplies, and asynchronous ac–dc–ac links. These power converters behave as nonlinear loads to ac supply system and cause harmonic injection, lower power-factor, poor voltage regulation, and utilization of ac network. Moreover, in a three-phase ac system some load unbalancing may be present due to the use of some typical loads such as traction and furnaces. Single-phase loads on a three-phase supply system result in an unbalance in system voltage and supply current. The unbalance in the voltage affects the performance of other loads, Manuscript received November 11, 1998; revised January 18, 1999. This work was supported by the Natural Science and Engineering Research Council of Canada. Recommended by Associate Editor, F. D. Tan. A. Chandra, and K. Al-Haddad are with the Department of Electrical Engineering. Ecole de Technologie Supérieure GREPCI, Montreal, Quebec H3C 1K3, Canada. B. Singh is with the Department of Electrical Engineering. Indian Institute of Technology Hauz Khas, New Delhi 110016 India. B. N. Singh is with the Department of Electrical Engineering and Computer Science, Tulane University, New Orleans, LA 70118 USA. Publisher Item Identifier S 0885-8993(00)03394-9. Fig. 2. Control scheme of the active filter. 0885-8993/00$10.00 © 2000 IEEE Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 496 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 capacitor is used as the shunt AF. An indirect current control technique [28] is employed to obtain PWM switching signals for the devices used in the CC-VSI working as an AF. Three-phase reference supply currents are derived using sensed ac voltages (at PCC) and dc bus voltage of the AF as feedback signals. Two proportional plus integral (PI) controllers are used to estimate the amplitudes of in-phase and quadrature components of reference supply currents. The control algorithm of the AF is implemented on a TMS320C31 DSP system. Test results during steady state and transient operating conditions of the AF are presented and discussed in detail to demonstrate voltage regulation/power-factor correction, harmonic elimination and load balancing capabilities of the AF system. II. SYSTEM CONFIGURATION AND CONTROL SCHEME Fig. 3. Digital signal processing (DSP) system hardware of the active filter. mainly the cage induction motors. In the past, a number of attempts have been made [1]–[28] on harmonic elimination, load balancing and power factor correction. Several texts [2], [6], [9], [10], [21], [22] have appeared on electric power quality and many solutions have been suggested to improve the power quality. A number of compensators have been reported only for load balancing [2], [3], [5], [7], [11], [13], [19], [20] using lossless passive elements (L and C) and active elements (solid state CSI and VSI). Similarly, several attempts have been made only for harmonic elimination [1], [4], [6], [8]–[10], [12], [14]–[28] using passive, active and hybrid filters to improve the performance and to reduce the size of an active filter. Many control techniques such as instantaneous reactive power theory [4], notch filters [16], flux based controller [17], power balance theory [18]–[20], sliding mode controllers [14], [15] etc. have been used to improve the performance of the active and hybrid filters. Most of these control algorithms need a number of transformations and are difficult to implement. Apart from the problems of harmonics, poor power-factor and unbalance, there is some voltage drop at the point of common coupling (PCC) due to reactive power burden of nonlinear loads. This paper presents an implementation of a simple and new control algorithm of a shunt active filter (AF) for ac voltage regulation at load terminals (at PCC), harmonic elimination, power-factor correction and load balancing of nonlinear loads. The control algorithm of the AF is made flexible and it can be modified for power-factor correction (unity), harmonic elimination and load balancing of nonlinear loads. The proposed control algorithm inherently provides a self-supporting dc bus of the AF. An insulated gate bipolar transistor (IGBT) based current controlled voltage source inverter (CC-VSI) with a dc bus Fig. 1 shows the fundamental building block of the shunt AF. The AF system is made of a standard three-phase IGBT based ) and a dc bus VSI bridge with the input ac inductors ( , ) to obtain a self-supporting dc bus for an effeccapacitor ( tive current control. A three-phase ac mains with line impedance ) is feeding power to a three-phase diode bridge recti( , fier with a resistive-inductive load. A provision is made with a switch to open an ac line of the load to realize an unbalanced nonlinear load. The values of circuit parameters of the system are given in the Appendix. Fig. 2 shows the control scheme of the AF. Three-phase voltages at PCC along with dc bus voltage of the AF are used for implementation of control scheme. In real time implementation of the AF a band pass filter plays an important role. The three-phase voltages ( , , and ) are sensed at PCC (Fig. 1) using potential transformers and conditioned in a band pass filter to meet the range of ADC channels and to filter out any distortion. The three-phase voltages ( , , and ) are inputs , and ) are outand three-phase filtered voltages ( , , and ) here puts from band pass filter. The voltages ( , in after are termed as the supply voltages. In real time control of the AF, a self-supporting dc bus of the AF is realized using a PI controller over the sensed ( ) and reference ( ) values of dc bus voltage of the AF. The PI voltage controller on of the dc bus voltage of the AF provides the amplitude , and ) of reference supply in-phase components ( , , and currents. The three-phase unit current vectors ( ) are derived in-phase with the supply voltages ( , , ). Another PI controller is used over the reference and and sensed ( ) values of peak supply voltage. The output of of quadrathis PI controller is considered as an amplitude , and ) of reference supply curture components ( , rents. The three-phase quadrature unit current vectors ( , and ) are derived from in-phase unit current vectors , , and ). The multiplication of in-phase ampli( with in-phase unit current vectors ( , , and tude ) results in the in-phase components ( , , and ) of three-phase reference supply currents ( , , and ). Simiwith quadralarly, multiplication of quadrature amplitude , , and ) results in the ture unit current vectors ( , , and ) quadrature components ( Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER Fig. 4. 497 Performance of the AF system under switch IN and steady state conditions with a three-phase nonlinear load. Fig. 5. Steady state response of the AF for voltage regulation and harmonic elimination with a three-phase nonlinear load. Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 498 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 Fig. 6. Steady state response of the AF for voltage regulation, harmonic elimination, and load balancing with a single-phase nonlinear load. of three-phase reference supply currents ( , , and ). Alge, , and ) and quadrature ( , braic sum of in-phase ( , and ) components results in the three-phase reference supply currents ( , , and ). For regulation of voltage at PCC the three-phase reference supply currents have two components. The first component is in-phase with the voltage at PCC to feed active power to the load and the losses of the AF. The second component is at quadrature with the voltage at PCC to feed reactive power of load and to compensate the line voltage drop by reactive power injection at the PCC. For power-factor correction to the unity, harmonic elimination and balancing of nonlinear load, the quadrature component of reference supply currents is set to zero by assigning a zero value to the quantity . For the voltage regulation at PCC, the supply currents should lead the supply voltages while for the power factor control to the unity, the supply currents should be in phase with the supply voltages. Since these two conditions, namely, voltage regulation at PCC and power-factor control to unity can not be achieved simultaneously [2], therefore, the control algorithm of the AF is made flexible to achieve either voltage regulation, harmonics compensation, load balancing or power-factor correction to unity, harmonics compensation, load balancing. With three-phase supply voltages ( , , and ) and dc bus voltage ( ) as feedback signals, the control algorithm of the AF provides the three-phase reference supply currents ( , , and ) as output signals. A carrier wave PWM current controller is used over reference supply currents ( , , and ) and sensed supply currents ( , , and ) to generate gating signals to the IGBT’s used in the VSI bridge working as the AF. In response to gating pulses to the AF, it regulates the voltage at PCC, eliminates harmonics, correct the power-factor at PCC and balances the unbalanced nonlinear load while maintaining a self-supporting dc bus of the AF. A deadbeat time of 8 s is set between upper and lower devices of a leg of VSI to avoid shoot through fault. An over current protection of devices of the AF is provided at gate drive level of each IGBT to ensure a safe operation of the VSI. The carrier frequency of PWM controller is set at 6.4 kHz. Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER Fig. 7. 499 Switch IN response of the AF for voltage regulation, harmonic elimination with a three-phase nonlinear load. III. DSP HARDWARE AND CONTROL ALGORITHM In this section, the details of hardware interfacing with DSP system and basic equations of control algorithm are given. A. Description of DSP System Hardware Fig. 3 shows the DSP system hardware of the AF. The DSP system [29] consists of a TSM320C31 digital signal processor, eight channels of 12 bit analog to digital converter (ADC), eight channels of 12-bit digital to analog converter (DAC), three hardware interrupts and three timer interrupts. The DSP system is serially interfaced to an IBM-PC. In PC the control algorithm is developed in C language and converted in assembly language codes using optimizing compiler. These assembly language codes are down loaded into the DSP board through serial port. , and ) and dc The three-phase supply voltages ( , bus voltage ( ) of the AF are input signals to the DSP board through its ADC interface. The dc bus voltage of the AF is sensed using an isolation amplifier (AD202) and scaled to feed to ADC channel. The synchronization of ac mains with the control algorithm in DSP system is obtained using one digital signal (hardware interrupt). This signal is generated using comparators and logic gates over the three-phase ac supply voltages. The three-phase ac supply voltages result in six zero crossing signals at 60 of intervals. Therefore, the digital signal continuously interrupts the DSP system at 60 time intervals of frequency of ac supply system. Using four analog signals and one hardware interrupt signal, the control algorithm of the AF is implemented in real time. The control algorithm of the AF generates three-phase reference supply currents. The three-phase reference supply currents ( , , and ) are input signals to DAC’s of DSP. The outputs of DAC’s are fed to a carrier wave PWM current controller. In PWM current controller the error signals of the reference ( , , and ) and sensed ( , , and ) supply currents (sensed using LEM hall-effect current Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 500 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 Fig. 8. Switch IN response of the AF for voltage regulation, harmonic elimination and load balancing with a single-phase nonlinear load. sensors) are compared with a carrier signals resulting in gating pulses for the IGBT’s of the AF. The error signal, , is processed in PI controller and output at th sampling instant is expressed as B. Basic Equations of Control Algorithm of the AF The three-phase reference supply currents are computed using three-phase supply voltages and dc bus voltage of the AF. These reference supply currents consist of two components, one in-phase and another in quadrature with the supply voltages. 1) Computation of In-Phase Components of Reference of in-phase component Supply Currents: The amplitude of reference supply currents is computed using PI controller ) of the AF and over the average value of dc bus voltage ( . Comparison of average and its reference counterpart reference values of dc bus voltage of the AF results in a voltage , at th sampling instant error, which is expressed as, (1) (2) and are proportional and integral gains of where and the dc bus voltage PI controller. The quantities, are the output of the voltage controller and voltage th sampling instant. The output error, respectively, at of PI controller is taken as amplitude of in-phase component of the reference supply currents. Three-phase in-phase components of the reference supply and in-phase currents are computed using their amplitude unit current vectors derived in-phase with the supply voltages and (3) Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER 501 Fig. 9. Dynamic response of the AF for voltage regulation, harmonic elimination, and load balancing under the load change from three-phase to single-phase. Fig. 10. Dynamic response of the AF for voltage regulation, harmonic elimination, and load balancing under the load change from single-phase to three-phase. where , derived as , and are in-phase unit current vectors and and where as (4) PI controller over the average value of amplitude ( ) of . Comparison supply voltage and its reference counterpart of average and reference values of amplitude of the supply , voltage results in a voltage error, which is expressed as, at th sampling instant is the amplitude of supply voltage and it is computed (6) (5) 2) Computation of Quadrature Components of Reference of quadrature compoSupply Currents: The amplitude nent of reference supply currents is computed using an another , is processed in PI controller and The error signal, at th sampling instant is expressed as output (7) Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 502 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 Fig. 11. Steady state response of the AF for power-factor correction, harmonic elimination with a three-phase nonlinear load. where and are proportional and integral gain conand stants of ac voltage PI controller. The quantities, are the output of voltage controller and voltage error, )th sampling instant. The output respectively, at ( of PI controller is taken as amplitude of quadrature component of the reference supply currents. Three-phase quadrature components of the reference supply currents are computed using and quadrature unit current vectors as their amplitude and (8) , , and are quadrature unit current vectors where and these are derived from in-phase unit current vectors as (9) 3) Computation of Total Reference Supply Currents: Threephase instantaneous reference supply currents are computed by adding in-phase and quadrature components expressed in (3) and (8) (10) For ac voltage regulation along with harmonic elimination and load balancing these reference supply currents are used directly. However, for power-factor correction along with of harmonic elimination and load balancing, amplitude , , and ) is set to zero and quadrature components ( , , and ) in this condition the in-phase components ( become the total reference supply currents ( , , and ). However, by giving a proper weight-age to two components of reference supply currents a reasonably good compromise may be achieved. Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER 503 Fig. 12. Steady state response of the AF for power-factor correction, harmonic elimination, and load balancing with a single-phase nonlinear load. The three-phase reference supply currents ( , , and ) are inputs to 12 bit DAC’s of DSP and outputs of DAC’s are fed to PWM current controller along with sensed supply currents ( , , and ). The PWM current controller generates gating signals for IGBT’s of the AF. IV. PERFORMANCE OF THE AF SYSTEM A number of tests have been carried out on the developed prototype model of the AF system for voltage regulation and power-factor correction along with load balancing and harmonic elimination. Test results on the AF are presented in Figs. 4–14 and Tables I and II, demonstrating its steady state and transient performance. From these results, the following observations are made. A. Effect of the AF on Power Quality To demonstrate voltage regulation capability of the AF, an inductor ( and , values are given in the Appendix) is intro- duced in each phase in series with the line connecting ac mains with the AF and load. This causes a voltage drop and distortion in the voltage waveforms ( , , and ) at PCC as shown in Fig. 4 for the phase a ( ). Fig. 4(a) shows “switch-in” response of the AF, whereas, Fig. 4(b) shows steady state response of the AF with a three-phase nonlinear load. In Fig. 4(a), all the quantities are shown for phase “ ” only and top to bottom waveforms ), load voltage at the PCC ( ), are the mains voltage ( supply voltage ( ) obtained from load voltage ( ) using a band pass filter and supply current ( ). It is to mention here that the supply voltage ( ) is recorded in the results pertaining to all other operating conditions of the AF system. It is observed from Fig. 4 that the load terminal voltage ( ) is quite distorted and has a THD of 18.3% without AF, however, its THD reduces to 4.3% when the AF is switched in. A comparative reduction in different harmonics present in load terminal voltage ( ) are given in Table I. Similarly, THD in supply currents also reduces to 4.2% from 27.4% when the AF is “switched-in.” Table II Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 504 Fig. 13. IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 Switch IN response of the AF for power-factor correction and harmonic elimination with a three-phase nonlinear load. presents various harmonics in the supply current for the cases with and without compensation. The high frequency switching ripples which are observed in the load voltage ( ) are filtered out with the help of a band pass filter and output of band pass fed to DSP system. The results shown filter is voltage signal in Fig. 4 and Tables I and II confirm that the AF system is able to improve the quality of power and reduces THD in the voltage (4.3% THD) and current (4.2% THD) at PCC. ) are sinusoidal, balanced and slightly leading with respect to , and ) which is necessary to comsupply voltages ( , pensate line impedance drop. Fig. 6 shows the steady state response of the AF for voltage regulation, harmonic elimination and load balancing with a single-phase nonlinear load. The AF regulates the ac load terminal voltage, eliminates harmonics and balances a single-phase load resulting in three-phase balanced, sinusoidal and slightly leading power-factor supply currents. B. Steady State Performance of the AF for Voltage Regulation, Harmonic Elimination, and Load Balancing C. Dynamic Response of the AF for Voltage Regulation, Harmonic Elimination, and Load Balancing Fig. 5 shows the steady state response of the AF for ac voltage regulation and harmonic elimination with a three-phase nonlinear load. The AF system regulates ac load terminal voltage at its reference value and reduces THD in the supply current to 4.2% from 27.4% THD in load current. The dc bus voltage of the AF is also regulated at its reference value and thus a self-supporting dc bus is obtained. The supply currents ( , , and Fig. 7 shows the “switch-in” response of the AF for voltage regulation, harmonic elimination and load balancing with a three-phase nonlinear load. It is observed that the ac load terminal voltage is raised from 37.48 V (rms) to its reference value set at 40 V (rms). With the AF system switched in, the supply currents become sinusoidal within a fraction of a cycle of ac mains. The dc bus voltage reaches to its steady state Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER Fig. 14. 505 Switch IN response of the AF for power-factor correction, harmonic elimination, and load balancing with a single-phase nonlinear load. value almost instantaneously due to fast dynamic response of the AF system. Fig. 8 shows the “switch-in” response of the AF with a single-phase nonlinear load. The supply currents become sinusoidal and balanced almost instantaneously which confirms fast response of the AF. The ac load terminal voltage and dc bus voltage of the AF reach to their respective desired values within a cycle of the ac mains. Fig. 9 shows the dynamic response of the AF for a load change from three-phase to single-phase. The ac load terminal voltage remains unaffected and the supply currents are reduced in amplitude but remain sinusoidal, balanced and slightly leading with respect to supply voltages. Similarly, Fig. 10 shows the dynamic response of the AF when a single-phase nonlinear load is changed to a three-phase. The three-phase supply currents are observed with an increased amplitude but remain sinusoidal, balanced and slightly leading with respect to supply voltage which is necessary to regulate ac load terminal voltage. D. Steady State Performance of the AF for Power-Factor Correction, Harmonic Elimination, and Load Balancing Fig. 11 shows the steady state response of the AF with a three-phase nonlinear load for power-factor correction and harmonic elimination. The AF is able to reduce harmonics in the supply currents (THD 4.0% from 27.4%) and it improves the supply power-factor to unity. The supply currents are balanced, sinusoidal and in-phase with the voltages. Fig. 12 shows the steady state response of the AF with a single-phase nonlinear load. It is observed that the AF is able to balance a nonlinear single-phase load resulting in sinusoidal, balanced and unity power-factor supply currents. The control algorithm also provides a self-supporting dc bus of the AF. E. Dynamic Performance of the AF for Power-Factor Correction, Harmonic Elimination, and Load Balancing Fig. 13 shows “switch-in” response of the AF with a threephase nonlinear load for power-factor correction and harmonic Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. 506 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 3, MAY 2000 TABLE I CONTENT OF HARMONICS IN LOAD VOLTAGE (EXPERIMENTAL RESULTS) TABLE II CONTENT OF HARMONICS IN SUPPLY CURRENTS (EXPERIMENTAL RESULTS) linear loads. Dynamic and steady state performances of the AF system have been observed under different operating conditions of the load. The performance of the AF system has been found to be excellent. The AF system has been found capable of improving the power quality, voltage profile, power-factor correction, harmonic elimination and balancing the nonlinear loads. The proposed control algorithm of the AF has an inherent property to provide a self-supporting dc bus and requires less number of current sensors resulting in an over all cost reduction. It has been found that for voltage regulation and power-factor correction to unity are two different things and can not be achieved simultaneously. However, a proper weight-age to in-phase and quadrature components of the supply current can provide a reasonably good level of performance and voltage at PCC can be regulated with a leading power-factor near to unity. It has been found that the AF system reduces harmonics in the voltage at PCC and the supply currents well below the mark of 5% specified in IEEE-519 standard. APPENDIX A. System Parameters (rms/phase) mH, and V, F, , Hz, , , mH, mH. B. PI Controllers Gain Constants 1) DC Bus Voltage PI Controller: . 2) AC Voltage PI Controller: . elimination. The AF system offers an instantaneous response and moment it is turned on it starts filtering the nonsinusoidal load currents resulting in balanced, sinusoidal and unity powerfactor supply currents. The dc bus voltage of the AF is maintained at its reference value and thus a self-supporting dc bus is obtained. Fig. 14 shows “switch-in” response of the AF with a single-phase nonlinear load. The supply currents become balanced, sinusoidal and in phase with the supply voltages resulting in unity power-factor of ac mains. The phase “a” current of the AF is same as the supply current because there is no load on this phase. The dc bus voltage of the AF is regulated at its reference value. The proposed control algorithm of the AF is found suitable to regulate ac load voltage, to correct the power-factor of ac mains to unity and harmonic reduction in the supply currents and terminal voltages along with load balancing. The proposed AF with an indirect current control technique applied over the sensed and reference supply currents reduces real time computation effort and requires a less number of current sensors. These aspects enhance the response of the AF due to processing of less number of signals and reduce the overall cost of the system. V. CONCLUSIONS An improved control algorithm of the AF system has been implemented on a DSP system for voltage regulation/power-factor correction, harmonic elimination and load balancing of non- REFERENCES [1] L. Gyugyi and E. C. Strycula, “Active AC power filters,” in Proc. IEEE-IAS Annu. Meeting Record, 1976, pp. 529–535. [2] T. J. E. Miller, Reactive Power Control in Electric Systems. Toronto, Ont., Canada: Wiley, 1982. [3] J. F. Tremayne, “Impedance and phase balancing of main-frequency induction furnaces,” Proc. Inst. Elect. Eng. B, pt. B, vol. 130, no. 3, pp. 161–170, May 1983. [4] H. Akagi, Y. Kanazawa, and A. Nabae, “Instantaneous reactive power compensators comprising switching devices without energy storage components,” IEEE Trans. Ind. Applicat., vol. IA-20, pp. 625–630, May/June 1984. [5] T. A. Kneschki, “Control of utility system unbalance caused by single-phase electric traction,” IEEE Trans. Ind. Applicat., vol. IA-21, pp. 1559–1570, Nov./Dec. 1985. [6] J. Arrillaga, D. A. Bradley, and P. S. Bodger, Power System Harmonics. Chichester, U.K.: Wiley, 1985. [7] M. Z. El-Sadak, “Balancing of unbalanced loads using static VAR compensators,” J. Electr. Power Syst. Res., vol. 12, pp. 137–148, 1987. [8] W. M. Grady, M. J. Samotyj, and A. H. Noyola, “Survey of active power line conditioning methodologies,” IEEE Trans. Power Delivery, vol. 5, pp. 1536–1542, July 1990. [9] J. W. Clark, AC Power Conditioners—Design, Applications. San Diego, CA: Academic, 1990. [10] G. T. Heydt, Electric Power Quality. West Lafayette, IN: Stars in a Circle, 1991. [11] J. Kearly, A. Y. Chikhani, R. Hackam, M. M. A. Salama, and V. H. Quintana, “Microprocessor controlled reactive power compensator for loss reduction in radial distribution feeders,” IEEE Trans. Power Delivery, vol. 6, pp. 1848–1855, Oct. 1991. [12] A. E. Emanuel and M. Yang, “On the harmonic compensation in nonsinusoidal systems,” IEEE Trans. Power Delivery, vol. 8, pp. 393–399, Jan. 1993. Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply. CHANDRA et al.: IMPROVED CONTROL ALGORITHM OF SHUNT ACTIVE FILTER [13] V. B. Bhavaraju and P. N. Enjeti, “Analysis and design of an active power filter for balancing unbalanced loads,” IEEE Trans. Power Electron., vol. 8, pp. 640–647, Oct. 1993. [14] S. Saetieo, R. Devaraj, and D. A. Torrey, “The design and implementation of a three-phase active power filter based on sliding mode control,” IEEE Trans. Ind. Applicat., vol. 31, pp. 993–1000, Sept./Oct. 1995. [15] B. Singh, K. Al-Haddad, and A. Chandra, “Active power filter with sliding mode control,” in Proc. Inst. Elect. Eng., Generation, Transm., Distrib., vol. 144, Nov. 1997, pp. 564–568. [16] M. Rastogi, N. Mohan, and A. A. Edris, “Hybrid-active filtering of harmonic currents in power systems,” IEEE Trans. Power Delivery, vol. 10, pp. 1994–2000, Oct. 1995. [17] S. Bhattacharya, A. Veltman, D. M. Divan, and R. D. Lorenz, “Flux based active filter controller,” in Proc. IEEE-IAS Annu. Meeting Record, 1995, pp. 2483–2491. [18] H. L. Jou, “Performance comparison of the three-phase active power filter algorithms,” in Proc. Inst. Elect. Eng., Generation, Transm, Distrib., vol. 142, Nov. 1995, pp. 646–652. [19] J. W. Dixon, J. J. Garcia, and L. Moran, “Control system for three-phase active power filter which simultaneously compensates power-factor and unbalanced loads,” IEEE Trans. Ind. Electron., vol. 42, pp. 636–641, Dec. 1995. [20] B. Singh, K. Al-Haddad, and A. Chandra, “A new control approach to three-phase active filter for harmonics and reactive power compensation,” IEEE Trans. Power Syst., vol. 13, pp. 133–138, Feb. 1998. [21] D. A. Paice, Power Electronic Converter Harmonics—Multipulse Methods for Clean Power. New York: IEEE Press, 1996. [22] R. C. Dugan, M. F. McGranaghan, and H. W. Beaty, Electrical Power Systems Quality. New York: McGraw-Hill, 1996. [23] J. Hafner, M. Aredes, and K. Neumann, “A shunt active power filter applied to high voltage distribution lines,” IEEE Trans. Power Delivery, vol. 12, pp. 266–272, Jan. 1997. [24] B. Singh, K. Al-Haddad, and A. Chandra, “Harmonic elimination, reactive power compensation and load balancing in three-phase, four wire electric distribution systems supplying nonlinear loads,” J. Electric Power Syst. Res., vol. 44, pp. 93–100, 1998. [25] H. Akagi, “Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems,” IEEE Trans. Power Delivery, vol. 12, pp. 354–363, Jan. 1997. [26] M. Aredes, K. Heumann, and E. H. Watanabe, “An universal active power line conditioner,” IEEE Trans. Power Delivery, vol. 13, pp. 545–551, Apr. 1998. [27] P. T. Cheng, S. Bhattacharya, and D. M. Divan, “Control of square-wave inverters in high-power hybrid active filter systems,” IEEE Trans. Ind. Applicat., vol. 34, pp. 458–472, May/June 1998. [28] B. N. Singh, A. Chandra, and K. Al-Haddad, “Performance comparison of two current control techniques applied to an active filter,” in Proc. 8th Int. Conf. Harmonics Quality Power ICHQP’98, vol. I, Athens, Greece, Oct. 14–16, 1998, pp. 133–138. [29] MX31 Modular Embedded System Developer’s Guide, Sunnyvale, CA, 1992. Ambrish Chandra (SM’87) was born in India in 1955. He received the B.E. degree from the University of Roorkee, India, in 1977, the M.Tech. degree from I.I.T., New Delhi, India, in 1980, and the Ph.D. degree from the University of Calgary, Calgary, Alta., Canada, in 1987. He worked as a Lecturer and later as a Reader at the University of Roorkee. He is a Professor in the Electrical Engineering Department, Ecole de Technologie Supérieure, Montreal, Que., Canada. His main research interests are power quality, active filters, reactive power compensation, and FACTS. 507 Bhim Singh was born in Rahamapur, U.P., India in 1956. He received the B.E. degree from the University of Roorkee, India, in 1977 and the M.Tech. and Ph.D. degrees from the Indian Institute of Technology (IIT), New Delhi, in 1979 and 1983, respectively. In 1983, he started working as a Lecturer and, in 1988 became a Reader in the Department of Electrical Engineering, University of Roorkee. In December 1990, he started as an Assistant Professor, became an Associate Professor in the Department of Electrical Engineering, IIT, in 1994, and a Professor in 1997. His field of interest includes CAD, power electronics, active filters, static VAR compensation, analysis, and digital control of electrical machines. Dr. Singh is a Fellow of IE(I) and IETE and a Life Member of ISTE, SSI, and NIQR. B. N. Singh (M’98) was born in 1968. He received the B.E. degree from M.M.M. Engineering College, Gorakhpur, India, in 1989, the M.E. degree from the University of Roorkee, India, in 1991, and the Ph.D. degree from Indian Institute of Technology, New Delhi, in 1996. In September 1996, he joined the Department of Electrical Engineering, École de Technologie Supérieure, Montréal, P.Q., Canada, as a Postdoctoral Fellow, where he worked in the area of active filters, UPFC, and FACTS. In February 1999, he joined the Department of Electrical and Computer Engineering, Concordia University, Montreal, as a Research Fellow, where he worked in the area of power supplies for telecommunication system. Recently, he joined the Department of Electrical Engineering and Computer Science, Tulane University, New Orleans, LA, as an Assistant Professor. His main research interests are power supplies, power electronics, power systems, electrical machines, and drives. Kamal Al-Haddad (S’82–M’88–SM’92) was born in Beirut, Lebanon, in 1954. He received the B.Sc.A. and the M.Sc.A. degrees from the Université du Québec à Trois-Rivières, P.Q., Canada, in 1982 and 1984, respectively, and the Ph.D. degree from the Institut National Polytechnique, Toulouse, France, in 1988. From June 1987 to June 1990, he was a Professor in the Engineering Department, Université du Québec, Trois-Rivières. In June 1990, he joined the teaching staff as a Professor in the Electrical Engineering Department, École de Technologie Supérieure, Université du Québec, Montreal, P.Q. His fields of interest are static power converters, harmonics, and reactive power control, switch mode and resonant converters, including the modeling, control, and development of industrial prototypes for various applications. Dr. Al-Haddad is a member of the Order of Engineering of Québec and the Canadian Institute of Engineers. Authorized licensed use limited to: NED UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 14,2010 at 05:41:50 UTC from IEEE Xplore. Restrictions apply.