28130.std Elec. Acc. Cntrl. and Intr. Det. System Rev Apr 2011.doc STANDARDS SECTION 28130 ELECTRONIC ACCESS CONTROL and INTRUSION DETECTION SYSTEM (Rev Apr 2011) PART 1 GENERAL 1.00 DESCRIPTION A. 1.01 1.02 Furnish and install a complete Electronic Access Control and Intrusion Detection System as specified. RELATED DOCUMENTS A. Washington State Information Services Board-Information Technology PolicySubmission Requirements-Computing and Telecommunications Architecture Standards-Building Wiring. http://isb.wa.gov/policies/portfolio/701S.doc B. American National Standard ANSI/TIA/EIA Telecommunications Building Wiring Standards. C. Drawings and general provisions of the Contract, including General and Supplemental Conditions and other Division 1 Specification Sections, apply to this Section. RELATED SECTIONS A. Refer to the following sections for additional requirements for the Communications Distribution System (CDS): 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Standards Section 07841 – Through-Penetration Fire Stop Systems. Standards Section 10019 – Space Identification-Standard Standards Section 26000 (16111) – Raceway System. Standards Section 26000 (16130) – Boxes (Sizes, Styles and Types). Standards Section 26000 (16650) – Electrical System-CDS. Standards Section 13200 (16652) – Requirements for Communication Rooms. Standards Section 27100 (16651) – Communications Distribution System. Standards Section 27100 (16651) – APPENDIX-A (CDS Approved Products). Standards Section 27100 (16651) – APPENDIX-B (CDS Glossary of Terms). Standards Section 27100 (16651) – APPENDIX-C (CDS Building Acronyms). Standards Section 27100 (16651) – APPENDIX-D (CDS Station Cable Record). Standards Section 27100 (16651) – APPENDIX-E (CDS Typical Rack Layout For Equipment). Page 1 of 2 28130.std Elec. Acc. Cntrl. and Intr. Det. System Rev Apr 2011.doc 13. 14. 15. 16. 1.04 Standards Section 27100 (16651) – APPENDIX-F (CDS Typical Rack Layout For Data Patch Panels). Standards Section 27320 (16630) – CDS Rescue Assistance Telephone System. Standards Section 27531 (16680) – CDS Clock System. Standards Section 27400 (16710) – CDS Multi-Media Systems. Access Control Requirements: 1. An area 4 foot wide and 8 foot tall of wall space shall be provided for the Equipment Panel backboard. 2. A 4 foot x 8 foot x ¾ inch AC plywood backboard shall be mounted on the wall in the designated area with the smooth side toward the center of the room. 3. A 4 foot x 3 foot x 11 inch Surface Mounted Equipment Panel shall be provided, and mounted on the plywood backboard. The exact location shall be identified by the EWUAccess Control Shop Representative. 4. The Surface Mounted Equipment Panel requires “Service Accessibility Space” so it will need to be mounted in an area with enough clearance for the door. 5. One (1) each 120 Volt 20 Amp circuit from an Emergency Generator Panel. 6. A UPS capable of 750VA for the TAC equipment shall be provided. 7. One each Type 3 Network Information Outlet (NIO) (1-Data Cable) shall be provided for the network router. 8. One each Type 3 Network Information Outlet (NIO) (1-Data Cable) shall be provided for the UPS monitor. 9. The ambient temperature range of the air shall be maintained between 50 and 100 degrees Fahrenheit. 10. Humidity range shall be maintained between 10% and 80% RH, non-condensing. End of Standards Section 28130 Page 2 of 2