GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 04 Airflow, m3/h SFP v 2.5 2.0 1.5 Available total pressure rise, Pa Extract air fan 85 4 3 1 80 2 L w,tot 70dB 75 Supply air fan 4 3 85 1 80 L w,tot 70dB 2 75 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018 Correction factors KOK , dB Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Sound path To outlet duct Size 04 Min. airflow (on airflow regulation) m3/s m3/h 288 0.08 Max. airflow m3/h 1620 m3/s 0.45 To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -8 -9 -6 -9 -12 -12 -12 -13 -6 -5 -2 -3 -15 -16 -4 -11 -20 -19 -16 -17 -6 -8 -6 -5 -16 -21 -14 -16 -29 -31 -29 -28 -8 -8 -15 -13 -28 -24 -27 -28 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -35 -33 -35 -38 -40 -40 -47 -46 6 -7 -9 -16 -14 -38 -36 -39 -41 -40 -42 -49 -47 7 -12 -13 -22 -20 -40 -39 -44 -44 -46 -47 -56 -54 8 -15 -16 -25 -25 -38 -39 -43 -44 -46 -47 -56 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 94 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 04 Delivery and Transport within the Site The GOLD PX 04 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Base frame/Base The GOLD PX 04 is supplied on a base frame with integrated openings for the forks of a fork-lift truck. The stand is available as an accessory. Installation/duct connection options A: Specify right-hand or left-hand version when ordering! Left-hand version Outside air Supply air Extract air Exhaust air Power connection 403 16 91 52* GOLD 91 GOLD 180 52 52 32 32 50 50 80 80 * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D F G H L Ø Weight, kg 04 800 825 240 345 230 460 920 2000 315 291-337 Clear Space for Inspection A clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood. Power connection 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Motor shaft power: 0.8 kW (0.41 kW)* motor control system, 1 x 230 V, 50 Hz *The motor control system limits the power of the take-off to the value specified. 20160422 We reserve the right to alter specifications. 95 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 05 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa 95 90 Ca 4 3 Ca p. va p. va r. 1 85 2 1L w,tot 70dB 75 80 Supply air fan 95 90 Ca Ca 4 3 r. 2 p. va p. va r. 2 r. 1 85 2 1L w,tot 70dB 75 80 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Correction factors KOK , dB Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Sound path To outlet duct Size 05 Min. airflow (on airflow regulation) m3/s m3/h 288 0.08 Max. airflow m3/h 2340 m3/s 0.65 To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -8 -9 -6 -9 -12 -12 -12 -13 -6 -5 -2 -3 -15 -16 -4 -11 -20 -19 -16 -17 -6 -8 -6 -5 -16 -21 -14 -16 -29 -31 -29 -28 -8 -8 -15 -13 -28 -24 -27 -28 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -35 -33 -35 -38 -40 -40 -47 -46 6 -7 -9 -16 -14 -38 -36 -39 -41 -40 -42 -49 -47 7 -12 -13 -22 -20 -40 -39 -44 -44 -46 -47 -56 -54 8 -15 -16 -25 -25 -38 -39 -43 -44 -46 -47 -56 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 96 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 05 Delivery and Transport within the Site The GOLD PX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Base frame/Base The GOLD PX 05 is supplied on a base frame with integrated openings for the forks of a fork-lift truck. The stand is available as an accessory. Installation/duct connection options A: Specify right-hand or left-hand version when ordering! Left-hand version Outside air Supply air Extract air Exhaust air Power connection 403 16 91 52* GOLD 91 GOLD 180 52 52 32 32 50 50 80 80 * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D F G H L Ø Weight, kg 05 800 825 240 345 230 460 920 2000 315 291-337 Clear Space for Inspection A clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood. Power connection 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz 20160422 We reserve the right to alter specifications. 97 GOLD Sizing, installation, dimensions and weights GOLD PX, plate heat exchanger, size 07 Airflow, m3/h SFP v 2.5 2.0 1.5 Available total pressure rise, Pa 95 Extract air fan 90 Ca Ca 4 3 va va r. 2 r. 1 2 1 L w,tot 70dB 95 75 80 4 85 Supply air fan 90 Ca Ca 3 p. p. p. va p. va r. 2 r. 1 2 1 L w,tot 70dB 75 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Correction factors, KOK , dB. Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Sound path To the outlet duct Size 07 Min. airflow (for airflow regulation) m3/s m3/h 288 0.08 Max. airflow m3/h 2700 m3/s 0.75 To the inlet duct* To unit’s surroundings** Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -8 -9 -6 -9 -12 -12 -12 -13 -6 -5 -2 -3 -15 -16 -4 -11 -20 -19 -16 -17 -6 -8 -6 -5 -16 -21 -14 -16 -29 -31 -29 -28 -8 -8 -15 -13 -28 -24 -27 -28 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -35 -33 -35 -38 -40 -40 -47 -46 6 -7 -9 -16 -14 -38 -36 -39 -41 -40 -42 -49 -47 7 -12 -13 -22 -20 -40 -39 -44 -44 -46 -47 -56 -54 8 -15 -16 -25 -25 -38 -39 -43 -44 -46 -47 -56 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 98 We reserve the right to alter specifications. 20160422 GOLD Sizing, installation, dimensions and weights GOLD PX, plate heat exchanger, size 07 Delivery and transport within the site The GOLD PX 07 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Base frame/Base The GOLD PX 07 is supplied on a base frame with integrated openings for the forks of a fork-lift truck. The stand is available as an accessory. Installation/duct connection options A: Specify right-hand or left-hand version when ordering. Left-hand version Outdoor air Supply air Extract air Exhaust air Power connection 403 16 91 52* GOLD 91 GOLD 180 52 52 32 32 50 50 80 80 * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D F G H L Ø Weight, kg 07 915 995 277.5 440 271 543 1085 2230 400 360-419 Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood. Power connection Capacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Capacity variant 1: Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz 20160422 We reserve the right to alter specifications. 99 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 08 Airflow, m3/h SFP v 2.5 1.5 Extract air fan 90 Available total pressure rise, Pa Ca Ca 4 3 p. va 2 1 L w,tot 75dB p. r. 2 r. 1 85 Supply air fan Ca Ca 4 p. 2 1 va 80 90 3 2.0 L w,tot 75dB va p. va r. 2 r. 1 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Correction factors K , dB OK Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 08 Min. airflow (on airflow regulation) m3/s m3/h 720 0.20 Sound path To outlet duct Max. airflow m3/h 3600 m3/s 1.00 To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -8 -9 -6 -9 -12 -12 -12 -13 -6 -5 -2 -3 -15 -16 -4 -11 -20 -19 -16 -17 -6 -8 -6 -5 -16 -21 -14 -16 -29 -31 -29 -28 -8 -8 -15 -13 -28 -24 -27 -28 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -35 -33 -35 -38 -40 -40 -47 -46 6 -7 -9 -16 -14 -38 -36 -39 -41 -40 -42 -49 -47 7 -12 -13 -22 -20 -40 -39 -44 -44 -46 -47 -56 -54 8 -15 -16 -25 -25 -38 -39 -43 -44 -46 -47 -56 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 100 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 08 Delivery and Transport within the Site The GOLD PX 08 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Base frame/Base The GOLD PX 08 is supplied on a base frame with integrated openings for the forks of a fork-lift truck. The stand is available as an accessory. Installation/duct connection options A: Specify right-hand or left-hand version when ordering! Left-hand version Outside air Supply air Extract air Exhaust air Power connection 403 16 91 52* GOLD 91 GOLD 180 52 52 32 32 50 50 80 80 * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D F G H L Ø Weight, kg 08 915 995 277,5 440 271 543 1085 2230 400 369-428 Clear Space for Inspection A clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood. Power connection Capacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 101 GOLD Sizing, installation, dimensions and weights GOLD PX, plate heat exchanger, size 11 Airflow, m3/h SFP v 2.5 2.0 1.5 90 Extract air fan Available total pressure rise, Pa Ca Ca 4 p. va p. va r. 2 r. 1 2 3 1 L w,tot 75dB 80 90 85 Supply air fan Ca Ca 4 p. va p. va r. 2 r. 1 2 3 1 L w,tot 75dB 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Correction factors KOK , dB Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 11 Min. flow (for airflow regulation) m3/s m3/h 720 0.20 Sound path To outlet duct Max. airflow m3/h 3960 m3/s 1.10 To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -8 -9 -6 -9 -12 -12 -12 -13 -6 -5 -2 -3 -15 -16 -4 -11 -20 -19 -16 -17 -6 -8 -6 -5 -16 -21 -14 -16 -29 -31 -29 -28 -8 -8 -15 -13 -28 -24 -27 -28 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -35 -33 -35 -38 -40 -40 -47 -46 6 -7 -9 -16 -14 -38 -36 -39 -41 -40 -42 -49 -47 7 -12 -13 -22 -20 -40 -39 -44 -44 -46 -47 -56 -54 8 -15 -16 -25 -25 -38 -39 -43 -44 -46 -47 -56 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 102 We reserve the right to alter specifications. 20160422 GOLD Sizing, installation, dimensions and weights GOLD PX, plate heat exchanger, size 11 Delivery and transport within the site The GOLD PX 11 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The GOLD PX 11 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. Right-hand version The three sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors. The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Left-hand version Duct connection options Outdoor air Supply air A: Specify right-hand or left-hand version when ordering. Extract air Exhaust air Power connection K 403 16 K 52* 91 91 GOLD GOLD GOLD J 50 50 E 52 E 52 50 J 50 80 D If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D E F G H J K L Ø Weight, kg 11 655 1199 324 1200 397 324 647 1295 935 551 2510 500 552-646 Division into sections for transport A D + 19 mm A Power connection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 141-167 kg, D = 270-312 kg. Clear space for inspection A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood. Capacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 103 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 12 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa 90 Ca Ca 3 p. va 2 1 L w,tot 75dB p. va r. 2 r. 1 80 85 Supply air fan 90 Ca Ca 3 p. va 2 1 p. va r. 2 r. 1 80 L w,tot 75dB 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 12 Min. airflow (on airflow regulation) m3/s m3/h 720 0.20 Max. airflow m3/h 5040 m3/s 1.40 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 1 2 3 1 2 3 -1 -1 -1 -8 -9 -6 -12 -12 -12 -6 -5 -2 -15 -16 -4 -20 -19 -16 -6 -8 -6 -16 -21 -14 -29 -31 -29 -8 -8 -15 -28 -24 -27 -29 -29 -36 4 5 -7 -7 -14 -35 -33 -35 -40 -40 -47 6 -7 -9 -16 -38 -36 -39 -40 -42 -49 7 -12 -13 -22 -40 -39 -44 -46 -47 -56 8 -15 -16 -25 -38 -39 -43 -46 -47 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 104 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 12 Delivery and Transport within the Site The GOLD PX 12 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The GOLD PX 12 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. Right-hand version The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Left-hand version Duct connection options A: Specify right-hand or left-hand version when ordering! Outside air Supply air Extract air Exhaust air Power connection K 403 16 K 52* 91 91 GOLD GOLD GOLD J 50 50 E 52 E 52 50 J 50 80 D If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size A B C D E F G H J K L Ø Weight, kg 12 655 1199 324 1200 397 324 647 1295 935 551 2510 500 574-668 Division into sections for transport A D + 19 mm A Clear space for inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 152-178 kg, D = 270-312 kg. A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 105 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 14 Airflow, m3/h 2.5 SFP v 2.0 1.5 90 Extract air fan Available total pressure rise, Pa Ca 2 Ca p. p. va 3 va r. 2 r. 1 1 L w,tot 75dB 80 90 85 Supply air fan Ca 2 Ca 3 p. va p. va r. 2 r. 1 1 L w,tot 75dB 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 14 Min. airflow (on airflow regulation) m3/s m3/h 720 0.20 Max. airflow m3/h 5940 m3/s 1.65 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 1 2 3 1 2 3 -1 -1 -1 -8 -9 -6 -12 -12 -12 -6 -5 -2 -15 -16 -4 -20 -19 -16 -6 -8 -6 -16 -21 -14 -29 -31 -29 -8 -8 -15 -28 -24 -27 -29 -29 -36 4 5 -7 -7 -14 -35 -33 -35 -40 -40 -47 6 -7 -9 -16 -38 -36 -39 -40 -42 -49 7 -12 -13 -22 -40 -39 -44 -46 -47 -56 8 -15 -16 -25 -38 -39 -43 -46 -47 -56 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 106 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 14 Delivery and Transport within the Site The GOLD PX 14 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. Right-hand version The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Duct connection options A: Specify right-hand or left-hand version when ordering! B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units). Left-hand version Outside air Supply air Extract air Exhaust air Power connection 403 M M 91 N GOLD GOLD E 52 E 52 50 50 80 D * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Size A B C D E F G H I J K L M N Weight, kg 14 765 1400 1136 1300 450 400 1000 1395 298 188 200 2830 208 109 667-773 Division into sections for transport A D + 19 mm A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 175-209 kg, D = 317-355 kg. A clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fan Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 107 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 20 Airflow, m3/h SFP v 2.5 2.0 1.5 90 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va p. va r. 2 r. 1 1 L w,tot 70dB 75 80 90 85 Supply air fan Ca Ca 2 p. va p. va r. 2 r. 1 1 L w,tot 70dB 75 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 20 Min. airflow (on airflow regulation) m3/s m3/h 1080 0.30 Max. airflow m3/h 7560 m3/s 2.10 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 -34 4 5 6 7 8 500 1000 2000 4000 8000 1 -11 -16 -14 -27 -33 -37 -38 2 -6 -9 -14 -28 -35 -39 -43 -39 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 108 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 20 Delivery and Transport within the Site The GOLD PX 20 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. Right-hand version The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Duct connection options A: Specify right-hand or left-hand version when ordering! B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units). Left-hand version Outside air Supply air Extract air Exhaust air Power connection 403 M M 91 N GOLD GOLD E 52 E 52 50 50 80 D * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Size A B C D E F G H I J K L M N Weight, kg 20 765 1400 1136 1300 450 400 1000 1395 298 188 200 2830 208 109 703-809 Division into sections for transport A D + 19 mm A Clear space for inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 193-227 kg, D = 317-355 kg. A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) Rated data per fan Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 109 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 25 Airflow, m3/h 2.5 SFP v 2.0 1.5 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va 1 L w,tot 70dB 75 p. va r. 2 r. 1 80 85 Supply air fan Ca Ca 2 1 L w,tot 70dB 75 80 p. va p. va r. 2 r. 1 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 25 Min. airflow (on airflow regulation) m3/s m3/h 1080 0.30 Max. airflow m3/h 9000 m3/s 2.50 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 -34 4 5 6 7 8 500 1000 2000 4000 8000 1 -11 -16 -14 -27 -33 -37 -38 2 -6 -9 -14 -28 -35 -39 -43 -39 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 110 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 25 Delivery and Transport within the Site The GOLD PX 25 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/ filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Duct connection options Left-hand version A: Specify right-hand or left-hand version when ordering! B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units). Outside air Supply air Extract air Exhaust air Power connection 403 M M 91 N GOLD GOLD E 52 E 52 50 50 80 D * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Size A B C D E F G H I J K L M N Weight, kg 25 835 1600 1336 1550 575 500 1200 1595 298 203 200 3220 193 94 905-1058 Division into sections for transport A D + 19 mm A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 225-265 kg, D = 455-528 kg. A clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) Rated data per fan Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 111 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 30 Airflow, m3/h SFP v 2.5 1.5 2.0 Available total pressure rise, Pa Extract air fan Ca Ca 2 p. p. va va r. 1 r. 2 90 1 L w,tot 70dB 75 80 85 Supply air fan Ca Ca 2 p. p. va va r. 2 r. 1 90 1 L w,tot 70dB 75 80 85 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 30 Min. airflow (on airflow regulation) m3/s m3/h 1800 0.50 Max. airflow m3/h 11520 m3/s 3.20 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 -34 4 5 6 7 8 500 1000 2000 4000 8000 1 -11 -16 -14 -27 -33 -37 -38 2 -6 -9 -14 -28 -35 -39 -43 -39 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 112 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD PX, plate heat exchanger, size 30 Delivery and Transport within the Site The GOLD PX 30 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/ filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. Right-hand version Duct connection options Left-hand version A: Specify right-hand or left-hand version when ordering! B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units). Outside air Supply air Extract air Exhaust air Power connection 403 M M 91 N GOLD GOLD E 52 E 52 50 50 80 D * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Size A B C D E F G H I J K L M N Weight, kg 30 835 1600 1336 1550 575 500 1200 1595 298 203 200 3220 193 94 945-1098 Division into sections for transport A D + 19 mm A Clear space for inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 245-285 kg, D = 455-528 kg. A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A (capacity variant 1) alt. 20 A (capacity variant 2) Rated data per fan Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 113 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 35 Airflow, m3/h 2.5 SFP v 2.0 1.5 Available total pressure rise, Pa Extract air fan Ca p. Ca va p. r. 2 va 1 r. 2 1 L w,tot 70dB 75 80 85 90 Supply air fan Ca p. va Ca va 2 r. p. 1 r. 2 1 75 L w,tot 70dB 80 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 35 Min. airflow (on airflow regulation) m3/s m3/h 1800 0,50 Max. airflow m3/h 14040 m3/s 3.90 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 114 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 35 Delivery and Transport within the Site The GOLD CX 35 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. The air handling unit can be split into three sections to facilitate transporting it within the building site. Upward Forward Fan arrangement 2 Fan arrangement 1 Right-hand version The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams. Upward Forward Upward Upward Forward Forward The coil heat exchanger system is filled with liquid from the factory. Duct connection options A: Specify right-hand or left-hand version when ordering! Fan arrangement 1 B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 2 Left-hand version C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Outside air Supply air Extract air Exhaust air Power connection 200 771 B** B** 200 250 771 250 N GOLD GOLD N 50 50 52 52 50 50 If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. ** Width of centre section's casing = B + 200 mm. Size A B C D E F G H I J K L N Weight, kg 35 948 1990 1726 824 200 600 1400 1985 392 153 295 2719 240 1635-1749 Division into sections for transport A D+19 mm A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 322-379 kg, D = 991 kg. A clear space of 1000 mm should be provided in front of the unit. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 20 A (capacity variant 1) alt. 25 A (capacity variant 2) Rated data per fan Motor shaft power 4.0 kW alt. 5.0 kW, motor control system, 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 115 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 40 Airflow, m3/h SFP v 2.5 2.0 1.5 Available total pressure rise, Pa Extract air fan Ca Ca 2 p. 1 L w,tot 75dB 80 va p. va r. 2 r. 1 85 90 Supply air fan Ca 2 Ca 1 L w,tot 75dB 80 p. va p. va r. 2 r. 1 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2016 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Min. and Max. Airflows Correction factors KOK , dB The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 40 Min. airflow (on airflow regulation) m3/s m3/h 2700 0,75 To outlet duct Max. airflow m3/h m3/s 1 2 14040 /18000 3,901/5,002 Capacity variant 1. 2 Capacity variant 2. 1 116 Sound path We reserve the right to alter specifications. To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 40 Delivery and Transport within the Site The GOLD CX 40 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. Upward Forward Upward Forward The air handling unit can be split into three sections to facilitate transporting it within the building site. Fan arrangement 1 The three sections are joined together by bolts and the electrical and control cables have quick connectors. Upward Fan arrangement 2 Right-hand version Upward Forward The air handling unit is delivered on wooden beams. Forward The coil heat exchanger system is filled with liquid from the factory. Duct connection options A: Specify right-hand or left-hand version when ordering! Fan arrangement 1 B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 2 Left-hand version C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Outside air Supply air Extract air Exhaust air Power connection 200 771 B** B** 200 250 771 250 N GOLD GOLD N 50 50 52 52 50 50 If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. ** Width of centre section's casing = B + 200 mm. Size A B C D E F G H I J K L N Weight, kg 40 948 1990 1726 824 200 600 1400 1985 392 153 295 2719 240 1685-1799 Division into sections for transport A D+19 mm A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 347-404 kg, D = 991 kg. A clear space of 1000 mm should be provided in front of the unit. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 20 A (capacity variant 1) alt. 32 A (capacity variant 2) Rated data per fan Motor shaft power: 5.0 kW (3.9 kW*) alt. 6.5 kW, motor control system, 3 x 400 V, 50 Hz *The motor control system limits the power of the take-off to the value specified. 20160422 We reserve the right to alter specifications. 117 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 50 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va p. va r. 2 r. 1 1 L w,tot 75dB 80 85 90 Supply air fan Ca Ca 2 p. va p. va r. 2 r. 1 1 L w,tot 75dB 80 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 50 Min. airflow (on airflow regulation) m3/s m3/h 2160 0,60 Max. airflow m3/h 18000 m3/s 5.00 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 118 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 50 Delivery and Transport within the Site Upward The GOLD CX 50 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. Upward Forward The air handling unit can be split into three sections to facilitate transporting it within the building site. Forward Fan arrangement 1 The unit is supplied on 100 mm high support feet made of steel. Fan arrangement 2 Right-hand version The three sections are joined together by bolts and the electrical and control cables have quick connectors. Upward Upward Forward The coil heat exchanger system is filled with liquid from the factory. Forward Duct connection options A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1 Fan arrangement 2 Left-hand version C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Outside air Supply air B** 200 Extract air Exhaust air 787 254 28* * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Power connection GOLD ** Width of centre section's casing = B + 200 mm. GOLD 28 76 76 Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory). Size A B D E F G H I J K L Weight, kg 50 1050 2318 856 150 800 1600 2253 423 115 360 2956 2170-2294 Division into sections for transport A D A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 440-502 kg, D = 1290 kg. A clear space of 1,100 mm should be provided in front of the unit. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 25 A (capacity variant 1) alt. 32 A (capacity variant 2) Rated data per fan Motor shaft power: 2 x 2.4 kW alt. 2 x 3.4 kW, motor control system, 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 119 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 60 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va p. va 95 r. 2 r. 1 1 L w,tot 75dB 80 85 90 Supply air fan Ca Ca 2 p. va p. va 95 r. 2 r. 1 1 L w,tot 75dB 80 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2016 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 60 Min. airflow (on airflow regulation) m3/s m3/h 3600 1.00 Max. airflow m3/h 23400 m3/s 6.50 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 120 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 60 Delivery and Transport within the Site Upward The GOLD CX 60 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. Upward Forward The air handling unit can be split into three sections to facilitate transporting it within the building site. Forward Fan arrangement 1 The unit is supplied on 100 mm high support feet made of steel. Fan arrangement 2 Right-hand version The three sections are joined together by bolts and the electrical and control cables have quick connectors. Upward Upward Forward The coil heat exchanger system is filled with liquid from the factory. Forward Duct connection options A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1 Fan arrangement 2 Left-hand version C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Outside air Supply air B** 200 Extract air Exhaust air 787 254 28* * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Power connection GOLD ** Width of centre section's casing = B + 200 mm. GOLD 28 76 76 Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory). Size A B D E F G H I J K L Weight, kg 60 1050 2318 856 150 800 1600 2253 423 115 360 2956 2250-2374 Clear space for inspection Division into sections for transport A D A The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 480-542 kg, D = 1290 kg. A clear space of 1,100 mm should be provided in front of the unit. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 A (capacity variant 1) alt. 50 A (capacity variant 2) Rated data per fan Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 121 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 70 Airflow, m3/h 2.5 SFP v 2.0 1.5 Extract air fan Ca va Available total pressure rise, Pa p. 2 r. Ca 95 p. va 2 1 r. 1 L w,tot 75dB 80 85 90 Supply air fan Ca p. va 2 2 r. Ca p. va r. 1 95 1 L w,tot 75dB 80 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 70 Min. airflow (on airflow regulation) m3/s m3/h 3600 1,00 Max. airflow m3/h 27000 m3/s 7.50 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 122 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 70 Delivery and Transport within the Site Upward The GOLD CX 70 is supplied as three units. One unit consists of the centre section with the heat exchanger. The other two units consist of fan/filter sections. Upward Forward Forward The three sections are joined together by bolts and the electrical and control cables have quick connectors. The unit is supplied on 100 mm high support feet made of steel. Fan arrangement 1 The coil heat exchanger system is filled with liquid from the factory. Fan arrangement 2 Right-hand version Duct connection options Upward A: Specify right-hand or left-hand version when ordering! Upward Forward B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Forward C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Fan arrangement 1 Fan arrangement 2 Left-hand version Outside air Supply air B** Extract air 200 Exhaust air 813 254 52* Power connection * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. GOLD GOLD ** Width of centre section's casing = B + 200 mm. 52 76 76 Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory). Size A B D E F G H I J K L Weight, kg 70 1275 2637 904 164 1000 1800 2640 319 161 419 3454 3156-3308 Division into sections for transport A D A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 740-816 kg, D = 1676 kg. A clear space of 1,100 mm should be provided in front of the unit. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 40 A (capacity variant 1) alt. 63 A (capacity variant 2) Rated data per fan Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system, 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 123 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 80 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va p. va r. 2 r. 1 95 1 L w,tot 75dB 80 85 90 Supply air fan Ca Ca p. va p. va r. 2 r. 1 95 2 1 L w,tot 75dB 80 85 90 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2016 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 80 Min. airflow (on airflow regulation) m3/s m3/h 5400 1,50 Max. airflow m3/h 34200 m3/s 9,50 Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, No. / mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 124 We reserve the right to alter specifications. 20160422 GOLD Sizing, Installation, Dimensions and Weights GOLD CX, coil heat exchangers, size 80 Delivery and Transport within the Site Upward The GOLD CX 80 is supplied as three units. One unit consists of the centre section with the heat exchanger. The other two units consist of fan/filter sections. Upward Forward Forward The three sections are joined together by bolts and the electrical and control cables have quick connectors. The unit is supplied on 100 mm high support feet made of steel. Fan arrangement 1 The coil heat exchanger system is filled with liquid from the factory. Fan arrangement 2 Right-hand version Duct connection options Upward A: Specify right-hand or left-hand version when ordering! Upward Forward B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Forward C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Fan arrangement 1 Fan arrangement 2 Left-hand version Outside air Supply air B** Extract air 200 Exhaust air 813 254 52* Power connection * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. GOLD GOLD ** Width of centre section's casing = B + 200 mm. 52 76 76 Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory). Size A B D E F G H I J K L Weight, kg 80 1275 2637 904 164 1000 1800 2640 319 161 419 3454 3256-3532 Division into sections for transport A D A Clear Space for Inspection The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 790-928 kg, D = 1676 kg. A clear space of 1,100 mm should be provided in front of the unit. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 63 A (capacity variant 1) alt. 80 A (capacity variant 2) Rated data per fan Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 125 GOLD Sizing, installation, dimensions and weights GOLD CX, coil heat exchangers, size 100 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan p. va r. 2 Ca Available total pressure rise, Pa Ca p. va 1 r. 2 1 L w,tot 75dB 80 85 90 95 Supply air fan Ca p. va 2 r. Ca p. va 1 r. 2 1 L w,tot 75dB 80 85 90 95 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 100 Min. airflow (on airflow regulation) m3/s m3/h 5400 1,50 Max. airflow m3/h 39 600 m3/s 11.0 Correction factors, KOK , dB. Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, no./mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 126 We reserve the right to alter specifications. 20160422 GOLD Sizing, installation, dimensions and weights GOLD CX, coil heat exchangers, size 100 Delivery and transport within the site Upward Forward The GOLD CX 100 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Accessories). Upward Fan arrangement 1 Fan arrangement 2 Upward The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect. Fan arrangement 5, supply air - lower level Upward Forward Upward Fan arrangement 4, supply air – upper level Exhaust air Upward Forward Fan arrangement 4, supply air - lower level Left-hand version B** 200 137 M 56* N Power connection N O If extract air flows through the lower level: The air handling unit must be raised at least 50 mm (higher than the upper edge of the base beams) to provide space for the water trap. This can be done by mounting adjustable feet (accessories). P ** Width of centre section's casing = B + 200 mm. Forward Fan arrangement 1 Fan arrangement 2 Upward Forward * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Forward Right-hand version A: Specify right-hand or left-hand version when ordering. B: The arrangement of the functional sections can vary. To be specified when ordering as fan arrangement 1, 2, 4 or 5. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level. C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connection size: 2500 x 800 mm. Extract air Upward Forward Fan arrangement 5, supply air – upper level Duct connection options Outdoor air Supply air Forward GOLD GOLD P 45 56 1048 122 1000 77 1048 3186 77 Size A B D E F G H I J K L N O P Weight, kg 100 1126 3340 1144 191 1200 2400 3440 520 210 470 3396 170 2500 1720 4374-4734 Transport at building site, dim. and weights Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 713-834 kg, filter section = 470-529 kg. Heat exchanger sections See dimensions D and P in the table above. Weight: Heat exchanger section = 1004 kg. Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Power connection 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 63 A (capacity variant 1) alt. 80 A (capacity variant 2) Rated data per fan Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system, 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 127 GOLD Sizing, installation, dimensions and weights GOLD CX, coil heat exchangers, size 120 Airflow, m3/h SFP v 2.5 2.0 1.5 Extract air fan Available total pressure rise, Pa Ca Ca 2 p. va 1 L w,tot 80dB 85 p. va r. 2 r. 1 90 95 Supply air fan Ca p. va 2 2 r. Ca p. va r. 1 1 L w,tot 80dB 85 90 95 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2016 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 120 Min. airflow (on airflow regulation) m3/s m3/h 9000 2.50 Max. airflow m3/h 50 400 m3/s 14.0 Correction factors, KOK , dB. Sound path To outlet duct To inlet duct* To air handling unit surroundings** Octave band, no./mid-frequency, Hz Range in the diagram 1 2 3 63 125 250 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 4 5 6 7 8 500 1000 2000 4000 8000 1 -10 -10 -8 -21 -28 -30 -35 -32 2 -5 -3 -8 -22 -30 -32 -40 -37 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 * The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air. 128 We reserve the right to alter specifications. 20160422 GOLD Sizing, installation, dimensions and weights GOLD CX, coil heat exchangers, size 120 Delivery and transport within the site Upward Forward The GOLD CX 120 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Accessories). Upward Fan arrangement 1 Fan arrangement 2 Upward The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect. Fan arrangement 5, supply air - lower level Upward Forward Upward Fan arrangement 4, supply air – upper level Exhaust air Upward Forward Fan arrangement 4, supply air - lower level Left-hand version B** 200 137 M 56* N Power connection N O If extract air flows through the lower level: The air handling unit must be raised at least 50 mm (higher than the upper edge of the base beams) to provide space for the water trap. This can be done by mounting adjustable feet (accessories). P ** Width of centre section's casing = B + 200 mm. Forward Fan arrangement 1 Fan arrangement 2 Upward Forward * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Forward Right-hand version A: Specify right-hand or left-hand version when ordering. B: The arrangement of the functional sections can vary. To be specified when ordering as fan arrangement 1, 2, 4 or 5. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level. C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connection size: 2500 x 800 mm. Extract air Upward Forward Fan arrangement 5, supply air – upper level Duct connection options Outdoor air Supply air Forward GOLD GOLD P 45 56 1048 122 1000 77 1048 3186 77 Size A B D E F G H I J K L N O P Weight, kg 120 1126 3340 1144 191 1200 2400 3440 520 210 470 3396 170 2500 1720 4580-5002 Transport at building site, dim. and weights Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 816-968 kg, filter section = 470-529 kg. Heat exchanger sections See dimensions D and P in the table above. Weight: Heat exchanger section = 1004 kg. Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Power connection 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 A (capacity variant 1) alt. 125 A (capacity variant 2) Rated data per fan Motor shaft power: 3 x 6.5 kW alt 3 x 10 kW, motor control system: 3 x 400 V, 50 Hz 20160422 We reserve the right to alter specifications. 129