SECTION 16320 MEDIUM VOLTAGE TRANSFORMERS (LIQUID FILLED) PART I - GENERAL 1.01 SUMMARY A. Section Includes: 1. B. 1.02 1.03 Liquid filled pad mounted transformers. Related Sections: 1. Section 02200 - Earthwork: Soil Compaction Requirements 2. Section 03300 - Cast-in-Place Concrete: Pads for Transformer Support 3. Section 16110 – Raceways 4. Section 09900 – Painting REFERENCES A. All characteristics, definitions and terminology shall be in accordance with the latest revision of applicable ANSI and NEMA standards. B. American Society of Testing and Materials (ASTM). C. Institute of Electrical and Electronic Engineers (IEEE). D. Manufacturer must be ISO 9001 certified. SUBMITTALS A. Require submittals under the provisions of Section 16010 - Basic Electrical Requirements and Section 01300 - Submittals. B. Submit shop drawings indicating outline dimensions, connection and support points, weight, specified ratings and materials. C. Submit product data indicating standard model design tests and options. D. Submit manufacturer’s installation instructions under provisions of Section 01300. JULY 2015 UCB STANDARDS 16320-1 1.04 1.05 OPERATION AND MAINTENANCE DATA A. Submit operation and maintenance data under provisions of Sections 01700, 01730, 16010 Division I. B. Include procedures for cleaning unit and replacing components. C. Submit product data indicating standard model design tests and options. D. Submit manufacturer’s installation instructions under provisions of Section 01300. QUALITY ASSURANCE A. 1.06 Manufacturer: Company specializing in distribution transformers with three (3) years documented experience. DELIVERY, STORAGE, AND HANDLING A. Store and protect products under provisions of Sections 01600 and 16010. B. Protect transformers as instructed by the manufacturer. PART 2 - PRODUCTS 2.01 MANUFACTURERS Medium Voltage Transformers: 2.02 A. ABB B. Cooper/Power Systems EQUIPMENT A. Pad Mounted Oil-Filled Transformers: 1. JULY 2015 Liquid-filled Transformer, FM labeled, UL listed: a. Three phase, pad mounted, self-cooled transformer unit. b. Indicate kVA capacity, secondary voltage. Transformers larger than 1000 kVA shall not be used without special written authorization from the Director of Utility Services. UCB STANDARDS 16320-2 c. Primary voltage 13.2 KV Three Phase Delta with wye secondary. Specify with 2-2 ½% above and 2-2 ½% below normal primary taps, with externally-operated no load tap changer. Secondary voltage as required. d. Impedance: Per ANSI Standards. Consult with the Director of Utility Services if the new transformer can be paralleled with an existing transformer. e. Cooling and Temperature Rise: 65oC, self cooled. f. Accessories: All accessories shall be housed in a side accessories cabinet having the full height of the transformer with a lockable Penta-head cabinet door. All gauges and pressure indication shall have remote alarm contact. g. JULY 2015 i. NSI tank ground pad ii. 1” filling plug mounted on the tank wall within the side accessory cabinet iii. Two (2) 1” Drain Valves with samplers. One shall be located in the HV compartment and the other in the side accessories cabinet iv. Tap changer handle v. Liquid level gauge vi. ¼” NPT with vacuum/pressure gauge vii. Pressure relief valve viii. Liquid temperature gauge ix. Two (2) nameplates; one shall be installed in the LV compartment and the other in the side cabinet. Dielectric fluid shall be non-toxic, non-bioaccumulating and be readily and completely biodegradable per EPA OPPTS 835.3100. The fluid shall have a minimum open cup fire point (ASTM D92) of 350 C and be FM approved, UL Classified less-flammable UCB STANDARDS 16320-3 Envirotemp FR3, all in accordance with current NEC Section 45023. h. Primary Terminations: i. Specify six (6) ANSI/IEEE 386 600 dead break bushings as specified by the Director of Utility Services for loop fed application. Parking stands shall be provided. Specify three (3) internal oil immersed, two-position load-break switches to allow alternate circuit service and isolation of transformer. The three (3) switches shall be wired as shown in the diagram at the end of this section. i. Primary Overcurrent Protection: Two fuse system consisting of Bayonet-type, oil immersed expulsion fuse in series with current limiting backup fuse. Current limiting backup fuse to be mounted inside the transformer under oil. The current limiting fuse should be located as near as practical to the incoming primary bushing, on the source side of the expulsion fuse. The two fuses shall be coordinated so that the expulsion fuse clears low energy faults on the secondary system and the current limiting fuse clears only high energy includes overload protection, can be provided as an alternate with approval from the Manager of Utilities Distribution. All transformer fusing shall be coordinated with upstream phase overcurrent devices. j. Copper windings or aluminum windings, as specified by Manger of Utilities Distribution. k. Efficiency standard per DOE 2010, 10 CFR Part 431 l. Cabinet to be sized to accommodate 600 AMP bushings. m. Provide three spare Bayonet fuses. PART 3 - EXECUTION 3.01 INSTALLATION A. Require installation in accordance with manufacturer’s instructions. B. Require safety labels per NEMA, and provide code listed and label option for the non-toxic dielectric fluid. JULY 2015 UCB STANDARDS 16320-4 C. Transformer clearances shall comply with Xcel Energy requirements. D. Transformers shall be looped into the primary electric distribution system E. All secondary conductors shall be terminated utilizing compression type 2 hole lugs. F. Transformer grounding per specification E16390 transformer installation. G. New transformer installation shall have fault indicator as per specification E16366. H. Transformer ID tag marking: Contractor is responsible to install transformer identification tag and cable ID on the new installed transformer. Install 2”x2” new non reflective weather resistant transformer identification tags. Cables ID tags on the transformer inside wall above each loop feed switch: Cable ID XX From XXX to XXX I. 3.02 Transformer start-up: The on site test shall be completed after it is set on it’s permanent pad and grounded. The transformer will not be started until all tests are complete and turned over to Owner and engineer (2 sets) for review and approval. FIELD QUALITY CONTROL A. Factory and field testing shall be performed under provisions of Section 01400. All field tests shall be witnessed by the University. All test reports shall be turned over to the University prior to transformer energization. Perform the following tests: 1. JULY 2015 Sample insulating liquid in accordance with ASTM 3612 D3613 and perform dissolved gas analysis (DGA) in accordance with ANSI/IEEE C57.104 and ASTM 3612. The oil shall be tested for: a. ASTM D-1533B Moisture in oil b. ASTM D-971 Inter Facial Tension c. ASTM D-974 Acid Number UCB STANDARDS 16320-5 B. d. ASTM D-1500 Color Number e. ASTM D-1524 Visual Exam f. ASTM D-1816 Dielectec Breakdown g. ASTM D-924 Power Factor 25C 2. Turns ratio test on all taps. 3. Power factor test or dissipation factor test. 4. Excitation. 5. Require oil testing 48 hours after energization. Contractor shall submit reports to University for keeping. Factory test transformer to ANSI/IEEE C57.12.91 and provide University the test results prior to setting the transformer. Field test transformer to ANSI/IEEE C57.12.91. All field tests to be witnessed by Owner. All test reports shall be turned over to Owner. 3.03 WARRANTY The contractor or the manufacture shall provide a minimum of 12 months warranty from installation date. A. The University of Colorado Utility department will periodically do a dissolved gas analysis and other tests to the transformer oil. If during the transformer warranty period the dissolved gas values exceed those specified below, responsibility and cost for further diagnosis, oil sampling, and testing shall transfer from The University of Colorado Utility department to the manufacturer or contractor. The manufacturer or contractor shall, under the original warranty, analyze the problem, take remedial action, and retest the transformer with sufficient frequency and over a sufficient duration to prove the cause of the gassing has been remedied and any internal damage caused in the transformer has been repaired. For transformers filled with type FR3 oil the dissolved gases and other test values shall be limited to the following amounts during the warranty period of the transformer. JULY 2015 UCB STANDARDS 16320-6 Oil type Hydrogen Methane Acetylene Ethylene Ethane H2 CH4 C2H2 C2H4 C2H6 Carbon Monoxide Carbon Dioxide CO CO2 To be measured and trended Soybean 118ppm 22ppm 1ppm 20ppm 247ppm 179ppm High Oleic Sunflower 45ppm 30ppm 1ppm 23ppm 84ppm 583ppm Synthetic 82ppm 135ppm 33ppm 215ppm 362ppm 1526ppm Water content ≤ 400ppm Power factor ≤ 3% Acid neutralization number ≤ 0.3 Color ≤ 1.5 Flashpoint ≥ 275°C 1. 2. 3. 4. 5. B. The University of Colorado Utility department will compare the trend in the concentrations of dissolved gasses measured at each dissolved gas analysis test. In particular only the trended values of CO2 are significant rather than the absolute values. If the rate of accumulation of any of the gasses significantly increases, the manufacturer or contractor will provide further testing under the warranty to determine the cause of the change in gassing rate. The manufacture or contractor shall provide any repairs necessary to remedy the cause of abnormal gassing. After remedying the problem causing the increased gassing the manufacturer shall provide additional testing to prove the problem has been remedied and provide a 6 months warranty extension to analyze the results. C. If the manufacturer has made an attempt to remedy a problem in the transformer causing high levels of dissolved gases or a significant increase in the rate of gas accumulation, and the transformer continues to accumulate gas levels above those specified or at an increasing rate the manufacturer shall replace the transformer under the terms of the warranty at no cost to the University of Colorado. 3.04 ADJUSTING Adjust primary taps to tap D on 13,200 volt nominal transformers. END OF SECTION 16320 JULY 2015 UCB STANDARDS 16320-7