Document

advertisement
G / E-Series
Digital Monitoring devices
Product Features
●
●
●
●
●
●
●
●
●
●
●
Din sized enclosure with Auto / manual Switch
LED indication for relay status
CT primary can be programmed up to 2500 in steps of 5. CT secondary will be factory set for 5.
User can set the in-rush time delay.
PVMD, PVMD-G :Monitors and trips the circuit after the set trip delay time when ever power
unhealthiness (phase failure, phase sequence, phase unbalance under voltage or over voltage)
occurs.
Displays all the 3 phase voltages in a scrolling fashion during healthy condition.
PVMD – Panel / Flush mounting, PVMD-G Din rail mounting.
PVIMD, PVIMD-G: Monitors and trips the circuit after the set trip delay time when ever power
unhealthiness (phase failure, phase sequence, phase unbalance under voltage, over voltage, under
current or over current)
Displays all the 3 phase voltages and 3 phase currents in a scrolling fashion during healthy condition.
User can program nominal current. Under current and over current limits can be set in percentage
with reference to nominal current .
PVIMD – Panel / Flush mounting, PVIMD-G Din rail mounting
Specifications
Model
PVMD
PVMD-G
PVIMD
PVIMD-G
Function
Phase Unbalance,Phase Reversal,Phase Failure, Under
and Over Voltage, Monitor and Control
Phase Unbalance,Phase Reversal,Phase Failure, Under and Over
Voltage, Under and Over Current Monitor and Control
Input Voltage
415V AC, 3 phase, 4 wire
Input Frequency
50Hz ± 10%
Input Current
N.A
Voltage(Accuracy)
±4V of display value
Trip Time(Accuracy)
±1% of set delay of value ±2 sec
Current(Accuracy)
N.A
Power consumption
5VA / 1W
Trip Setting
Phase Unbalance-> 1-20%(Adj.)
Under Voltage-> 5 to 100V AC
Over Voltage-> 5 to 100V AC
Phase Unbalance-> 1-20%(Adj.)
Under Voltage-> 5 to 100V AC
Over Voltage-> 5 to 100V AC
Over Current-> 105% to 800%
Under Current->20%* to 95%
Minimum sensing current
N.A
0.5A
Maximum setting current
N.A
5A(Above 5A-> Ext.CT can be used, CT setting max.2500/5 in steps of
5)
Trip time delay
1 to 250 secs settable for UB, OV, UV
1 to 250 secs settable for UB, OV, UV, OC, UC
Current inputs (AR, AY, AB) lb=5A
± 5% of lb ± 1 digit (lb=5A)
Phase Failure trip time delay Less than 5 sec
Phase reverse trip time delay Instantaneous
Power On Delay
10 sec Max.
Inrush current delay
N.A
Control output
1 c/o rated for 10A @ 250V AC / 28V DC resistive load
Recovery time
2sec minimum
Ambient temperature
Operation: -100C to +550C, Storage: -250C to 800C
Humidity
Max. 85% RH @ 400C
Service life (under no load)
106 operations minimum
1 to 60secs settable
Electrical life (under full load) 105 operations minimum
Rated frequency of operation 1800 ± 5% operations per hour maximum
Insulation resistance
>100M ohms @ 500V DC
Di-electrical strength
1. 2.5KV AC, 50Hz for 1minute. (Between current carrying and non-current carrying parts).
2. 1.5KV AC, 50Hz for 1minute. (Between contacts and control circuit).
3. 750VAC, 50Hz for 1minute. (Between non-continuous contacts of the relay).
Electrical connection
Screw type terminals with self lifting clamps
Mode of operation
Manual / Auto
Dimension (over-all)
96 x 96 x 97.5 mm (W x H 76 x 78 x 115 mm (W x H x
x D)
D)
* Applicable for more than 2.5 Amps nominal current
96 x 96 x 97.5 mm (W x H x D)
76 x 78 x 115 mm (W x H x D)
Connections
Dimensions
Accessories
Instruction Manual-----1No
RC Filter-----1No
Hints On Correct Use
Tools and Fasteners Kindly use star – type screw driver for tightening the screws.
NOTE: Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary
supply (control power).The disconnecting device should be within the reach of the equipment and the operator.
Caution
●
●
●
●
●
●
●
●
●
●
●
Apply appropriate personal protective equipment(PPE) and follow safety work practices
Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
If the equipment is not used in the manner specified by the manufacturer, the protection provided by the equipment may be impaired.
NEVER work alone.
Turn OFF all power supplying the energy meter and the equipment in which it is installed before working on it.
The successful operation of this equipment depends upon proper handling, installation and operation. Neglecting fundamental installation
requirements may lead to personal injury as well as damage to electrical equipment or other property.
NEVER bypass external fusing.
NEVER apply the voltages at Program Lock and Auto Reset terminals.
Before performing Dielectric or Megger testing on any equipment in which the monitoring device is installed, disconnect all the input and
output wires to the monitoring device. High voltage testing may damage electronic components contained in the monitor
The monitoring device should be installed in a suitable electrical enclosure.
EAPL is not responsible for any consequential damages arising out of use of our products, though the technology is cautiously chosen and
implemented like any other well designed good electric device.