EEL303: Power Engineering I - Tutorial 5 1. A single circuit 50 Hz, 3-phase transmission line has the following parameters per km: R=0.2 ohm, L=1.3mH and C=0.01µ F. The voltage at the receiving end is 132 KV. If the line is open at the receiving end, find the rms value and phase angle of the following: (a) The incident voltage to neutral at the receiving end (reference). (b) The reflected voltage to neutral at the receiving end. (c) The incident and reflected voltages to neutral at 120 km from the receiving end. Solution: The series impedance per unit length of the line z = r + jx = (0.2 + j1.3 × 314 × 10−3 ) = (0.2 + j0.408) = 0.454̸ 63.88 T he shunt admittance = jwc = j314 × 0.01 × 10−6 3.14 × 10−6 ̸ 90 √ √ z 0.454 T he characteristic impedance Zc = = × 105 ̸ (63.88 − 90) = 380̸ −13.06 y 0.314 √ √ γ = yz = 0.314 × 0.454 × 10−6 ̸ (90 + 63.88)/2 = (0.2714+j1.169)×10−3 = (α+jβ) T he receiving end line to neutral voltage Vr = 132 × 1000 √ = 76200volts 3 The receiving end current under open circuited condition Ir = 0 (a) The incident voltage to neutral at the receiving end (x=0) is Vr + Ir Zc 2 Since, it is no load condition, Ir = 0 Incident voltage = Vr 76200 = = 38100volts 2 2 (b) Similarly, the reflected voltage to neutral at the receiving end Vr − Ir Zc Vr = = 38100volts 2 2 (c) The incident voltage at a distance of 120 km from the receiving end Vr+ = Vr exp(αx)exp(jβx) Vr+ = 76.2exp(0.2712 × 120 × 10−3 exp(j1.69 × 120 × 10−3 ) = 78.7̸ 8.02 The incident voltage at a distance of 120 km from the receiving end = 78.7 ̸ 8.02 = 39.35̸ 8.02 2 Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 5 Vr− = Vr exp(−αx)exp(−jβx) Vr+ = 76.2exp(−0.0325)exp(−j0.140) = 73.76̸ − 8.02 The rreflected voltage at a distance of 120 km from the receiving end = 73.76 ̸ − 8.02 = 36.88̸ − 8.02 2 2. Determine the efficiency of the line in the above problem if the line is 120 km long and delivers 40 MW at 132 KV and 0.8 p.f. lagging. Solution: 40 × 1000 T he receiving end currentIr = √ = 218.7amps 3 × 132 × 0.8 From the above problem, Zc = 380̸ − 13.06 For 120 km length of the line, exp(αx)exp(jβx) = 1.033̸ − 8.02 exp(−αx)exp(−jβx) = 0.968̸ − 8.02 Taking Vr as reference, Ir = 218.7̸ − 36.8 Vr + Ir Zc exp(αx)exp(jβx) 2 76200 + 380 × 218.7̸ − 13.06̸ − 36.8 Vs+ = × 1.033̸ 8.02 = 74.63̸ − 18 2 Vr − Ir Zc Vs− = exp(−αx)exp(−jβx) 2 76200 + 380 × 218.7̸ − 49.86 × 0.968̸ − 8.02 = 32.619̸ 62.37KV Vs− = 2 Vs = Vs+ + Vs− = 74.63̸ − 18 + 32.619̸ 62.37 = 86077 + j5751 = 86.26̸ 3.82 Vs+ = Now, Electrical Engineering Dept - IIT Delhi Page 2 of 7 EEL303: Power Engineering I - Tutorial 5 Vr Vr + Ir − Ir Z Z Is = c exp(αx)exp(jβx) − c exp(−αx)exp(−jβx) 2 2 Vs+ Vs− Is = − = 200.39̸ − 29.9 Zc Zc P ower at the sending end = 3×|Vs ||Is |cosϕs = 3×86.26×200.39cos33.72 = 43.132M W % Ef f iciency = 40 × 100 = 92.7% 43.132 3. Determine the ABCD parameters of the line of above problem and verify the sending end quantities found in the above problem. Solution: γl = (0.2712 + j1.169)120 × 10−3 = 0.03254 + j0.1402 A = coshγl = cosh(0.03245 + j0.1402) A = cosh0.03254cos0.1402 + jsinh0.03254sin0.1402 = 0.99 + j0.004435 = 0.99̸ 0.26 B = Zc sinhγl sinhγl = sinhαlcosβl + jcoshαlsinβl sinhγl = sinh0.03254cos0.1402+jcosh0.03254sin0.1402 = 0.031958+j0.1386 = 0.1422̸ 77 B = Zc sinhγl = 380̸ − 13.06 × 0.1422̸ 77 = 54.03̸ 64 Vs = AVr + BIr = 0.99̸ 0.26 × 76200 + 54.03̸ 64 × 218.7̸ − 36.8 Vs = 85908 + j5380 = 86.07̸ 3.588 4. A three phase 50 Hz transmission line is 400 km long. The voltage at the sending end is 220 KV. The line parameters are r=0.0125 ohm/km, x=0.4 ohm/km and y = 2.8 × 10−6 mho/km. Find the following: (a) The maximum permissible line length if the receiving end no-load voltage is not to exceed 235 KV. (b) For part (a), the maximum permissible line frequency, if the no-load voltage is not to exceed 250 KV. Solution: The total line parameters are: R=0.125 × 400 = 50 ohms Electrical Engineering Dept - IIT Delhi Page 3 of 7 EEL303: Power Engineering I - Tutorial 5 X = 0.4 × 400 = 160 ohm Y = 2.8 × 10−6 × 400 ̸ 90 = 1.12 × 10−3 ̸ 90 mho Z = R+jX = (50+j160) 168 ̸ 72.6 mho YZ = 1.12 × 10−3 ̸ 90 ×168 ̸ 72.6 = 0.188 ̸ 162.6 (a) Maximum permissible no-load receiving end voltage = 235 KV |A| = | 220 Vs |= = 0.936 Vr 235 Now, |A| = 1 + YZ 2 l2 × j2.8 × 10−6 × (0.125 + j0.4) = (1 − 0.56 × 10−6 l2 ) + j0.175 × 10−6 l2 2 Since, the imaginary part will be less than 1/10th of real part, |A| can be approximated as |A| = (1 − 0.56 × 10−6 l2 ) = 0.936 |A| = 1 + l2 = 1 − 0.936 0.56 × 10−6 l=338 km. (b) Vs 220 |= = 0.88 Vr 250 1 f f |A| = 1 + × j1.12 × 10−3 × (50 + j160 × ) 2 50 50 Neglecting the imaginary part, we can write |A| = | |A| = 1 − 1 f2 × 1.12 × 1.12 × 10−3 × 160 2 = 0.88 2 50 Simplifying, we obtain the maximum permissible frequency as f=57.9 Hz 5. A 275 KV transmission line has the following line constraints: A=0.85̸ 5; B=200̸ 75 (a) Determine the power at unity power factor that can be received if the voltage profile at each end is to be maintained at 275 KV. (b) What type and rating of compensation equipment would be required if the load is 150 MW at unity power factor with the same voltage profile as in part (a). (c) With the load as in part (b), what would be the receiving end voltage if the compensation equipment is not installed. Electrical Engineering Dept - IIT Delhi Page 4 of 7 EEL303: Power Engineering I - Tutorial 5 Figure 1: Solution: (a) Given, |Vs | = |Vr | = 275 KV; α = 5, β = 75. Since, the power is received at unity power factor, Qr = 0 = 275 × 275 0.85 sin(75 − δ) − × (275)2 sin(75 − 5) 200 200 0 = 378sin(75 − δ) − 302 which gives, δ = 22. Pr = 275 × 275 0.85 cos(75 − 22) − × (275)2 cos(75 − 5) = 227.6 − 109.9 = 117.7M W 200 200 (b) Now |Vs | = |Vr | = 275 KV Power demand by load = 150 MW at UPF PD = Pr =150 MW; QD =0 150 = 275 × 275 0.85 cos(75 − δ) − × (275)2 cos(75 − 5) = 227.6 − 109.9 = 117.7M W 200 200 150 = 378cos(75 − δ) − 110 δ = 28.46 Qr = 275 × 275 0.85 cos(75−28.46)− ×(275)2 cos(75−5) = 274.46−302 = −27.56M V AR 200 200 Thus, in order to maintain 275 KV at the receiving end, Qr = -27.56 MVAR must be drawn along with the real power of Pr = 150MW. The load being 150 MW at unity power factor, i.e., QD =0, compensation equipment must be installed at the receiving end. Electrical Engineering Dept - IIT Delhi Page 5 of 7 EEL303: Power Engineering I - Tutorial 5 -27.56 + QC = 0 QC = 27.56 MVAR i.e., the compensation equipment must feed positive VARs into the line. (c) Since, no compensation equipment is provided Pr = 150MW; Qr = 0 Now, |Vs | = 275 KV, |Vr | = ? Figure 5 Substituting this data in Pr and Qr , we have 275 × |Vr | 0.85 cos(75 − δ) − × |Vr |2 cos70 200 200 275 × |Vr | 0.85 0= sin(75 − δ) − × |Vr |2 sin70 200 200 150 = (1) (2) From, Eq. (2), we get sin(75 − δ) = 0.0029|Vr | √ cos(75 − δ) = (1 − 0.00292 |Vr |2 ) Substituting in Eq. (1), we obtain √ 150 = 1.375|Vr | (1 − 0.00292 |Vr |2 ) − 0.00145|Vr |2 (3) (4) (5) Solving the quadratic and retaining the higher value of |Vr |, we obtain |Vr | = 244.9 KV. 6. Input to a single-phase short line shown in below Figure is 2000 KW at 0.8 lagging power factor. The line has a series impedance of (0.4+j0.4) ohms. If the load voltage is 3KV, find the load and receiving end power factor. Also find the supply voltage. Figure 2: Electrical Engineering Dept - IIT Delhi Page 6 of 7 EEL303: Power Engineering I - Tutorial 5 Solution: Sending end active/reactive power = receiving end active/reactive power + active/reactive line losses. For active power, |Vs ||I|cosϕs = |Vr ||I|cosϕr + |I|2 R (6) |Vs ||I|sinϕs = |Vr ||I|sinϕr + |I|2 X (7) For reactive power, Squaring eq. (6) and (7), adding and simplifying, we get |Vs |2 |I|2 = |Vr |2 |I|2 + 2|Vr ||I|2 (|I|Rcosϕr + |I|Xsinϕr ) + |I|4 (R2 + X 2 ) (8) From the numerical values given, |Z|2 = (R2 + X 2 ) = 0.32 2000 × 103 = 2500 × 103 0.8 |Vs ||I|cosϕs = 2000 × 103 |Vs ||I| = |Vs ||I|sinϕs = 2000 × 103 × 0.6 = 1500 × 103 (9) (10) (11) (12) From eq. (6) and (7), we get |I|cosϕr = 2000 × 103 − 0.4|I|2 3000 (13) |I|sinϕr = 1500 × 103 − 0.4|I|2 3000 (14) Substituting all the known values in Eq. (8), we have 0.32|I|4 − 11.8 × 106 |I|2 + 6.25 × 1012 = 0 (15) |I| = 725amps (16) Substituting for |I| in Eq. (13), we get cosϕr = 0.82 (17) LoadPr = |Vr ||I|cosϕr = 3000 × 725 × 0.82 = 1790KW (18) |Vs ||I|cosϕs = 2000 2000 = 3.44KV |Vs | = 725 × 0.8 (19) Now, Electrical Engineering Dept - IIT Delhi (20) Page 7 of 7