Compact NSX Wiring diagrams

advertisement
Compact NSX
Wiring diagrams
Contents
Functions and characteristics
Installation recommendations
Dimensions and connection
A-1
B-1
C-1
Compact NSX100 to 630
559E4000.indd
Fixed circuit breakers
Plug-in / withdrawable circuit breakers
Motor mechanism
SDx module with Micrologic
SDTAM module with Micrologic M
D-2
D-4
D-6
D-8
D-9
Additional characteristics
Catalogue numbers
Glossary
E-1
F-1
G-1
version: 1.0
D-1
Compact NSX100 to 630
Wiring diagrams
Fixed circuit breakers
Power
Micrologic
Remote operation
a (+)
DB115707
N
a (+)
Z5
Z3
Z4
Z2
3P or 4P
Z1
Upstream CB
NSX cord
L1 L2 L3
BPO
SDE
81
82
84
BPF
Q
auto
manu
ou
Z5
Z3
Z4
T2
I
B2
B4
A2
C2
MX
A4
D2
MN
Z2
Z1
HL
+ T1
0
I
A1
L1
C1
D1
U
a (-)
manu
SDE
a (-)
Motor mechanism (MT)
NSX cord
Z5
Z4
Z1
L1 L2 L3
Z2
N
Z3
3P + N
a (220/240 V)
+ -
BSCM
I
Q
U
Z2
Z1
B4
HL
Downstream CB
T1
Z5
auto
manu
0
I
A1
ENVT
Z4
Z3
T2
ENCT
H2 T1
a
H1 T2
Communicating motor
mechanism (MTc)
Micrologic A or E
A/E
Communication
H(WH), L(BL): data
- (BK), + (RD): 24 V DC power supply
A/E
ZSI (Zone Selective Interlocking)
Z1: ZSI OUT SOURCE
Z2: ZSI OUT
Z3: ZSI IN SOURCE
Z4: ZSI IN ST (short time)
Z5: ZSI IN GF (ground fault)
Note: Z3, Z4, Z5 for NSX400/630 only.
A/E
E
D-2
ENCT: external neutral current transformer:
- shielded cable with 1 twisted pair (T1, T2)
- shielding earthed at one end only (CT end).
Connection L = 30 cm max.
- maximum length of 10 metres
- cable size 0.4 to 1.5 mm2
- recommended cable: Belden 8441 or equivalent.
ENVT: external neutral voltage tap for connection to the
neutral via a 3P circuit breaker.
Remote operation
MN:
undervoltage release
or
MX:
shunt release
Motor mechanism (MT)
A4:
A2:
B4, A1:
L1:
B2:
opening order
closing order
power supply to motor mechanism
manual position (manu)
SDE interlocking (mandatory for correct operation)
BPO:
BPF:
opening pushbutton
closing pushbutton
Communicating motor mechanism (MTc)
B4, A1:
BSCM:
motor mechanism power supply
breaker status and control module
version: 2.0
559E4100.indd
DB115708
Indication contacts
Terminals shown in red O must be connected by the customer.
72
VT
Fault
74
102
104
124
WH
YE
134
CAO1
RD
WH
GY
121
101
SDV
131
CAF2 CAF1
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in normal position.
Open
71
SD
SDE
Closed
RD
94
92
84
82
Fault
91
21
OF1
Fault
81
12
14
Closed
11
22
32
24
OF2
31
OF3
41
OF4
34
44
42
Open
Indication contacts
OF2 / OF1: device ON/OFF indication contacts
OF4 / OF3: device ON/OFF indication contacts (NSX400/630)
SDE:
fault-trip indication contact (short-circuit, overload, ground fault, earth
leakage)
SD:
trip-indication contact
CAF2/CAF1: early-make contact (rotary handle only)
CAO1:
early-break contact (rotary handle only)
SDV:
earth leakage fault trip indication contact (add-on Vigi module)
Colour code for auxiliary wiring
RD: red
VT:
WH: white
GY:
YE: yellow
OR:
BK: black
BL:
GN: green
559E4100.indd
violet
grey
orange
blue
version: 2.0
D-3
Compact NSX100 to 630
Wiring diagrams
Plug-in / withdrawable circuit breakers
Power
Micrologic
Remote operation
DB115709
a (+)
a (+)
Z5
Z3
Z4
Z2
Z1
Upstream CB
SDE
NSX cord
BPO
3P or 4P
BPF
L1 L2 L3
84
B2
MX
B4
C2 OR
MN
BL
RD
A2
A2 WH
B4
A4
A4 OR
D2
BL
22/32
Z2 YE
D2
24/34
L
H
Z1 VT
84
A1
B4
A2
C2
82 84
RD
BK
BL
WH
+
N
81
T1
I
BK
L1
A1
WH
D1/C1
a (-)
0
A1
C1
D1
44
GN Z4
42
RD Z5
BK Z3
41
U
or
L1
auto
manu
T2
I
GN
Q
manu
a (-)
SDE
Motor mechanism (MT)
NSX cord
Z5
HL
Z4
a (220/240 V)
+ -
Z1
L1 L2 L3
Z2
N
Z3
3P + N
BSCM
Z2
Z2 YE
B4 GN
Z1
Z1 VT
B4
Downstream
Q
I
U
T1
RD Z5
Z5
I
OR A1
GN Z4
Z4
0
A4
BK Z3
ENCT
H2 T1
auto
manu
T2
Z3
ENVT
a
H1 T2
Communicating motor
mechanism (MTc)
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in normal position.
D-4
version: 2.0
559E4100.indd
Indication contacts
Carriage switches
559E4100.indd
352
354
VT
312
GY
GY
314
YE
YE
351
CD
311
GY 71
CE
Disconnected
71
GY
VT
72
74
72 YE
VT
74 VT
102
104
YE
124
WH
101
BK 91
91
Terminals shown in red v / O must be connected by the customer.
WH
BK 81
81
violet
grey
orange
blue
121
GY 11
11
Colour code for auxiliary wiring
RD: red
VT:
WH: white
GY:
YE: yellow
OR:
BK: black
BL:
GN: green
RD
GY 21
21
ENCT: external neutral current transformer:
- shielded cable with 1 twisted pair (T1, T2)
- shielding earthed at one end only (CT end).
Connection L = 30 cm max.
- maximum length of 10 metres
- cable size 0.4 to 1.5 mm2
- recommended cable: Belden 8441 or equivalent.
ENVT: external neutral voltage tap for connection to the
neutral via a 3P circuit breaker.
Connected
Fault
SDV
131
GY 31
Note: Z3, Z4, Z5 for NSX400/630 only.
E
CAO1
CAF2 CAF1
Micrologic A or E
A/E
Communication
H(WH), L(BL): data
- (BK), + (RD): 24 V DC power supply
A/E
ZSI (Zone Selective Interlocking)
Z1: ZSI OUT SOURCE
Z2: ZSI OUT
Z3: ZSI IN SOURCE
Z4: ZSI IN ST (short time)
Z5: ZSI IN GF (ground fault)
A/E
Open
134
94
SD
SDE
Closed
RD
92
94 RD
84
84 RD
92 GN
82
82 GN
12
14
12 YE
14 VT
22
24
22 YE
32
34
32 YE
24 VT
OF1
Fault
31
OF2
Fault
BK 41
OF3
Closed
41
OF4
34 VT
42
44
42 GN
44 RD
DB115710
Open
Remote operation
MN:
undervoltage release
or
MX:
shunt release
Motor mechanism (MT)
A4:
A2:
B4, A1:
L1:
B2:
BPO:
BPF:
opening order
closing order
motor mechanism power supply
manual position (manu)
SDE interlocking (mandatory for automatic or remote
recharging)
opening pushbutton
closing pushbutton
Communicating motor mechanism (MTc)
B4, A1:
BSCM:
motor mechanism power supply
breaker status and control module
Indication contacts
OF2 / OF1: device ON/OFF indication contacts
OF4 / OF3: device ON/OFF indication contacts (NSX400/630)
SDE:
fault-trip indication contact
(short-circuit, overload, ground fault, earth leakage)
SD:
trip-indication contact
CAF2/CAF1: early-make contact
(rotary handle only)
CAO1:
early-break contact
(rotary handle only)
SDV:
earth leakage fault trip indication contact (add-on Vigi
module)
version: 2.0
D-5
Wiring diagrams
Compact NSX100 to 630
Motor mechanism
Motor mechanism (MT) with automatic reset
DB114666
a (+)
SDE
81
82
84
BPF
B2
A4
B4
BPO
After tripping initiated by the "Push to trip" button or by
the undervoltage (MN) release or the shunt (MX)
release, device reset can be automatic, remote or
manual.
A2
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in normal position.
Following tripping due to an electrical fault (with an
SDE contact), reset must be carried out manually.
Q
0
I
L1
A1
auto
manu
manu
SDE
a (-)
DB114667
Motor mechanism (MT) with remote reset
a (+)
SDE
81
82
84
B4
A2
B2
Reset
A4
BPO BPF
Q
I
A1
0
L1
auto
manu
manu
SDE
a (-)
a (+)
D-6
81
82
84
B2
Q
auto
manu
0
I
A1
BPO:
BPF:
SDE:
circuit breaker
opening order
closing order
motor mechanism power supply
manual position (manu)
SDE interlocking (mandatory for correct
operation)
opening pushbutton
closing pushbutton
fault-trip indication contact (short-circuit,
overload, ground fault, earth leakage)
L1
Q:
A4 :
A2:
B4, A1:
L1:
B2:
A4
Symbols
SDE
BPF
B4
BPO
A2
DB114668
Motor mechanism (MT) with manual reset
manu
SDE
a (-)
version: 2.0
559E4100.indd
DB114669
Communicating motor mechanism (MTc)
NSX cord
B4
HL
+ -
a (220/240 V)
BSCM
Q
0
I
A1
auto
manu
a
DB115436
Schematic representation of the communicating motor mechanism (MT).
DB114670
RSU screen for the communicating motor mechanism (MTc)
B4
Auto
SD
SD
Manu
RSU utility setup screen for the communicating motor
mechanism.
SDE
220
VAC
Open
command
OF
Open motor
Close
command
OF
Enable
automatic
reset
Close motor
Enable
reset
even if
SDE
Reset
command
Reset motor
A1
Single-line diagram of communicating motor mechanism
Opening, closing and reset orders are transmitted via the communication network.
The "Enable automatic reset" and "Enable reset even if SDE" parameters must be
set using the RSU software via the screen by clicking the blue text.
"Auto/manu" is a switch on the front of the motor mechanism.
Symbols
Q:
B4, A1:
BSCM:
circuit breaker
motor mechanism power supply
breaker status and control module
Terminals shown in red O must be connected by the customer.
559E4100.indd
version: 2.0
D-7
Compact NSX100 to 630
Wiring diagrams
SDx module with Micrologic
Connection
DB115711
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in normal position.
a (+) 24 à 415 V
STD
or output 1
Micrologic 2
Micrologic 5
Micrologic 6
SD2
SD4
SDT
SDT or output 1
SDT or output 1
PAL Ir or output 2
SDG or output 2
SD4
SD2
SD3
Symbols
SD1, SD3: SDx-module power supply
SD2:
output 1 (80 mA max.)
SD4:
output 2 (80 mA max.)
PAL Ir
or SDG
or output 2
SDx
Q
SD1
Terminals shown in red O must be connected by the customer.
a (-)
DB115712
Operation
tr at 6 Ir
> 105 % Ir
> 90 % Ir
I
PAL Ir
SDG
SDT
Q
Circuit breaker
trip order
I:
Circuit breaker
reset
charge current
PAL Ir: thermal overload pre-alarm
D-8
SDG:
ground-fault signal
SDT:
thermal-fault signal
Q:
circuit breaker
version: 2.0
559E4100.indd
SDTAM module with Micrologic M
Connection
DB115713
The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in normal position.
a (+) 24 to 415 V
Manual
reset
Symbols
SD1, SD3: SDTAM-module power supply
SD2:
thermal-fault signal output
(80 mA max.)
SD4:
contactor-control output
(80 mA max.)
Micrologic 2-M
Micrologic 6 E-M
SD2
SD4
SDT
SDT
KA1
KA1
KM1
SD4
SD2
SD3
Closing
order
KA1
SDT
SDTAM
Opening
order
6 8
4
10
2
12
1
14
OFF
15
Auto reset (minutes)
Q
KA1
SD1
KM1
KM1
Terminals shown in red O must be connected by the customer.
a (-)
DB115714
Operation
Class (tr) at 7.2 Ir
> 95 % T°
400 ms
< 95 % T°
I
SDT
KA1
KM1
Q
400 ms before
circuit-breaker
tripping order
%T°
%T°
559E4100.indd
I:
charge current
SDT:
thermal-fault signal
KA1:
auxiliary relay (e.g. RBN or RTBT relay)
KM1:
motor contactor
Q:
circuit breaker
version: 2.0
Contactor
closing order
Manual or
automatic reset
D-9