Nonmetallic Sheathed Cable 300 Volts, Copper Conductors

advertisement
Building Wire
NMD90
300 Volts, Copper Conductors
Nonmetallic Sheathed Cable
APPLICATIONS
For use primarily in residential wiring, including branch circuits for outlets, switches, etc. May be installed in both exposed and concealed work in dry or damp locations where not exposed to mechanical damage. The maximum allowable conductor temperature is 90°C. The minimum recommended
installation temperature is -25°C for 2 conductor cables and -10°C for 3 conductor cables. Cables
should be stored at temperatures above 0°C for 24 hours prior to installing.
CONDUCTORS
Solid conductors: Soft, uncoated copper
Stranded conductors: Soft uncoated copper compressed stranded
90°C insulation
With bonding
conductor
300 volts
CONDUCTOR INSULATION AND JACKET
Colour-coded PVC (polyvinyl chloride), rated 90°C dry with clear nylon (polyamide) jacket.
BONDING CONDUCTOR
Soft, uncoated copper
ASSEMBLY
Two-conductor constructions have the insulated conductors laid parallel. With the bare bonding conductor laid parallel between the insulated conductors. The entire construction is encased in a durable
PVC jacket. Three-conductor constructions have the insulated conductors and bare bonding conductor twisted together before being encased in a durable PVC jacket.
INSULATION AND JACKET COLOUR
PVC (polyvinyl chloride) jacket applied over the complete assembly: 14 AWG - White, 12 AWG - Yellow, 10 AWG - Orange, 8 AWG or larger - White. For two-conductor cables, one conductor has white
insulation and the second has black insulation. For the three-conductor cables, one conductor has
white insulation, the second has black insulation, and the third has red insulation. A blue overall jacket
is available in two-conductor 14 AWG cable, and a red overall jacket is available in two-conductor 14-8
AWG cables with phase conductors being red and black.
INDUSTRY STANDARDS*
CSA C 22.2 No. 48, Master Contract 251402
Canadian Electric Code
FT1
ASTM
RoHS Compliant
SURFACE PRINT
Sample: CERROWIRE-A CSA AWG 14 CU 2 CDRS NMD90 NYLON (-25° C) 300 VOLTS FT1
2012, Cerro Wire LLC
All Rights Reserved
©
*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and
application.
Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563
www.cerrowire.com
REV-04/2013
A Marmon Group/
Berkshire Hathaway Company
Building Wire
NMD90
Nonmetallic Sheathed Cable
300 Volts, Copper Conductors
Product Code
Number &
Package Code
W/Ground
1472-1402xx
Insulated
Conductors
PVC
Thickness
mm
AWG &
No. Cond.
14-2
Solid
0.76
Bonding
Conductor
AWG
14
Allowable Ampacities at
30°C*
Cable
Dimension
mm
60°C
75°C
90°C
9.86 x 4.88
15
15
15
Approx. Net
Wt. KG/KM
101
1472-1403xx
14-3
Solid
0.76
14
8.77
15
15
15
129
1472-1602xx
12-2
Solid
0.76
14
10.71 x 5.30
20
20
20
129
1472-1603xx
12-3
Solid
0.76
14
9.69
20
20
20
170
1472-1802xx
10-2
Solid
0.76
12
12.21 x 5.84
30
30
30
182
1472-1803xx 10-3
Solid
0.76
12
10.85
30
30
30
243
1472-4002xx 8-2
Stranded
0.89
10
16.15 x 7.92
40
50
55
311
1472-4003xx
8-3
Stranded
0.89
10
14.47
40
50
55
410
1472-4202xx
6-2
Stranded
1.14
8
20.12 x 9.40
55
65
75
469
1472-4203xx
6-3
Stranded
1.14
8
17.65
55
65
75
629
1472-4402xx
4-2
Stranded
1.14
8
19.66
70
85
95
669
1472-4403xx
4-3
Stranded
1.14
8
19.66
70
85
95
902
1472-4503xx
3-3
Stranded
1.14
6
22.05
85
100
115
1189
1472-4602xx
2-2
Stranded
1.14
6
23.62
95
115
130
1034
1472-4603xx
2-3
Stranded
1.14
6
25.20
95
115
130
1400
•
•
•
xx packaging add code (9 and 10 Digits).
All sizes are available in 75m (package code-GM) and 150m (package code-JM).
* Allowable ampacities are for general use as specified by the Canadian Electrical Code, 2012, Table 2.