DC String Combiner Box Fused up to 1000V

advertisement
DC String Combiner Box Fused up to 1000V
Ideal for commercial PV systems of 3 and 4 string design, the PV
combiner box from IPD provides overcurrent protection as well
as DC isolation. Fitted with the latest Telergon DC isolator this
4-string combiner is easy to install and quick to connect.
SWITCHING
Designed around the latest high current DC switch from
Telergon, ZFV55, the IPD combiner box includes multiple
knock-out entries as well as high UV stability. The ZFV55 is tested
to meet the latest International Standard IEC 60947.3 with
switching capability of DC21B. The ZFV55 complies with the
requirements of AS5033 2014.
OVERCURRENT
The Mersen PV fuse links used in this combiner box are tested to
the latest fuse Standard IEC 60269.6. This Standard was released
in 2011 and is specifically included in the fuse standard to test
the cyclic loading and long term reliability of fuses when used in
photovoltaic systems.
ENCLOSURE
Note:
Available with optional Dehn
Photovoltaic surge protection on
request, ask your local IPD rep
for details.
The high-quality Hensel enclosure products are made of material
that is UV, impact, dust and waterproof, self-extinguishing,
flame-retardant, halogen and silicone-free. This product and
quality philosophy has made Hensel the world Number 1 brand
for electrical distribution solutions in difficult environments.
A
C
IPD Photovoltaic offering
B
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
D
A = DC String Combiner boxes
B = AC String Inverter Panels
C = AC Distribution Panel
D = AC Grid Protection Panels
www.ipdgroup.com.au
Ref.0315E
DC Combiner Box
Description:
- Small DC String combiner box including Overcurrent and DC isolation functions. Optional Surge protection.
Application:
- PV string protection and isolation.
Certification:
- International Electrotechnical Commission IEC 60947.3, IEC 60269.6, IEC 529.
Number
DC
Strings
4
4
Max
Voltage
1000V DC
1000V DC
Surge
Protection
-
Included
Part No.
PVDC41
PVDC41/S
Notes:
For the requirements of AS 5033 2012 Appendix B, with 2x contacts in series in
Positive (+) and 2x contacts in series in the negative (-):
900V Voc string, 4 x strings with Isc max of 8.9A (before Table 4.2 of AS 5033 2014).
1000V Voc string,
3 x Strings with Isc max of 8.9A (before Table 4.2 of AS 5033 2014).
1. If the series bridges are removed then the above ratings are not applicable.
2.Voc string = Voc ARRAY + Yv x Tmin x TSTC x M (as per Clause 4.2 of AS5033 2014).
CIRCUIT
Up to 4 string inputs
(Optional)
Grid Protection
Inverter
DIMENSIONS
Customers
MSBD
Grid
Knock-Outs/Entries
10 x M20
2 x M32/40
IPD INDUSTRIAL PRODUCTS
28 x M25
6 x M40/50
Phone: 1300 556 601
www.ipdgroup.com.au