Specifications Limited Service Controllers The main fire pump controller shall be a factory assembled, wired and tested Limited Service Controller conforming to all the requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. The controller shall be manufactured in the United States and be listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cUL), approved by Factory Mutual, and approved by the City of New York for fire pump service. The controller shall be of the combined manual and automatic type suitable for full voltage starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, gasketed, wall mounted steel enclosure. The controller components shall include a thermal magnetic circuit breaker with a minimum withstand rating of not less than: 3-20 H.P. — 200-240 Volts — 10,000 Amps RMS Symmetrical 25-30 H.P. — 200-240 Volts — 18,000 Amps RMS Symmetrical 3-30 H.P. — 380-600 Volts — 14,000 Amps RMS Symmetrical If the available fault current of the system exceeds these ratings, the controllers shall be supplied with a withstand rating as shown below: Horsepower 3-30 3-30 Voltage Withstand Rating Amps RMS Sym. 200-480 65,000 550-600 18,000 The circuit breaker shall have an externally mounted operating handle mechanically interlocked with the enclosure door so that entrance • FTA750 to the controller is not allowed with the handle in the ON position except by a hidden tool operated defeater. The circuit breaker handle shall be capable of being padlocked in the open or OFF position with up to three padlocks for installation and maintenance safety. The circuit breaker handle shall be in full control of the circuit breaker. The controller door shall have a locking type handle. The controller shall have externally mounted, on the enclosure flange, POWER ON and PHASE REVERSAL pilot lights, START and STOP pushbuttons and an EMERGENCY RUN mechanism. The START pushbutton and EMERGENCY RUN mechanism shall be separate units and not combined. The POWER ON pilot light shall be wired through contacts on the phase monitor to give true power on indication. Loss of power in any phase or loss of the control circuit transformer shall cause the light to go out. The PHASE REVERSAL pilot light shall be wired through contacts on the phase monitor to give true indication of incorrect phase angle relationships. The controller shall be supplied with a pressure switch having a range of 0-300 psi (0-21 kg/cm2) and with independent high and low pressure settings. The pressure switch shall be mounted inside the controller to prevent unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a solidly welded bulkhead pipe coupling without any other supporting members and field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The adjustment knobs shall be capable of being sealed after final adjustment. The controller shall have a minimum run period timer set for ten minutes. The minimum run timer shall include an integral timer running pilot light to indicate when the run timer FTA750 Specifications • Limited Service Controllers is in the timing mode. Terminals shall be provided to field convert the controller from automatic to manual shutdown. Terminals shall be provided so that standard duty rated, normally open pushbutton stations can be wired to the controller. Terminals shall be provided so that a remote deluge valve contact may be wired to the controller to start the unit. The controller shall be supplied with interlock and shutdown circuits as standard. Individual PHASE FAILURE, PHASE REVERSAL and PUMP OPERATING alarm contacts shall be wired to terminals. These contacts shall be both normally open and normally closed and be electrically isolated for wiring to either remote alarm panels as supplied by the controller manufacturer, or for use with remote telephone dropout type alarm systems. A factory built in alarm shall be provided in the fire pump controller, requiring only 120 Volt supervisory power. This alarm shall give an audible alarm for PUMP OPERATING, PHASE FAILURE, or PUMP FAILURE and a visual alarm for SUPERVISORY VOLTAGE AVAILABLE. This alarm shall be electrically isolated from the remote alarm contacts so that 24 VDC or separate 120 VAC remote alarms can be utilized. All alarm contacts shall be rated 125 VAC maximum 10 amperes pilot duty. They shall also be suitable for direct switching of low energy alarm circuits — 6 VDC minimum, 10 MA, 0.6 VA minimum. The control circuit transformer shall be of the molded winding construction type with built in molded terminals and shall be fuse protected from external loads. The fuse shall be installed on the transformer. The manufacturer shall test the entire controller assembly prior to shipment. This test shall include, but no be restricted to, each function the controller may be required to perform including remote alarms, remote start, automatic start with manual shutdown, automatic stop, remote deluge valve start, pressure drop start and manual start-stop. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 volts. The controller shall be manufactured by Firetrol, Inc. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP750-01(H)