Bussmann® LOW-PEAK® LPN-RK Dual-Element, Time-Delay Fuses Class RK1 – 250 Volt ⁄Ω¡º-60A Dimensional Data 2" (± 0.31) 0.81" (± 0.008) 35A to 60A ⁄Ω¡ºA to 30A Catalog Symbol: LPN-RK_SP Dual-Element, Time-Delay – 10 seconds (minimum) at 500% rated current (8 seconds for 0-30A sizes) Current-Limiting Ampere Rating: ⁄Ω¡º to 60 Amperes Voltage Rating: 250 Volts AC (or less) Interrupting Rating: 300,000A RMS Sym. 20,000AIR @ 125 VDC (UL) Agency Approvals: UL Listed – Special Purpose*, Guide JFHR, File E56412 CSA Certified (200,000AIR), Class 1422-02, File 53787 Class RK1 per CSA C22.2, No. 248.12 3" (± 0.31) 0.56" (± 0.008) General Information: • Current limitation for maximum short-circuit protection. • High speed-of-response is highly sensitive to fault currents, but insensitive to starting current and transient surges. • Provides long time-delay for temporary motor start-up. • Time-delay permits 125% FLA sizing for back-up, motor running protection. • Help protect motors from burn-out due to single-phasing. • Design of heat absorber reduces watts loss. • PTP fuse tube provides resistance to arcing, moisture and flame. • When properly sized, provides Type 2 protection for IEC starters. • 2:1 coordination ratio with other LOW-PEAK or Bussmann Class L fuses. Fuse Reducers For Class R Fuses Desired Fuse (Case) Size Equipment Fuse Clips 60A 100A *Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses. 200A Catalog Number (Pairs) 250V 30A No. 263-R 30A No. 213-R 60A No. 216-R 60A No. 226-R Catalog Numbers LPN-RK-⁄Ω¡ºSP LPN-RK-2SP LPN-RK-9SP LPN-RK-⁄fiΩ¡ººSP LPN-RK-2⁄Ω¢SP LPN-RK-10SP LPN-RK-¤Ω¡ºSP LPN-RK-2⁄Ω™SP LPN-RK-12SP LPN-RK-‹Ω¡ºSP LPN-RK-2°Ω¡ºSP LPN-RK-15SP LPN-RK-›Ω¡ºSP LPN-RK-3SP LPN-RK-17⁄Ω™SP LPN-RK-⁄Ω™SP LPN-RK-3¤Ω¡ºSP LPN-RK-20SP LPN-RK-flΩ¡ºSP LPN-RK-3⁄Ω™SP Fuseblocks 30 Amp Case 1 Pole 2 Pole 3 Pole Box Lug R25030-1CR R25030-2CR R25030-3CR Screw R25030-1SR R25030-2SR R25030-3SR R25030-1PR R25030-2PR R25030-3PR LPN-RK-25SP Pressure Plate 60 Amp Case LPN-RK-°Ω¡ºSP LPN-RK-4SP LPN-RK-30SP LPN-RK-1SP LPN-RK-4⁄Ω™SP LPN-RK-35SP 1 Pole 2 Pole 3 Pole LPN-RK-1⁄Ω•SP LPN-RK-5SP LPN-RK-40SP Box Lug R25060-1CR R25060-2CR R25060-3CR LPN-RK-1⁄Ω¢SP LPN-RK-5flΩ¡ºSP LPN-RK-45SP Screw R25060-1SR R25060-2SR R25060-3SR LPN-RK-1›Ω¡ºSP LPN-RK-6SP LPN-RK-50SP R25060-1PR R25060-2PR R25060-3PR LPN-RK-1flΩ¡ºSP LPN-RK-6⁄Ω¢SP LPN-RK-60SP Pressure Plate LPN-RK-1°Ω¡ºSP LPN-RK-8SP — CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. Carton Quantity and Weight Ampere Ratings Weight** Carton Qty. Lbs. Kg. 0–30 10 0.5 0.227 35–60 10 1.2 0.544 **Weight per carton. Bussmann rev. 9/10/97 Form No. LPN-RK 0-60 Page 1 of 2 BIF Doc #1003 Bussmann® LOW-PEAK® LPN-RK AMPERE RATING 60A 4 6.25 300 30A AMPERE RATING 15A 20A 300 ⁄Ω¡º-60A Time-Current Characteristic Curves–Average Melt .1 .15 .2 .3 .4 .6 1 1.6 2.5 3.2 5 8 10 12 .5 .8 1.25 2 Dual-Element, Time-Delay Fuses Class RK1 – 250 Volt 100 100 1 10 1,000 100 1 .1 .01 10 .1 RMS SYMMETRICAL CURRENT IN AMPERES TIME IN SECONDS TIME IN SECONDS 10 1 B 400,000 10,000 30 .01 1,000 60 10,000 20 100,000 100 AMPERE RATING .1 RMS SYMMETRICAL CURRENT IN AMPERES 200,000 100,000 1,000 10,000 A 1,000 INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS Current-Limitation Curves RMS SYMMETRICAL CURRENTS IN AMPERES A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS) Bussmann rev. 9/10/97 This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Form No. LPN-RK 0-60 Page 2 of 2 BIF Doc #1003