112 CHAPTER 5 INTERLINE POWER FLOW CONTROLLER SYSTEM 5.1 GENERAL In the IPFC structure, a number of inverters are linked together at their DC terminals. Each inverter can provide a series reactive compensation, as an SSSC, for its own line. However, the inverters can transfer real power between them via their common DC terminal. This capability allows the IPFC to provide both reactive and real power compensation for some of the lines and thereby optimize the utilization of the overall transmission systems. The main objective of an IPFC is to optimize both real and reactive power flow among multilines, and transfer power from overloaded to under loaded lines. The model of the closed loop controlled IPFC is developed using MATLAB and the simulation results are presented. The closed loop control of the IPFC is obtained using the PI controller. 5.2 MODEL OF THE IPFC USING MATLAB An elementary IPFC, composed of voltage source converters 1 and 2 with a common DC link, provides the series compensation for lines 1 and 2. Controlling the real power flow is achieved by approximately adjusting the angle of the IPFC in lines 1 and 2. The reactive power flow is achieved by adjusting the input voltage of lines 1 and 2. The model of the IPFC is developed and simulated using MATLAB simulink. 113 5.2.1 Model of a Basic Transmission Line using MATLAB The transmission line is designed with the resistance of the line and the reactance. The transmission line is simulated for AC sources of 110kV and 120 kV. The circuits of the primary and secondary lines are shown in Figures 5.1 and 5.2 respectively. The voltage at the sending and receiving ends is observed. The power across the load resistor and load inductor is also taken for an uncompensated line. The primary transmission line consists of the voltage source V1 and the source impedance is represented as Z1. The impedance of the transmission lines is represented as Z2 and Z3. The load in the primary transmission line is represented using ZL1. Figure 5.1 Model of the primary transmission line The secondary transmission line consists of the voltage source V2 and the source impedance is represented as Z1. The impedance of the transmission lines is represented as Z2 and Z3. The load in the secondary transmission line is represented using ZL2. 114 Figure 5.2 Model of the secondary transmission line From the values of the Power Engineer’s hand book, appropriate values are calculated for the real time application, and such values are used as impedance of primary and secondary transmission lines. From the impedance values, the loads of the primary and secondary transmission lines are calculated. Source voltage V=110kV ZT = (118 + j 217) ohm ZL = (432 + j 324) ohm I = (V/ZT) = 165.5, -45.77o A. VR = I*ZL= 714161.245, P = VR*I*cos -8.94o V = (714161.245, -8.94o) * (165.5, -45.77o) * (0.8) P = 9.46146 MW Q = VR*I*sin = (714161.245, -8.94o) * (165.5, -45.77o) * (0.6) Q = 7.096 MVAR The Schematic of the transmission line models for 120kV and 110kV are shown in Figures 5.3 and 5.4 respectively. 115 Figure 5.3 Model of the basic transmission line for 120kV Figure 5.4 Model of the basic transmission line for 110kV The reactive power in the load for 120kV and 110kV basic transmission lines is shown in Figures 5.5 and 5.6 respectively. This power was obtained without using any interlink. By introducing the IPFC controller the power is improved. 116 Figure 5.5 Reactive power in the 120kV transmission line Figure 5.6 Reactive power in the 110kV transmission line The reactive power in the 120kV and 110kV transmission lines is 7.825 MVAR and 7.086 MVAR respectively. This transmission line values coincide with the theoretical value of 7.096 MVAR. 5.2.2 Model of the Closed Loop Controlled IPFC The circuit model of the closed loop IPFC system with primary and secondary loads is shown in Figure 5.7. The load voltage is sensed and it is rectified. It is then compared with a reference signal. The multiple PWM technique is used. The output of the pulse generator is used to drive the switches of the inverter. Subsystem 1 represents the pulse generation module, which is shown in Figure 5.8. Subsystem 2 senses the voltage across the 117 primary load, and subsystem 3 senses the voltage across the secondary load. Subsystems 2 and 3 are shown in Figures 5.9 and 5.10 respectively. Subsystem 4 represents the circuit of the PI controller. Figure 5.7 Circuit of the closed loop controlled IPFC 118 Terminator7 1 2 m a g 2 Conn2 T erminator3 Terminator6 XL7 g 1 Ideal Switch2 k m m Terminator1 Thyristor1 g Pulse Generator2 a Thyristor2 a g 2 Ideal Swi tch1 Conn3 k m Terminator 1 3 g Conn1 2 1 g Ideal Switch a g Pulse Generator3 Conn4 2 Ideal Switch3 Thyristor3 m 4 m Thyristor Pulse Generator 1 g k m k m Terminator2 Terminator4 Terminator5 Pulse Generator1 AND Pulse Generator6 1 Pulse Generator4 In1 >= Repeating Sequence Logical Operator3 AND Logical Operator Relational Operator Pul se Generator5 Pulse Generator7 AND AND Logical Operator2 Logi cal Operator1 Figure 5.8 Subsystem 1 of the closed loop IPFC Diode4 1 Conn1 Diode5 Diode7 2 RL10 Conn2 RL11 + v - V5 1 Out1 Diode6 Figure 5.9 Subsystem 2 of the closed loop IPFC 119 Diode 1 2 Diode3 Conn2 RL8 RL9 Conn1 + v - V4 Diode1 1 Out1 Diode2 Figure 5.10 Subsystem 3 of the closed loop IPFC Simulation is done with the primary line input as 120kV and the secondary line input as 110kV. The reactive power output of the secondary load is 7.108MVAR. The reactive power output of the closed loop IPFC system with unequal voltages is shown in Figure 5.11. Figure 5.11 Reactive power of the secondary load with unequal voltages in the closed loop IPFC The model of the closed loop IPFC system is shown in Figure 5.7. Simulation is done with equal voltages on the input sides [primary and secondary line inputs as 110kV]. The reactive power output of the secondary load is 7.109MVAR. The reactive power output of the closed loop IPFC system with equal voltages is shown in Figure 5.12. 120 Figure 5.12 Reactive power of the secondary load with equal voltages in the closed loop IPFC The model of the closed loop IPFC system is shown in Figure 5.7. Simulation is done with equal voltages on the input sides and different phase angles [primary line input source voltage at 110kV with phase angle 15o and secondary line source voltage at 110kV with 30o phase angle]. Due to the difference in the phase angle, there is an increase in the real power of the secondary load when compared to the primary load. The real power of the primary load is 8.8 MW and that of the secondary load is 9.51 MW with the primary line operating at 110 and secondary line operating at 110 15 kV 30 kV as shown in Figure 5.13. By controlling the phase angle, the flow of real power between lines having equal input voltages can be controlled. 121 a b Figure 5.13 Real power of the primary load and the secondary load a. Real power of the primary load b. Real power of the secondary load 5.2.3 Model of the IPFC in a Four-Bus Test System In this section, we illustrate the proposed IPFC dispatch strategy for maximizing the voltage stability limited power transfer in a four-bus test system. Perhaps the most common approach in the voltage stability analysis is to increase the system loading Pload and observe the resulting voltage variation V on the critical buses. The analysis is frequently presented in the form of Power Voltage (PV) curves, which are now being used in many power control centers. To generate consistent PV curves, we modify the IPFC control strategy slightly by enforcing the desired circulating power Pc at all operating conditions, regardless of whether the VSCs are at their rated capacities or not. That is, if both VSCs are below their rated capacities, then, besides requesting 122 a specific power circulation level, the series VSCs will regulate the line active power flows. The reactive power flow is no longer enforced. The four-bus test system shown in Figure 5.14 has two equivalent generators and two equal amounts of loads at bus2 and bus4. Figure 5.14 The four-bus test system From the reference Xuan Wei et al (2004), there are two transmission paths with line 3-4 weaker than line 1-2 (stronger line 1-2 and weaker line 3-4). An IPFC is sited at bus 1 with each VSC on one of the parallel lines on the two transmission paths. It is noted that by closing the switches A and B, the IPFC is bypassed, which is referred to as the uncompensated system. The IPFC is in service if switches A and B are opened. By increasing the loads Pload1 at bus 2, Pload2 at bus 4 and the necessary amount of generation at bus 1and bus 3, we can investigate the variation of voltage V2 at bus 2 and V4 at bus 4, with and without the IPFC. Note that a positive Pc denoted that power is circulating from VSC2 on line 34 to VSC1 on line 1-2. 123 5.2.3.1 Model of the closed loop IPFC with variations in the firing angle of VSC1 The single-phase four bus closed loop IPFC system has been simulated in MATLAB Simulink, using the power system toolbox as shown in Figure 5.15. Switches A and B are opened for the time period of 0.3 sec to 0.6 sec. Then the IPFC is in service during the above mentioned time period, which is referred to as the compensated system. Switches A and B are closed for the remaining time period; the IPFC is bypassed, which is referred to as the uncompensated system. By increasing the loads at bus 2 and bus 4, we can investigate the variation of the output voltage and real power at bus 4, with and without the IPFC. The electrical data of the system used in the present work is as below: Generator 1 & 2 : 15.7kV Transformer : 15.7/ 400 kV, 1000MVA, r=0.0059p.u., l = 0.127 p.u. Series transformer : 3/ 45 kV, 160 MVA, r = 0.005p.u., l = 0.06 p.u. Transmission line : r = 3.2 / 100km, l = 103 mH/100km, c = 1.1 F/ 100km Continuous i - + pow ergui T2 T1 1 2 Z1 i 1 Z2 1 2 V ZL1 ZL3 2 T3 V1 PQ + v - I Vo3 p,q Scope1 T1 Conn1 Out2 Conn2 Subsystem3 Conn2 Conn1 Conn4 Conn3 In1Out1 Subsystem1 1 Subsystem 2 T4 + i - z2 V i1 z1 PQ I 1 1 2 ZL2 2 V2 + v - p1,q1 Scope2 Vo T6 T5 Conn1 Out2 Conn2 Subsystem2 124 Figure 5.15 Circuit model of the closed loop IPFC system with changes in the firing angle of VSC1 125 Without the IPFC, the output of the stronger line is 2.1*(108) W and 2.8*(108) VAR and the output of the weaker line is 2.0289*(108) W and 2.7098*(108) VAR, which are shown in Figures 5.16 and 5.17 respectively. 8 3 x 10 P(w) 2 a 1 0 0 0.1 0.2 0.3 0.4 0.5 Time(s) 0.6 0.7 0.8 0.9 1 8 3 Q(var) b x 10 2 1 0 0 0.1 0.2 0.3 0.4 Time(s) 0.5 0.6 0.7 0.8 Figure 5.16 Real power and reactive power of the stronger line a. Real power of the stronger line. b. Reactive power of the stronger line. 8 3 x 10 P(w) 2 a 1 0 0 0.1 0.2 0.3 0.4 0.5 Time(s) 0.6 0.7 0.8 0.9 1 0.1 0.2 0.3 0.4 0.5 Time(s) 0.6 0.7 0.8 0.9 1 8 b Q(var) 3 x 10 2 1 0 0 Figure 5.17 Real power and reactive power of the weaker line a. Real power of the weaker line. b. Reactive power of the weaker line 126 The subsystem of the closed loop controlled IPFC system with firing angle changes in VSC1 is shown in Figure 5.18. A reference signal is compared with a ramp signal, and its output is given as pulse to switches of the converter. The firing angle of the pulse generators in VSC1 is varied, and the corresponding variations in real power and output voltage are observed for different loads. As referred from the reference [43], Xuan Wei (2004), the power was exchanged from VSC1 to VSC2 or vice versa. By increasing the power circulation from VSC1 to VSC2 for the load considered in the range of 600 MW to 800 MW, reactive power is taken from the stronger line 1-2 and injected into the weaker line 3-4, allowing a higher voltage at bus 4. Conversely, the load is considered in the range of 800 MW to 950 MW, by increasing the power circulation from VSC2 to VSC1, bus 4 voltage is decreased and bus 2 voltage is raised. 127 Timer g m 1 2 Timer1 g m 1 2 Ideal Switch Ideal Switch1 T5 T7 P5 P6 S1 1e-06 + - Conn3 4 R2 Conn4 m 2 m 2 V1 v 3 S2 g a g a S5 S7 g 1 m k m k g 1 1 Conn1 T3 T6 + v - T4 P8 g 1 V8 g 1 P7 S6 S3 S4 m 2 g a m 2 g a S8 m k m k T8 T2 2 R1 T1 Conn2 + v - V4 P3 P1 AND AND 1 LO2 Scope2 LO1 >= P11 P2 AND AND LO3 LO 4 Figure 5.18 Subsystem of the closed loop IPFC with changes in the firing angle of VSC1 For the load considered in the range of 600 MW to 800 MW, the real power flows from VSC1 to VSC2 and the output power variations in the weaker line 3-4 are as shown in Figure 5.19. For the load considered in the range of 800 MW to 950 MW, the real power flows from VSC2 to VSC1 is as shown in Figure 5.20. 128 Figure 5.19 Real power in the weaker line for 650 MW load Figure 5.20 Real power in the weaker line for 900 MW load The change in real power for various loads from 600MW to 950MW with the change in power (Pc) is shown in Figure 5.21. The change in the output voltage for various loads from 600MW to 950MW is shown as power voltage curve in Figure 5.22. 129 Figure 5.21 Change in the real power of the weaker line Figure 5.22 Power voltage curve of the weaker line 5.2.3.2 Model of the closed loop IPFC with variations in the firing angle of VSC2 with reference to the sending end voltage The model of the closed loop controlled IPFC system with firing angle variations in VSC2 taking sending end voltage as reference is shown in Figure 5.17, and the subsystem is shown in Figure 5.23. A reference signal is compared with a ramp signal, and its output is given as pulses to the switches of the converter. The firing angle of the pulse generators in VSC2 is varied 130 and the corresponding variations in the reactive power & output voltage of the weaker line are observed for different loads. Timer g m 1 2 Timer1 g m 1 2 Ideal Switch Ideal Switch1 P2 T10 T9 P1 4 S1 g 1 3 S2 m 2 g a g a S5 S7 Conn3 R2 m 2 m k m k g 1 Conn4 1 C 2 T3 V8 T11 g 1 m T12 + v - T4 Conn2 S3 S4 m 2 g a g g 1 m k S6 T8 m 2 + - k v Conn1 a V1 T2 P4 R1 T1 + v - P3 V4 P7 P5 AND AND 1 Scope3 LO2 LO1 >= P8 Scope2 P6 AND AND LO3 LO4 Figure 5.23 Subsystem of the closed loop IPFC with changes in the firing angle of VSC2 taking the sending end voltage as reference The reactive power variation in the weaker line 3-4 with a load in the range of 600 MW to 750 MW is shown in Figure 5.24. It is observed that 131 the reactive power increases from 1.6858*(10^8) VAR to 1.8934*(10^8) VAR, and voltage increases from 1.631*(10^4) V to 1.73*(10^4) V. Thus, there is a reactive power flow from VSC1 to VSC2. Figure 5.24 Reactive power in the weaker line for 650 MW load For the load considered in the range of 800MW to 950 MW, the reactive power variation in the weaker line is shown in Figure 5.25. It is observed that the power decreases from 1.92*(10^8) VAR to 1.89*(10^8) VAR and voltage decreases from 1.87*(10^4) V to 1.73*(10^4) V. Thus, there is a reactive power flow from VSC2 to VSC1. Figure 5.25 Reactive power in the weaker line for 900 MW load 132 The change in the output voltage for the loads considered in the range of 600MW to 950MW, with the change in reactive power (Qc) for bus 4 is shown in Figure 5.26. Figure 5.26 Change in the reactive power of the weaker line 5.2.3.3 Model of the closed loop IPFC with variations in the firing angle of VSC2 with reference to the receiving end voltage The model of the closed loop controlled IPFC system with firing angle changes in VSC2, taking the receiving end voltage as reference is shown in Figure 5.17, and the subsystem is shown in Figure 5.27. A reference signal is compared with a ramp signal and its output is given as pulse to the switches of the converter. The firing angle of the pulse generators in VSC2 is varied, and the corresponding variations in the reactive power and output voltage of the weaker line are observed for different loads. 133 Timer g m 1 2 T imer1 Ideal Switch g m 1 2 Ideal Switch1 P4 P3 T10 1 g 3 4 Conn3 Conn4 2 2 m S2 m a S1 g a g S5 S7 1 g k m k m T9 1 C 2 T3 1 g R2 S3 m m S4 a g 1 g k S6 S8 2 k m V8 T 11 T12 g + v - T4 Conn2 2 + - m v Conn1 a V1 T2 T1 P5 R1 P13 + v - V4 0 0 >= 1 Constant >= Constant1 2 -1 In1In3 Product1 In2 3 >= Product >= P9 P1 AND AND ramp ramp LO2 LO1 Figure 5.27 Subsystem of the IPFC with changes in the firing angle of VSC2 taking the receiving end voltage as reference For a load of 650 MW, the reactive power output in the weaker line is shown in Figure 5.28. It is observed that the power increases from 1.97*(10^8) VAR to 1.99*(10^8) VAR, and the voltage increases from 1.7*(10^4)V to 1.73*(10^4) V. Thus, there is a flow of reactive power from VSC1 to VSC2. Figure 5.28 Reactive power in the weaker line for 650 MW load 134 5.3 CONCLUSION The IPFC is simulated for the compensation and power flow management of the multiline transmission system. In the IPFC structure, the converters are linked together at their DC terminals. Each inverter can provide a series reactive compensation, as an SSSC, for its own line. However, the converters can transfer real power between them through their common DC terminal. This capability allows the IPFC to provide both real and reactive compensation for some of the lines and thereby optimize the utilization of the overall transmission system. In particular, the IPFC can equalize both real and reactive power flow in the lines, relieve the overloaded lines from the burden of the reactive power flow, compensate against resistive as well as reactive voltage drops, and provide a concerted multiline counter measure during dynamic disturbances. A new dispatch strategy for an IPFC operating at the rated capacity is proposed. When the IPFC operates at its rated capacity, it can no longer regulate the line active power flow set point or the reactive power flow set point or both. In such cases, the dispatch strategy switches to a power circulation set point control to co-optimize both series VSCs, without exceeding one or both rated capacities. The dispatch results show that the IPFC can improve the power transfer in the system. The power circulation between the two VSCs can be used to adjust bus voltages to improve the voltage stability limit transfer. The simulation results are in line with the predictions. The IPFC is capable of balancing the power through the lines. The power quality is improved since the IPFC permits additional power. The circuit models for the IPFC system are developed using MATLAB. These models are used for simulating a four bus system. The simulation results using MATLAB are presented. The IPFC increases the real power transfer and improves the voltage profile.