M Low Voltage Expert Guides N° 3 Low voltage switches M O OFF I ON OFF O OFF ON OFF O I interpact O ON I interpact INS250 Ui 500V Uimp 6kV INS250 Ui 500V Uimp 6kV Ue(V AC22A 500 80 Ue(V AC22A 500 80 IEC 947.3 UTE VDE BS CEI IEC 947.3 UTE VDE BS CEI O push OFF MERLIN GERIN I masterpact push ON M32 H1 Ui 1000V 50/60Hz Ue 380/440V 480/690V Icu 100kA 85kA Ics 100kA 85kA Icw 75kA 1s O OFF discharged IEC 947-2 00000 .4 .2 .1 connected test M disconnected MERLIN GERIN MERLIN GERIN multi 9 TEST MENSUEL ON 63AID n 0,030A 230Va I ON interpact IDsi OFF O -25 OFF N 1 N 2 T INS80 Ui 500V Uimp 6kV Ith 80A@ 60°C Ue( Ie(A AC22 50 8 AC23 44 8 AC23 50 6 DC23 25 6 I OFF O IEC 947.3 UTE VDE BS CEI 23318 E58422 M M M M M M M M M Contents 1. Electrical switchgear ................................................................. 3 1.1 Functions performed by electrical switchgear .................................... 3 1.2 Functions performed by the switch ..................................................... 3 2. The switch .................................................................................. 4 2.1 Switches in LV distribution .................................................................. 4 2.1.1 Switch applications ............................................................................ 5 2.1.2 Market values .................................................................................... 5 2.2 Main functions ...................................................................................... 6 2.2.1 Functions applicable to all switches ................................................. 6 2.2.2 Specific functions ............................................................................... 9 2.2.3 Summarising table .......................................................................... 11 3. Switch standards ..................................................................... 12 3.1 General .............................................................................................. 12 3.2 Normal standard values for domestic switches (IEC 60669-1) ....... 12 3.3 Normal standard values of industrial switches (IEC 60947-3) ........ 13 3.3.1 The definitions ................................................................................. 13 3.3.2 Standard usage values ................................................................... 13 3.3.3 Utilisation categories ....................................................................... 14 3.3.4 Suitability for isolation ..................................................................... 14 3.3.5 Electromagnetic Compatibility (EMC) ............................................ 17 3.3.6 Test Sequences ............................................................................... 17 4. The Schneider Electric choice ............................................... 19 4.1 The Schneider Electric technical choices ......................................... 19 4.1.1 Isolation ........................................................................................... 19 4.1.2 Front face class II ............................................................................ 21 4.1.3 "Emergency stop" control ................................................................ 21 4.1.4 The switch is an environmentally-friendly product .......................... 21 4.2 Installing switches: the "Schneider Electric" system ........................ 22 4.2.1 The installation system .................................................................... 22 4.2.2 Consistency of the circuit-breaker/switch ranges ........................... 24 4.2.3 Positioning the offer by applications ............................................... 26 4.3 Choosing a Schneider Electric switch .............................................. 27 4.3.1 Choice criteria ................................................................................. 27 4.3.2 Location and application table ........................................................ 28 4.3.3 The switches available in the Schneider Electric offer ................... 29 4.3.4 Switch range technical data ............................................................ 30 1 Contents (cont.) 5. Additional technical information ........................................... 31 Characteristic tables ................................................................................ 32 Switch-disconnectors selection ............................................................... 34 Interpact INS40 to 160 ............................................................................. 34 Interpact INS250 ...................................................................................... 36 Interpact INS320 to 630 ........................................................................... 38 Interpact INV100 to 250 with visible break ............................................. 40 Interpact INV320 to 630 with visible break ............................................. 42 Interpact IN1000 to 2500 ......................................................................... 44 Switch-disconnectors ............................................................................... 46 Compact ................................................................................................... 46 Compact CM ............................................................................................. 50 Masterpact ................................................................................................ 52 Co-ordination ............................................................................................ 56 Modular switches and residual current circuit-breakers .......................... 56 Upstream: circuit-breakers or fuses / Downstream: modular switches ... 57 Upstream: fuses or circuit-breakers / Downstream: modular residual ... 58 current circuit-breakers Upstream: NS100/160 / Downstream: Multi 9 circuit-breakers ............... 59 Industrial switch-disconnectors ................................................................ 60 Protection of switch-disconnectors ........................................................... 62 2 In short Electrical Switchgear 1.1 Functions performed by electrical switchgear National and international standards define the method for making electrical distribution circuits as well as the purpose and functions of switchgear. There are three main functions, namely: ■ circuit protection takes three main fault types into account: ❏ overloads, ❏ short-circuits, both of which adversely affect the lifetime of cables and loads, ❏ insulation faults, harmful for persons and equipment. ■ isolation is used to separate a circuit or a device from the remainder of the installation to allow 100% safe operation, ■ control allows the user to take voluntary action on installation operation: ❏ when such action takes place in normal operating conditions (on load, with no overcurrent) in order to energise or de-energise all or part of the installation, control is said to be “functional”, ❏ when such action is essential (whatever the load condition of the installation) in order to immediately de-energise all or part of the installation, control is said to be of the “emergency stop” kind. Three main functions: ■ protection, ■ isolation, ■ control, of electrical circuits. The switch is used for: ■ control, ■ often isolation. For protection it must be combined with: ■ a circuit-breaker, ■ fuses, ■ a residual current device (if necessary). Switchgear Fuse Disconnector Switch Disconnector - fuse Switch - fuse Contactor Circuit-breaker Functions perfomed Protection Overloads ■ (3) A variety of switchgear perform all or some of these three main functions. The following table situates the role of the main switchgear: Isolation Shortcircuit Control Insulation fault ■ ■ ❏ (1) (2) ❏ ■ ■ ■ ■ ■ ■ ❏ (1) (2) ❏ ■ ■ ■ ❏ (2) ❏ ■ ■ Table A ■ Basic function of the switchgear considered (always performed). (1) Possible with a switch with automatic opening. ❏ Additional function possible (not always performed). (2) Possible with addition of a "Residual Current Device (RCD)". (3) gG fuse only 1.2 Functions performed by the switch The switch is mainly: ■ a control device: ❏ control is normally manual, ❏ it can be electrical on opening (we then talk of a switch with automatic opening), ❏ able to break and make a circuit on-load. It does not need any energy to remain open or closed (2 stable positions). ■ for safety reasons, the switch is often equipped with a suitability for isolation function, ■ the switch must always be used in coordination with an overload and shortcircuit protection device. 3 The switch E58423 2.1 Switches in LV distribution coupling switch industrial power distribution switchboard tertiary power distribution switchboard 15 -40 kA ≤ 1000 A 20 -80 kA ≤ 1600 A replacement source modular product subdistribution switchboard industrial distribution switchboard ≤ 160 A ≤ 160 A : 15 - 25 kA ≤ 400 A : 20 - 80 kA 15 - 25 kA local isolation enclosure local isolation enclosure small tertiary distribution enclosure ≤ 10 kA ≤ 63 A automation cubicle source changeover switch local isolation enclosure automation enclosure ≤ 25 kA ≤ 10 kA ≤ 63 A ≤ 125 A ≤ 630 A M M ≤ 15 kA ≤ 5 kA ≤ 40 A M M NB: immediately beside the machine or built into the machine building utilities building final distribution continuous process Figure 0: Diagram showing a standard installation covering most of the cases observed in real life. 4 individual machine manufacturing process M In short 2.1.1 Switch applications Switches are characterised by market values taking into account: ■ 6 applications, ■ the installation method, ■ user habits such as type of isolation: with visible isolation or positive break indication. These market values induce choices of technology and reference standards. 052384 E35050 Coupling ■ Local or subdistribtion isolation switch for Tertiary Building applications: These switches are of the industrial type and are installed in subdistribution switchboards or industrial enclosures. They comply with standard IEC 60947-1,-3 (1) and can have a modular profile. Suitability for isolation and electrical data defined for utilization categories greater than or equal to AC 22 are vital functions. ■ Local or subdistribtion isolation switch for Domestic Building applications: These switches comply with standard IEC 60947-1,-3 (1) or IEC 60669-1(1). Suitability for isolation is an essential function. Earth leakage protection is an additional function that is often requested. ■ Local or subdistribution isolation switch for industrial applications of the Continuous Process type: These switches, of the industrial type, comply with standard IEC 60947-1,-3 (1) and can have a modular profile. They can occasionally control motors and perform the “emergency stop” function. Suitability for isolation is an essential function. 041625 ■ Subdistribution isolation switch for industrial applications of the Manufacturing Process type: These switches, of the industrial type, comply with standard IEC 60947-1,-3 (1). They can have a modular profile and perform the “emergency stop” function. Suitability for isolation is an essential function. ■ Thermal withstand General functions 052164 ■ isolation ■ on-load opening ■ safety ■ Local isolation switch for industrial applications of the Manufacturing Process type: These switches, of the industrial type, comply with standard IEC 60947-1,-3 (1) and can have a modular profile. Suitability for isolation is an essential function. In some utilisation cases they can perform: ❏ the “emergency stop” function, ❏ direct control of motors. 2.1.2 Market values 053419 E29925 Local isolation 054361 Entified, namely: ■ Power switchboard isolation and coupling switch: These switches are of the industrial type and are installed in power or subdistribution switchboards in tertiary or industry. They comply with standard IEC 60947-1,-3 (1). Suitability for isolation and a high thermal withstand (particularly for the coupling function) are vital functions. ■ direct motor control ■ emergency stop Figure 1b: Functions table According to its position in the installation, its application and assembly in the installation system, the switch must meet certain market values in terms of: ■ adaptability to installation systems, ■ standard requirements (installation). Market values must also be considered, relating to habits such as: ■ operating handle types (front, side, etc.), ■ accessory level, ■ assembly habits, ■ visible isolation, or other habits linked to operator safety such as: ■ rapid identification of the isolation device in the middle of other devices, ■ robustness appearance of switchgear performing the on-load circuit control and isolation function, ■ etc. The summary of applications and market values leads us to consider the functionalities listed in the table opposite. (1) As from the beginning of 1998 IEC standards have received new numbering in IEC 60xxx. However their content remains the same. 5 In short 2.2 Main functions 2.2.1 Functions applicable to all switches Suitability for isolation is an important function that the switch must possess. 2.2.1.1 Standards To satisfy the previous applications, two technologies are available: ■ industrial type switches for industrial and tertiary applications, ■ industrial type switches for domestic applications. On-load breaking is a natural function of the switch. The reference standards for switches are: ■ in industry and the tertiary sector: ❏ standards IEC 60947-1 and IEC 60947-3 / European standards EN 60947-1 and EN 60947-3. ■ in domestic applications: ❏ standard IEC 60669-1. The additional safety, emergency stop and earth leakage protection functions are accessible to switches. 2.2.1.2 Isolation Operation of an electrical installation requires the possibility of working with power off on all or part of this installation in order to perform maintenance and servicing or to make modifications. ■ Padlocking a feeder Installation standards define the compulsory feeder padlocking operations to guarantee safety of the operations. Switchgear separating the relevant feeder must be recognised as “suitable for isolation” and possess a locking system in the "open" position. ■ Position of isolation in the installation An isolation device must be installed at the origin of each circuit distribution point in order to ensure optimum continuity of supply ("incoming end" of the enclosure/ subdistribution cubicle). 2.2.1.3 Switch/disconnector E58482 Some switches perform this function in addition to their circuit control function. They are then switches/disconnectors whose symbol, shown opposite, must be clearly shown on the front face of the device installed. MERLIN GERIN interpact INS 250 kV IEC 947.3 Ui 750V Uimp 8kV Ith 250A 60°C AC22A Ue(V) 690 Ie (A) 250 A 690 250 IEC 947.3 CEI UTE UNE VDE BS CEI UTE AC23A DC23A (2/4PS) BS UNE VDE 500 690 250 250 125(2P) 250(4P) 250 (2/4PS) 250 DC23A 125(2P) 250(4P) 250 250 Figure 2: Marking a switch suitable for isolation The “isolation” function is performed in 2 ways: ■ visible isolation, ■ positive break indication. The industrial switch construction standard IEC 60947-3 defines the rules and the tests to be performed to guarantee this function (see section 3.3.4). 6 ■ Suitability for isolation Isolation is explicitly defined and recognised by standard IEC IEC 60947-1-3 for industrial type switches/disconnectors. A switch/disconnector complying with this standard for the isolation function unconditionally meets the additional tests and requirements of the installation standards. ■ Implementation and utilisation precautions Switchgear suitable for isolation must: ❏ have multi-pole breaking, i.e. the live conductors, including the neutral (except for the PEN conductor that must never be broken) must be able to be simultaneously broken, ❏ be lockable in the “open” position in order to avoid all risk of accidental reclosing, essential on industrial type devices, ❏ be able to meet overvoltage withstand conditions. Before working on the part of the installation downstream of a switch/ disconnector, the user must: ❏ open the switch, ❏ then, in all cases, compulsorily check absence of power, (if the switch has visible isolation, see section 334 of the Standards - suitability for isolation), ❏ check contact opening. ■ Choice of isolation Choice of isolation mode depends on: ❏ market habits, ❏ switch rating. The manufacturer must: ❏ propose safe, reliable solutions guaranteeing customer safety, ❏ ensure the best possible value (quality and performance) for money. ■ Comparison of the 2 isolation types The table below summarises the advantages and drawbacks of each solution. Isolation mode Handle position Operating guarantee Possible checks (1) With positibe break indication Mechanical test By the manufacturer Handle position, position clearly identified With visible isolation No testing demanded(1) By the operator Visual: ■ problem of legibility ■ problem of interpretation in the strict sense of the standard Table B 2.2.1.4 On-load breaking The operator must be able to safely and easily put his electrical installation out of operation regardless of load conditions. For switches, on-load breaking is essential and tests are required by standard IEC 60947-3. Switch electrical performance depends on its position in electrical distribution: Type of current to be controlled: The utilization categories defined by standard IEC 60947-3 specify the various requirements to be met according to the circuits to be controlled. ■ When the switch is installed at a high upstream level in LV distribution, the loads supplied are numerous and mixed: the current to be controlled is of the inductive type. Utilization category AC22 is recommended for this type of switch. ■ When the switch is installed at the incoming end of the distribution enclosure (or cubicle), the loads supplied may be not very inductive (power supply, lighting, convector, etc.). Utilization category AC21 is sufficient for this type of application. However, the same type of enclosure can be used to supply a mixed installation with motors: utilization category AC22 is then necessary. To simplify the choice and guarantee proper operation, whatever application is performed, utilization category AC22 is always recommended at this level. ■ When the switch is placed directly on a motor feeder and used as a control device, it must meet: ❏ a utilization category AC23, if control is occasional (normal control by a contactor), ❏ a specific utilization category AC3, if the switch is the main motor start-up and stopping device. 7 E62416 Number of operation The nearer the switch to the loads, the greater the number of operations. A suffix attached to the utilization category -A (frequent operations) or B (infrequent operations) defines operation frequency. In electrical distribution, the number of operations to be performed is never very great (a few thousand). 2.2.1.5 Additional safety functions Additional functions are often requested for switches ensuring local and subdistribution isolation. MN release ■ The “emergency stop” control This is performed in 2 ways: ❏ remotely by an emergency pushbutton either by a contactor or by a switch with automatic opening. The controlled switch is installed in a switchboard or enclosure in standard manner. It is necessarily equipped with an automatic tripping device and, in many cases, with auxiliary indicating contacts, ❏ directly by means of a switch. Safety regulations and/or installation standards specify that in this case the device must be easy to identify and access. Identification is based on choice of colours: - operating device (red handle), - front face (yellow front plate). Pushbutton emergency stop 052967 ■ Insulation fault protection Insulation fault protection can be provided by a Residual Current Device (RCD) associated with or incorporated into a switch depending on the application in question. ❏ Subdistribution switchboard isolation switch The RCD is associated with a controlled switch (with automatic tripping). The RCD provides protection of persons (indirect contacts) and protection against fire. It must be selective with the downstream RCDs. ❏ Final distribution switchboard and enclosure isolation switch The RCD is built into the switch and is normally dedicated to a single protection function: persons (direct contact), fire, etc. 053419 INS switch: local emergency stop ID si 2P 63 A 30 mA. Residual current circuit-breaker 8 NB: In all cases, the chosen switchgear will be able to break overloads and abnormal currents, thus excluding from this function devices only of the disconnector type. In short 2.2.2 Specific functions 2.2.2.1 The coupling function Depending on the position of the switch in the LV installation and on the operator’s specific needs, the coupling function can be automatic or manual. E62417 Switches can be used to perform: ■ coupling functions, ■ local isolation and disconnection functions. In this case they have specific features. 1600 A 1600 A coupling switch 80 kA - 1 s E62418 Figure 4a: Coupling the network at main LV board level main source replacement source floor subdistribution switchboard source changeover switch Automatic coupling ■ This function is normally built into the “source changeover” function (e.g. 2 sources and 1 coupling). Should one of the sources fail, the loads are automatically coupled to the second source. This is performed at the supply end of LV distribution. ■ This function is mainly found in the main LV switchboard or the incomers of the subdistribution switchboard (see fig. 4a and 4b). ■ Specific features The switches are located near the sources: the lsc are high (from 30 to 80 kA). Time discrimination is often used: the fault currents are not limited. This results in a need for high withstand performance in short-circuit conditions: ❏ thermal stress withstand: the main LV switchboard specifications may impose a withstand of 80 kA - 1s for a busbar in a 3000A main LV switchboard, ❏ making capacity lcm: the coupling may close and make a high short-circuit current. Switchgear has a motor mechanism. An electrical and mechanical interlocking with the other source changeover switch components is necessary. NB: When this function is combined with the automatic source changeover function, it can be performed by circuit-breakers with only instantaneous protection to limit stresses on the installation in event of closing on a short-circuit. Manual coupling ■ This function is normally used to couple: ❑ a set of loads on an emergency network, ❑ a set of loads on a moving generator. The switch manually and locally performs the transfer to the emergency replacement network. This load transfer is occasional and programmed. ■ This function is mainly found on the incomers and feeders of the subdistribution switchboards (see fig. 4c). ■ Features: switches are at the heart of distribution: ❑ they are normally protected by limiting type circuit-breakers, ❑ occasional, voluntary coupling considerably limits the risk of anomalies (particularly during coupling). The switch has standard features and is of the manual type. Device interlocking is necessary. Table summarising the coupling function Technical data E62419 Figure 4b: Coupling a high-rise building replacement/standby network GE moving generator set Figure 4c: Manual coupling on high-rise building moving GE Electrodynamic withstand icw (A rms) Making capacity Icm (A peak) Control: motor manual Utilization category On-load breaking Interlock Assembly Standards 800 A 800 A to 2000 A to > 3000 A 40 kA 2000 A 35 kA for 1s 75 kA 3000 A 50 kA for 1s 105 kA 85 kA for 1s 187 kA ❑ ■ (1) AC22 vital AC23 important Yes Yes Industrial switchboard IEC 60947-3 ■ ❏ AC22 vital AC23 important Yes Yes Industrial switchboard IEC 60947-3 ■ ❏ AC22 vital AC23 important Yes Yes Power switchboard IEC 60947-3 ■ ❏ AC22 vital AC23 important Yes Yes Power switchboard IEC 60947-3 20 kA Table C ❑ possible, ■ recommended. (1) as soon as coupling is local. Masterpact type switches. 9 2.2.2.2. The motor "isolation" function When a “motor circuit” is supplied and protected from a centralised power supply to guarantee safety and simplify maintenance, a local control and isolation device is frequently required. These functions are performed by a separate device known as a “local isolation enclosure” containing an on-load breaking switch. Switch features n In most cases, motor control is performed by a contactor. The switch only performs “occasional” control of the motor: utilization category is AC23. n For some small motors (< 18.5 kW), the switch may be considered to be the main control device of the motor: utilisation category is AC3. 052384 ■ Industrial switches used mainly in tertiary and industrial power switchboards. They comply with standard IEC 60947-3 and are for example Interpact or Masterpact type switches. E35050 n Additional functions: the switch function is completed by locking in the “open” position to ensure safe maintenance of the feeder. This switch can also be used as an emergency stopping device (red front plate, yellow handle). 1000 3P Interpact IN switch 10 E52164 ■ Modular profile industrial switches used mainly in subdistribution switchboards. They comply with standard IEC 60947-3 and are switches of the INS type. E56650 Masterpact NI NA (63 A) 4P Interpact INS63 switch 4P Interpact INV160 switch 2.2.3 Summarising table Main usage values Power Industrial Subdistribution Small tertiary Automationn Local isolation according to applications distribution switchboards switchboards distribution enclosures enclosures switchboard & automation (modular enclosures cubicles products) 400 to 2500 A 40 to 400 A 20 to 160 A ≤ 63 A ≤ 40/63 A 10 to 630 A yes yes yes essential essential essential by positive contact indication or visible isolation yes essential yes essential yes essential essential essential essential important not very important 20 to 80 kA essential essential important important important ■ I ≤ 160 A : 15 to 25 KA ■ I ≤ 400 A : 20 to 80 kA important not very important essential not very important not very important 10 kA important essential essential important important 3 to 5 kA essential essential important essential essential ■ I ≤ 63 A : 15 kA ■ I ≤ 630 A : 25 kA essential important not applicable essential important not applicable Current range LV switch basic functions Circuit on-load control Isolation Padlocking the isolated status Other usage values Padlocking Handle rotary direct front front extended side extended Maximum short-circuit level Type of controlled circuit (1) AC21A AC22A AC23A AC3 Mounting system front and mounting plates for functional enclosures universal mounting plates 45 mm tip symmetrical rail essential essential essential important not very important ■ I ≤ 63 A : 15 kA ■ I ≤ 160 A : 25 kA essential important not very important not applicable essential important not very important essential not applicable not applicable essential ≤ 40/63A essential > 63 A rare ■ ■ ■ ■ ■ ■ ■ Table D 053419 ■ Local control and isolation switches used for direct control of frequently operated loads. They comply with standard IEC 60947-3 with an AC23 or AC3 utilization category depending of their rating and the application. They are installed on a door or at the back of the cubicle. They are Vario type switches. 054361 ■ Modular type switches used mainly in subdistribution switchboards and distribution enclosures. They comply with standard IEC 60669-1 and are Multi 9 type switches. E29925 (1) See section 3.3.3. “Utilisation categories”. NG 125 NA E56385 ID si bi 63 A 30 mA E31913 Vario (VCF-O) Vario (VBF-OGE) 056652 400 A 4P Interpact INS switch Red/yellow INS250 11 In short Switch Standards The switch must comply with: ■ standard IEC 60669-1 for domestic applications, ■ standards IEC 60947-1 and 60947-3 for tertiary and industrial applications. These standards specify the main technical data of the switches: rated currents and voltages, utilisation category, etc. Standard IEC 60947-3 completely defines the suitability for isolation of industrial switches. 3.1 General Low Voltage switchgear standards lay down all the general common and specific requirements and measures. They particularly specify: ■ equipment definitions, ■ its technical data, ■ information on the equipment, ■ normal operating, assembly and transportation conditions, ■ construction and operating specifications, ■ tests. The switches comply with standards (1): ■ IEC 60947-1 (general requirements) and IEC 60947-3 (specific switch requirements) for industrial switches, ■ IEC 60699-1 for domestic switches. 3.2 Normal standard values for domestic switches (IEC 60669-1) ■ Rated voltages and currents ❏ rated voltage: preferably 130 V, 230 V, 250 V, 277 V, 400 V, 415 V, 440 V, ❏ rated current: preferably 6 A, 10 A, 16 A, 20 A, 25 A, 32 A, 40 A, 63 A. ■ Breaking capacity The standard stipulates a “suitable breaking capacity”. This conformity is verified by a test depending on rated voltage and current as given below. Switch type Rated voltage Ue ≤ 250 V > 250 V Current voltage Ie ≤ 16 A > 16 A Test characteristics Test voltage k1 x Ue 1,1 1 Test current k2 x Ie 1,25 1,2 Table E The standard stipulates 200 breaks at cos ϕ = 0.3 with rates specified according to rated current. ■ Normal operation Switches must withstand the following number of operations, for their rated voltage and current: Rated voltage ≤ 250 V > 250 V All voltages All voltages Rated current ≤ 16 A ≤ 16 A 16 A < Ie ≤ 40 A > 40 A Operations 40 000 20 000 10 000 5 000 Table F ■ Suitability for isolation Standard IEC 60699-1 does not give any recommendations regarding visible isolation or positive break indication. The tests required are also less demanding than for industrial switches: ❏ for dielectric testing, a 50/60 Hz voltage of between 2000 V and 4000 V (depending on application point) is applied for 1 minute. A check is run to ensure that the insulation resistor retains a minimum value (2 to 5 MΩ according to the test), ❏ no impulse wave testing required. Moreover, the domestic switch test conditions match class AC22, see section 3.3.3. (1) IEC standards were renumbered in IEC 60xxx at the beginning of 1998, but their content remains the same. 12 3.3. Normal standard values of industrial switches (IEC 60947-3) The specifications and tests relating to each switchgear type include 2 documents: ■ the general requirements of standard IEC 60947-1, ■ the specific standard for the equipment considered. For switches, standard IEC 60947-3 completes, amends or replaces the specifications of the general requirements of standard IEC 60947-1. E58428 3.3.1 The definitions Figure 6: Switch The standard gives specific definitions, including those for: ■ The switch: a mechanical connection device: ❏ able to make, withstand and break currents in normal conditions, including overloads, ❏ able to withstand currents in abnormal conditions, such as short-circuits, for a specified period of time, ❏ able to break on no-load (with no load downstream). E58429 ■ The disconnector: a mechanical connection device: ❏ meeting the specifications for the isolation function in the opening position, ❏ able to withstand currents in normal conditions as well as currents in abnormal conditions, such as short-circuits, for a specified period of time. ■ The switch/disconnector: ❏ a switch meeting the specifications for the isolation function in the opening position. E58427 Figure 7: Disconnector 3.3.2 Standard usage values Figure 5: Switch/disconnector ■ Conventional thermal current, lth (A) The maximum current that a switch can permanently convey without excessive temperature rise. This value is associated with a utilisation temperature given by the manufacturer: e.g. lth = 400 A, lth = 25 A at 40°C. Normally lth = lu (lu = unbroken current). lth actually corresponds to the switch rating. ■ Short-circuit making capacity, lcm (A peak) The short-circuit current value that the switch can make, on closing on a shortcircuit, without being damaged. ■ Electrodynamic withstand (A peak) The maximum current, in peak value, that the main contacts can withstand without repulsion. e.g. 10 kA peak. This value must be taken into account for protection by circuit-breaker or fuse. This value is not a standard one. When it is not declared, it corresponds to the short-circuit making capacity (lcm). ■ Thermal withstand, lcw (A rms-s or in A2s) The overcurrent that the switch can withstand for a given time without being damaged. e.g. lcw = 3 kA rms for 3 seconds. ■ Rated operational current, le (A) The switch’s utilisation current, depending on the application (resistive or inductive circuit: see below section 3.3.3. “Utilization categories”). 13 3.3.3 Utilization categories The standard identifies three types of utilization categories: ■ AC21: resistive loads, ■ AC22: mixed loads, ■ AC23: inductive loads, ■ AC3: direct control of a single motor. As regards DC current devices, categories are respectively: DC20, DC21…, DC3, etc. A letter, A or B, is associated with each ACxy category, according to whether or not the device is designed for frequent switching operations: ■ A: frequent operations: from 2 000 to 10 000 operations (mechanical and electrical) as per rating, ■ B: non frequent operations: from 400 to 2 000 operations (mechanical and electrical) as per rating. 3.3.3.1 Table of rated operational currents Utilization categories Frequent Infrequent operations operations AC21A AC21B AC22A AC22B AC23A AC23B AC3 Technical data Applications Resistive loads, including moderate overloads (cos ϕ = 0.95) Mixed resistive and inductive loads, including moderate overloads (cos ϕ = 0.65) Squirrel-cage motors and other highly inductive loads (cos ϕ = 0.45 for Ie > 100 A) (cos ϕ = 0.35 for Ie ≤ 100 A) Squirrel-cage motors and other highly inductive loads (cos ϕ = 0.45 pour Ie > 100 A) (cos ϕ = 0.35 pour Ie ≤ 100 A) Final Distribution (excluding motor feeders) MV and Power Industrial Distribution with motor feeders Motor feeders, Occasional motor control (1) Direct main control of a single motor Table G (1) In this application case, the control is performed by a contactor. 3.3.3.2 Example A switch with a rating of 125A and category AC23 must be able to: ■ make a current of 10 ln (1 250 A) with a cos ϕ of 0.35, ■ break a current of 8 ln (1 000 A) with a cos ϕ of 0.35. 3.3.4 Suitability for isolation Standard IEC 60947-1 clearly defines the general rules governing suitability for isolation. Standard IEC 60947-3 specifies the requirements to be respected to perform the switch isolation function. These standards are based on: ■ the construction rules, ■ the tests to be performed. 3.3.4.1 The construction rules The construction rules stipulate (among others): ■ the clearances and the distances between open contacts (> 1mm/kV) or, if this is not the case, verification by sampling device withstand to voltage impulses, ■ presence of a device indicating the real position of the contacts (operating handle if its position is representative of that of all the contacts), ■ when an interlocking position is provided, the setting in the “interlocked” position must be possible only if the contacts are “open”. 14 3.3.4.2 Visible isolation or isolation with positive break indication Isolation can be achieved in two ways: ■ visible isolation, in which the operator directly views, through a transparent screen, the physical separation of the main contacts, ■ isolation with positive break indication: in this case a mechanical device guarantees that the position of the main contacts reflects the position of the handle. In other words, the switch handle must only indicate the open position if the main contacts are effectively separated. The standard defines for this a mechanical verification test (the “welded contact” test). The standard specifies that a switch suitable for isolation must be equipped with padlocking of the isolated status. The “interlocked” position must only be possible when contacts are “open”. 3.3.4.3 Tests to be performed E58426 E58425 Three specific tests must be performed: ■ Impulse wave withstand (Uimp)(1) Conditions are those defined by standard IEC 60947-1, i.e.: ❏ either a distance between contacts greater than that given for a nonhomogeneous field, ❏ or the withstand to an impulse wave whose level is defined according to the value Uimp declared by the manufacturer. The impulse wave withstand tests (1.2/50 µs wave), defined in IEC 60947-1, of a value Uimp variable according to the place of installation, are representative of lightning and switching overvoltages. They must be performed by the manufacturer if he announces a value for Uimp. U 0,9 Uimp 0,5 12,3 kV 0,1 0 t1 t2 1,2 Figure 9 - 1.2-50 voltage wave 50 tµs Figure 10 - Impulse wave withstand between the input and the output of a switch (1) All electrical installations can be subjected to occasional overvoltages with many causes such as: ■ lightning overvoltages, ■ switching overvoltages, ■ overvoltages due to a fault, ■ overvoltages further to an MV/LV flashover. The study of these overvoltages (origin, value, location, etc.) and the rules to be applied for protection, form the elements of insulation coordination. These studies recorded in standard documents define the voltage level Uimp to be applied to a device to ensure that it guarantees the safety of the de-energised part. 15 ❏ Voltage impulse withstand level Network voltage and the position of the switchgear in the electrical network determine the overvoltage levels to which electrical switchgear risk being subjected (table H1 of standard IEC 60947-1). Uses E58430 Rated voltage of the installation M At the incoming end of the installation/MSB On distribution and final circuits At the load level 230/400 V 6 4 2.5 400/690 V 8 6 4 Figure 11: Impulse voltage according to equipment location in an LV installation ❏ Example: - 8 kV at the origin of the installation for a 400 / 690 V network, - 6 kV at electrical distribution level for a 400 / 690 V network. Industrial switchgear can be used close to the origin of the installation. In this case the chosen technical data will be: - Uimp 8 kV, - Ui 690 or 750 V. ❏ Values of impulse wave withstand voltage for devices suitable for isolation with Uimp = 8 kV. Application of voltage Impulse voltage Impulse voltage between: (in kV) at 2000 m (in kV) at sea level Phases 8 Upstream/downstream 10 Phases/earth 8 9,8 12,3 (1) 9,8 Table H (1) 14.7 kV if the device is declared front face class II. ■ Measuring leakage current with the device open Test performed at 110% of device operational voltage. Maximum leakage currents accepted per pole: ❏ 0.5 mA on a new device, ❏ 2 mA on a device having been previously tested for: - general operating characteristics, - suitability for operation in service (mechanical and electrical durability), - making and breaking capacities. E58424 ■ Mechanical test “Verification of the robustness mechanism of the control device and of the position indication” or “welded contact tests”. This test is performed for devices declared suitable for isolation with positive break indication. With the contacts held in the closed position, the handle is subjected to a force F equal to 3 times the effort required to operate it (with a minimum value at 150 N and a maximum value at 400 N) for 10 seconds. While the force is being exerted, interlocking of the switching device must not be possible. After testing, when the handle is released, indication of the “open” position must not be inexact. 90° F Figure 8: Robustness testing of the control device 16 3.3.4.4 Marking switches suitable for isolation E58482 Switches complying with the stipulated construction rules and having successively passed all the tests described above are declared suitable for isolation. The symbol “switch - disconnector” (opposite) must appear on the front face and be visible once the device is installed. MERLIN GERIN interpact INS 250 kV IEC 947.3 Ui 750V Uimp 8kV Ith 250A 60°C AC22A Ue(V) 690 Ie (A) 250 A 690 250 IEC 947.3 CEI UTE UNE VDE BS CEI UTE AC23A DC23A (2/4PS) BS UNE VDE 500 690 250 250 125(2P) 250(4P) 250 (2/4PS) 250 DC23A 125(2P) 250(4P) 250 250 Figure 9: Switch - disconnector 3.3.5. Electromagnetic Compatibility (EMC) ■ Immunity: The mechanical connection devices are not affected by electromagnetic disturbances. No tests are required. ■ Emission: Disturbances can only be generated during electrical switching operations and are limited to switching overvoltages of a lower level than shock resistance. Consequently, emission specifications are considered to be satisfactory and no tests are required. 3.3.6. Test Sequences Besides the specific isolation aspect, standard IEC 60947-3 lays down sequence operating tests. Each sequence includes several tests and is used to verify part of the device characteristics. These operating tests are summarised in the table below. The operating mode of these tests results in consideration of real operating conditions, thus guaranteeing users that products really are suitable for operating conditions. Some information on standard IEC 60947-3: Test sequences Sequence 1 Sequence 2 Sequence 3 General operating sequences ■ temperature rise ■ dielectric ■ making and breaking capacity (in service) ■ dielectric ■ leakage current measurement (≤ 2 mA) ■ temperature rise ■ suitability for isolation test Suitability for isolation in service ■ mechanical and electrical durability ■ dielectric ■ leakage current measurement (≤ 2 mA) ■ temperature rise Suitability for short-circuit operation ■ measurement of the short time withstand current (Icw) ■ making capacity in short-circuit (Icm) ■ dielectric ■ leakage current measurement (≤ 2 mA) ■ temperature rise Table I These sequences are repeated on a number of samples in order to cover all the performances announced for the device. 17 The Schneider Electric choice Schneider Electric offers switch ranges of the Merlin Gerin and Telemecanique brands. These devices cover all the requirements of Low Voltage electrical power distribution, namely: ■ industrial switch/disconnector ranges meeting standard IEC 60947-1-3 from 12 to 6 300 A, ■ domestic switch/disconnector ranges meeting standard IEC 60669 from 1 to 125 A and in some cases standard IEC 60947-3, ■ switch/disconnector ranges for motor feeders meeting standard IEC 60947-1-3 from 12 to 175 A. The ranges of switches proposed: ■ are perfectly coordinated with the Schneider Electric protection devices, ■ fit perfectly into the Schneider installation systems, thus optimising their implementation, ■ are suitable for isolation. 18 In short 4.1 The Schneider Electric technical choices 4.1.1 Isolation In its capacity as a manufacturer, Schneider Electric has chosen to completely guarantee operator safety by necessarily offering switches satisfying the isolation mode with positive break indication. Circuit isolation is a function that must be performed in complete safety. 4.1.1.1 Choice of isolation For those ranges of switches, Schneider Electric has chosen : the isolation mode with positive contact indication. To ensure maximum user safety, the isolation mode with positive contact indication is the most effective solution from a technical standpoint. The position of the control device guarantees absence of voltage. 4.1.1.2 Positive contact indication ■ Advantages For devices with positive contact indication, the position of the control device in the rest position reflects contact opening. This function is: ❏ guaranteed by the manufacturer (inherent safety guarantee) and is no longer the operator’s responsibility, ❏ possible whatever kind of accessories are used: extended handle, handle through door, etc. ■ Implementation requirements There are no special requirements linked to use of this technology type. With positive contact indication, the position of the control device must reflect contact position by means of a “reliable and tamper-proof” mechanical device, the tests for which are defined by standards. Consequently, there is no longer any risk of incorrect judgement by the user, as is the case for switches with visible isolation only. 4.1.1.3 Visible isolation Visible isolation is sometimes imposed by installation standards (in France, for example, standards NF-C 13-100 and NF C 14-100 concerning connection). ■ Advantages Visible isolation appears to offer operators additional safety as they can observe contact opening. ■ Implementation requirements As indicated page 9, before working on the installation part downstream of a switch/disconnector, the user must: ❏ open the switch, ❏ then, in all cases, check absence of voltage. If the switch has visible isolation (refer to “Standards - suitability for isolation”) the user must : ❏ check contact opening. Isolation is in actual fact guaranteed by the operator who has validated contact opening. Visibility is perfect when the device is new and mounted in an enclosure without a door. For visibility to be guaranteed over time, a certain number of design requirements are necessary. 19 The following table lists the phenomena that might interfere with contact position interpretation: Application case Device status after electrical switching operations Use of switch with an extended or side handle in an enclosure with plain door Use of switch with an extended or side handle in an enclosure with transparent door Observations Current breaking pollutes the aperture and visible isolation becomes questionable and even invisible. For guaranteed isolation, it is necessary to open the enclosure door to check that contacts are really separated. Otherwise, there is a risk op padlocking a device that is not open. There is a real danger for the user (1). It all depends on equipment assembly and place of installation. The result may may be very similar to the above case. Table J (1) The standard does not impose mechanical tests on the interlocking linking the position of the handle to that of the contacts for devices with visible isolation. 4.1.1.4 Schneider “visible isolation” technology Schneider Electric has developed a specific range of switches (INV range). For these switches with visible isolation, Schneider gives priority to maximum safety: ■ isolation with positive contact indication is guaranteed in addition to visible isolation, ■ the main switch contacts are placed at the rear of the device. Consequently, the range is optimised to offer the best compromise between user safety and visibility of main contacts: class 2 classification of devices is maintained, ■ the transparent cover allowing contact visibility is guaranteed for 200 electrical switching operations. Beyond this number, its interchangeability will allow maintained visibility, ■ isolation with positive break indication is maintained. Schneider has chosen to assume responsibility for the isolation function. 20 E62421 4.1.2 Front face class II casing class II front face class II The Schneider Electric devices are front face Class II: this Class is maintained when the device is equipped with direct control via a metal front plate (case of a Devices must be designed according to specific building considerations: ■ case of devices with positive break indication. There are two insulating enclosures (double insulation front face): safety is maximum, ■ case of devices with visible isolation. Class II is obtained by demanding criteria to be respected (for devices with an Ui 750/800 V): ❏ impulse wave withstand at 14.7 kV, ❏ backing up of creepage distances. These criteria have a certain effect on device construction, as devices with visible isolation cannot have a double insulating barrier: - the main contacts are located at the rear of the switch to ensure maximum safety, - visibility of main contacts is thus slightly less good, but user safety is maximum. 052967 Figure 10: Class II diagram 4.1.3 “Emergency stop” control ■ By manual control The INS, INV and VARIO switch ranges, are also available in the “emergency stop switch” version, conform to VDE recommendations. These switches can be identified by their colours: red handle, yellow case front face. Switch characteristics and performance are identical to those of standard switches. ■ By automatic control The switch is standard and trip-free. To perform a safety function, tripping will use an MN coil. This coil will be de-activated by the emergency stop normally closed contact. E29925 054361 Plastron INS VARIO NG 125 NA .4 .2 .1 E62420 4.1.4 The switch is an environmentally-friendly product Anxious to protect the environment, Schneider Electric takes three types of action: ■ first, it produces products of a modular design and thus completely separable into single-material components, ■ second, it uses: ❏ materials containing no harmful substances, in particular no cadmium, mercury or asbestos, ❏ carefully selected thermoplastics for the moulded parts of the device. Elimination of these materials, even by incineration, does not give off polluting substances. ■ third, it implements non-polluting manufacturing processes: ISO 14001 certification of its products’ manufacturing sites. N Figure 11: Green products 21 4.2 Installing switches: the Schneider Electric system 4.2.1 The installation system E45106 048763 Power distribution switchboards These incoming switchboards, in the tertiary or industrial sector, are mainly equipped with industrial switchgear of the Masterpact/Compact/Interpact type. The control and isolation switch is an industrial device with the following ratings: ■ 400 A to 1000 A in the tertiary sector, ■ 400 A to 1600 A in the industrial sector. Applicable standard: IEC 60947-3. 052838 ndustrial subdistribution switchboards or automation cubicles As a rule, the incomer is an industrial device with a rating ≤ 400 A. According to its rating, the most frequent cases are: ■ for incomers ≤ 160 A, feeders of the Multi 9 type and switchboards designed to receive this switchgear type, ■ for incomers from 160 to 400 A, industrial type feeders such as the Compact NS: ❏ in industrial distribution switchboards, ❏ in automation cubicles, ■ for incomers from 40 to 400 A, control and monitoring feeders installed on universal mounting plates. Applicable standard: IEC 60947-3. 22 Subdistribution switchboards (modular products) The incomer is normally a modular type device ≤ 160 A. Feeders are mostly made with modular switchgear. All the devices are mounted in equipment systems adapted to the modular switchgear (e.g. Prisma, Pragma). Applicable standard: IEC 60947-3. E52516 Small final distribution enclosures As a rule the incomer is a modular type device ≤ 63 A. Feeders are low rating Multi 9 circuit-breakers. All the devices are mounted in a small modular enclosure. The choice of INS63 or l63 depends on the type of application: ■ INS63 for the commercial and tertiary sectors. Applicable standard: IEC 60947-3. ■ l63/ll00 for housing and domestic applications. It is often used as a direct control switch on final circuits (e.g. control of heating, convector, etc.). Applicable standard: IEC 60669-1. Coffretauto2 E45108 052125 Coffrisofrontnb Local isolation enclosures Equipped with industrial switchgear for all ratings (up to 630 A) or with modular switchgear for low ratings (up to 63 A). They are used to control and isolate machines and utilities locally (e.g. boiler plants, lift machinery). Applicable standard: IEC 60947-3. Automation enclosures The current range for this application is normally limited to 40 A. The enclosure is frequently built into the machine. The switches dedicated to this application are usually designed specifically for it (standard ratings: 16/25 A). This type of device normally includes many accessory possibilities (auxiliary switches, optional door mounting, etc.). Applicable standard: IEC 60947-3. 23 4.2.2 Consistency of the circuit-breaker/switch ranges 4.2.2.1 Size and accessories 055994 At power distribution level - 100 A to 630 A - it is essential for switch ranges to be completely consistent with circuit-breaker ranges. Schneider Electric thus offers Interpact INS / INV ranges that are fully in line with the Compact NS circuit-breaker ranges. Consistency is ensured for: ■ accessories (auxiliaries, rotary handle, etc.) shared by the 2 ranges, ■ dimensional features (pole pitch, physical size, etc.), particularly important, ■ design and colour. Figure 12: Common Interpact INS and Compact NS accessories E54475 E62422 This rationalisation guarantees this range perfect incorporation in the Prisma functional installation systems. Furthermore, this switchgear can: ■ be mounted on symmetrical rail or on a functional mounting plate, ■ use the cabling accessories of Prisma Distribloc, Polybloc, etc. N N N Figure 13a: Mounting Interpact NG125NA in a Prisma cubicle. 24 Figure 13b: Mounting Interpact INS with Distribloc connection in a Prisma cubicle. 4.2.2.2 Control auxiliaries E62423 ■ Rotary handles to satisfy all installation systems. In particular, the INS/INV switches can be equipped with direct and extended rotary handles of the front or lateral type. The extended rotary handle maintains isolation with positive contact indication. ■ Connection accessories. To simplify connection of some large diameter cables, a single-piece spreader (also usable for Compact NS circuit-breaker ranges) allows: ❏ increase in pole pitch ❏ use of the connection and isolation accessories of the larger-sized device ❏ factory-guaranteed isolation quality. ¿5...8 Figure 14: INS connection and control auxiliairies 4.2.2.3 Manual source changeover switches E55272 E54481 A comprehensive manual source changeover switch range is available with an interlocking system: ■ key-operated, ■ with rotary handles, ■ single-piece (INS switch). O Figure 15: Single-piece Interpact INS source changeover switch This last option ensures rationalisation of the function: ❏ by optimised size of switchgear ❏ by implementation of a single 3-position rotary handle. This guarantees greater ease of mounting and safety of implementation. Consistency with the circuit-breaker ranges is respected thanks to identical fixing centres and thus the same cabling gauge. A downstream coupling accessory completes the simplicity of the source changeover switch function (the same for two switchgear). 25 035050 024262 052384 E58483 4.2.3 Positioning the offer by applications coupling switch industrial power distribution switchboard 056385 tertiary power distribution switchboard 15 -40 kA 20 -80 kA ≤ 1600 A 086081 ≤ 1000 A replacement source 054361 modular product subdistribution switchboard industrial distribution switchboard ≤ 160 A automation cubicle ≤ 160 A : 15 - 25 kA ≤ 400 A : 20 - 80 kA source changeover switch 052164 15 - 25 kA small tertiary distribution enclosure local isolation enclosure ≤ 10 kA ≤ 63 A local isolation enclosure local isolation enclosure automation enclosure ≤ 25 kA ≤ 10 kA ≤ 63 A ≤ 15 kA kA 5-15 ≤ 5 kA ≤ 40 A ≤ 125 A 054629 ≤ 630 A M M M M E31913 M building utilities building final distribution continuous process Figure 21: Diagram showing a standard installation covering most of the cases observed in real life 26 E52580 086087 NB: immediately beside the machine or built into the machine individual machine manufacturing process In short The switch must be chosen according to: ■ the characteristics of the network on which it is installed, ■ the location and the application, ■ coordination with the upstream protection devices (in particular overload and short-circuit). 4.3 Choosing a Schneider Electric switch 4.3.1 Choice criteria 4.3.1.1 Network characteristics Nominal voltage, nominal frequency and nominal current are determined in the same way as for a circuit-breaker: ■ nominal voltage = nominal voltage of the network, ■ frequency = network frequency, ■ nominal current = rated current of a value immediately higher than the downstream load current. Note that the rated current is defined for a given ambient temperature and that a derating may have to be taken into account. 4.3.1.2 Location and application This determines the type and characteristics or main functions that the switch must possess. There are 3 function levels (see table opposite): ■ Basic functions virtually common to all switch types: ❏ isolation, control, padlocking, safety. ■ Additional characteristic functions ❏ direct formulation of the needs of the user and of the switch environment, i.e.: - industrial type performance, - need for emergency stopping, - lsc level, - type of interlocking, - type of control, - utilisation category, - mounting system. ■ Specific functions ❏ linked to operation and to installation requirements, i.e.: - earth leakage protection, - motor mechanisms, - remote opening (“emergency stop” function), - withdrawability. The following table enables choice of switch according to requirements. ■ Choice table Comparison of the application table (§ 4.3.2) and the switch technical data table (§ 4.3.4) lets you specify which switch range should be used. 4.3.1.3 Coordination All switches must be protected by an overcurrent protection device placed upstream. The "additional technical information" tables below give the SCPD (circuit-breaker or fuse) guaranteeing proper coordination with switches in event of a downstream short-circuit, according to the electrodynamic withstand or the shortcircuit making capacity of the device. 27 4.3.2 Location and application table Switch technical data according to location and application. Power distribution switchboards Industrial Subdistribution switchboards switchboards and automation (modular cubicles products) Small tertiary distribution enclosures Automation enclosures Local isolation enclosures 400 to 6300 A 40 to 630 A ≤ 125 A ≤ 40/125 A 10 to 630 A yes ■ yes ■ ■ ■ 3 to 5 kA ■ I ≤ 63 A : 10 kA ■ I ≤ 630 A : 25 kA ■ ■ ■ I ≤ 63 A ■ ■ ■ ❏ ■ ■ ❏ ❏ Current range LV switch basic functions Circuit on-load control Isolation Padlocking the isolated status Padlocking Additional functions / technical data Maximum short-circuit level yes yes yes yes ■ ■ ■ ■ by isolation with positive break indication or visible isolation ■ ■ ■ ■ 20 to 80 kA ■ I ≤ 160 A : 15 to 25 kA ■ I ≤ 400 A : 20 to 80 kA Motor mechanism technical data ■ ■ ❏ AC21A AC22A AC23 AC3 20 to 160 A ■ I ≤ 63 A : 15 kA ■ I ≤ 160 A : 25 kA ■ ❏ 10 kA ■ ❏ Handle rotary direct front front extended side extended Mounting on plate symmetrical rail (45 mm tip) Specific functions Earth leakage protection Other draw-out, auxiliary switches, auxiliary releases, remote control emergency stop Table K ■ Compulsory. ❏ Possible. 28 ■ ■ ❏ ■ ❏ ■ ■ ❏ ❏ ❏ ❏ ❏ ■ ■ ❏ ❏ ■ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ■ ■ ■ ■ ❏ ❏ 4.3.3 The switches available in the Schneider Electric offer Renewal and standardisation of the Interpact range is part of the Schneider Electric global offer. Schneider Electric offers its customers several ranges of switches. Choice depends on: ■ the application, ■ the additional functions to be implemented (safety level, convenience, etc.). The following table summarises the possibilities offered by all the Schneider Electric ranges according to the applications described above. Applications Incoming switches for Products main distribution industrial switchboards power switchboards 400 - 6300 A 40 - 630 A Vario (Télémécanique) Multi 9 I/ID (modular profile) Multi 9 I-NA (profil modulaire) Interpact INS (modular profile) NG125 NA (modular profile) Interpact INS ■ (industrial) Compact NA ❏ (industrial) Masterpact HI/HF ■ (industrial) ■ automation cubicles subdristribution switchboards 40 -630 A 20 - 160 A ❏ (1) ■ ❏ (1) ■ ❏ (1) small tertiary distribution enclosures ≤ 125 A ≤ 40/125 A Local isolation switches local isolation enclosures 10 - 630 A ■ ■ automation enclosures ■ ❏ ❏ ■ ■ ■ ■ ■ ■ ■ ■ ❏ ■ Table L ■ Very common. ❏ Fairly common. (1) Fairly common, but totally suitable for these application types. Interpact INS 056385 Interpact INS 055999 Multi 9 switch 054629 E29925 ■ Manually controlled switch Vario Masterpact NA 52384 86087 86085 054320 ■ Remotely controlled switch (MN, MX, earth leakage protection) NG125 NA NSA160 NA Compact NS250 NA 29 4.3.4 Switch range technical data Table M below lists the main technical data of the switches in the Schneider Electric ranges. Range Performance type Clip-on on rail Main functions Emergency stop Other functions Fixed/draw-out Auxiliary range available Rating range (A) Vario Industrial Tertiary ■ Isolation Positive break indication Visible isolation Manual (7) Remote Residual current Remote control fuse/switches Fixed Draw-out ■ ■ Table M (1) OF contact on switches - OF contact and MX, MN coil on residual current circuit-breakers. (2) OF or CAM contact. (3) Only 40 to 160 A (modular profile). (4) Specific INS/INV emergency stop switches. (5) Only on ratings 40/63/100/125. (6) With MN auxiliaries. (7) Yellow front plate/red handle. (8) Associated Vigi bloc. 30 Interpact I-NA ■ ■ ■ ■ ■ ■ ■ ■ (5) Compact Masterpact ID NG125NA INS INV IN NA/NI CMI NI HI ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ HF ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ (5) ■ ■ (6) ■ ■ (6) ■ ■ ■ ■ 12 16 20 25 32 40 63 80 100 125 160 175 250 320 400 500 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 Multi 9 I (1) ■ (1) ■ (3) ■ (4) ■ ■ (3) (4) (6) (8) ■ ■ (1) ■ ■ ■ ■ ■ ■ ■ ■ (1) ■ ■ (1) ■ ■ (1) ■ (2) ■ (8) ■ ■ ■ (8) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ (8) Additional technical information Characteristic tables Switch-disconnectors selection Interpact Interpact Interpact Interpact Interpact Interpact INS40 to 160 INS250 INS320 to 630 INV100 to 250 with visible break INV320 to 630 with visible break IN1000 to 2500 Switch-disconnectors Compact Compact CM Masterpact Co-ordination p p p p p p 34 36 38 40 42 44 p 46 p 46 p 50 p 52 p 56 p 56 p 57 p 58 p 59 p 60 p 62 E62335 Applications Modular switches and residual current circuit-breakers Upstream: circuit-breakers or fuses / Downstream: modular switches Upstream: fuses or circuit-breakers / Downstream: modular residual current circuit-breakers Upstream: NS100/160 / Downstream: Multi 9 circuit-breakers Industrial switch-disconnectors Protection of switch-disconnectors p 32 p 34 31 E29925 Additional technical information Characteristic tables Vario switch-disconnectors IN (A) V02 Number of poles 3 to 6 Electrical characteristics as defined by IEC 60947-3 Conventional thermal current (A) Ith Rated insulation level (V) Ui Impulse-withstand voltage (kV peak) Uimp Rated operational voltage (V) Ue Rated operational current (A) Ie Short-circuit making capacity Short-time withstand current Suitability for isolation Endurance (CO cycles) Icm (kA peak) Icw (kA rms) at 40 °C AC 50/60 Hz AC22A AC23A 230V to 690V 230V 415V 500V 690V 1s b mechanical electrical AC-21 054630 Signalling auxiliaries Auxiliary contacts IN (A) AC 50/60 Hz mechanical electrical AC-22 AC 50/60 Hz mechanical electrical AC-23 AC 50/60 Hz mechanical electrical AC-22 Auxiliaries OF 057451 Multi 9 I-NA switches IN (A) Number of poles Un (V) Endurance (CO cycles) Suitability for isolation as defined by IEC 60947-3 Auxiliaries OF/SD/MX/MN 054361 Multi 9 NG125NA switches IN (A) Number of poles Un (V) Endurance (CO cycles) Auxiliaries OF/SD/MX/MN Vigi block 053419 Multi 9 ID switches IN (A) Number of poles Un (V) Sensitivity as in class AC 50/60 Hz AC A Sensitivity type si Endurance (CO cycles) Auxiliaries OF/SD/MX/MN v OF only s selective (1) only 2P (2) only 4P 32 100000 100000 b Multi 9 I(3) switches Number of poles Un (V) Endurance (CO cycles) 12 690 8 690 12 10,6 8,1 8,9 8,6 0,5 0,14 mechanical electrical AC-22 V01 V0 V1 V2 V3 V4 V5 V6 3 to 6 3 to 6 3 to 6 3 to 6 3 to 6 3 to 6 3 3 20 690 8 690 20 14 11 11,9 12,3 0,5 0,14 25 690 8 690 25 19,7 14 16,7 17,5 1 0,3 32 690 8 690 32 19,7 21 16,7 17,5 1 0,38 40 690 8 690 40 25,8 28 28,5 17,5 1 0,48 63 690 8 690 63 50,3 40 44 25 2,1 0,75 80 690 8 690 80 61,2 55 54 33 2,1 0,96 125 690 8 690 125 71,9 66 64,5 42 2,8 1,5 175 690 8 690 160 96,6 80 79 49 2,8 2,1 b b b b b b b b 100000 100000 100000 100000 100000 100000 100000 100000 30000 30000 30000 30000 30000 30000 30000 30000 b b b b b b b b 20/32 (avec voyant) 40/63 1 250 200000 30000 2 to 4 415 200000 30000 1 250 50000 20000 2 to 4 415 50000 20000 100 1 250 50000 10000 2 to 4 415 50000 10000 125 1 250 50000 2500 2 to 4 415 50000 2500 b b b b b b b b 40 63 2 and 4 250/415 25000 5000 2 and 4 250/415 25000 5000 b b b b 60 80 100 125 3 and 4 500 10000 5000 3 and 4 500 10000 5000 3 and 4 500 10000 5000 3 and 4 500 10000 5000 b b b b b b b b 16 25 40 63 80 100 100 125 2 230/400 10(1) 2 and 4 230/400 10(1)-30-300-500 2 and 4 230/400 30-100(2)-300-500 300s-500s 30-300-500(2) 100s(2)-300s 30-500s 20000 10000 2 and 4 230/400 30-300-500 300s-500s 300(2)-300s 500s(2) 500s 20000 10000 2 and 4 230/400 300-300s 4 230/400 30-100 4 230/400 30-100-300-500 20000 10000 30-300 20000 10000 30-300 20000 10000 b b b v v 20000 10000 30 20000 10000 2 and 4 230/400 30-100-300-500 300s(2)-500s(2) 30-100(2)-300-500(2) 100s(2)-300s(1) 30 20000 10000 b b b 10(1)-30-300-500(2) 300s 300-500-300s (3) switches and residual current switches must always be used together with a device providing overload and short-circuit protection (4) IF MX, MN or OF are used, an OFS contact is compulsary 33 052164 Additional technical information Switch-disconnectors selection Interpact INS40 to 160 Interpact INS switch-disconnectors Number of poles 052168 Interpact INS80 switch-disconnector Interpact INS160 switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500 V 660-690 V DC 125 V (2P in series) 250 V (4P in series) Rated duties uninterrupted duty intermittent duty Short-circuit making capacity Icm (kA peak) min. (switch-disconnector alone) max. (with upstream protection circuit breaker) Short-time withstand current Icw (A rms) 1s 3s 20 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC22A 500 V AC22A 690 V AC23A 220-240 V AC23A 380-415 V AC23A 440 V AC23A 500 V AC23A 690 V elect. DC DC23A 250 V Positive contact indication Degree of pollution Upstream protection See the "Technical details" section, page 4.0000 Installation and connection Fixed, front connection symmetrical rail backplate Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases and motor mechanism Direct and extended front / lateral rotary handle Locking by padlocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions and spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA 34 3/4 poles 3 poles 4 poles INS40 INS63 INS80 INS100 INS125 INS160 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 40 690 8 500 250 AC 22 A AC 23 A 40 40 40 40 40 40 40 32 DC 22 A DC 23 A 40 40 40 40 n class 120 - 60% 15 75 63 690 8 500 250 AC 22 A AC 23 A 63 63 63 63 63 63 63 40 DC 22 A DC 23 A 63 63 63 63 n class 120 - 60% 15 75 80 690 8 500 250 AC 22 A AC 23 A 80 80 80 72 80 63 80 40 DC 22 A DC 23 A 80 80 80 80 n class 120 - 60% 15 75 100 750 8 690 250 AC 22 A AC 23 A 100 100 100 100 100 100 100 100 100 63 DC 22 A DC 23 A 100 100 100 100 n class 120 - 60% 20 154 12 5 750 8 690 250 AC 22 A AC 23 A 125 125 125 125 125 125 125 125 125 80 DC 22 A DC 23 A 125 125 125 125 n class 120 - 60% 20 154 160 750 8 690 250 AC 22 A AC 23 A 160 160 160 160 160 160 160 160 160 100 DC 22 A DC 23 A 160 160 160 160 n class 120 - 60% 20 154 3000 1730 670 n 20000 1500 1500 1500 1500 1500 1500 yes III 3000 1730 670 n 20000 1500 1500 1500 1500 1500 1500 yes III 3000 1730 670 n 20000 1500 1500 1500 1500 1500 1500 yes III 5500 3175 1230 n 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III 5500 3175 1230 n 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III 5500 3175 1230 n 15000 1500 1500 1500 1500 1500 1500 1500 1500 yes III n n n n n n n n n n n n n - n - n - n - n - n - n n - n n - n n - n n - n n - n n - n n - n n - n n - n n n - n n n - n n n - 90 x 81 x 62,5 0,5 0,6 90 x 81 x 62,5 0,5 0,6 90 x 81 x 62,5 0,5 0,6 135 x 100 x 62,5 0,8 0,9 135 x 100 x 62,5 0,8 0,9 135 x 100 x 62,5 0,8 0,9 35 056648 Additional technical information Switch-disconnectors selection Interpact INS250 Interpact INS switch-disconnectors Number of poles 056652 Interpact INS250 switch-disconnector Interpact INS250 emergency-off switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue CA 50/60 Hz DC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V DC 125 V (2P in series) 250 V (4P in series) Rated duties uninterrupted duty intermittent duty Short-circuit making capacity Icm min. (switch-disconnector alone) (kA peak) max. (with upstream protection circuit breaker) Short-time withstand current Icw 1s (A rms) 3s 20 s 30 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V AC23A 690 V elect. DC DC23A 250 V Positive contact indication Degree of pollution Upstream protection See the "Co-ordination table" section Installation and connection Fixed, front connection Fixed, rear connection Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions, spreaders and one-piece spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA (2) mounted with adaptation kit for direct rotary handle 36 3/4 poles 3 poles 4 poles INS250-100 INS250-160 INS250-200 INS250 3, 4 3, 4 3, 4 3, 4 100 750 8 690 250 AC 22 A AC 23 A 100 100 100 100 100 100 100 100 100 100 DC 22 A DC 23 A 100 100 100 100 n class 120 - 60% 30 330 160 750 8 690 250 AC 22 A AC 23 A 160 160 160 160 160 160 160 160 160 160 DC 22 A DC 23 A 160 160 160 160 n class 120 - 60% 30 330 200 750 8 690 250 AC 22 A AC 23 A 200 200 200 200 200 200 200 200 200 200 DC 22 A DC 23 A 200 200 200 200 n class 120 - 60% 30 330 250 750 8 690 250 AC 22 A AC 23 A 250 250 250 250 250 250 250 250 250 250 DC 22 A DC 23 A 250 250 250 250 n class 120 - 60% 30 330 8500 4900 2200 1800 n 15000 1500 1500 1500 1500 1500 1500 yes III 8500 4900 2200 1800 n 15000 1500 1500 1500 1500 1500 1500 yes III 8500 4900 2200 1800 n 15000 1500 1500 1500 1500 1500 1500 yes III 8500 4900 2200 1800 n 15000 1500 1500 1500 1500 1500 1500 yes III n n n n n n n n n n n n (2) - n n n n (2) - n n n n (2) - n n n n (2) - n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 37 056385 Additional technical information Switch-disconnectors selection Interpact INS320 to 630 Interpact INS switch-disconnectors Number of poles 056390 Interpact INS400 switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V DC 125 V (2P in series) 250 V (4P in series) Rated duties uninterrupted duty intermittent duty Short-circuit making capacity Icm min. (switch-disconnector alone) (kA peak) max. (with upstream protection circuit breaker) Short-time withstand current Icw 1s (A rms) 3s 20 s 30 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V AC23A 690 V elect. DC DC23A 250 V Positive contact indication Degree of pollution Upstream protection See the "Co-ordination table" section Interpact INS400 emergency-off switch-disconnector Installation and connection Fixed, front connection Fixed, rear connection Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions, spreaders and one-piece spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA 38 3/4 poles 3 poles 4 poles INS320 INS400 INS500 INS630 3,4 3,4 3,4 3,4 320 750 8 690 250 AC 22 A AC 23 A 320 320 320 320 320 320 320 320 320 320 DC 22 A DC 23 A 320 320 320 320 n class 120 - 60% 50 330 400 750 8 690 250 AC 22 A AC 23 A 400 400 400 400 400 400 400 400 400 400 DC 22 A DC 23 A 400 400 400 400 n class 120 - 60% 50 330 500 750 8 690 250 AC 22 A AC 23 A 500 500 500 500 500 500 500 500 500 500 DC 22 A DC 23 A 500 500 500 500 n class 120 - 60% 50 330 630 750 8 690 250 AC 22 A AC 23 A 630 500 630 500 630 500 630 50 630 500 DC 22 A DC 23 A 630 630 630 630 n class 120 - 60% 50 330 20000 11500 4900 4000 n 10000 1500 1500 1500 1500 1500 1500 yes III 20000 11500 4900 4000 n 10000 1500 1500 1500 1500 1500 1500 yes III 20000 11500 4900 4000 n 10000 1500 1500 1500 1500 1500 1500 yes III 20000 11500 4900 4000 n 10000 1500 1000 1500 1500 1500 1000 yes III n n n n n n n n n n n n - n n n n - n n n n - n n n n - n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 39 056650 Additional technical information Switch-disconnectors selection Interpact INV100 to 250 with visible break Interpact INV switch-disconnectors Number of poles 056654 Interpact INV250 switch-disconnector Interpact INV250 emergency-off switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz CC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V CC 125 V (2P in series) 250 V (4P in series) Rated duties uninterrupted duty intermittent duty Short-circuit making capacity Icm min. (switch-disconnector alone) (kA peak) max. (with upstream protection circuit breaker) Short-time withstand current Icw 1s (A rms) 3s 20 s 30 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC21A 690 V AC22A 500 V AC22A 690 V AC23B 440 V AC23B 500 V AC23B 690 V elect. CC DC22A 250 V DC23B 250 V Positive contact indication Degree of pollution Upstream protection See the "Co-ordination table" section Installation and connection Fixed, front connection Fixed, rear connection Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions and spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA (2) mounted with adaptation kit for direct rotary handle 40 3/4 poles 3 poles 4 poles INV100 INV160 INV200 INV250 3, 4 3, 4 3, 4 3, 4 100 750 8 690 250 AC21A AC22A 100 100 100 100 100 100 100 100 100 DC21A DC22A 100 100 100 100 n class 120 - 60% 30 330 160 750 8 690 250 AC23B AC21A AC22A 100 160 160 100 160 160 100 160 160 80 160 160 160 DC23B DC21A DC22A 100 160 160 100 160 160 n class 120 - 60% 30 330 200 750 8 690 250 AC23B AC21A AC22A 160 200 200 160 200 200 160 200 200 80 200 200 200 DC23B DC21A DC22A 160 200 200 160 200 200 n class 120 - 60% 30 330 250 750 8 690 250 AC23B AC21A AC22A 200 250 250 200 250 250 200 250 250 100 250 250 250 DC23B DC21A DC22A 200 250 250 200 250 250 n class 120 - 60% 30 330 8500 4900 2200 1800 n 15000 1500 1500 300 300 1500 300 yes III 8500 4900 2200 1800 n 15000 1000 1000 200 200 1000 200 yes III 8500 4900 2200 1800 n 15000 1000 1000 200 200 1000 200 yes III 8500 4900 2200 1800 n 15000 1000 1000 200 200 1000 200 yes III n n n n n n n n n n n n - n n n n (2) - n n n n - n n n n (2) - n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 140 x 136 x 86 2 2,2 (2) (2) AC23B 250 250 250 100 DC23B 200 200 41 056395 Additional technical information Switch-disconnectors selection Interpact INV320 to 630 with visible break Interpact INV switch-disconnectors Number of poles 056398 Interpact INV630 switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V DC 125 V (2P in series) 250 V (4P in series) Rated duties uninterrupted duty intermittent duty Short-circuit making capacity Icm min. (switch-disconnector alone) (kA peak) max. (with upstream protection circuit breaker) Short-time withstand current Icw 1s (A rms) 3s 20 s 30 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC21A 690 V AC22A 500 V AC22A 690 V AC23B 440 V AC23B 500 V AC23B 690 V elect. DC DC22A 250 V DC23B 250 V Positive contact indication Degree of pollution Upstream protection See the "Co-ordination table" section Interpact INV630 emergency-off switch-disconnector Installation and connection Fixed, front connection Fixed, rear connection Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases and motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions and spreaders Terminal shields and shrouds Phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA 42 3/4 poles 3 poles 4 poles INV320 INV400 INV500 INV630 3, 4 3, 4 3, 4 3, 4 320 750 8 690 250 AC21A AC22A 320 320 320 320 320 320 320 320 320 DC21A DC22A 320 320 320 320 n class 120 - 60% 50 330 400 750 8 690 250 AC23B AC21A AC22A 320 400 400 320 400 400 320 400 400 160 400 400 400 DC23B DC21A DC22A 320 400 400 320 400 400 n class 120 - 60% 50 330 500 750 8 690 250 AC23B AC21A AC22A 400 500 500 400 500 500 400 500 500 200 500 500 500 DC23B DC21A DC22A 400 500 500 400 500 500 n class 120 - 60% 50 330 630 750 8 690 250 AC23B AC21A AC22A 500 630 630 500 630 630 500 630 630 220 630 630 630 DC23B DC21A DC22A 500 630 630 500 630 630 n class 120 - 60% 50 330 20000 11500 4900 4000 n 10000 1000 1000 200 200 1000 200 yes III 20000 11500 4900 4000 n 10000 1000 1000 200 200 1000 200 yes III 20000 11500 4900 4000 n 10000 1000 1000 200 200 1000 200 yes III 20000 11500 4900 4000 n 10000 1000 1000 200 200 1000 200 yes III n n n n n n n n n n n n - n n n n - n n n n - n n n n - n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 185 x 205 x 120 4,6 4,9 AC23B 500 500 500 250 DC23B 500 500 43 035053 Additional technical information Switch-disconnectors selection Interpact IN1000 to 2500 Interpact IN switch-disconnectors Number of poles Interpact IN1000 switch-disconnector Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 60 °C Rated insulation level (V) Ui AC 50/60 Hz Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational current (A) Ie AC 50/60 Hz 220-240 V 380-415 V 1000 440-480 V (1) 500 V 660-690 V DC 125 V (2P) 250 V (4P) Short-circuit making capacity Icm min. (switch-disconnector alone) (kA peak) max. (with upstream protection circuit breaker) Short-time withstand current Icw 1s (A rms) 3s 20 s Suitability for isolation Endurance (category A) (CO cycles) mechanical elect. AC AC22A 500 V AC22A 690 V AC23A 440 V AC23A 500 V elect. DC DC23A 250 V DC23A 500 V Positive contact indication Degree of pollution Upstream protection See the "Co-ordination table" section Installation and connection Fixed, front connection symmetrical rail backplate Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases Motor mechanism Direct and extended front rotary handle Direct and extended lateral rotary handle Locking by padlocks and by keylocks Manual source-changeover system Installation and connection accessories Bare cable connectors Terminal extensions and spreaders Terminal shields and phase barriers Front-panel escutcheon Dimensions and weights Overall dimensions H x W x D (mm) Approximate weight (kg) (1) suitable for 480 V NEMA (2) IN1000: 630 A for AC23A / IN1600: 800 A for AC23A (3) 1450 A at 60 °C 44 3 4 3 4 poles poles poles poles fixed, fixed, fixed, fixed, front front front front connection connection connection connection IN1000 IN1600 IN2500 3, 4 3, 4 3, 4 1000 690 8 690 250 AC 21 A 1000 1000 (2) 1000 1000 1000 DC 22 A 1000 1000 75 176 1600 (à 50° C) 690 8 690 250 AC 21 A 1600 1600 (2) 1600 1600 1600 DC 22 A 1600 1600 75 105 AC 22 A 1000 1600 800 800 DC 23 A 1000 1000 (3) AC 22 A 1600 2500 1200 1200 DC 23 A 1600 1600 2500 690 8 690 250 AC 21 A 2500 2500 2500 2500 2500 DC 21 A 2500 2500 105 105 35000 20000 7800 n 3000 500 500 500 yes III 35000 20000 7800 n 3000 500 500 500 yes III 50000 28500 11000 n 3000 500 500 500 (DC21A) yes III n n n n - n - n - n n n n n n n n n n n n - n n n - n n n - 340 x 300 x 118 410 x 300 x 118 12 15 340 x 300 x 118 410 x 300 x 118 15 18 340 x 440 x 200 410 x 440 x 200 35 45 AC 22 A 2500 DC 22 A - 45 E62587 Additional technical information Switch-disconnectors Compact Compact switch-disconnectors Number of poles Electrical characteristics as defined by IEC 60947-3 Conventional thermal current (A) Ith Rated insulation level (V) Ui Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue push to trip push to trip Rated operational current (A) Ie Short-circuit making capacity Icm (kA peak) Short-time withstand current Icw (A rms) 86085 push to trip Suitability for isolation Endurance (category A) (CO cycles) 86087 Compact NSA125NA at 60 °C AC 50/60 Hz DC AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500 V 660/690 V DC 250 V (1P) 500 V (2P) min. (switch-disconnector alone) max. (with upstream protection circuit breaker) (2) 1s 3s 20 s mechanical elect. AC AC22A 500 V AC22A 690 V elect. AC AC23A 440 V AC23A 500 V elect.DC DC23A 250 V DC23A 500 V Positive contact indication Degree of pollution Protection Earth-fault protection Compact NS100NA Compact NS100NA to NS250NA switchdisconnectors are obtained by mounting an NA switch-disconnector module on the basic NS100 to NS250 frames. Compact NSA125NA and NSA160NA switch-disconnectors are supplied fully assembled. Switch-disconnector protection According to installation standards, an upstream protection is required. Nonetheless, due to reflex tripping, Compact NS100NA to NS250NA switchdisconnectors self-protect for all fault currents greater than 10 kA. Installation and connection Fixed, front connection Installation on symmetrical rail Fixed, rear connection Plug-in (on base) Withdrawable (on chassis) Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Control auxiliairies Auxiliary releases Motor mechanism Toggle operated Direct and extended front rotary handle Lateral rotary handle Locking by padlocks and by keylocks Manual/automatic source-changeover system Installation and connection accessories Bare cable connectors, terminal extensions and spreaders Terminal shields and phase barriers Front-panel escutcheon Dimensions and weights Dimensions H x W x D (mm) Weight (kg) (1) suitable for 480 V NEMA (2) upstream connection: see the "Co-ordination table" section (3) extended only 46 add-on Vigi module Vigirex relay 2/3 poles fixed, front connection 4 poles fixed, front connection 3 poles fixed, front connection 4 poles fixed, front connection NSA125NA NSA160NA NS100NA NS160NA NS250NA 3, 4 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 125 500 8 500 250 AC 22 A 125 125 125 125 AC 23 A 125 125 125 100 160 500 8 500 250 AC 22 A 160 160 160 160 AC 23 A 160 160 160 125 DC 22 A DC 23 A DC 22 A DC 23 A 100 750 8 690 500 AC 22 A 100 100 100 100 100 DC 22 A 100 100 2,6 330 160 750 8 690 500 AC 22 A 160 160 160 160 160 DC 22 A 160 160 3,6 330 250 750 8 690 500 AC 22 A 250 250 250 250 250 DC 22 A 250 250 4,9 330 2,1 330 2,1 330 1500 1500 580 n 10000 5000 1500 1500 580 n 10000 5000 5000 AC 23 A 100 100 100 100 100 DC 23 A 100 100 AC 23 A 160 160 160 160 160 DC 23 A 160 160 AC 23 A 250 250 250 250 250 DC 23 A 250 250 1800 1800 690 n 50000 2500 2500 960 n 40000 3500 3500 1350 n 20000 5000 50000 30000(50000-In/2) 40000 20000(40000-In/2) 20000 10000(20000-In/2) 5000 5000 30000(50000-In/2) 20000(40000-In/2) 10000(20000-In/2) yes III yes III yes III yes III yes III n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n (3) n n (3) n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 90 x 120 x 82,5 210 x 120 x 82,5 1,1 1,4 90 x 120 x 82,5 90 x 120 x 82,5 1,1 1,4 105 x 161 x 86 140 x 161 x 86 1,5 2,0 105 x 161 x 86 140 x 161 x 86 1,6 2,0 105 x 161 x 86 140 x 161 x 86 1,8 2,2 47 E62587 Additional technical information Switch-disconnectors Compact (continued) Compact switch-disconnectors Number of poles Electrical characteristics as defined by IEC 60947-3 Conventional thermal current (A) Ith Rated insulation level (V) Ui Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue push to trip push to trip Rated operational current (A) Ie Short-circuit making capacity Icm (kA peak) Short-time withstand current Icw (A rms) 86083 push to trip Suitability for isolation Endurance (category A) (CO cycles) Compact NS400NA at 60 °C AC 50/60 Hz DC AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500 V 660/690 V DC 250 V 500 V min. (switch-disconnector alone) max. (with upstream protection circuit breaker) (2) 1s 3s 20 s mechanical elect. AC AC22A 500 V AC22A 690 V elect. AC AC23A 440 V AC23A 500 V elect. DC DC23A 250 V DC23A 500 V 86081 Positive contact indication Degree of pollution Protection Earth-fault protection add-on Vigi module Vigirex relay Installation and connection Fixed, front connection Installation on symmetrical rail Fixed, rear connection Plug-in (on base) Withdrawable (on chassis) Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Insulation-monitoring module Compact C1251NI Switch-disconnector protection According to installation standards, an upstream protection is required. Nonetheless, due to reflex tripping, Compact NS400 and 630NA switchdisconnectors self-protect for all fault currents greater than 15 kA. Control auxiliairies Auxiliary releases Motor mechanism Toggle operated Direct and extended front rotary handle Lateral rotary handle Locking by padlocks and by keylocks Manual/automatic source-changeover system Installation and connection accessories Bare cable connectors, terminal extensions and spreaders Terminal shields and phase barriers Front-panel escutcheon Dimensions and weights Dimensions H x W x D (mm) Weight (kg) (1) suitable for 480 V NEMA (2) upstream connection: see the "Co-ordination table" section (3) 8 seconds 48 3 4 3 4 poles poles poles poles fixed, fixed, fixed, fixed, front front front front connection connection connection connection NS400NA NS630NA C801NI C1251NI 3, 4 3, 4 3, 4 3, 4 400 750 8 690 500 AC 22 A 400 400 400 400 400 DC 22 A 400 (1P) 400 (2P) 7,1 330 630 750 8 690 500 AC 22 A 630 630 630 630 630 DC 22 A 630 (1P) 630 (2P) 8,5 330 800 750 8 690 500 AC 22 A 800 800 800 800 800 DC 22 A 800 (2P) 800 (3P) 20 330 1250 750 8 690 500 AC 22 A 1250 1250 1250 1250 1250 DC 22 A 1250 (2P) 1250 (3P) 30 154 AC 23 A 400 400 400 400 400 DC 23 A 400 (1P) 400 (2P) AC 23 A 630 630 630 630 630 DC 23 A 630 (1P) 630 (2P) AC 23 A 800 800 800 800 800 DC 23 A 800 (2P) 800 (3P) 5000 5000 1930 n 15000 6000 6000 2320 n 15000 10000 10000 (3) 6300 n 12000 15000 15000 (3) 9450 n 15000 15000 6000(12000-In/2) 15000 4000(8000-In/2) 10000 1500(3000-In/2) 10000 1500(3000-In/2) 6000(12000-In/2) 4000(8000-In/2) 1500(3000-In/2) 1500(3000-In/2) yes III yes III yes III yes III n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 140 x 255 x 110 185 x 255 x 110 5,2 6,8 140 x 255 x 110 185 x 255 x 110 5,2 6,8 374 x 210 x 172 374 x 280 x 172 13 17 374 x 210 x 172 374 x 280 x 172 13 17 AC 23 A 1250 1250 1250 1250 1250 DC 23 A 1250 (2P) 1250 (3P) 49 024262 Additional technical information Switch-disconnectors Compact CM Compact CM switch-disconnectors Number of poles Electrical characteristics as defined by IEC 60947-1 / 60947-3 Conventional thermal current (A) Ith at 40 °C Rated insulation level (V) Ui Impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Rated operational current (A) Ie AC23A 660 V Short-circuit making capacity (kA peak) Short-time withstand current Icw Icw (kA rms) duration (s) Suitability for isolation Endurance mechanical electrique 690 V - In/2 690 V - In Compact CM switch-disconnector The Compact CM switch-disconnector offers the same complementary functions as the Compact CM circuit breaker: n OF auxiliary switch for ON/OFF position indication n MX shunt release and MN undervoltage release n add-on motor mechanism module n installation accessories n connection accessories Protection Earth-fault protection Installation and connection Fixed front connection rear connection Indication and measurement auxiliaries Auxiliary contacts Control auxiliairies Auxiliary releases (MN, MX) Motor mechanism Locking by padlocks Locking by keylocks Installation and connection accessories Connection accessories Dimensions and weights Dimensions H x W x D (mm) Weight (kg) 50 add-on module (Vigirex earth-fault protection relay) 3 4 3 4 poles poles poles poles fixed, fixed, fixed, fixed, front front front front connection connection connection connection CM1600NI CM2000NI CM2500NI CM3200NI 3, 4 3, 4 3, 4 3 1600 750 2000 750 2500 750 3200 750 690 1600 65 32 3 n 10000 5000 2000 690 2000 65 32 3 n 10000 5000 2000 690 2500 65 32 3 n 10000 5000 2000 690 3200 65 32 3 n 10000 5000 2000 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 430 x 418 x 451 430 x 573 x 451 41 56 430 x 418 x 451 430 x 573 x 451 46 61 540 x 418 x 451 540 x 573 x 451 48 63 550 x 418 x 451 83 51 052384 Additional technical information Switch-disconnectors Masterpact Masterpact switch-disconnectors Number of poles Electrical characteristics as per IEC 947-2 and EN 60947-2 Rated current (A) In 40 °C Rating of 4th pole (A) Rated insulation voltage (V) Ui Rated impulse withstand voltage (V) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Type of switch-disconnector Short-time withstand current (kA rms) Masterpact M10NI Making capacity (kA peak) electrodynamic withstand (kA peak) Suitability for isolation Closing time Endurance (C-O cycles) x 1000 Icw AC 50/60 Hz Icm AC 50/60 Hz mechanical with maintenance no maintenance no maintenance 440 V - In 690 V - In 690 V electrical motor control (AC3-947-4) (1) 0,5 s 1s 3s 440 V 500/690 V Protection STR 08 dummy unit (no protection) STR 18 I protection against short-circuits when closing Installation and connections Connection Version drawout fixed Indication and measurement auxiliaries Auxiliary switches Control auxiliaries Auxiliary releases (MN, MNR, MX, XF) Motor mechanism (MCH) Operation counter (CDM) Installation and connection accessories Locking by padlock or keylock/mismatch protection Safety shutters (VO) Interphase barriers (EIP) Partitioning fixture (AC) Arc-chute cover (CC) Terminal-block cover (CB) Door frame (CDP) Transparent cover (CCP) (1) closing at 6 x Ie, and opening at 0.17 x Un 52 M08 M10 M12 M16 3, 4 3, 4 3, 4 3, 4 800 800 1000 8000 690 1000 1000 1000 8000 690 1250 1250 1000 8000 690 1600 1600 1000 8000 690 NI 40 30 22 84 84 84 n 70 ms 20 10 10 10 10 HI 65 50 32 105 105 143 HF 65 50 32 143 143 143 NI 40 30 22 84 84 84 n HI 65 50 32 105 105 143 HF 65 50 32 143 143 143 NI 40 30 22 84 84 84 n HI 65 50 32 105 105 143 HF 65 50 32 143 143 143 NI 40 30 22 84 84 84 n HI 65 50 32 105 105 143 HF 65 50 32 143 143 143 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 20 10 10 10 10 n n n n n n n n n n n n front and rear connections n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 53 052388 Additional technical information Switch-disconnectors Masterpact (cont.) Masterpact switch-disconnectors Number of poles Electrical characteristics as per IEC 947-2 and EN 60947-2 Rated current (A) In 40 °C Rating of 4th pole (A) Rated insulation voltage (V) Ui Rated impulse withstand voltage (V) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Type of switch-disconnector Short-time withstand current (kA rms) Icw AC 50/60 Hz Icm AC 50/60 Hz mechanical with maintenance no maintenance no maintenance 440 V - In 690 V - In 690 V Masterpact M50HI Making capacity (kA peak) electrodynamic withstand (kA peak) Suitability for isolation Closing time Endurance (C-O cycles) x 1000 electrical motor control (AC3-947-4) (1) 0,5 s 1s 3s 440 V 500/690 V Protection STR 08 dummy unit (no protection) STR 18 I protection against short-circuits when closing Installation and connections Connection Version drawout fixed Indication and measurement auxiliaries Auxiliary switches Control auxiliaries Auxiliary releases (MN, MNR, MX, XF) Motor mechanism (MCH) Operation counter(CDM) Installation and connection accessories Locking by padlock or keylock/mismatch protection Safety shutters (VO) Interphase barriers (EIP) Partitioning fixture (AC) Arc-chute cover (CC) Terminal-block cover (CB) Door frame (CDP) Transparent cover (CCP) (1) closing at 6 x Ie, and opening at 0.17 x Un 54 M20 M25 M32 M40 M50 M63 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 2000 2000 1000 8000 690 2500 2500 1000 8000 690 3200 3200 1000 8000 690 4000 4000 1000 8000 690 5000 2500 1000 8000 690 6300 3200 1000 8000 690 NI 55 55 50 84 84 121 n 70 ms 15 10 9 7 7 HI 75 75 57 105 105 165 HF 75 75 57 165 165 165 NI 55 55 50 84 84 121 n HI 75 75 75 105 105 165 HF 75 75 75 165 165 165 HI 75 75 75 105 105 165 n HF 75 75 75 165 165 165 15 10 9 7 7 15 10 9 7 7 15 10 8 6 6 15 10 8 6 6 15 10 8 6 6 15 10 4 2,6 2,6 15 10 4 2,6 2,6 n n n n n n n HI 75 75 75 105 105 165 n 80 ms 10 5 3 2,5 2,5 HF 75 75 75 165 165 165 HI 100 100 100 187 187 220 n HF 100 100 100 220 220 220 HI 100 100 100 187 187 220 n HF 100 100 100 220 220 220 10 5 3 2,5 2,5 10 5 3 2,5 2,5 10 5 3 2,5 2,5 10 5 2 1,5 1,5 10 5 2 1,5 1,5 n n n n n n n front and rear connections n n n n n n rear connections n n n n (3P only) n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n (3P only) n n n n n n n n n n n n n n n n n n n 55 Additional technical information Co-ordination Modular switches and residual current circuit-breakers Presentation The choice of a switch should be made according, among other things, to coordination with the device for protection against short-circuits, installed upstream. The switch, whether it be a residual current circuit-breaker or not, has a breaking capacity and withstand to limited short-circuit currents and should be protected against short-circuits which develop downstream (electrodynamic protection). The following tables indicate the maximum short-circuit efficient in kA from which the switch is protected thanks to co-ordination with the corresponding circuit-breaker placed up-stream. Caution: the switch should also be protected against overloads. When the residual current circuit-breaker and the downstream circuit-breakers are to be found on the same switchboard, set up according to the rules, the protection of the residual current circuit-breaker from shortcircuit currents can be ensured by each of the circuit-breakers placed downstream. The corresponding values are the same as in the case of co-ordination with a device located upstream. The table below allows co-ordination tables to be selected which should be taken into account depending on the upstream and downstream devices. Summary page 57 58 59 upstream device C60 NC100, C120, NG125, NS100, NS160 DPN N, C60 NC100, C120, NG125, NS100N, NS160N NS100/160 b An enclosure’s outgoer, where the Isc on the busbars is 20 kA, supplies loads with current ratings of 30, 20 and 10 A respectively in single phase, 230 V b The installation’s neutral system is the TT earthing system b The outgoer located on the upstream switchboard, which supplies this enclosure, is protected by a 2-pole C120N circuit-breaker. E62590 Example CS120N 2p ID 63 A 20 kA C60N 30 A 56 C60N 20 A C60N 10 A circuit-breaker/RCCB-ID upstream I 20, 32, 40-63, 100-125, I-NA 40-63 ID 2P, 4P ID and multi 9 circuit-breakers Which residual current circuit-breaker should you choose to equip the enclosure’s incoming feeder? b Choose an ID residual current circuitbreaker with a rating u 30+20+10 u 60A, or an ID rating of 63 A b Short-circuit withstand of the ID 63A combined with C120N: the table (page 58) includes 10 kA, which is not enough to withstand 20 kA b It is possible to co-ordinate each of the enclosure’s outgoing lines since the feeders are located in the the same enclosure as the switch b Choose C60N type circuit-breakers for feeders with a short-circuit withstand of 20 kA. Short-circuit withstand of the ID 63A combined with C60N is of 20 kA and is suitable. Coordination Upstream: circuit-breakers or fuses Downstream: modular switches Short-circuit current withstand of the circuit-breaker-switch combination (kA rms) Protection by circuit-breaker upstream downstream Multi 9 switch (240 V) l 20 l 32 l 40 - 63 l 100 - 125 I-NA 40 I-NA 63 NG125NA 63 - 80 A 100 A 125 A Multi 9 switch (415 V) l 20 l 32 l 40 - 63 l 100 - 125 I-NA 40 I-NA 63 NG125NA 63 - 80 A 100 A 125 A Interpact switch (415 V) INS40 INS63 INS100 INS125 INS160 circuit-breaker C60 a N H L 6,5 5,5 7 6,5 5,5 7 6,5 5,5 7 6,5 5,5 7 10 20 20 30 30 40 30 4,5 4 5 4,5 4 5 4,5 4 5 4,5 4 5 5 10 10 15 15 20 15 10 10 10 10 10 10 NC100 H C120 N H NG125 a N H L NS100 N H L NS160 N H L 3 3 5 7 10 10 3 3 5 7 10 10 4,5 4,5 6,5 15 15 15 4,5 4,5 6,5 15 10 10 4,5 4,5 6,5 15 15 15 4,5 4,5 6,5 15 15 15 4,5 4,5 6,5 15 15 15 6 6 6 6 6 6 6 6 6 6 6 6 20 20 20 20 20 30 30 30 20 20 20 50 50 50 70 70 70 100 100 100 70 70 85 85 100 100 70 70 70 85 85 85 100 100 100 2 2 3 5 7 7 2 2 3 5 7 7 3 3 6 10 7 7 3 3 6 10 3 3 6 10 15 15 3 3 6 10 3 3 6 10 15 15 10 10 10 10 10 16 16 16 16 16 16 25 25 25 36 36 36 50 50 50 25 25 36 70 36 70 25 36 36 25 70 70 25 70 70 10 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 16 16 16 25 25 25 25 25 36 36 36 36 36 50 50 50 50 50 25 25 25 36 36 70 36 36 70 25 25 36 36 36 25 25 70 70 70 25 25 70 70 70 4 4 4 4 Breaking capacity of switches (kA) upstream downstream Switch (240 V AC) y 40 A 50/63 A 100/125 A Switch (415 V AC) y 40 A 50/63 A 100 A 125 A circuit-breaker C60 a N H L NC100 C120 H N 21 21 42 42 63 63 84 63 42 42 10,5 10,5 21 21 32 32 42 32 21 21 21 H NG125 N H L 42 42 42 63 63 63 105 105 105 154 154 154 220 220 220 21 21 21 21 32 32 32 32 53 53 53 53 75 75 75 75 105 105 105 105 b Use a circuit-breaker with the same rating as the switch Protection by fuse gG Short-circuit current withstand of switches (I and I-NA) in kA (rms) upstream In (A) downstream type l 20 l 32 I 63 l 100 I-NA 40 I-NA 63 gG fuse 20 32 40 63 100 8 8 10 (1) (1) 80 30 30 6 20 20 short-circuit current withstand (kA rms) of switches 2,5 2,5 4,6 6,5 4 4 (1) kA rms 57 Additional technical information Co-ordination Upstream: fuses or circuit-breakers Downstream: modular residual current circuit-breakers Protection by fuse Short-circuit current withstand of the fuse ID residual current circuit-breaker combination (kA rms) upstream/downstream In (A) 400 V/415 V network (or IT earthing system) 2P switch 25 40 63 80 down./up. ratings (A) gG upstream fuses 16 25 32 40 50 63 80 100 100 100 100 80 50 30 20 20 100 100 100 80 50 30 20 20 Protection by circuit-breaker upstream/downstream In (A) 230 V/240 V network 2P switch 25 40 downstream/upstream circuit-breaker DPN DPN N C60a C60N C60H C60L NC100H NC100LH NS100N NS160N NG125N NG125L C120H C120N 6 7,5 10 20 30 50 10 20 6 6 15 15 15 10 upstream/downstream 6 7,5 10 20 30 40 10 20 6 6 15 15 15 10 100 100 100 80 50 30 20 20 100 100 100 80 50 30 20 20 63 80 100-125 100 100 100 80 50 30 30 30 100 100 100 80 50 30 20 10 100 100 100 80 50 30 20 10 100 100 100 80 50 30 20 10 100 100 80 50 30 30 20 10 100 100 100 80 50 30 20 10 Short-circuit current withstand of the circuit-breaker ID residual current circuitbreaker combination (kA rms) 63 20 30 30 10 20 6 6 15 15 15 10 80 10 20 6 6 15 10 10 10 In (A) 400 V/415 V network (or IT earthing system)* 2P switch 25 40 63 80 downstream/upstream circuit-breaker DPN DPN N C60a C60N C60H C60L NC100H NC100LH NS100N NS160N NG125N NG125L C120H C120N 2 3 5 10 15 20 7 20 4 4 15 15 7 7 2 3 5 10 15 20 7 20 4 4 15 15 7 7 100-125 230 V/240 V network 4P switch 25 40 10 15 15 7 20 4 4 15 15 7 7 5 10 4 4 15 15 5 5 100 230 V/240 V network 4P switch 25 40 63 80 100 10 20 6 5 7 7 10 10 6 7,5 10 20 30 50 10 20 6 6 15 15 15 10 20 30 30 10 20 6 6 15 15 15 10 10 20 6 6 10 10 10 10 10 20 6 5 7 7 10 10 100 400 V/415 V network 4P switch 25 40 63 80 100 5 10 4 4 7 7 5 5 2 3 5 10 15 20 7 20 4 4 15 15 7 7 10 15 15 7 20 4 4 15 15 7 7 5 10 4 4 15 15 5 5 5 10 4 4 10 7 5 5 6 7,5 10 20 30 40 10 20 6 6 15 15 15 10 2 3 5 10 15 20 7 20 4 4 15 15 7 7 (*) supply (Ph + N): case of double fault Note: do not forget to take the derating of the residual current circuit-breakers into account depending on the ambient temperature. 58 Coordination Upstream: NS100/160 Downstream: Multi 9 circuit-breakers Residual current circuitbreaker Residual current circuit-breaker installed between an upstream NS100/160 and downstream M9 circuit-breaker In (A) 230 V network 2P switch 25 40 downstream circuit-breaker DPN DPN N C60a C60N C60H C60L NC100H NC100LH 6 7,5 10 20 30 50 10 20 In (A) 400 V network (or IT earthing system) 2P switch 25 40 63 80 downstream circuit-breaker DPN DPN N C60a C60N C60H C60L NC100H NC100LH 2 3 5 10 15 20 7 20 6 7,5 10 20 30 40 10 20 2 3 5 10 15 20 7 20 63 20 30 30 10 20 10 15 15 7 20 80 10 20 5 10 100 230 V network 4P switch 25 40 63 80 100 10 20 6 7,5 10 20 30 50 10 20 20 30 30 10 20 10 20 10 20 100 400 V network 4P switch 25 40 63 80 100 5 10 2 3 5 10 15 20 7 20 10 15 15 7 20 5 10 5 10 6 7,5 10 20 30 40 10 20 2 3 5 10 15 20 7 20 59 Additional technical information Co-ordination Industrial switch-disconnectors Example A low voltage distribution switchboard 400 V / 230 V, with a short-circuit current of 35 kA at the level of the busbar, possesses an outgoing feeder with a nominal current of 60 A. The wiring system which supplies this outgoing feeder is protected with a NS100H (R.B.: 70 kA) switch. This wiring feeds a sub-distribution switchboard, where the intention is to install, at the incoming feeder, a circuit breaker to ensure that the control and isolation functions are performed. The short-circuit current at the level of the sub-distribution switchboard is 30 kA. Which switch is the right one ? If the auxiliary functions such as remote control, earth leakage protection are requested, then the Compact NA switch would be the appropriate switch ; its coordination characteristics are given in the tables which follow (page 62 and following). The NS100NA switch is also appropriate, due to the fact that the association withstand with the NS100H is 70 kA. Furthermore, the NS100NA switch is self-protected from 10 kA upwards. If no auxiliary function is requested - or if it is matter of auxiliary functions in the form of auxiliary contacts, rotary handles - then the Interpact INS100 would be suitable (see tables page 62 and following). E62588 The table reading page 63 shows that the INS100 characteristics, when coordinated with the NS100H, become (following item) : b 70 kA for the Isc withstand b 154 kA peak for the making capacity. Icc = 35 kA NS100H coordination 1 = 60 A Icc = 35 kA The rating of the INS100 is compatible with the line's nominal current: 60 A. Reading of tables (pages 62/63) E62589 By coordination: b Isc withstand is more than sufficient: 70 kA b Making capacity on the peak Isc 154 kA is considerably higher than the requirement. Note: for Isc = 30 kA, Imax peak ~ 75 kA. switch type and its characteristics (after coordination) making capacity INS100 Isc NS100H-L 70 154 60 type of upstream protection 61 E51067 Additional technical information Protection of switchdisconnectors Interpact INS switch-disconnectors / upstream protection By circuit breaker 380/415 V push to trip 90 %Ir 105 alarm STR Io .9 .8 23 SE Ir .93 .95 .98 .85 1 .5 4 3 Im5 6 8 2 .88 .63 .8 1 x Io Ir Im 10 1.5 Ir x x In test ¿5...8 By circuit breaker 440/480 V (*) By circuit breaker 500 V (INS40 to INS80) 500/525 V (INS100 to INS160) By circuit breaker 690 V By fuse 500 V (*) suitable for 480 NEMA (1) mandatory protection by an external thermal (2) no external thermal protection 62 type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type aM (1) / max. rating Isc max. making capacity type gG (2) / max. rating Isc max. making capacity type gG (1) / max. rating Isc max. making capacity type BS (2) / max. rating Isc max. making capacity type BS (1) / max. rating Isc max. making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak INS40 INS63 INS80 INS100 INS125 INS160 NS100N / 40 25 52 NS100H-L / 40 36 75 NS160N / 40 25 52 NS160H-L / 40 25 52 NSC100N / 40 18 37 NG125N / 40 25 52 NG125H / 40 36 75 NG125L / 40 50 105 NSA160N / 40 30 63 NS100N / 40 25 52 NS100H-L / 40 35 73 NS160N / 40 25 52 NS160H-L / 40 25 52 NSC100N / 40 18 37 NS100N / 40 18 36 NS100H-L / 40 18-25 36-53 NS160N / 40 15 30 NS160H-L / 40 15 30 NSC100N / 40 10 17 40 80 176 32 100 220 125 100 220 32 80 176 125 and 100M125 80 176 NS100N / 63 25 52 NS100H-L / 63 36 75 NS160N / 63 25 52 NS160H-L / 63 25 52 NSC100N / 63 18 37 NG125N / 63 25 52 NG125H / 63 36 75 NG125L / 63 50 105 NSA160N / 63 30 63 NS100N / 63 25 52 NS100H-L / 63 35 73 NS160N / 63 25 52 NS160H-L / 63 25 52 NSC100N / 63 18 37 NS100N / 63 18 36 NS100H-L / 63 18-25 36-53 NS160N / 63 15 30 NS160H-L / 63 15 30 NSC100N / 63 10 17 63 80 176 50 100 220 125 100 220 50 and 32M50 80 176 125 and 100M125 80 176 NS100N / 80 25 52 NS100H-L / 80 36 75 NS160N / 80 25 52 NS160H-L / 80 25 52 NSC100N / 80 18 37 NG125N / 80 25 52 NG125H / 80 36 75 NG125L / 80 50 105 NSA160N / 80 30 63 NS100N / 80 25 52 NS100H-L / 80 35 73 NS160N / 80 25 52 NS160H-L / 80 25 52 NSC100N / 80 18 37 NS100N / 80 18 36 NS100H-L / 80 18-25 36-53 NS160N / 80 15 30 NS160H-L / 80 15 30 NSC100N / 80 10 17 80 80 176 63 100 220 125 100 220 63 and 32M63 80 176 125 and 100M125 80 176 NS100N / 100 25 52 NS100H-L / 100 70 154 NS160-250N / 100 36 75 NS160-250H-L / 100 70 154 NSC100N / 100 18 37 NG125N / 100 25 52 NSA160N / 100 30 63 NS100N / 100 25 52 NS100H-L / 100 65 143 NS160-250N / 100 35 73 NS160-250H-L / 100 65 143 NSC100N / 100 18 37 NS100N / 100 18 36 NS100H-L / 100 35-100 73-220 NS160-250N / 100 22 46 NS160-250H-L / 100 22 46 NSC100N / 100 10 17 NS100N / 100 8 14 NS100H-L / 100 10-75 17-165 NS160-250N / 100 8 14 NS160-250H-L / 100 10-20 17-40 100 80 176 80 100 220 160 100 220 80 and 63M80 80 176 160 and 100M160 80 176 NS160-250N / 125 36 75 NS160-250H-L / 125 70 154 NG125N / 125 25 52 NSA160N / 125 30 63 NS160-250N / 125 35 73 NS160-250H-L / 125 65 143 NS160-250N / 125 22 46 NS160-250H-L / 125 22 46 NS160-250N / 125 8 14 NS160-250H-L / 125 10-20 17-40 125 55 121 100 100 220 160 100 220 100 and 63M100 80 176 160 and 100M160 80 176 NS160-250N / 160 36 75 NS160-250H-L /160 70 154 NS160N / 160 30 63 NS160-250N / 160 35 73 NS160-250H-L /160 65 143 NS160-250N / 160 22 46 NS160-250H-L /160 22 46 NS160-250N / 160 8 14 NS160-250H-L /160 10-20 17-40 160 33 69 125 100 220 160 100 220 125 and 100M125 80 176 160 and 100M160 80 176 63 E51067 Additional technical information Protection of switchdisconnectors Interpact switch-disconnectors / upstream protection By circuit breaker 380/415 V push to trip 90 %Ir 105 alarm STR Io .9 .8 23 SE Ir .93 .85 1 .5 .95 4 3 Im5 6 8 2 .88 .98 .63 1 .8 x Io Ir Im 10 1.5 Ir x x In test By circuit breaker 440/480 V (*) ¿5...8 By circuit breaker 500 V By circuit breaker 525 V By circuit breaker 690 V By fuse 500 V (*) suitable for 480 NEMA (1) mandatory protection by an external thermal (2) no external thermal protection 64 type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type aM (1) max. rating Isc max. making capacity type gG (2) max. rating Isc max. making capacity type gG (1) max. rating Isc max. making capacity type BS (2) max. rating Isc max. making capacity type BS (1) max. rating Isc max. making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak INS250-100 INV100 INS250-160 INV160 INS250-200 INV200 INS250 INV250 INS320 INV320 INS400 INV400 NS100-160-250N/100 25-36-36 53-75-75 NS100-160-250H/100 70 154 NS100-160-250L/100 150 330 NS100-160-250N/100 25-25-35 53-53-73 NS100-160-250H/100 65 143 NS100-160-250L/100 130 286 NS100-160-250N/100 18 36 NS100-160-250H/100 50 105 NS100-160-250L/100 kA rms 220-154-154 NS100-160-250N/100 18 36 NS100-160-250H/100 35 73 NS100-160-250L/100 100-50-50 220-105-105 NS100-160-250N/100 8 14 NS100-160-250H/100 10 17 NS100-160-250L/100 75-20-20 165-40-40 100 100 220 80 100 220 100 100 220 80 and 63M80 80 176 250 and 200M250 80 176 NS160-250N/160 36 75 NS160-250H/160 70 154 NS160-250L/160 150 330 NS160-250N/160 35 73 NS160-250H/160 65 143 NS160-250L/160 130 286 NS160-250N/160 30 63 NS160-250H/160 50 105 NS160-250L/160 100-70-70 154 NS160-250N/160 22 46 NS160-250H/160 35 73 NS160-250L/160 50 105 NS160-250N/160 8 14 NS160-250H/160 10 17 NS160-250L/160 20 40 160 100 220 125 100 220 160 100 220 125 and 100M125 80 176 250 and 200M250 80 176 NS250N/200 36 75 NS250H/200 70 154 NS250L/200 150 330 NS250N/200 35 73 NS250H/200 65 143 NS250L/200 130 286 NS250N/200 30 63 NS250H/200 50 105 NS250L/200 70 154 NS250N/200 22 46 NS250H/200 35 73 NS250L/200 50 105 NS250N/200 8 14 NS250H/200 10 17 NS250L/200 20 40 200 100 220 160 100 220 200 100 220 160 and 100M160 80 176 250 and 200M250 80 176 NS250N/250 36 75 NS250H/250 70 154 NS250L/250 150 330 NS250N/250 35 73 NS250H/250 65 143 NS250L/250 130 286 NS250N/250 30 63 NS250H/250 50 105 NS250L/250 70 154 NS250N/250 22 46 NS250H/250 35 73 NS250L/250 50 105 NS250N/250 8 14 NS250H/250 10 17 NS250L/250 20 40 250 100 220 160 100 220 200 100 220 200 and 100M200 80 176 250 and 200M250 80 176 NS400-630N/320 45 94 NS400-630H/320 70 154 NS400-630L/320 150 330 NS400-630N/320 42 88 NS400-630H/320 65 143 NS400-630L/320 130 286 NS400-630N/320 30 63 NS400-630H/320 50 105 NS400-630L/320 70 220-154 NS400-630N/320 22 46 NS400-630H/320 35 73 NS400-630L/320 100-50 220-105 NS400-630N/320 10 17 NS400-630H/320 20 40 NS400-630L/320 75-35 165-73 320 100 220 250 100 220 320 100 220 250 and 200M250 80 176 355 and 315M355 80 176 NS400-630N/400 45 94 NS400-630H/400 70 154 NS400-630L/400 150 330 NS400-630N/400 42 88 NS400-630H/400 65 143 NS400-630L/400 130 286 NS400-630N/400 30 63 NS400-630H/400 50 105 NS400-630L/400 100-70 100-70 220-154 NS400-630N/400 22 46 NS400-630H/400 35 73 NS400-630L/400 100-50 220-105 NS400-630N/400 10 17 NS400-630H/400 20 40 NS400-630L/400 75-35 165-73 400 100 220 315 100 220 400 100 220 315 and 200M315 80 176 355 and 315M355 80 176 65 E51067 Additional technical information Protection of switchdisconnectors Interpact switch-disconnectors / upstream protection By circuit breaker 380/415 V push to trip 90 %Ir 105 alarm STR Io .9 .8 23 SE Ir .93 .95 .98 .85 1 .5 4 3 Im5 6 8 2 .88 .63 .8 1 x Io Ir Im 10 1.5 Ir x x In test By circuit breaker 440/480 V (*) ¿5...8 By circuit breaker 500 V By circuit breaker 525 V By circuit breaker 690 V By fuse 500 V (*) suitable for 480 NEMA (1) mandatory protection by an external thermal (2) no external thermal protection 66 type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type / max. rating (A) Isc max. making capacity type aM (1) max. rating Isc max. making capacity type gG (2) max. rating Isc max. making capacity type gG (1) max. rating Isc max. making capacity type BS (2) max. rating Isc max. making capacity type BS (1) max. rating Isc max. making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak (A) kA rms kA peak INS500 / INV500 INS630 / INV630 IN1000 IN1600 IN2500 NS630N/500 45 94 NS630H/500 70 154 NS630L/500 150 330 NS630N/500 42 88 NS630H/500 65 143 NS630L/500 130 286 NS630N/500 30 63 NS630H/500 50 105 NS630L/500 70 154 NS630N/500 22 46 NS630H/500 35 73 NS630L/500 50 105 NS630N/500 10 17 NS630H/500 20 42 NS630L/500 35 73 500 100 220 400 100 220 500 100 220 400 80 176 450 and 400M450 80 176 NS630N/630 45 94 NS630H/630 70 154 NS630L/630 150 330 NS630N/630 42 88 NS630H/630 65 143 NS630L/630 130 286 NS630N/630 30 63 NS630H/630 50 105 NS630L/630 70 154 NS630N/630 22 46 NS630H/630 35 73 NS630L/630 50 105 NS630N/630 10 17 NS630H/630 20 42 NS630L/630 35 73 500 100 220 500 100 220 630 100 220 500 80 176 450 and 400M450 80 176 C1001-1251N/1000 40 84 C1001-1251H/1000 40 84 C1001L/1000 80 176 C1001-1251N/1000 40 84 C1001-1251H/1000 40 84 C1001-1251N/1000 35 73 C1001-1251H/1000 35 73 C1001L/1000 35 73 C1001-1251N/1000 35 73 C1001-1251H/1000 35 73 C1001L/1000 35 73 C1001-1251N/1000 25 53 C1001-1251H/1000 40 42 - CM / 1600 35 73 Masterpact / 1600 35 75 CM / 1600 35 73 Masterpact / 1600 35 75 CM / 1600 35 73 Masterpact / 1600 35 73 CM / 1600 35 73 Masterpact / 1600 35 73 CM / 1600 35 73 Masterpact / 1600 35 73 - CM / 1600 35 73 Masterpact / 2500 50 105 Masterpact / 2500 50 105 CM / 2500 50 105 Masterpact / 2500 50 105 CM / 2500 50 105 Masterpact / 2500 50 105 Masterpact / 2500 50 105 - 67 E62693 Additional technical information Protection of switchdisconnectors Compact switch-disconnectors / upstream protection By circuit breaker push to trip STR 90 %Ir 105 Im .9 8 2 1 1.5 22 DE 50/60H z test 6 3 .95 .98 .63 alarm 5 4 Ir .85 .8 .7 Ir Im 10 xIr xIn push to trip By fuse type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type aM (1) max. rating (A) Isc max. (500 V) making capacity (500 V) type gl (2) max. rating (A) Isc max. (500 V) making capacity (500 V) type gl (1) max. rating (A) Isc max. (500 V) making capacity (500 V) type BS (2) max. rating (A) Isc max. (500 V) making capacity (500 V) type BS (1) max. rating (A) Isc max. (500 V) making capacity (500 V) kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak Compact switch-disconnectors / upstream protection NS400NA By circuit breaker By fuse (1) mandatory protection by an external thermal (2) no external thermal protection 68 type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type / max. rating (A) Isc max. (380/415 V) making capacity (380/415 V) type aM (1) / max. rating (A) Isc max. (500 V) making capacity (500 V) type gl (2) max. rating (A) Isc max. (500 V) making capacity (500 V) type gl (1) max. rating (A) Isc max. (500 V) making capacity (500 V) type BS (2) / max. rating (A) Isc max. (500 V) making capacity (500 V) type BS (1) / max. rating (A) Isc max. (500 V) making capacity (500 V) kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak NSA125NA NSA160NA NS100NA NS160NA NS250NA NS160N / 125 36 75 NS160H / 125 70 154 NS160L / 125 150 330 NSA160N / 125 30 63 125 55 121 100 100 220 160 100 220 100 and 63M100 80 176 160 and 100M160 80 176 NS160N / 160 36 75 NS160H / 160 70 154 NS160L / 160 150 330 NSA160N / 160 30 63 160 33 69 125 100 220 160 100 220 125 and 100M125 80 176 160 and 100M160 80 176 NS100N / 100 25 52 NS160-250N / 100 36 75 NS100-250H / 100 70 154 NS100-250L / 100 150 330 NSA160N / 100 30 63 100 80 176 80 100 220 160 100 220 80 and 63M80 80 176 160 and 100M160 80 176 NS160-250N / 160 36 75 NS160-250H / 160 70 154 NS160-250L / 160 150 330 NSA160N / 160 30 63 160 33 69 125 100 220 160 100 220 125 and 100M125 80 176 160 and 100M160 80 176 NS250N / 250 36 75 NS250H / 250 70 154 NS250L / 250 150 330 250 100 220 200 100 220 250 100 220 200 and 100M200 80 250 and 200M250 80 176 NS630NA C801NI C1251NI NS400-630N / 400 45 94 NS400-630H / 400 70 154 NS400-630L / 400 150 330 400 100 220 315 100 220 400 100 220 315 and 200M315 80 176 355 and 315M355 80 176 NS630N / 630 45 94 NS630H / 630 70 154 NS630L / 630 150 330 500 100 220 500 100 220 630 100 220 500 80 176 450 and 400M450 80 176 C801-1251N / 800 50 105 C801-1251H / 800 70 154 C801-1001L / 800 150 330 - C1251N / 1250 50 105 C1251H / 1250 70 154 - 69 Notes 70 DBTP104GUI/E - © 2000 Schneider Electric - All rights reserved Schneider Electric Industries SA 5, rue Nadar 92506 Rueil Malmaison Cedex France As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Tel : +33 (0)1 41 29 82 00 Fax : +33 (0)1 47 51 80 20 http://www.schneiderelectric.com DBTP104GUI/E Published by: Schneider Electric Designed by: AMEG Printed by: 03-00