5. Troubleshooting 5.1 Troubleshooting for circuit-breaker proper (MCCB/ELCB) Trouble Cause Closing impossible Foreign matters to be removed No resetting To be reset once again Abnormal operation Resetting impossible Wear due to trip endurance Poor reset mechanism (*) Resetting impossible Tripping impossible See below (*) See below Incessant use of voltage trip operation To be replaced with new one, Voltage trip to be replaced by electric operation End of service life To be replaced with new one Poor adjustment To be returned for repairing Non-excitation of undervoltage coil Carelessness To be excited Resetting time has not elapsed Wait until the bimetal is cooled down Breakage by initial trouble To be returned for repairing switching spring End of service life To be replaced by new one Fusion of contact due to excessive interruptive current To be replaced by circuit-breaker with large breaking capacity Broken handle Breakage and/or fatigue of the Excessive operation power Handle to be replaced Poor positional relationship between the external handle and the Handle to be replaced circuit-breaker Revision of positional relationship Excessive shock from exterior To be replaced with new one Poor electrification OFF impossible Countermeasure Foreign matter in switching mechanism Insulating material mingled between contacts To be returned for repairing (with unremovable cover) Corrosion by infiltrating rain water, etc. To be replaced with new one Fused conductive portion To be replaced by new one with larger breaking capacity Large consumption of contact Excessive interrupting current Short-circuit current cut off. End of service life To be replaced with new one Application of overcurrent Breakage of rated changeover screw Excessive tightening torque (tighten with 3 to 4.5 kg-cm of torque) Too high an ambient temperature Troublesome operation under normal load Too high a temperature rise Deviation of applied frequency (thermaladjustable electromagnetic type 800AF or higher) Rating selection to be changed Board hermetically closed Ventilation Loosened connection to terminal Retighten Erroneous selection (frequency) Load current strained with much high component Distortion factor to be decreased by reactor Rather small measurements by error of measuring instrument due to distorted current To be measured correctly by a meter with true effective value, and correct selection of rating Troublesome operation Selection of rating to be changed Correct the setting of rated current display Tightening forgotten of the changeover screw of rated current Correct retightening of the rated current changeover screw with tightening torque: 3 to 4.5 kg-cm MCCB LED is on Failure of rated current changeover portion To be returned for repairing Erroneous action while Exothermic reaction due to repeated starting current Erroneous selection To be replaced by a unit with higher rating starting Too long a starting time Erroneous selection To be replaced by a unit with higher rating Operating while in use Short-circuit on line side Too high a starting current Electromagnetic setting to be change or the unit to be replaced by one with higher rating Too high a starting rush current Electromagnetic setting to be change or the unit to be replaced by one with higher rating Transient current when changing delta connection to star one. Transient current due to reversible operation Electromagnetic setting to be change or the unit to be replaced by one with higher rating Rush current at the time of instantaneous restart Electromagnetic setting to be change or the unit to be replaced by one with higher rating Rare short-circuit of motor Motor to be repaired Bimetal reset incomplete after instantaneous tripping To be fully restored Abnormal current running simultaneously with closing (short-circuit closing) Circuit to be checked to remove the cause Transmission was made with antenna of transceiver (5W or higher) Transceiver to be used at a distance at least 1 m from the electronic closely mounted on the electronic MCCB and earth leakage breaker MCCB Shift from the short-circuit of another conductor Cause to be removed To be replaced with new one Accumulated dust Cause to be removed To be replaced with new one Cause to be removed To be replaced with new one Fall of conductor on line side Too high a temperature on the terminal side Temperature rise To be replaced with circuit-breaker of suitable frequency type during starting Poor tightening Poor maintenance Retighten Contact heavily consumed End of service life To be replaced by new one Increased contact resistance Intrusion of rust and dust Foreign matters to be removed Too high a temperature on Complete electromagnetic type used in high frequency (400 Hz, for instance) Suitable frequency to be selected To be changed into thermal type. the lateral side of the Load current distorted containing much high frequency component Distortion factor to be decreased by reactor Selection of rating to be changed mould Erroneous measurement dependent on feeling To be measured with a measuring instrument Loosened stud Retighten Poor contact between the conductive portion of stud and the body terminal Reassemble the stud Groove machining forgotten for reduction of eddy-current exothermic reaction of rear-connected type iron mount plate (400AF or higher) Groove to be provided Too high a rated current selected To be replaced by a unit with lower rating Exothermic reaction of the tightened portion of stud No operation with tester No operation (electronic MCCB) To be returned for repairing Erroneous selection (temperature correction) Electronic Overcurrent Too small a setting of rated current Instantaneous action 79 Foreign matter to be removed (with removable cover) No tripping with over Suitable frequency to be selected Wrong frequency applied current Tripping of backup circuit-breaker Too low a current for instanta- Instantaneous electromagnetic switch to be lowered neous tripping of backup breaker Raise the electromagnetic setting of backup breaker or change the rating Overcurrent display LED does not come on. Or, though it comes on, it goes off sonner than normal. The battery of breaker tester has come at the end of its service life. Battery to be replaced. Overcurrent display LED comes on and goes off after prescribed time. But, no tripping. Poor tripping mechanism To be returned for repairing. 5.2 Troubleshooting for leakage operation portion Trouble Cause Countermeasure Operates simultaneously Too long a wire and too large a ground electrostatic with closing (such operation capacity causes the leak current to flow Trouble- of leakage mechanism as some popping-out of the leakage Normal operation due to leak current action display button) Refer to 5.4 Operates during use Leakage operation and the Poor lamp or its end of service life Abnormal Display button does not come out due to poor like by test button, but no operation adjustment display Trouble in electronic circuit No Depressing the test button No voltage applied operation does not lead to operation Poor continuity of contact Rated sensitivity current to be changed, or ELCB to be installed near load Leak point to be repaired To be replaced by new one To be returned for repairing To be replaced by new one Apply specified voltage Remove foreign matter on the contact 5.3 Troubleshooting of accessories Trouble Operation disabled NFM/NVM (electric operation device) Continuous idling One turn of idling when closing Closing disabled UVT (undervoltage tripping No tripping even device) with no voltage Cause Countermeasure Too low a capacity of the Increase the diameter of the wire wire of operational circuit Voltage drop of operational power supply Too low a capacity of the Improve the operational power supply operational power supply Burnt resistor/motor Regularize the wiring Regular operational voltage to be applied Self-sustaining auxiliary switch contact to be used for automatic resetting The contact for automatic resetting to be used as that for alarm switch Push button to be provided with interlock Voltage tripping in OFF state or tripping by undervoltage OFF operation once to reset and ON operation again The circuit-breaker proper has automatically cut off and tripped Erroneous frequency or voltage applied Power supply to be improved No pulling Too large a voltage drop Voltage to be improved Trouble in circuit-breaker tripping mechanism No tripping action Coil burnt out AL (alarm switch), AX (auxiliary switch), EAL (earth-leakage Malfunction alarm, switch), MG (Insulation switch) PAL (pre-alarm) To be returned for repairing (replacement of resister/motor) Erroneous wiring Erroneous voltage applied Operation of ON and OFF circuits at the same time or erroneous manipulation Insufficient voltage SHT (voltage tripping device) Excessive continuous operation To be returned for repairing Operational voltage drop Power supply to be improved Erroneous voltage applied Power supply to be improved To be returned for repairing (replacement of Continous excitation coil, auxiliary contact to be provided for of coil protection from burning) Continuous excitation under a voltage To be returned for repairing (replacement of inferior to the operating voltage coil), power supply to be improved Poor auxiliary contact for prevention of burning Abnormal voltage applied Poor contact due to overcurrent Erroneous wiring Erroneous wiring when installing To be returned for repairing (replacement of coil, contact to be repaired) To be returned for repairing (replacement of coil) To be returned for repairing Regular wiring to be made referring to the name plate To be returned for repairing (to be replaced with that for microload) Microload Erroneous selection Loosened attaching screws Insufficient tightening To be returned for repairing (re-adjustment) Vibration during transportation 80 5.4 Analysis of unnecessary operation Operation of ELCB by the causes on purpose, leak current, electrification, ground fault etc., is normal, while operation by other causes such as surge and induction is unnecessary (called stray operation or nuisance trip). It seems that quite a number of users have the preconception that earth leakage circuit breakers are troublesome as they operate unreasonably. Therefore, unnecessary operation is analyzed and selection of correct ELCB is stated in the following text. 5.4.1 Classification of ELCB operation ELCB operation is classified as follows; (1) Operation by leak current, electrification, ground Normal operation fault etc. Those attributable to ELCB Operation Unnecessary operation Those attributable to circuit and others (2) Fault of earth leakage circuit breaker (3) Inadequate sensitivity current (too sensitive) (4) (5) (6) (7) (8) (9) Operation by surge Operation by circulation current Operation by induction Operation by wrong wire connection Operation by inadequate earth Operation by influence of at ground fault of shunt circuit (10) Operation by overload or short-circuit (11) Operation by environment (vibration, impact etc.) (12) Operation by carrier phone unit (13) Operation by electromagnetic wave (14) Operation by inverters (15) Others (Operation of surge absorber etc.) 5.4.2 Detail of operation (1) Normal operation Operation of ELCB according to each purpose. Primary examples are shown below. 1 Deterioration of equipment insulation ...... This is often the case with water handling devices such as washing machine and those subjected to high impact such as press machine. 2 Deterioration of wire insulation ................ This is often the case with joints and terminals of temporarily installed electric lines. 3 Faulty work .............................................. Ground fault by damage or disconnection of cables during work. 4 Careless handling .................................... Electrification by wetting and ground fault by surge or dropped foreign matter. (2) Fault of ELCB Failure caused by deterioration and corrosion of parts but fault of the leak detecting unit is rare. In some cases, closing becomes unstable because of wear of the magnet or the switching mechanism. Besides such fault, ELCB of low balancing characteristic tends to operation when the motor starts. It is, therefore, necessary, to use ELCB made by reliable manufacturers. (3) Inadequate sensitivity current ELCB operates if the sensitivity current is too sensitive compared with normal leak current of the circuit. This is a matter of selection. In most cases, leak current from circuits is attributable to static capacity to ground of the wire. Of some electric furnaces and sheath heaters, the insulation resistance comes down when cooled even if the insulation resistance is enough at high temperature, and it takes time to find out the cause of ELCB operation. As to leak current from circuits, it must also be noted that ELCB is operated not only by leak current under normal condition but also by transient leak current to ground at switching or at start-up. Transient leakage at start-up is generated through static capacity to the frame of winding as potential distribution of winding at start-up differs from that during operation. 81 (4) Operation by surge To surge by secondary transfer of inductive lightening of wires, non-operation test by lightening impulse is set forth in JIS C-8371, and surge resistivity is ensured. Circuit of the lightening impulse non-operation test is shown at right. Almost all NVs of Mitsubishi are provided with a DPDC surge discrimination circuit for judging leak current to ground by ground fault current and surge so as to improve unnecessary operation preventing function. 7kV U V C R W Lightening impulse voltage generator C : 0.03µF R : 0.1MΩ Test circuit of lightening impulse non-operation (5) Operation by loop circuit (circulation current) In the parallel circuits connected at load side, diverted current of each phase isn’t necessarily equal between the right and the left branches. If A phase is diverted into 11A and 9A, for example, the difference of 1A is to be circulating in the loop. Parallel use of two ELCBs is therefore prohibitive as the circulation current causes operation of the earth leakage circuit breaker. (5) Operation by induction Those with loop circuits are susceptible to induction. Taking a loop as a loop antenna, the primary winding of ZCT is to be connected with the antenna, and induction is easily generated. When a common earth wire is used, place the ZCT at the position of the continuous line in the drawing, then the primary conductor of the ZCT forms a loop. To avoid this, the ZCT must be placed at the position shown by the dotted line in the drawing. Induction can also be generated in the input circuit of the earth leakage relay, and it is necessary to braid the lead wires between the earth leakage relay, and the ZCT. ELCB 1.2×50µS A ELCB 11A B ELCB 1A 10A Load 9A 10A 20A Parallel circuits M ZCT ZCT Common earth wire Steel base Ground fault detection by earth wire 82 (7) Operation by wrong wire connection Failure in passing the neutral wire through the ZCT for the lines of single phase 3-wire or 3 phase 4wire is a simple mistake. In this case, the ELCB is operated by single phase load current. ZCT Load Wrong wire connection of 3 phase 4-wire line On the other hand, the common earth wire shall not go through the ZCT as it can be cause malfunction at leakage. M ZCT Common earth wire Wrong connection of common earth wire (8) Operation by inadequate earth Though the wire is grounded at the earth side, the wire shall not be earthed at the load side. By the voltage of voltage drop in the line at the earth side, a part of the load current is diverted as shown by I’T, and the ELCB is operated. M IT I'T Inadequate double ground (9) Operation of sound circuit at ground fault of shunt circuit Not only the ELCB in the ground fault circuit but also the one in the sound circuit is operated in some cases through the circuit as illustrated below. This can be avoided by keeping sensitive current suitably for the leak current by static capacity to ground. Fault circuit Sound circuit Operation of sound circuit by static capacity to ground (10) Operation by overload and short-circuit It is natural that the devices having overload or short-circuit operation elements operate at short-circuit. However, ELCB is commonly used for many other purposes, and it tends to be overlooked that ELCB operate even at an overload and a short-circuit failure. Moreover, even the one dedicated to ground fault is sometimes operated by an excessive overload and short-circuit because balance performance of ELCB is limited. In these cases, however, overload and short-circuit can be noticed if they are significant. (11) Environment of vibration, impact, high temperature etc. These factors may be taken almost equal to those of Mitsubishi’s MCCB. Heat resistivity of electronic circuits tends to be fell unreliable. To Mitsubishi’s ELCB, enough allowance is given to ratings of the parts, the parts which can withstand high temperature operation are used, and the ICs incorporating tempereture compensation circuits are used to ensure stable operation even in varying temperature environment. 83 (12) Operation by carrier phone unit Malfunctions of the ELCB can result in some cases when attached to a line provided with a carrier phone, which enables calls through the power line. Since the carrier phone forcefully gives high frequency signals (normally 50kHz to 400kHz) between the line and the ground, the ELCB detects the high frequency signals as if they are leak current and leads to malfunction. Malfunction or not depends largely on magnitude of the high frequency signals, high frequency characteristic of the ELCB, and degree of rated sensitive current. (13) Operation by electromagnetic wave When a portable type transceiver is placed near the ELCB at transmission, particularly intense magnetic field is generated easily resulting in malfunction. Generally speaking, frequency bands of portable type transceivers are 27/28MHz, 50/50MHz, 150MHz, 400MHz, and 900MHz, and the output is about 0.5 to 5W. It is confirmed that the ELCB is free from any malfunction when different kinds of transceivers of 5W output are used for transmission being placed at 1m from the ELCB. (14) Operation by inverters Inverters operate many high-frequency components as they turn A.C. power supply to D.C. through rectification, then turn to A.C. again by switching through transistors. Increased static capacity to ground sometimes causes malfunctions as the high frequency components are kept flowing by the static capacity to ground. To use ELCB in general in an inverter circuit, it is necessary to select those of lower sensitive current than usual in order avoid unnecessary operation. For ground fault detection of high sensitivity in inverter circuit and yet for stable ground fault detection at both the primary and the secondary sides of the inverters, it is necessary to use an ELCB designed for higher harmonic earth-leakages and surges, which is hardly affected by high frequency components, as the measure against the inverter. It is also essential to install the ELCB at the primary side of the inverter, and never at the secondary side. Inverter ELCB 1C1 IM 1C2 Applicable circuit to inverter (15) Others A load equipment is protected by a surge absorber As electronic arrangement of load equipSurge ment advances, surge absorbers are inLoad equipment stalled in the equipment more and more to ELCB Circuit and protect them against surge. As the surge abroute of leak Load sorbers connected to the ground discharge IS current to equipment ground the surge to the ground, a high leak current Discherge gap type absorber is generated to the ground, for a short time IS though, and unnecessary operation of the Gapless surge absorber ELCB is resulted in some cases. Most Mitsubishi’s ELCB are provided with a Leak current to ground through surge absorber DPDC surge discriminating circuit for judging ground fault current by failure such as faulty insulation from leak current to ground by surge, and improvement in the performance of preventing unnecessary operation is realized even when the surge absorber is installed between the line and the ground. 84