TACOTHERM FRESH PETA C / CL ADVANTAGES Efficient High transmission performance and low pressure loss thanks to microplate plate heat exchanger Compact and versatile Model with and without circulation pump, dual-zone return stratification Cascading possible Secure Integration in building control system via optionally available modbus interface Integrated safety subassembly and soft-close valves Simple Valves and components are fully preassembled as well as fully wired ready for connection FRESH HOT WATER STATION WITH HIGH-EFFICIENCY PUMPS ■■ ■■ ■■ ■■ ■■ ■■ Fresh hot water station for hygienically heating drinking water in accordance with the continuous flow principle with and without dual-zone return stratification of the storage tank. DESCRIPTION The TacoTherm Fresh Peta C / CL fresh hot water station is used for heating drinking water on demand in accordance with the cyclical principle in conjunction with a storage tank for existing and new heating systems, wood-burning boilers, heat pumps and solar systems. The station replaces the storage of hot drinking water in an additional storage unit and thus provides a high degree of protection against Legionella by avoiding water stagnation. INSTALLATION POSITION Vertical wall-mounting in the vicinity of the hot water storage tank or on the tank itself. OPERATION Drinking water is heated to the defined dispensing temperature in the TacoTherm Fresh Peta C / CL in accordance with the continuous flow principle. The integrated heat exchanger is supplied with as little hot water from the storage tank as is required to maintain a constant dispensing temperature. A low return temperature of the heating water to the storage tank can be expected owing to the special design of the heat exchanger. In recording the temperature difference and flow rate data, the electronic regulator simultaneously records and stores the quantity of heat consumed. The TacoTherm Fresh Peta C / CL can be supplied optionally with a switching valve for storage stratification. This pump and also the load valve are controlled by the integrated regulation system by means of a separate program. BUILDING CATEGORIES Apartment blocks Housing estates Multiple dwelling units Residential care facilities and hospitals Administration and service buildings Hotels and restaurants, industrial kitchens School buildings and sports facilities Commercial and industrial buildings, industrial facilities Facilities with partial use – for example barracks, camping sites, etc. ■■ ■■ SYSTEM/BASIC DIAGRAM ■■ ■■ ■■ T ■■ ■■ T ■■ ■■ TACOTHERM FRESH PETA C / CL | FRESH HOT WATER STATION TECHNICAL DATA General TacoTherm Fresh Peta controller with display Weight (empty): 46 kg Overall dimensions (incl. hood): W 528 mm × H 854 mm × D 193 mm Material Base plate: Galvanized sheet steel Hood: Varnished sheet steel Pumps: Primary: Cast iron Secondary: PPS (plastic, approved for drinking water) Valve housing: Brass Pipes: Primary/secondary DN 32, stainless steel 1.4403 Circulation DN 25, stainless steel 1.4403 Microplate plate heat exchanger: Plates and connector pieces: Stainless steel 1.4401 Heat exchanger solder: 99.99 % copper (nickel solder model available on request) Seals: AFM flush seal Primary side Operating temperature TO max: 95 °C Operating pressure PO max: 10 bar Primary pump: Grundfos UPML 25-105 Secondary side Modules on secondary side with drinking water certifications Operating temperature TO max: 85 °C Operating pressure PO max: 10 bar Safety valve (intrinsic safety) 10 bar discharge pressure Circulation pump: Grundfos UPM3 CIL Performance data See design diagram Electrical connection data Mains voltage: 230 VAC ± 10 % Mains frequency: 50...60 Hz Power consumption: max. 250 W, 3.5 AT fuse Optional interface for M-BUS Protection type: IP 40 Flow media Heating water (VDI 2035; SIA 384/1; ÖNORM H 5195-1) Cold water ■■ ■■ ■■ TYPE OVERVIEW TacoTherm Fresh Peta C / CL | Fresh hot water station Order no. Rp Version Version 273.6632.000 1 ¼" IT C Without dual-zone stratification 273.6630.000 1 ¼" IT CL With dual-zone stratification Without dual-zone stratification and 272.6030.000 1 ¼" IT circulation Modbus interface for integration with 296.7027.000 1 ¼" IT building control system DIMENSIONAL DRAWING ■■ 518 ■■ ■■ 4 ■■ 177 92 44 322 12 42 ■■ 6 35 1 6 SPECIFICATION TEXT See www.taconova.com ■■ ■■ 8 ■■ 9 7 515 11 648 ■■ 854 ■■ 12 ■■ ■■ 470 10 13 5 ■■ 42 85 ■■ 2 116 3 6 ■■ 257 ■■ PRODUCT DIAGRAM 4 6 1 ■■ ■■ ■■ T ■■ T T 8 ■■ 9 • V 7 11 ■■ T ■■ T ■■ 13 10 M ■■ ■■ ■■ 5 2 3 ■■ ■■ 1 2 3 4 5 6 Primary hot water flow Primary hot water return 1 (integration of storage tank below) Primary hot water return 2 (integration of storage tank in center in CL models) Circulation Cold water connection Hot water connection 7 8 9 10 11 12 13 Primary pump Circulation pump Flow rate sensor Safety valve Heat exchanger Regulator Switching valve (CL version) TACOTHERM FRESH PETA C / CL | FRESH HOT WATER STATION FLOW AND PRESSURE LOSS DIAGRAMS COLD WATER HEATING AT 50K (10 ... 60 °C) TacoTherm Fresh Peta CL TacoTherm Fresh Peta CL TacoTherm TacoTherm Fresh Peta Fresh CL Peta CL D) Secondary pressure loss 40 40 55 55 Dispensing 60 (l/min) 55 40 55volume 70 60 60 60 22 20 19.5 18 16 14 12 10 10 25 Rücklauftemperaturen 65 °C Rücklauftemperaturen Rücklauftemperaturen Hot water demand (l/h) 3600 3500 3000 2500 2000 1500 1000 500 10 4000 3600 4000 3500 3600 3500 3600 3500 3000 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 1500 1000 1000 1000 500 500 10 500 10 10 25 60 70 60 70 Zapfmenge l/min 60 60 Zapfmenge l/min 70 volume (l/min) Kaltwassererwärmung um 50K (10-60°C) Zapfmenge l/min Zapfmenge l/min Kaltwassererwärmung um 50K (10-60°C) Kaltwassererwärmung Kaltwassererwärmung um 50K (10-60°C) B)(10-60°C) Residual 400 um 50K 65 °C 70 °C 400 65°C 350 400 400 65°C4000 350 65°C75 °C 65°C3600 300 350 350 70°C3500 300 70°C 250 300 300 70°C 250 70°C3000 40 40 40 55 Dispensing 55 55 55 70 200 250 200 75°C 150 200 200 150 100 150 150 kW 100 Leistung 100 100 KW 50 50 0 50 50 55 70 0 60 55 0 60 70 0 55 70 70 60 Zapfmenge l/min 250 Output 25 25 25 40 75°C 75°C 75°C 75 °C 75°C 25 25 25 40 70°C 70°C 70°C 70 °C 70°C 4000 water heating at 50K A) Cold 4000 65°C 65°C 65°C 65°C 40 40 40 55 kW W Return temperature (° C) 24 lust lust lust mbar mbar mbar Druckver Druckver Druckver Zapfmenge l/min Zapfmenge l/min Rücklauftemperaturen Zapfmenge l/min Zapfmenge l/min C) Return temperatures 24 24 24 22 22 22 20 19.5 20 19.5 20 19.5 18 18 18 16 16 16 14 14 14 12 12 10 12 10 70 70 70 60 Dispensing volume (l/min) 75°C 75°C2500 75°C Leistung 2000 Leistung KW KW Leistung 1500 KW 1000 Restförderhöhe Restförderhöhe head 4000 | Primary pressure loss Restförderhöhe Restförderhöhe Heizwasserbedarf H Heizwasserbedarf H Heizwasserbedarf H Liter Liter Liter r/h r/h r/h 10 25 25 25 40 Rücklauftemperatu Rücklauftemperatu Rücklauftemperatu °Cur °C°C ur ur 0 Zirkulationpumpe UPM3 Heizwasserbedarf Heizwasserbedarf Heizwasserbedarf LLiter/h LLiter/h LLiter/h 100 5500 4750. 0 4300 3750 3200 2750 2250 Zirkulationpumpe Zirkulationpumpe UPM3 UPM3 Zirkulationpumpe UPM3 Hot water demand (l/h) 200 Druckverlust Druckverlust Zirkulation Zirkulation Druckverlust Zirkulation kW WkW WkW W 300 Druckverlust Zirkulation 3 Heizwasserbedarf Literr/h H 400 Druckverlust sek. Druckverlust mbar 500 Druckverlust sek. 1 Rücklauftemperatu ur °C 600 l/h 1 Secondary pressure loss 2 Secondary pressure loss in circulation Druckverlust sek. Druckverlust3 sek. Pump characteristic in circulation kW 700 2 Heizwasserbedarf LLiter/h Pressure loss (mbar) 800 800 800 700 800 700 600 700 600 500 600 500 400 500 400 300 400 300 200 300 200 100 200 100 0 100 0 10 0 10 10 25 Grundfos UPML 25105 Druckverlust Sekundär Druckverlust Sekundär Druckverlust Sekundär Druckverlust Sekundär mbar Zapfmenge l/min 500 mbar Zapfmenge l/min mbar mbar 100 Zapfmenge l/min 4000 3600 4000 3500 3600 3500 3600 3500 3000 3000 3000 2500 2500 2500 2000 2000 2000 1500 1500 1500 1000 1000 1000 500 500 100 500 100 300100 (∆p) (∆p) (∆p) (∆p) 300 300 550 500300 500 550 500 550 725550 700500 700725 700725 900700725 Pressure loss (mbar) EXAMPLE FOR INTERPRETING THE FLOW RATE AND PRESSURE LOSS DIAGRAMS Given Hot water dispensing volume: 60 l/min Primary heating flow temperature: 70 °C ■■ ■■ Sought Hot water demand (l/h) Primary heating return temperature in °C Secondary pressure loss in mbar Primary pressure loss in mbar ■■ ■■ ■■ ■■ Approach In Diagram A) the hot water demand at the intersection point of the dispensing volume of 60 l/min and primary flow temperature of 70 °C is 3600 l/h. In Diagram B) the primary pressure loss for a hot water demand of 3600 l/h is 550 mbar. The pump delivery head is 725 mbar, discounting the pressure loss this gives rise to a residual pump head of 175 mbar (Δp). ■■ ■■ ■■ ■■ In Diagram C) the primary return temperature for a given dispensing volume of 60 l/min and the selected flow temperature of 70 °C is 19.5 °C. In Diagram D) the secondary pressure loss for the given data is 400 mbar 900 900 900 TACOTHERM FRESH PETA C / CL | FRESH HOT WATER STATION FLOW AND PRESSURE LOSS DIAGRAMS COLD TacoTherm WATER HEATING Fresh AT 35K (10 ... 45 °C) Peta CL TacoTherm Fresh Peta CL D) Secondary pressure TacoTherm TacoTherm Freshloss Fresh Peta CL Peta CL Druckverlust Sekundär C) Return temperatures 11 20 20 19 19 20 18 18 19 17 17 18 16 15.8 16 17 15.8 15 15 16 14 15.8 14 15 13 13 14 12 12 13 11 11 12 10 10 10 11 10 10 Return temperature (° C) 20 18 17 16 15.8 15 14 13 12 10 67 70 67 70 40 55 67 55 70 67 70 85 48 °C 50 °C Rücklauftemperaturen Rücklauftemperaturen 48°C55 °C 50°C 55°C 55 C60 °C 60°C 65 °C 70 °C 70°C 75 °C 65°C 75°C 10 25 25 10 25 25 40 40 40 67 70 67 70 55 55 Dispensing volume 67 40 55 55 70 (l/min)67 70 85 Kaltwassererwärmung Kaltwassererwärmung um 35K (10-45°C) um 35K (10-45°C) 350 2500 3000 2500 300 2000 2500 2000 250 Hot water demand (l/h) 3600 3000 3500 3000 1000 500 10 48 °C 50 °C 55 °C 400 200 1500 2000 1500 150 1000 1500 1000 500 1000 500 10 10 500 10 25 100 25 25 25 40 70°C 65°C 75°C 75°C 70°C Kaltwassererwärmung um 35K (10-45°C) Zapfmenge l/min Kaltwassererwärmung um 35K (10-45°C)Zapfmenge l/min 3600 3500 1500 65°C 60°C 70°C Zapfmenge l/min Zapfmenge l/min 85 4000 2000 48°C 48°C 50°C 50°C 48°C 55°C 55 C 55°C 55 C 50°C 60°C 60°C 55°C 55 C 65°C 75°C 85 85 4000 3600 3500 3600 4000 3500 2500 Zapfmenge l/min Zapfmenge l/min Rücklauftemperaturen Rücklauftemperaturen Zapfmenge l/min Zapfmenge l/min 85 A) Cold 4000 water heating at 35K 3000 Druckve Druckve Druckve mbar mbar mbar erlust erlust erlust 85 40 40 55 55 67 70 67 70 40 55 55 70 67 67 70 85 Dispensing volume (l/min) 50 0 B) Residual 400 48°C 400 48°C 350 50°C 350 60 °C 50°C 400 4000 48°C 48°C 55°C 300 3600 55°C 300 350 50°C 65 °C 50°C 3500 60°C 250 60°C 55°C 70 °C 55°C 250 300 65°C 3000 200 75 °C 65°C 60°C 60°C 70°C 200 250 70°C 2500 150 65°C 65°C 75°C 150 200 75°C 70°C 70°C 100 Leistung 2000 100 KW 150 Leistung 75°C 75°C KW 50 1500 50 100 Leistung Leistung 0 KW KW 1000 0 85 50 mbar l/min mbar 85 l/min 500 0 85 mbar mbar100 l/min l/min Restförderhöhe Restförderhöhe head 4000 | Primary pressure loss Restförderhöhe Restförderhöhe 4000 3600 3500 3600 4000 3500 3600 3000 3500 3000 (∆p) (∆p) 2500 3000 2500 (∆p) (∆p) 2000 2500 2000 1500 2000 1500 1000 1500 1000 500 1000 500 100 500 100 100300 300 300 500 550 500 550 700 725 700 725 900 900 300500 550 500700 550 725 700900 725 900 Pressure loss (l/min) NOTE REQUIREMENTS FOR FLOW MEDIA The stations heat interface units use a copper-soldered stainless steel plate heat exchanger as standard. It must be checked prior to use in the framework of system planning whether the issues of corrosion protection and scale formation have been sufficiently taken into account in accordance with DIN 1988200 and current drinking water analyses according to DIN EN 8065. See datasheet „Plate Heat Exchanger Requirements - Limit Values for Drinking Water Quality“. CONTACT AND FURTHER INFORMATION TACONOVA.COM Taconova Group AG | Neunbrunnenstrasse 40 | CH-8050 Zurich | T +41 44 735 55 55 | F +41 44 735 55 02 | group@taconova.com Subject to modification. 04/2016 19 25 40 55 55 Dispensing volume (l/min) Heizwasserbedarf Heizwasserbedarf Heizwasserbedarf Liter/hLiter/h Liter/h 10 25 40 40 5500 4750. 0 4300 3750 3200 2750 2250 Rücklauftemp Rücklauftemp Rücklauftemp peratur peratur °C peratur °C °C 10 25 25 Hot water demand (l/h) 0 Heizwasserbedarf Liter/h 100 Zirkulationp umpe 85UPM3 l/h Druckverlus t sek. Druckverlus tDruckverlus Zirkulation t Zirkulation Druckverlus t Zirkulation Zirkulationp umpe Zirkulationp UPM3 umpe UPM3 Zirkulationp umpe UPM3 kkWkkW Heizwasserbedarf Heizwasserbedarf Heizwasserbedarf Liter/h Liter/h Liter/h 200 Druckverlus t Zirkulation 1 Secondary pressure loss Druckverlus2 Secondary pressure loss in circulation tDruckverlus sek. 3 Pump characteristic in circulation t sek. kkW 300 3 Rücklauftemp peratur °C 400 Druckverlus t sek. kW 500 Druckve erlust mbar 600 1 Heizwasserbedarf Liter/h 700 Druckverlust Sekundär 2 Druckverlust Druckverlust Sekundär Sekundär kkW Pressure loss (mbar) 800 800 800 700 700 800 600 600 700 500 500 600 400 400 500 300 300 400 200 200 300 100 100 200 0 0 10 100 10 0 Grundfos UPML 25105 Grundfos UPML 25Grundfos 105 UPML 25105 Grundfos lUPML /h 25l105 /h prima r l/h mba r 5 5 0 01 0 0 45755000. 02 0 0 44735000. 03 0 0 3 7 50 04 0 0 45 30 5 3775500. 05 0 0 43200 3200 2750 4 3 0 06 0 0 2250 3 7 5 07 0 0 2750 2250800 3200 2750900 2250 1000 1000 p p p