Impact of Short Circuit Current Rating on UL1995 Equipment Son Dinh Application Design Engineer OEM Technology and Solutions Center Schneider Electric What is this Short Circuit Current Rating (SCCR) requirement? The National Electrical Code (NEC) is primarily concerned with preventing fires, not damage to electrical apparatuses. NEC’s interest in the SCCR is the amount of momentary electrical current that a device can withstand before it will produce an uncontainable fire and/or explosion. If the fault current is less than the equipment’s SCCR, then the equipment should mitigate, the preceding hazards. The SCCR rating (rated in kA) is different than the current rating (Amps) of a device. The current rating is the designed continuous current that the device can handle without reduction of the anticipated life (or tripping, in the case of a circuit breaker). The NEC, Article 409, is a code article that specifies the minimum requirements for an industrial control panel. Article 409 was created in response to panel failures and general misuse. The requirements are a consolidation of requirements applicable to all control panels that were previously contained in the other various articles of the NEC. NEC 409 is titled “Industrial Control Panels”, however, the requirements are also applicable to other specialty panels such as Crane and Hoist, Elevator, Industrial Machinery, and Air Conditioning and Refrigeration control panels as stated in NEC 409.3 and Table 409.3. There are three sentences in NEC 409.110(3) that require a control panel to have a marked short circuit current rating (SCCR). (Extracted from NFPA 70 – National Electrical Code 2008 edition) Currently the NEC only recognizes two methods to determine a panels’ SCCR rating. a. Short-circuit current rating of listed and labeled assembly, b. Short-circuit current rating established utilizing an approved method, Impact of Short Circuit Current Rating on UL1995 Equipment Method (a) would require 3rd party testing and certification and for method (b) the only recognized approved method by the NEC is UL 508A, Supplement SB as stated in the Fine Print Notation (FPN) of the requirement. Furthermore, NEC Article 440 specifies the installation and construction requirements for Air-Condition and Refrigeration Equipment. Article NEC 440-4(B) requires HVAC equipment with multiple motors and/or loads to be marked with the SCCR rating of the motor controllers or industrial control panel. Satisfying this requirement will require a major shift in control panel design for most manufacturers. Therefore, the driver of this SCCR requirement is the NEC, specifically Articles 409 and 440. What is UL 508A, Supplement SB? Underwriters Laboratories (UL) standard for Industrial Control Panels is UL 508A. It is one of the most popular methods used by manufacturers for ensuring a quality industrial control panel construction and for satisfying the requirements of the NEC. Some of the requirements contained in UL 508A are enclosure environmental rating, electrical spacings, component usage, wire ampacity sizing, sizing of overcurrent protection, and markings to name a few of the topics covered by the standard. However, a full discussion of UL 508A is well beyond the scope of this paper. Within UL 508A, section Supplement SB contains the requirements for designing and rating a control panel for a short circuit current rating (SCCR). These requirements allow the engineering of a panel’s SCCR rating without performing short circuit testing on the panel assembly which is destructive and cost prohibitive for most control panel builders. This method is commonly termed “the weakest-link” method since the panel’s overall SCCR rating is based on the lowest SCCR rating of any power component or power assembly that forms the power circuitry of the control panel. For the majority of panel builders, the most practical means to assign a SCCR rating to a control panel is through the use of UL 508A, Supplement SB. Currently UL 508A, Supplement SB is the only approved method other than performing short circuit testing on the panel to comply with the SCCR requirement of NEC 409.110(3). If compliance with UL 508A is met, then compliance with NEC 409 will also be met. What is UL 1995? Underwriters Laboratories (UL) standard UL1995 is the bi-national standard (US & Canada) for Heating and Refrigeration equipment. Examples of equipment within the scope of UL1995 are heat pumps, air conditioners, chillers, and air handlers. UL1995 currently does not require Heating Ventilation AirConditioning (HVAC) equipment or the control panel to have a marked SCCR rating. NEC Article 440, specifies the installation and construction requirements for Air-Condition and Refrigeration Equipment. NEC 440-4(B) requires HVAC equipment with multiple motors and combination loads to be marked with a SCCR rating. (Extracted from NFPA 70 – National Electrical Code 2008 edition) In response to this NEC requirement, UL issued a Certification Requirement Decision (CRD) bulletin for UL1995 in February of 2008. The CRD contains proposed new requirements that will require HVAC equipment manufacturers to mark their equipment with a SCCR rating. One of the methods allowed is using UL 508A, Supplement SB. The CRD is currently optional until the requirements are officially added to the standard. Therefore, UL1995 now has optional requirements for the determination of a SCCR rating for the HVAC equipment that allows 3rd party certified and labeled equipment to be rejected (red-tagged) by the Authority Having Jurisdiction (AHJ) due to non-compliance with NEC 4404(B) if it is enforced. 2 of 6 Impact of Short Circuit Current Rating on UL1995 Equipment What is the minimum SCCR level? The SCCR requirement does not specify a minimum short circuit current value. It only requires that the equipment or panel be marked with a SCCR value. The intent is that the panels’ SCCR value will be used to judge its’ suitability and acceptance based on the available short circuit fault current to the equipment or panel at the installation site. In order to obtain the available short circuit fault current, a short circuit fault study would need to be conducted by a qualified engineer. The following table in Appendix A illustrates an approximate maximum available fault current on the secondary output (480V, 3 phase) of a power distribution transformer based on the transformers’ kVA rating. For the higher available fault currents to be possible, it would require a very large power distribution transformer. Furthermore, Ohm’s Law proves that this fault current will be reduced the further downstream the equipment or panel is located relative to the power distribution transformer. The figure in Appendix B illustrates an example of the reduction of available fault current as a result of conductor impedance and the equipment’s distance relative to the power distribution transformer. What is the impact on HVAC equipment? Some or all of the following effects may be experienced by HVAC equipment manufacturers in complying with the SCCR requirement. • • • • Increases engineering time and labor to determine SCCR rating, Short circuit testing may be needed to achieve desired SCCR rating, Specific component selection and usage required to achieve the desired SCCR rating, Redesign of equipment. In order to achieve a desired SCCR rating by using UL 508A, Supplement SB, engineers will need to verify and document the SCCR ratings of all of the power components. For the majority of components, the marked SCCR rating is not the stand alone SCCR rating for the component. The component is additionally marked to state that it is suitable for up to a certain SCCR rating and voltage when protected by the specified short circuit protective device(s). The exceptions to this are short circuit protective devices like circuit breakers and fuses and other devices that have been tested without any additional upstream short circuit protection. The following is an example of how a component’s SCCR rating may appear. Therefore, to maintain the component’s SCCR rating, one must abide with the specified short circuit protection type and stated maximum size. According to UL, the SCCR rating(s) for a component can appear on the product label, on the product carton, on an instruction sheet that is provided with the component, or on UL’s website (for some products). Additionally, components and assemblies can be tested and specifically described in the equipment or panel manufacturer’s 3rd party certification file. In some cases, the equipment or panel manufacturer may choose to have the equipment or assembly short circuit tested for a desired SCCR rating. This may be the only option if the equipment or panel uses custom or proprietary electrical components or assemblies that lack the desired SCCR rating. In some cases, depending on several factors (number of variations, weakest-link, redesign costs, lack of solutions, etc.), it may be more cost effective to test a current design instead of performing a redesign of the equipment or panel. 3 of 6 Impact of Short Circuit Current Rating on UL1995 Equipment Generally, in order to achieve a rating of more than 5kA, component selection is critical. It is very difficult to inter-mix components from various manufacturers and expect to achieve a higher SCCR rating for the power circuit. This is because most component manufacturers have no vested interest in testing their component in conjunction with a competitor’s component if they offer a competing component (i.e. contactor and overload relay). Furthermore, achieving a higher SCCR rating is often more difficult because fewer product options may exist that meet these rating requirements. This is analogous to NEMA environmentally rated components. There exists more product availability with a NEMA 12 versus a NEMA 4X due to the difficulty in achieving a 4X rating. UL 508A, Supplement SB is structured on the weakest-link method. Therefore, the overall panel SCCR rating is determined based on the lowest SCCR rated power component. If component substitutions are used from a different or the same manufacturer in order to achieve the desired SCCR rating, design changes will be very likely since industrial components are not “plug-&-play” and often have different dimensions and terminal connections that require updates to the panel layout, drawings, and bill of materials to achieve the desired SCCR rating. Designing a one size fits all panel with a high SCCR rating (for example, 65kA), will likely increase the cost of the equipment. This is because 65kA solutions generally cost more than an equivalent solution with a lower SCCR rating. Also, for a given component, it may have different SCCR ratings at different voltages (for example, 65kA @240V and 25kA@480V). So at 480V, a different solution would be required if the 65kA component rating is desired. Further more, some components may have the desired SCCR rating but only at a Wye voltage rating (480/277 or 600/347) instead of a Delta voltage rating, see example below If using Wye voltage rated component(s), this automatically limits the panel for use on a Wye voltage system because a component must be used within its marked and certified ratings. In all cases, a panel will need to be minimally engineered and documented in order to substantiate the panel’s marked SCCR rating. The degree of impacts previously discussed will vary depending on the components currently used in the panel and their SCCR rating along with the overall desired SCCR rating for the panel or equipment. For more information on UL 508A, Supplement SB, visit Schneider Electric’s website at www.us.squared.com/UL 508A. 4 of 6 Impact of Short Circuit Current Rating on UL1995 Equipment APPENDIX A Approximate available short circuit fault current at the secondary terminals of a power distribution transformer. For most typical installations, far lower levels are the norm particularly when the utility source fault level and impedance are taken into account. 5 of 6 Impact of Short Circuit Current Rating on UL1995 Equipment APPENDIX B Illustrates that short circuit fault current is a factor of the power distribution transformer size (reference Appendix A) and the impedances of the power conductors and other equipment upstream of the end equipment or control panel. 6 of 6