FBP140XLP Instruction Manual
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS
BE OBSERVED INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION: To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power
Risk of Fire/
is supplied to the unit.
Electric Shock
If not qualified, consult an
2. CAUTION: This fixture provides more than one power supply output source. To reduce the risk of electrical
electrician.
shock, disconnect both normal and emergency sources by turning off the A.C. Branch circuit and by
disconnecting the unit connector.
3. The battery is sealed, non-maintenance, and is not replaceable in the field. Please contact manufacturer for
information on service. Do not attempt to service the battery please.
Keep away from flammable
4. DO NOT USE OUTDOORS. The product is for use with grounded, UL Listed, indoor fixtures except in heated air
vapors or materials.
outlets or hazardous locations.
5. The product requires an unswitched A.C. Power source of either 120 or 277 volts. Properly cap the unused A.C.
Lead.
6. Do not mount near gas or electric heaters.
7. The product should be mounted in locations and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
Risk of Electrical
Shock
8. The product will cold strike and operate one 2´ through 4´ (17-40W) instant start, rapid start, program rapid start,
Disconnect power at fuse
U shape or circline, T8 or T12 standard or energy saving fluorescent lamp for 90 minutes at reduced light
or circuit breaker before
installing or servicing.
output.
9. The product is compatible with all A.C. magnetic and electronic ballasts including multiple lamp
ballasts with one lamp operating in the emergency mode.
For use in temperature rating
20°C — 50°C
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
11. Do not use this equipment for other than intended use.
12. Install in accordance with the National Electrical Code and local regulations.
C
US LISTED
13. Installation and servicing should be performed by qualified personnel.
14. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility
Emergency Lighting Unit
before final installation.
Indoor Damp Location Listed
15. The battery is sealed,non-maintenance,and is not replaceable in the field. Please contact
manufacturer for information on service. Do not attempt to service the battery please.
CONTAINS NICKEL-CADMIUM
16. The rated operating time in the emergency mode with battery is 1-1/2 hours and the recharge
RECHARGEABLE BATTERY.
time shall not be less than 24 hours.
MUST BE RECYCLED OR
17.
SAVE THESE INSTRUCTIONS
DISPOSED OF PROPERLY.
Ni - Cd
INSTALLATION INSTRUCTIONS
CAUTION: BEFORE INSTALLING, MAKE CERTAIN THE A.C. POWER IS OFF AND THE BATTERY CONNECTOR IS
DISCONNECTED.
1. MOUNTING THE FBP140XLP
Remove the ballast channel cover. Mount the FBP140XLP in the ballast channel at least 1/2 inch away from the A.C. Ballast(s) using screw with large
enough head to securely hold battery.
When battery packs are remote mounted, the remote distance can not exceed of the distance from ballast to lamp specified by the A.C. Ballast
manufacturer. For example, if the A.C. Ballast manufacturer recommends no more than 25´ remote distance, then the battery pack should not exceed 12´.
Under no circumstances should the battery pack exceed a distance of 50´ from the lamp.
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the National Electrical Code and
local regulations. For additional wiring diagrams consult Customer Service.
1
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
7/09
ADX091238
SURE-LITES
3. INSTALLING THE TEST BUTTON, INDICATOR LIGHT (TBIL)
Recessed Troffer Fixture (Figure 1A) - Select a convenient location with proper clearance in the ballast cover and drill or punch a 7/8˝ hole. Insert the 7/8˝
bushing into the hole. Push the plastic tube through the bushing. Route the leads of the TBIL through the plastic tube. Connect the LED wires from the unit
to the TBIL (Red to Red, White to White/Red). Push the entire assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube
should be adjusted so that the TBIL is within 1/4˝ of the fixture lens. The TBIL must be visible after installation.
Recessed Troffer, Surface Mounted or Strip Fixture (Figure 2A or 2B) - Select a convenient location on the fixture so the TBIL can be seen after installation. Allow for proper clearance inside the fixture and drill or punch a 1/2˝ hole. In some cases KOs are provided on the ballast channel cover. Remove the
nut from the TBIL. Push the TBIL housing into the 1/2˝ hole and secure with the nut. Connect the LED wires from the TBIL to the Red and White/Red wires
on the battery pack (Red to Red, White to White/Red). The TBIL must be visible after installation.
Figure 1A
Figure 2A
Recessed Troffer Fixture
Recessed Troffer with or without Lens
or Surface Mounted Fixture
FIXTURE
BALLAST CHANNEL COVER
FIXTURE
FBP140XLP
TBIL
FBP140XLP
PLASTIC TUBE
7/8” BUSHING
BALLAST CHANNEL COVER
TBIL
FIXTURE LENS
TEST BUTTON, INDICATOR LIGHT (TBIL)
Figure 2B
Strip Fixture
FIXTURE
TBIL
+
RED
LEAD
WHITE
LEAD
FBP140XLP
–
OBSERVE PROPER POLARITY
4. WIRING THE A.C. INPUT
Step 1.
The FBP140XLP and A.C. Ballast must be on the same branch circuit.
Step 2.
The FBP140XLP requires an unswitched A.C. Power source of either 120 or 277 volts. Select the proper voltage lead and cap the unused lead.
Step 3.
When the FBP140XLP is used with a switched fixture, the A.C. input to the FBP140XLP must be connected ahead of the fixture switch.
Refer to Figure 3 for switched and unswitched fixture wiring diagrams.
2
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
7/09
ADX091238
SURE-LITES
5. BALLAST WIRING BLOCK DIAGRAM
Figure 3
BLACK
BLACK
WHITE
WHITE
HOT A.C. LINE
HOT A.C. LINE
WHT/BLK
WHT/BLK
WHITE
COMMON
WHITE
COMMON
(277V) ORG
(277V) ORG
1
WHITE
INDICATOR
LIGHT
FBP140XLP
– WHT/RED
+ RED
RED
1
(120V) BLK
INDICATOR
LIGHT
Select proper voltage lead. Cap unused lead.
1
(120V) BLK
WHITE
– WHT/RED
RED
1
FBP140XLP
+ RED
Select proper voltage lead. Cap unused lead.
6. LABELS
Attach the appropriate labels adjacent to the TBIL. The Caution label and relamping label must be on the fixture in a readily visible location to anyone
attempting to service the fixture. Relamping label should be annotated to indicate the proper lamps to be used during relamping.
7. COMPLETING INSTALLATION
When the installation is complete, join the FBP140XLP unit connector and replace the ballast cover ensuring no wires are pinched. Switch the AC Power on.
OPERATION
Normal Mode - A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The FBP140XLP is in the standby charging mode.
The TBIL will be lit providing a visual indication that the battery is being charged.
Emergency Mode - The A.C. Power fails. The FBP140XLP senses the A.C. Power failure and automatically switches to the Emergency Mode. One lamp
is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. Power is restored, the FBP140XLP switches the system back to the Normal
Mode and resumes battery charging.
TESTING & MAINTENANCE
Pressing the red lens on the TBIL turns off the light on the TBIL and forces the unit into emergency mode. This interrupts power to the emergency lamp
only. The emergency lamp is now being lit by the FBP140XLP unit and will be less bright than the other lamps in the system. To simulate a BLACK OUT use
the switch or circuit breaker to turn off A.C. Power.
Initial Testing - Allow the unit to charge at least 60 minutes, then press the TBIL to conduct a short discharge test.
The FBP140XLP is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code, outlines the following
schedule:
Monthly - Insure that the TBIL is illuminated. Conduct a 30 second discharge test by depressing the TBIL. One lamp should operate at
reduced output.
Annually - Insure that the TBIL is illuminated. Conduct a full discharge test. The unit should operate the lamp for the a full 90 minutes at reduced
output. Allow a 24 hour charge before conducting 90 minute test.
Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
3
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
7/09
ADX091238
SURE-LITES
TYPICAL WIRING DIAGRAMS
For wiring diagrams for ballasts not shown, consult Cooper Lighting Customer Service at 1-800-955-4908 or email - parts@cooperlighting.com
3 TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
TBIL
WHITE
WHT/BLK
1 SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3 CONNECT BLU/WHT AND YELL/BLK
WIRES TOGETHER.
4
TBIL
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
4
WHT/BLK
4 LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
LAMP
FBP140XLP
2 UNIT
CONNECTOR
*LAMP
3 TEST ACCESSORY LEADS-
3
WHT/BLK
4
3 TEST ACCESSORY LEADS-
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
WHT/BLK
4 LAMP SELECTOR LEADS-REFER
4 LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
WHITE
LAMP
VIOLET
VIOLET
RED
2 UNIT
CONNECTOR
- WHT/RED
FBP140XLP
BLK (120V)
WHITE
4
3
TBIL
WHITE
WHT/BLK
1
2
1
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
VIOLET
VIOLET
RED
- WHT/RED
+
1 SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
4
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
5 LAMP SELECTOR LEADS-REFER
*AC/EMERGENCY
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
8. THREE LAMP INSTANT START BALLAST
BLACK
WHITE
RED
BLUE
A.C.
Ballast
BLUE
BLUE
3
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
LAMP
ORG (277V)
FBP140XLP
2 UNIT
CONNECTOR
LAMP
*LAMP
BLK (120V)
WHITE
5
4
TBIL
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
WHITE
WHT/BLK
4 LAMP SELECTOR LEADS-REFER
*AC/EMERGENCY
RED
WHITE
WHT/BLK
3 TEST ACCESSORY LEADS-
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
UNSWITCHED
COMMON
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3 CONNECT BLU/WHT AND YELL/BLK
WIRES TOGETHER.
4
WHITE
SWITCHED OR
UNSWITCHED
LINE
2 DO NOT MATE CONNECTOR UNTIL
VIOLET
ORG (277V)
+
LAMP
*LAMP
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
RED
BLUE/WHT
BLUE/WHT
RED
RED
SWITCHED OR
UNSWITCHED
LINE
5
TBIL
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
4 LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
7. THREE LAMP RAPID START SERIES LAMP
PARALLEL YELLOW FILAMENT
A.C.
Ballast
2 UNIT
CONNECTOR
*LAMP
1
BLK (120V)
WHITE
FBP140XLP
3 TEST ACCESSORY LEADS-
WHT/BLK
*AC/EMERGENCY
BLACK
WHITE
BLUE
BLUE
YELLOW
YELLOW
ORG (277V)
VIOLET
RED
WHITE
SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
2 DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3
TBIL
WHITE
3
BLUE
LAMP
1
4
+
CONNECTOR
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
RED
*LAMP
COMMON
RED
BLUE
- WHT/RED
2 UNIT
UNSWITCHED
BLACK
WHITE
+
LAMP
1
BLK (120V)
WHITE
FBP140XLP
VIOLET
BLUE
BLUE
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
VIOLET
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
RED
YELLOW
YELLOW
RED
RED
WHT/RED
BLACK
WHITE
6. TWO LAMP INSTANT START BALLAST
RED
5. TWO LAMP RAPID START OSRAM SYLVANIA
SERIES LAMP PARALLEL YELLOW FILAMENT
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
*AC/EMERGENCY
WHITE
*AC/EMERGENCY
COMMON
SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
2 DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3
WHITE
UNSWITCHED
1
TBIL
REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
1
BLK (120V)
WHITE
VIOLET
RED
RED
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
VIOLET
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
BLUE
BLUE
RED
YELLOW
YELLOW
SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
2
TBIL
WHITE
BLACK
WHITE
- WHT/RED
RED
WHITE
COMMON
1
4
UNSWITCHED
4. TWO LAMP RAPID START SERIES LAMP
SERIES YELLOW FILAMENT
+
2 UNIT
CONNECTOR
1
BLK (120V)
WHITE
VIOLET
LAMP
*LAMP
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
FBP140XLP
VIOLET
RED
RED
RED
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
- WHT/RED
YELLOW
YELLOW
BLUE
BLUE
+
BLACK
WHITE
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
RED
3. TWO LAMP RAPID START SERIES / PARALLEL LAMP
PARALLEL YELLOW FILAMENT
5 LAMP SELECTOR LEADS-REFER
*AC/EMERGENCY
WHITE
*AC/EMERGENCY
UNSWITCHED
COMMON
2 DO NOT MATE CONNECTOR UNTIL
5
WHITE
1
BLK (120V)
WHITE
VIOLET
2 UNIT
CONNECTOR
*LAMP
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
FBP140XLP
YELLOW
RED
VIOLET
3
RED
RED
A.C.
Ballast
- WHT/RED
WHITE
SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
2
3
BLACK
BLUE
BLUE/WHT
YELL/BLK
+
VIOLET
COMMON
1
4
UNSWITCHED
BLUE
RED
1
BLK (120V)
WHITE
VIOLET
RED
- WHT/RED
2 UNIT
CONNECTOR
*LAMP
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
FBP140XLP
+
A.C.
Ballast
RED
RED
RED
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
WHITE
BLACK
WHITE
BLUE
BLUE
2. ONE LAMP INSTANT START BALLAST
WHITE
1. ONE LAMP RAPID START BALLAST
*AC/EMERGENCY
SWITCHED OR
UNSWITCHED
LINE
1
UNSWITCHED
COMMON
1 SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
2 DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3 CONNECT BLU/WHT AND YELL/BLK
WIRES TOGETHER.
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
5 LAMP SELECTOR LEADS-REFER
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
4
NOTE: Use the proper input voltage lead, cap unused leads
4
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
7/09
ADX091238
SURE-LITES
TYPICAL WIRING DIAGRAMS
For wiring diagrams for ballasts not shown, consult Cooper Lighting Customer Service at 1-800-955-4908 or email - parts@cooperlighting.com
10. FOUR LAMP INSTANT START BALLAST
LAMP
LAMP
RED
RED
3
LAMP
2 UNIT
CONNECTOR
LAMP
LAMP
*LAMP
WHITE
TBIL
1 SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
5
2 DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3 CONNECT BLU/WHT AND YELL/BLK
WIRES TOGETHER.
4
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
*AC / EMERGENCY
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
5 LAMP SELECTOR LEADS-REFER
*AC/EMERGENCY
WHT/BLK
WHITE
4
WHT/BLK
WHITE
UNSWITCHED
COMMON
TBIL
*LAMP
1
BLK (120V)
FBP140XLP
VIOLET
BLUE
VIOLET
YELLOW
A.C.
Ballast
RED
COMMON
YELLOW
SWITCHED OR
UNSWITCHED
LINE
ORG (277V)
- WHT/RED
WHITE
UNSWITCHED
VIOLET
LAMP
RED
UNIT
CONNECTOR
WHITE
1
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
WHITE
FBP140XLP
VIOLET
BLUE/WHT
BLUE/WHT
RED
RED
ORG (277V)
BLK (120V)
.
- WHT/RED
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
+
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
RED
WHITE
WHITE
BLACK
BLUE
BLACK
+
SWITCHED OR
UNSWITCHED LINE
RED
9. FOUR LAMP RAPID START SERIES LAMP
PARELLEL YELLOW FILAMENT
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING .
11. THREE LAMP RAPID START PARALLEL LAMP
PARALLEL YELLOW FILAMENT
12. FOUR LAMP RAPID START PARALLEL LAMP
PARALLEL YELLOW FILAMENT
SWITCHED OR
UNSWITCHED LINE
*LAMP
TBIL
ORG (277V)
LAMP
LAMP
BLK (120V)
WHITE
1
UNSWITCHED
COMMON
VIOLET
UNIT
CONNECTOR
LAMP
VIOLET
FBP140XLP
RED
A.C.
Ballast
+
COMMON
WHITE
RED
VIOLET
UNSWITCHED
VIOLET
WHITE
BLACK
1
- WHT/RED
LAMP
RED
UNIT
CONNECTOR
LAMP
BLK (120V)
WHITE
ORG (277V)
FBP140XLP
- WHT/RED
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
RED/WHT
RED/WHT
BLUE
BLUE
RED
RED
YELLOW
YELLOW
+
A.C.
Ballast
RED
WHITE
WHITE
BLACK
SWITCHED OR
UNSWITCHED LINE
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
BLUE/WHITE
BLUE/WHITE
RED/WHT
RED/WHT
BLUE
BLUE
RED
RED
YELLOW
YELLOW
TBIL
*LAMP
WHITE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
WHITE
WHT/BLK
WHT/BLK
*AC/EMERGENCY
*AC / EMERGENCY
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS ON PAGE 6
TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
NOTE: Use the proper input voltage lead, cap unused leads
5
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
7/09
ADX091238
SURE-LITES
LAMP SELECTOR LEAD INSTRUCTIONS
2 UNIT
CONNECTOR
UNSWITCHED
WHITE
5
4
TBIL
WHITE
1
BLK (120V)
VIOLET
LAMP
*LAMP
RED
BLUE
FBP140XLP
VIOLET
3
ORG (277V)
+
A.C.
Ballast
BLUE
BLUE/WHT
YELL/BLK
YELLOW
RED
RED
RED
BLUE
WHITE - WHT/RED
BLACK
WHITE
SWITCHED OR
UNSWITCHED
LINE
WHT/BLK
*AC/EMERGENCY
1 SELECT PROPER VOLTAGE
LEAD CAP UNUSED LEAD.
2 DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
3 CONNECT BLU/WHT AND YELL/BLK
WIRES TOGETHER.
4 TEST ACCESSORY LEADSREFER TO INSTALLATION
INSTRUCTIONS FOR PROPER
POLARITY WIRING.
5 LAMP SELECTOR LEADS - REFER
TO INSTALLATION INSTRUCTIONS
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
This unit features 6˝ Lamp Selector Leads (violet) for optimizing light output of specific lamps. The unit is shipped
from the factory with these leads disconnected. For some lamps these leads should be connected. If disconnected
leads should be capped.
*See chart below.
This unit can be used with most 2´ - 4´ lamps. Refer to the chart below for the
type of lamp operated in emergency mode.
OPTION
LAMP TYPE
EMERGENCY
OPERATION
*VIOLET LEADS
WIRING
DIAGRAMS
1
2´ T8, or T12
Single or Bipin (up to 20W)
One Lamp
Connected
1,2,3,4,5,6,7,8,9
2
4´ T8, or T12
Single or Bipin (up to 40W)
One Lamp
Disconnected
and Capped
1,2,3,4,5,6,7,8,9
6