Molded Case Circuit Breakers Solid-state trip types Description Solid-state trip types, SA1000E, 1200E, 1600E ■ Description • Equipped with a load current pre-trip alarm Constantly monitors the load current, and outputs an alarm when the set current is exceeded. • Adjustable rated current The rated current is easy to vary in 5 to 6 steps using an adjustment dial. • Wide-range-adjustable trip characteristics The current and time for instantaneous tripping and short-/ long-time delay tripping can be set by the user. • Adjustable ground fault tripping determinate and set a current level for ground fault detection in the ranging between 10% to 40% of the rated CT current. ■ Breaking SA E capacities Series Breaker ampere frame Basic type S 1000 SA1003E SA1004E 1200 1600 ■ Type KKD06-133 Pole Rated current (A) Insulation Breaking capacity [Icu/Ics] voltage AC (kA) Ui (V) 230V 400V 440V IEC60947-2 500V 600V DC 250V 3 4 500-600-700-800-900-1000 500-600-700-800-900-1000 690 690 100/75 100/75 65/49 65/49 65/49 65/49 45/34 45/34 25/19 25/19 - SA1203E SA1204E 3 4 600-700-800-1000-1200 600-700-800-1000-1200 690 690 100/75 100/75 65/49 65/49 65/49 65/49 45/34 45/34 25/19 25/19 - SA1603E SA1604E 3 4 800-900-1000-1200-1400-1600 800-900-1000-1200-1400-1600 690 690 125/94 125/94 85/64 85/64 85/64 85/64 65/49 65/49 45/34 45/34 - number nomenclature SA1203E / 1200 X M WKF F=AC200V 06 I I=AC100V Basic type Rated current Mounting and connection Blank: Front mounting, front connection X: Front mounting, rear connection E: Flush mounting, rear connection Operating device Blank: Manual operation M: Motor operating Internal accessory W: Auxiliary switch K: Alarm switch F: Shunt trip R: Undervoltage trip Control voltage for protection function I= : Adjustable pre-alarm U= : Adjustable ground fault current trip Rated voltage 100 to 120V AC 200 to 240V AC Allowable voltage 85 to 132V 170 to 264V Protection function Adjustable pre-alarm Adjustable ground fault current trip Operating voltage for accessory F= : Shunt trip device R= : Undervoltage trip device M= : Motor operating mechanism ■ Ordering information Specify the following: 1.Type number Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/147 Molded Case Circuit Breakers Solid-state trip types Quick selection guide ■ S series 1000A 3 4 SA1003E SA1004E Adjustable 500-600-700-800 -900-1000 AC Rated insulation voltage(V) 690 DC 600V AC Rated breaking capacity(kA) 25/19 25/19 500V AC [IEC 60947-2] 45/34 45/34 440V AC (Icu/Ics) 65/49 65/49 415V AC 65/49 65/49 400V AC 65/49 65/49 380V AC 85/64 85/64 230V AC 100/75 100/75 250V DC Dimensions 210 280 a d a c (mm) 370 370 b 120 120 b c Page 95 171 171 d Protection function Long-time delay tripping time (s) 5-30 (at 6In) (Adjustable) Short-time delay tripping current (A) 2In-10In (Adjustable) Short-time delay tripping time (s) 0.1-0.3 (Adjustable) Instantaneous tripping current (kA) 3.0-12 (Adjustable) Ground fault current tripping or pre-alarm Mass(kg) Front mounting, front connection 22 28 Tripping device Solid-state Trip button Provided Mounting Front mounting, front connection No mark Front mounting, rear connection Bar Stud X Flush mounting, rear connection Bar Stud E Internal accessories Auxiliary switch W Alarm switch K Shunt trip F Undervoltage trip R Pre-Alarm I Ground fault trip U External accessories Operating handle N-type N G-type G Terminal cover Long TB Insulation barrier Interphase B Handle locking cover L Lead-wire terminal block A Frame Pole Type Rated current(A) 1200A 3 4 SA1203E SA1204E Adjustable 600-700-800-1000 -1200 690 25/19 25/19 45/34 45/34 65/49 65/49 65/49 65/49 65/49 65/49 85/64 85/64 100/75 100/75 210 280 370 370 120 120 171 171 1600A 3 4 SA1603E SA1604E Adjustable 800-900-1000-1200 -1400-1600 690 45/34 45/34 65/49 65/49 85/64 85/64 85/64 85/64 85/64 85/64 100/75 100/75 125/94 125/94 210 280 370 370 140 140 191 191 3.75-15 (Adjustable) 4.8-19.2 (Adjustable) 22 Solid-state Provided 27 Solid-state Provided 28 Bar stud Bar stud Available – Not available 06/148 35 Bar stud Bar stud Factory-mounted accessory Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Protection function Protection function • Long-time delay tripping (Rated current adjustable) • Adjustable instantaneous tripping 800 700 1200 600 I3 15 10 20 5 T1 600% [A] 3 Ict I1 Current setting range, 300 to 1200% of rated primary current Ict Instantaneous tripping current adjustable range 0.03 300 [h] • Adjustable short-time delay tripping Coordination with solid-state trip type MCCB % [lct] 1200 Coordination with thermal-magnetic trip type MCCB 6 6 4 2 I2 10 I1 Current setting range, 200 to 1000% of the rated current I1 0.2 0.3 0.1 0.15 0.25 0.1 T2 0.3 2.5 0.1 0.3 SEC Time setting range, 100 to 300ms. ramp characteristic [l1] 1000 • Adjustable ground fault tripping 0.9 0.7 IP 0.3 0.2 1.0 I1 Pre-alarm current setting range, 70 to 100% of the rated current I1. Pre-trip alarm operating time, 40s constant. [l1] Tripping time Tripping time 0.25 0.1 T2 % 0.8 % 0.2 0.15 200 • Adjustable pre-trip alarm 70 100 I1 Current setting range, 200 to 1000% of the rated current I1 [l1] 40 06 10 I2 7.5 1000 % 8 2 0.3 SEC Time setting range, 100 to 300ms 200 4 OFF ON T2 SEC at 10 l1 8 Tripping time Tripping time OFF ON T2 SEC at 10 l1 12 30 SEC at 6 Time setting range, 5 to 30s at 600% of the rated current I1 600 1200 Tripping time Tripping time h RATED CUR. (A) Current setting range 9 6 1000 0.1 Instantaneous tripping current adjustable range I6 Ict Current setting range, 10 to 40% of the rated primary current 0.3 0.4 0.2 0.8 0.1 TS 0.1 0.8 SEC Time setting range, 100 to 800ms 10 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 0.4 % [lct] 40 06/149 Molded Case Circuit Breakers Solid-state trip types Protection function ■ Pre-trip ■ Multi alarm function Constantly monitors the load current, and outputs an alarm when it exceeds the set current. Helpful for preventive maintenance and power management. The pre-trip alarm operates via an LED on the breaker surface and a contact output. Separate power supply is necessary. The pre-trip alarm setting range allows adjustment to 70, 80, 90, or 100% of the rated current. protection function Wide-range-adjustable trip characteristics with high precision. Either ground fault tripping or the pre-trip alarm can be selected as an option (not both). Adj. long-time delay tripping Adj. short-time delay tripping Tripping time Tripping time (s) Adj. pre-trip alarm 40 70 80 90 Rated current 100 (%) Adj. ground fault, tripping Adj. instantaneous tripping Ground fault current • Pre-trip alarm characteristics Minute 20 10 8 6 4 2 Pre-trip alarm pick up current adjustable range 70% I1[A] 10% 100% I1[A] 10% Operating time Minute Operating time • Ground fault tripping characteristics Pre-trip alarm operating time: 40s (4s) 180 120 90 60 50 40 30 10 8 6 4 1 40 Ground fault tripping current adj. range 10% ICT[A] 15% 40% ICT[A] 15% 20 1 10 8 6 4 15 20 30 300 400 500 40 50 100 150 200 Percent of the setting current I1 1000 (%) 2 Second Second 180 120 90 60 40 30 20 2 40 20 10 Over current 1 0.8 0.6 0.4 0.2 0.1 0.08 Ground fault tripping time 0.04 adj. range 100 200 300 400 800 [msec] 0.02 0.01 1 06/150 1.5 2 3 4 5 7 10 15 20 30 40 50 Percent of the CT rated current Ict 70 100 (%) Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Terminal connection Terminal Connection/Front mounting, Front Connection • MCCBs and cables according to the screw size and tightening torque as shown in the table below. MCCB type Screw and Bolt SA1003E, SA1004E SA1203E, SA1204E Size [mm] Tightening torque [N·m] M12 x 55 40.2 to 65.7 – – Hexagonal head bolt SA1603E, SA1604E Not supplied 06 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/151 Molded Case Circuit Breakers Solid-state trip types Internal accessories Available configurations 3P 4P Right Left handle Right Left Auxiliary switch: W Alarm switch: K Shunt trip: F Undervoltage trip: R Lead wire handle SA1003E SA1203E SA1603E SA1004E SA1204E SA1604E Auxiliary switch SPDT W Alarm switch SPDT K Shunt trip F Under voltage trip R W+K W+F W+R K+F K+R W+K+F W+K+R W2 W2+K W2+F W2+R W2+K+F W2+K+R 06/152 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Internal accessories Auxiliary switch and alarm switch These devices indicate the MCCB’s operation status electrically. • Auxiliary switch (W) Auxiliary switch indicates the ON/OFF status of MCCB. • Alarm switch (K) Alarm switch indicates the trip status of MCCB. MCCB trips at the time when the following condition occurs: · Overcurrent · Short-circuit current Ratings of auxiliary switch (W) and alarm switch (K) • Standard type AC Voltage (V) DC Minimum load Voltage (V) Current (A) Resistive load Inductive load Current (A) Resistive load Inductive load 480 3 2 250 0.3 0.3 250 5 5 125 0.3 0.6 125 5 5 30 5 4 30V DC 5V DC 26.7mA 160mA Note: Inductive load condition: Power factor 0.4 or more (AC), time constant 7ms or less (DC) • For low level circuit AC Voltage (V) Voltage (V) Resistive load 125 Minimum load DC Current (A) Resistive load 30 0.1 Current (A) 30V DC 5V DC 0.1 06 1mA 1mA Note 1: When ordering, specify WD, KD. • Operation of auxiliary switch and alarm switch Type of Accessory Handle position ON Auxiliary switch (W) OFF 11 TRIP 14 11 12 Alarm switch (K) 91 12 94 92 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 14 91 94 92 06/153 Molded Case Circuit Breakers Solid-state trip types Internal accessories Shunt trip (F) and undervoltage trip device (R) • Shunt trip (F) The purpose of the shunt trip device is to trip the MCCB remotely. • Undervoltage trip device (R) The undervoltage trip device trips the MCCB when the MCCB primary voltage is lower than the specified voltage. • Ratings of shunt trip device (F) Rated voltage Coil energized current (A) *1 Allowable voltage fluctuation (V) Maximum operating time (ms) *2 100-115V AC 1.1 85-126.5 30 200-480V AC 0.93 170-528 24V DC 2.52 18-26.4 48V DC 1.55 36-52.8 100-115V DC 0.67 75-126.5 200-230V DC 0.35 150-253 Note *1: The current value at rated voltage maximum value (60Hz AC) *2: The time period from when the rated voltage is applied to the shunt trip coil until the MCCB main contact opens. • : The shunt trip device operation is short-time rating. To prevent the device from burning, continuous signal to the device should not be applied. • Ratings of undervoltage trip device (R) Rated voltage Coli power consumption (VA) 100-120V AC 5 or more Tripping voltage range (V) Closing voltage (V) Maximum applicable Maximum operating time (ms) *2 voltage (V) 30 70-20 85 or more 132 or less 200-240V AC 140-40 170 or more 264 or less 380-450V AC 266-76 323 or more 495 or less Coil energized current (A) *1 Tripping voltage range (V) Closing voltage (V) Maximum applicable Maximum operating time (ms) *2 voltage (V) 24V DC 22.7 16.8-4.8 20.4 or more 26.4 or less 100-115V DC 6.0 70-20 85 or more 126.5 or less Rated voltage 30 Note *1: The current value at rated voltage maximum value *2: The time period from when the rated voltage is applied to the shunt trip coil until the MCCB main contact opens. • : When you turn on the tripped MCCB, perform the reset operation first and then turn ON the MCCB. • Wiring diagram and terminal symbol Wiring diagram and terminal symbol F With burn-out-preventive contact ~ (-) Undervoltage trip device R With UVR controller U< UC1 UC2 06/154 C1 ~ S1 (+) C2 S2 Without UVR controller Controller Type of accessory Shunt trip device D1 P1 D1 U1 U< D2 P2 D2 U2 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Internal accessories UVR controller • When using AC type undervoltage trip device (R), be sure to use a UVR controller. • UVR controllers are equipped with standard type MCCBs at factory shipment. Separately installed type controllers are also available. • UVR controller wiring diagram Installing UVR controller on MCCB Installing UVR controller separately MCCB or fuse MCCB or fuse LINE LINE ON UVR controller ON P2 P1 OFF UC2 UC1 P2 P1 UC2 UC1 UVR controller OFF Lead wire (450mm long) On MCCBs at factory shipment, lead wires of terminals UC1 and UC2 are provided. P2 P1 ON A Frame size MCCB type 1000, 1200 SA1003E, SA1004E A Unit: mm B 114(138) 72 114(138) 92 06 SA1203E, SA1204E UC2 1600 UC1 OFF 16 80 12 15 18 15 16 • Installing position of UVR controller on MCCB and terminal arrangement SA1603E, SA1604E Notes: • Terminal screw tightening torque: M3.5 screw, 0.88-1.18N m • Applicable wire size 2.0mm2 max. UVR controller terminal screw M3.5 21 B • UVR controller outline dimensions, mm Controller mounting hole ø4.5 16 16 10 6 View from P Terminal screw M3.5 7.8 59 6 10 16 45 57.5 88 100 18 15 80 15 9 22 25 6 21 *1 OCR controller Bracket *1: For separate installation, install an OCR controller together with the UVR controller P Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/155 Molded Case Circuit Breakers Solid-state trip types External accessories Variation of external accessory 4. Interphase barrier 3. Terminal cover (for front mounting) 5. Handle locking cover 2. Auxiliary handle 1. External operating handle (G type) 1. External operating handle Mounted on the control panel or switchboard to externally operate MCCB installed inside control panel or switchboard. The following 3 type handles are available. · Panel front mounted type (G type) The external operating handle is mounted on the control pane or switchboard doors. · MCCB mounted type (N type) This external operating handle is directly mounted to the MCCB installed inside the panels. 2. Auxiliary handle Reduce the required force to turn ON/OFF/RESET the MCCB. 6. Lead-wire terminal block 3. Terminal cover (TB) Used to protect fingers touching live parts. · For front mounting MCCBs 4. Interphase barrier (B) The interphase barrier reinforces the insulation between terminals to prevent accidents. 3. Terminal cover (for front mounting) 4. Interphase barrier 06/156 5. Handle padlocking device (L) MCCB handles can be locked at either the ON or OFF position with this device. Prepare padlocks commercially available. 1. External operating handle (N type) 6. Lead-wire terminal block (A) MCCB side mounted lead-wire terminal block. Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types External accessories Operating handle (N type) • The N type operating handle is directly mounted on the MCCBs. • N type MCCB type Type Dust-proof packing SA1003E, SA1004E SA1203E, SA1204E SA1603E, SA1604E BZ6N101C BZ-NPC Panel KKD06-278 Decorative plate N type handle on MCCB Decorative plate Retaining plate • Operating method · The MCCB ON, OFF, and RESET operation can be made by turning the handle. When the MCCB trips, the handle moves to the TRIP position. · If you turn the RELEASE screw with a screwdriver, the door can be opened while the MCCB is closed. · The handle can be locked using a padlock to hold MCCB at either ON or OFF position. Prepare a commercially available padlock. Recommended padlock shackle size is ø3.5-6mm. Panel door cutting • Dimensions, mm 06 150 Decorative plate I P ON ø138 112 OFF 150 T R 4-ø15 Lock lever Max. 84 Release screw 112 Panel thickness 1.2 to 3.2 51 A±2 MCCB mounting dimensions H>0 Operating handle position viewed from MCCB LOAD side 3H+130 or more 3H+70 or more 338 hinge Applicable MCCB type A SA1003E, SA1004E SA1203E, SA1204E 197 SA1603E, SA1604E 217 MCCB Ordering information Specify the type number. 70 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Mounting hole 4-ø9 06/157 Molded Case Circuit Breakers Solid-state trip types External accessories Operating handle (G type) • The G type operating handle is mounted on the panel front. • G type MCCB type Type SA1003E, SA1004E BZ6G101C SA1203E, SA1204E SA1603E, SA1604E MCCB Handle Padlock (Not supplied) Handle ON KKD06-272 Legend OFF plate Interlock release screw G type handle on panel front • Operating method · The MCCB ON, OFF, and RESET operation can be made by turning the handle. When the MCCB trips, the handle moves to the TRIP position. · If you turn the RELEASE screw with a screwdriver, the door can be opened while the MCCB is closed. · The handle can be locked using a padlock to hold MCCB at OFF position. Prepare a commercially available padlock. Recommended padlock shackle size is ø8mm. • Dimensions, mm Handle unit Decorative plate Door panel (ON side) 142 (MAX.) Decorative plate Legend plate Sling plate Handle CL 142 (MAX.) B MCCB CL 60 70 35 70 ø40 ø12 130 Legend plate mounting screw 2-M3 70 Handle CL 140 Mounting hole ø12 Retaining plate (Not supplied) 105 47.4 58 CL 105 (OFF side) 10 Door panel 1.6 to 3.2t Retaining plate V 18.5 60 15 50 125 MCCB CL Applicable MCCB type A B SA1000E, SA1200E 199.4 3 SA1600E 219.4 Ordering information Specify the type number. 06/158 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types External accessories 32 Auxiliary handle • Reduce the required force to turn ON/OFF/RESET the MCCB. • One auxiliary handle is supplied with one MCCB as standard. 105 Attaching and removing handle Pull out the lock pins on both right and left sides in the direction of the arrows, and put the auxiliary handle onto the handle of the MCCB. The auxiliary handle is fixed with spring force. When removing, pull out the lock pins the same way in the direction of arrows and take off the auxiliary handle. 37 Lock pin 60 26 78 Applicable MCCB type Type SA1003E, SA1004E SA1203E, SA1203E SA1603E, SA1603E Supplied as standard Handle padlocking device • When the handle padlocking device is locked, the MCCB handle can be locked in the OFF (open) position. • Use the commercially available padlocks with shackle of diameter 4-8mm. Applicable MCCB type Type SA1003E, SA1004E SA1203E, SA1203E SA1603E, SA1603E BZ6L101C Han dle le ON R ngth to its end ø8 or less F OF Padlock (max. 3 padlocks mountable) Use of handle padlocking device Put the handle padlocking device's lock lever at UNLOCK (lock release) position and attach the padlocking device to the MCCB handle. Once the lock lever is turned to the LOCK (locked) position, the MCCB handle ON (closed) operation and OFF (open) operation are prohibited. When using the MCCB with the handle being locked, lock with the padlock(s) in this state. 06 KKD06-275 ON Lock lever Ordering information Specify the type number. Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/159 Molded Case Circuit Breakers Solid-state trip types External accessories Terminal cover • Finger protection guards against electric shock from accidentally touching live terminals. • Specify when you order the main unit of the MCCB. Applicable MCCB type Type Quantity supplied SA1003E, SA1203E BZ6TB101C 2 pieces SA1004E, SA1204E 4P:285 3P:215 Mounting screw height 3.5 115 Mounting screw M4 130 99 Hole used for megger test (located at each terminal) *1: Use wire of size 100m2 or less. When using wire of 150mm2, please cusult with Fuji. *2: Not applicable to 3-pole MCCBs with terminal block (option) Ordering information Specify the type number. Interphase barrier • The interphase barrier reinforces the insulation between terminals to prevent accidents. Applicable MCCB type Type Quantity supplied SA1003E, SA1203E, SA1603E BZ6B101C3 2 pieces SA1004E, SA1204E, SA1604E BZ6B101C4 3 pieces 95 4P CL When mounting the interphase barrier to the MCCB, insert the barrier into the MCCB’s groove from upward. 110 110 3P CL 95 Ordering information Specify the type number. 06/160 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types External accessories Lead-wire terminal block The lead-wire terminal blocks are applicable to front-mounting or rear-mounting MCCBs with internal accessories. The lead-wire from internal accessories are already connected to terminals. One terminal block consists of 6 pairs of terminals. The mountable accessories are determined according to the types and quantity of internal accessories. Mounting position and standard terminal arrangement CL 9.6 114 51 Terminal block 15 S1 80 62 S2 CL ⑫ ⑪ ⑩ ⑨ ⑧ ⑦ ⑥ ⑤ ④ ③ ② ① 27.5 C CL D 21 A B (OCR controller) 06 Indication ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ Terminal number 91 94 92 11 14 12 21 24 22 Terminal symbol ALc1 ALa1 ALb1 AXc1 AXa1 AXb1 AXc2 AXa2 AXb2 Accessories ⑪ PALc PALa ⑫ W2 W1 K ⑩ Dimensions, mm A B C D SA1003E, SA1203E SA1004E, SA1204E 194 184 72 72 57 57 27 27 SA1603E SA1604E 194 184 92 92 77 77 47 47 MCCB type Notes: 1. Terminal screw M3.5 2. Terminal screw tightening torque 0.88-1.18N m 3. Applicable wire size 2.0mm2 (Max.) x 2 wires Ordering information Specify the type number. Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/161 Molded Case Circuit Breakers Solid-state trip types Characteristic curves Operating characteristic SA1000E SA1200E 120 90 60 120 90 60 40 30 40 30 6 4 2 1 Max. value Min. value Operating time 40 20 10 Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable 20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable 15% range Short-time delay 100, 150, 200, 250, 300 [ms] tripping time adjustable Operating time range +50 [ms] -20 [ms] 2 600, 700, 800, Rated current adjustable range 1000, 1200 [A] 10 6 4 2 1 Max. value Min. value 40 3kA to 12kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable 20% range Ict: CT current 1000A 6 I2t 4 Switch ON 20 10 2 1 0.6 0.4 Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable 20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable 15% range Short-time delay 100, 150, 200, 250, 300 [ms] tripping time adjustable Operating time range +50 [ms] -20 [ms] 3.75kA to 15kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable 20% range Ict: CT current 1250A 6 I2t 4 Switch ON Second Second 20 500, 600, 700, Rated current adjustable range 800, 900, 1000 [A] 10 Minute Minute 20 Operating time ■ 1 0.6 0.4 2 It 0.2 Switch OFF 0.1 0.08 0.06 I2t 0.2 Switch OFF 0.1 0.08 0.06 0.04 0.04 0.02 0.02 Max. total fault clearing time 0.01 1 1.5 2 3 4 5 6 7 8 10 15 Multiple of rated current(A) 20 30 40 50 Max. total fault clearing time 100 0.01 1 1.5 2 3 4 5 6 7 8 10 15 Multiple of rated current(A) 20 30 40 50 100 SA1600E 120 90 60 40 30 Minute 20 800, 900, 1000, Rated current adjustable range 1200, 1400, 1600 [A] 10 6 4 2 1 Max. value Operating time 40 Min. value 20 10 Short-time delay 100, 150, 200, 250, 300 [ms] tripping time Operating time adjustable range +50 [ms] -20 [ms] 4.8kA to 19.2kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable 20% range Ict: CT current 1600A 6 I2t 4 Switch ON 2 Second Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable 20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable 15% range 1 0.6 0.4 I2t 0.2 Switch OFF 0.1 0.08 0.06 0.04 0.02 Max. total fault clearing time 0.01 06/162 1 1.5 2 3 4 5 6 7 8 10 15 Multiple of rated current(A) 20 30 40 50 100 Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Dimensions ■ Dimensions, mm SA1000E, 1200E Front mounting, front connection 4-pole 14 CL 13 N Mounting hole CL 370 310 95 CL 4-pole 3-pole CL CL 28 18 M8 Mounting screw 70 80 8 45 70 105 140 210 70 Breaker Auxiliary handle (Detachable) 78 CL Panel drilling 31 8 32 15 80 CL 338 3-pole ø9 105 70 175 17 280 80 14 29 120 171 Front mounting, rear connection Panel drilling 3-pole 4-pole 3-pole C L M8 Mounting screw 4-pole C L CL Breaker 21 34 73 98 15 R 6 C Lof window 73 111 32 8 70 Panel ø13 45 15 13 140 CL 172 338 120 CL 258 CL 06 4-pole 3-pole CL ø9 12 Insulation plate Panel cutting 70 70 ø50 Insulation tube for center pole Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 70 230 81 70 300 Panel cutting dimensions include space of 1.5mm to the handle window frame. 06/163 Molded Case Circuit Breakers Solid-state trip types Dimensions ■ Dimensions, mm SA1600E Front mounting, front connection 4-pole CL CL 20 Panel drilling 11 Insulation panel 30 100 4-pole 3-pole CL Auxiliary handle (Detachable) 78 CL CL CL 370 310 95 32.55 N CL 70 70 210 70 70 17 ø13 280 M8 Mounting screw 70 ø9 105 15 70 105 18 8 100 32 20 28 45 Breaker 338 3-pole 80 20 46 140 191 Front mounting, rear connection Panel drilling 4-pole 3-pole CL Mounting angle 3-pole Panel cutting 4-pole 3-pole CL 4-pole CL CL ø9 Breaker 73 M6 Mounting screw CL 98 15 R 6 CL of window 70 73 30 Connecting length 30 115 70 85 115 130 CL 172 338 30 65 45 CL 06/164 34 ø12 15 70 70 70 230 81 70 300 Insulation tube Panel cutting dimensions include space of 1.5mm to the handle window frame. Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice