Molded Case Circuit Breakers Solid-state trip types Solid-state trip types, SA1000E, 1200E, 1600E ■ Features • Equipped with a load current pre-trip alarm Constantly monitors the load current, and outputs an alarm when the set current is exceeded. • Adjustable rated current The rated current is easy to vary in 5 to 6 steps using an adjustment dial. • Wide-range-adjustable trip characteristics The current and time for instantaneous tripping and short-/ long-time delay tripping can be set by the user. • Adjustable ground fault tripping determinate and set a current level for ground fault detection in the ranging between 10% to 40% of the rated CT current. ■ KKD06-133 SA E Type number nomenclature SA1203E / 1200 X M WF K F=AC200V I I=AC100V Basic type Rated current Mounting and connection Blank: Front mounting, front counection X: Front mounting, rear counection E: Flush mounting, rear counection P: Plug-in mounting D: Draw-out Operating device Blank: Manual operation M: Motor operating Internal accessory W: Auxiliary switch K: Alarm switch F: Shunt trip R: Undervoltage trip Control voltage for protection function I= : Adjustable pre-alarm U= : Adjustable ground fault current trip Rated voltage 100 to 120V AC 200 to 240V AC Allowable voltage 85 to 132V 170 to 264V Protection function Adjustable pre-alarm Adjustable ground fault current trip Operating voltage for accessory F= : Shunt trip device R= : Undervoltage trip device M= : Motor operating mechanism ■ Ordering information Specify the following: 1.Type number Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/133 06 Molded Case Circuit Breakers Solid-state trip types ■ S series Frame Pole Type Rated current(A) 1000A 3 4 SA1003E SA1004E Adjustable 500-600-700-800 -900-1000 690 Rated insulation voltage(V) AC DC 50 Rated breaking 550V AC JIS C8370 65 capacity 460V AC (sym) (kA) 220V AC 100 250V DC 25/19 IEC 60947-2 690V AC 25/19 (Icu/Ics) 660V AC 25/19 600V AC BS 4752 (sym)* 45/34 500V AC 65/49 440V AC 65/49 400V AC 230V AC 100/75 250V DC 210 280 a Dimensions d a c 370 b (mm) b 120 c 171 d Protection function Long-time delay tripping time (s) 5-30 (at 6In) (Adjustable) Short-time delay tripping current (A) 2In-10In (Adjustable) Short-time delay tripping time (s) 0.1-0.3 (Adjustable) Instantaneous tripping current (kA) 3.0-12 (Adjustable) Ground fault current tripping or pre-alarm Mass(kg) Front mounting, front connection 22 28 Tripping device Solid-state Trip button Provided Mounting Front mounting, front connection No marrk Front mounting, rear connection X Bar Stud Flush mounting, rear connection E Bar Stud Plug-in mounting P Internal accessories Auxiliary switch W Alarm switch K Shunt trip F Undervoltage trip R External accessories Motor operating mechanism M Lead-wire terminal block Note: * For SA1200E and SA1600E 06/134 1200A 3 4 SA1203E SA1204E Adjustable 600-700-800-1000 -1200 690 50 65 100 25/19 25/19 25/19 45/34 65/49 65/49 100/75 210 280 370 120 171 1600A 3 4 SA1603E SA1604E Adjustable 800-900-1000-1200 -1400-1600 690 65 85 130 45/34 45/34 45/34 65/49 85/64 85/64 125/94 210 280 370 140 191 3.75-15 (Adjustable) 4.8-19.2 (Adjustable) 22 Solid-state Provided 27 Solid-state Provided 28 Bar stud Bar stud - 35 Bar stud Bar stud - Available – Not available Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Protection function • Long-time delay tripping (Rated current adjustable) • Adjustable instantaneous tripping 800 1000 1200 600 I3 Current setting range 15 10 20 5 3 Ict Current setting range, 300 to 1200% of rated primary current Ict Instantaneous tripping current adjustable range I1 Time setting range, 5 to 30s at 600% of the rated current I1 0.03 300 [h] 1200 % • Adjustable short-time delay tripping Coordination with solid-state trip type MCCB [lct] Coordination with thermal-magnetic trip type MCCB 6 6 4 8 2 10 I2 I1 Current setting range, 200 to 1000% of the rated current I1 0.2 0.3 0.1 0.15 0.25 0.1 T2 0.3 2.5 0.2 0.15 0.1 1000 [l1] • Adjustable ground fault tripping 0.9 0.7 IP 0.3 0.2 1.0 I1 Pre-alarm current setting range, 70 to 100% of the rated current I1. Pre-trip alarm operating time, 40s constant. [l1] Tripping time Tripping time 0.3 SEC Time setting range, 100 to 300ms. ramp characteristic % 0.8 % 0.25 0.1 T2 200 • Adjustable pre-trip alarm 70 100 I1 Current setting range, 200 to 1000% of the rated current I1 [l1] 40 06 10 I2 7.5 1000 % 8 2 0.3 SEC Time setting range, 100 to 300ms 200 4 OFF ON T2 SEC at 10 l1 Tripping time Tripping time OFF ON T2 SEC at 10 l1 12 30 SEC at 6 T1 600% [A] Tripping time Tripping time h RATED CUR. (A) 600 1200 9 6 700 0.1 Instantaneous tripping current adjustable range I6 Ict Current setting range, 10 to 40% of the rated primary current 0.3 0.4 0.2 0.8 0.1 TS 0.1 0.8 SEC Time setting range, 100 to 800ms 10 % Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 0.4 [lct] 40 06/135 Molded Case Circuit Breakers Solid-state trip types ■ ■ Pre-trip alarm function Constantly monitors the load current, and outputs an alarm when it exceeds the set current. Helpful for preventive maintenance and power management. The pre-trip alarm operates via an LED on the breaker surface and a contact output. Separate power supply is necessary. The pre-trip alarm setting range allows adjustment to 70, 80, 90, or 100% of the rated current. Multi protection function Wide-range-adjustable trip characteristics with high precision. Either ground fault tripping or the pre-trip alarm can be selected as an option (not both). Adj. long-time delay tripping Adj. short-time delay tripping Tripping time Tripping time (s) Adj. pre-trip alarm 40 70 80 90 Rated current 100 (%) Adj. ground fault, tripping Adj. instantaneous tripping Ground fault current • Pre-trip alarm characteristics Minute 20 10 8 6 Pre-trip alarm pick up current adjustable range 4 70% I1[A] 10% 100% I1[A] 10% 2 Operating time Minute Operating time • Ground fault tripping characteristics Pre-trip alarm operating time: 40s (±4s) 180 120 90 60 50 40 30 10 8 6 4 1 40 Ground fault tripping current adj. range 10% ICT[A] 15% 40% ICT[A] 15% 20 1 10 8 6 4 15 20 30 300 400 500 6007008001000 (%) 40 50 60 70 80 90100 150 200 900 Percent of the setting current I1 2 Second Second 180 120 90 60 40 30 20 2 40 20 10 Over current 1 0.8 0.6 0.4 0.2 0.1 0.08 Ground fault tripping time 0.04 adj. range 100 200 300 400 800 [msec] 0.02 0.01 1 06/136 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 607080100 (%) 90 Percent of the CT rated current Ict Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types Operating characteristic SA1000E SA1200E 120 90 60 120 90 60 40 30 40 30 6 4 2 1 Max. value Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable ±20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable ±15% range Short-time delay 100, 150, 200, 250, 300 [ms] tripping time adjustable Operating time range +50 [ms] -20 [ms] Min. value 40 Operating time 20 500, 600, 700, Rated current adjustable range 800, 900, 1000 [A] 10 20 10 3kA to 12kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable ±20% range Ict: CT current 1000A 6 I 2t 4 Switch ON Minute Minute 20 6 2 1 Max. value Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable ±20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable ±15% range Short-time delay 100, 150, 200, 250, 300 [ms] tripping time adjustable Operating time range +50 [ms] -20 [ms] Min. value 40 20 10 3.75kA to 15kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable ±20% range Ict: CT current 1250A 6 I 2t 4 Switch ON 2 Second 2 Second 600, 700, 800, Rated current adjustable range 1000, 1200 [A] 10 4 Operating time ■ 1 0.6 0.4 1 0.6 0.4 I2t 0.2 Switch OFF 0.1 0.08 0.06 I2t 0.2 Switch OFF 0.1 0.08 0.06 0.04 0.04 0.02 0.02 06 Max. total fault crearing time 0.01 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100 Multiple of rated current(A) Max. total fault crearing time 0.01 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100 Multiple of rated current(A) SA1600E 120 90 60 40 30 Minute 20 800, 900, 1000, Rated current adjustable range 1200, 1400, 1600 [A] 10 6 4 2 1 Max. value Operating time 40 Long-time delay 5, 10, 15, 20, 30 [s] tripping time Operating time adjustable ±20% range Short-time delay 2, 4, 6, 8, 10 tripping current x I1 [A] Operating current adjustable ±15% range Short-time delay 100, 150, 200, 250, 300 [ms] tripping time Operating time adjustable range +50 [ms] -20 [ms] Min. value 20 10 4.8kA to 19.2kA Instantaneous tripping current (3 to 12 x ICT [A] ) Operating current adjustable ±20% range Ict: CT current 1600A 6 I2t 4 Switch ON Second 2 1 0.6 0.4 I2t 0.2 Switch OFF 0.1 0.08 0.06 0.04 0.02 Max. total fault crearing time 0.01 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100 Multiple of rated current(A) Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice 06/137 Molded Case Circuit Breakers Solid-state trip types ■ Dimensions, mm SA1000E, 1200E Front mounting, front connection 4-pole Panel drilling CL 14 31 8 32 15 80 CL 13 4-pole 3-pole CL N Auxiliary handle (Detachable) Mounting hole 370 310 95 78 CL CL CL CL 28 18 M8 Mounting screw 70 80 8 45 70 105 140 210 70 Breaker 338 3-pole ø9 105 70 175 17 280 80 14 29 120 171 Front mounting, rear connection Panel drilling 3-pole 4-pole 3-pole CL M8 Mounting screw 4-pole CL CL Breaker 21 06/138 34 73 ø50 Insulation tube for center pole 98 15 6 R ø13 45 70 Panel CL of window 73 111 32 8 15 13 140 CL 172 338 120 CL 258 CL 4-pole 3-pole CL ø9 12 Insulation plate Panel cutting 70 70 70 230 81 70 300 Panel cutting dimensions include space of 1.5mm to the handle window frame. Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Molded Case Circuit Breakers Solid-state trip types ■ Dimensions, mm SA1600E Front mounting, front connection 3-pole 4-pole CL Panel drilling CL 20 11 30 100 Insulation panel 4-pole 3-pole CL Breaker 370 CL CL CL CL 32 70 70 17 ø13 80 280 210 M8 Mounting screw 70 ø9 105 15 70 105 45 70 18 8 100 20 28 70 338 Auxilliary handle (Detachable) 78 310 95 32.5 N 20 46 140 191 Front mounting, rear connection Panel drilling 4-pole 3-pole CL Mounting angle 3-pole Panel cutting ø9 CL CL Breaker 73 M6 Mounting screw 98 15 CL of window R 6 CL 70 73 30 Connecting length 30 115 70 85 115 130 CL 172 338 30 65 45 34 ø12 CL 06 4-pole 3-pole CL 4-pole 15 70 70 70 230 81 70 300 Insulation tube Fuji Electric FA components & Systems Co., Ltd./D & C Catalog Information subject to change without notice Panel cutting dimensions include space of 1.5mm to the handle window frame. 06/139