Find faults fast(er) with faulted circuit indicators One of the best ways to locate a fault in the shortest time. F inding faults quickly is the key to decreasing customer outage time after a fault has occurred. In the past, often it took longer to find the fault than repair the fault. Faulted circuit indicators (FCIs) have emerged over the past couple of decades as one of the best ways to locate a fault in the shortest possible time. Unlike thumping or radar-locating equipment, a faulted-circuit indicator will not tell you the exact location of the fault, but will tell you the section of line where the fault has occurred. The early designs and applications of fault indicators provided a great deal of education for utility engineers, operating personnel and faultedcircuit indicator manufacturers. While history is the best teacher, it is also the most expensive and when specifying you should be sure not to make the same mistakes people have made in the past. Following are three items of interest that should be understood and considered when making recommendations for the installation and operation of faulted-circuit indicators. False Tripping The FCI knows only that the current in the cable to which it is attached has surpassed its trip level. The FCI indicates a faulted circuit by displaying a red target. In the case where active components of the electrical distribution system contribute to the fault current flowing into the faulted portion of line, FCIs that are not between the source and the fault may be tripped. This tripping is caused by a discharge of active components downstream of the location of the faulted spot on the line. Some of the items that can contribute to this discharging situation are: • Capacitor banks • Three-phase delta connected circuits • Long lengths of URD cable • Rotating machinery loads URD cables are capacitors by their construction and are probably the most overlooked part of active components in the URD arena. Computer simulations show that URD cable discharge can be several hundred amperes with its time to decay depending upon circuit parameters. As you would suspect, higher voltage URD cables (i.e. 25kV, 35kV) deliver higher peakcurrent amperes. The length of the cable is a determining factor in both the magnitude of the current and the time for it to decay. Figure 1 ( next page) shows a simple URD circuit illustrating the current flow into the fault that may cause the indicators to trip. It has been the recommendation of FCI manufacturers to use the highest level of trip current possible so that the trip level is above the active component discharge current, but below the fault current at that location on the line. This is shown in Figure 2 (next page). Depending upon the available fault current at the application point of the FCI, this recommendation may be easier said than done. It was with this motive in mind that a project was initiated to develop a faulted-circuit indicator that would not only indicate the presence of a fault on that section, but point to the direction of the current flow. The directional fault indicators provide a road map to finding the faulted section of line. Figure 3 shows that a directional fault indicator will lead the operating personnel to the faulted section of line regardless of whether the additional fault current downstream from the fault is caused by an additional source or by active components on the distribution system. When using non-directional FCI’s, the recommendation of selecting a trip current as high as possible to avoid false tripping by active components still applies, but if problems persist in these locations a directional fault indicator is the answer. NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. ® POWER SYSTEMS, INC. 573-682-5521 Fax 573-682-8714 http://www.hubbellpowersystems.com ANDERSON ® ® ® UNITED STATES • 210 N. Allen • Centralia, Mo 65240 • Phone: 573-682-5521 • Fax: 573-682-8714 • e-mail: hpscontact@hps.hubbell.com CANADA • 870 Brock Road South • Pickering, Ontario L1W 1Z8 • Phone: 905-839-1138 • Fax: 905-831-6353 • e-mail: jpearl@hubbell-canada.com MEXICO • Av. Coyoacan No. 1051 • Col. Del Valle • 03100 Mexico, D.F. • Phone: 525-575-2022 • Fax: 525-559-8626 • e-mail: vtasdf@hubbell.com.mx ©Copyright 2000 Hubbell • 210 North Allen Street • Centralia, MO 65240 ® 1 Bulletin 16-9202 Figure 1 False Resets on Secondary Reset FCIs Probably the best fault indicator to be applied on padmount transformers is a device that has the sensor connected to the primary cable and then a connection from the sensor through an EPDM cable to the secondary spade of the transformer. Since the insulating material EPDM is used in the connection, leakage current of microamps is used to both power the FCI and indicate the presence of a normal circuit by sensing the secondary voltage. Normally, the reset level or the secondary voltage that the indicator considers to be “normal” is 35-40% of nominal (e.g., approximately 45 volts on a 120 volt secondary). Figure 2 2 Now consider a situation where a delta-connected load is being served by a grounded wye-grounded wye transformer protected by single Figure 3 phase devices as shown in Figure 4 (next page). If one of the phases of the transformer is not energized as a result of the opening of a singlephase protective device, the secondary spades of the transformer will indicate some voltage on all three phases. Let’s assume in our situation that B phase is the circuit that is not energized by the source as a result of a single-phase open protective device; the A & C phases would be at full line potential, while the B phase would have voltage present on the secondary spade (b) as a result of backfeed. It is not uncommon for this voltage to be high enough to reset the fault indicator on this B phase. You should now see the problem. There is a fault on B phase, but the FCI has reset to the normal condition as a result of backfeed, and this incorrect reading is no help to operating personnel trying to locate the fault. The answer is to raise the level of secondary voltage that the fault indicator considers “normal” to a point much closer to full secondary voltage. This feature that many utilities specify for their three-phase applications is known as reset restraint. Reset restraint is a percentage range (e.g. 70-95%) of the full secondary voltage before the faulted-circuit indicator considers the system to be truly energized and “normal” taking into account any fluctuations normally seen on the system. Current reset devices are also susceptible to false reset in this scenario, since they will see backfeed current in the circuit shown in Figure 4 on the next page. Calibrating for a Specific Diameter Cable When applying a secondary reset FCI to three-phase transformers that could serve delta loads, always consider the use of reset restraint. What if you want to put an FCI on a conductor other than the diameter for which it is calibrated? Ask for a trip current vs. cable diameter chart. A sample chart is shown in On many fault indicators the user's cable diameter of application is requested for factory calibration. During production, the unit is installed on a cable (the same size as the user specifies) and is calibrated for proper current, + 10%. The diameter of cable for which the FCI has been factory calibrated for is permanently stamped on the FCI units. The permanent hot stamp marking appears as a “C” followed by a number. For example, a unit stamped C1.1 is calibrated for 1.1 inch diameter cable to trip at the specified trip current + 10%. 3 Figure 5. In this case, the unit is a 200 amp trip, factory calibrated for 0.475” conductor. The range of conductors is 0.28” through 0.57”. Not all faulted-circuit indicators require the cable diameter for calibration, but when it’s required, ask yourself, “what is the range of conductors on which the unit may be applied?” To request a chart, the following should be provided: 1) Type of unit (e.g. Current reset, Secondary reset, Electrostatic reset) 2) Desired trip current in amps 3) Diameter range of conductor - min., max. 4) Calibration point within the range In the example shown in Figure 5, items are: 1) Type of unit: ERL (Electrostatic Reset) 2) Desired trip current: 200 amps 3) Diameter range: min. = 0.28", max. = 0.57" 4) Calibration point: 0.457" Figure 4 Trip Rating vs. Cable Diameter for ERL200 Calibrated at 0.475" A helpful hint: if you know the range of cable you have, calibrate for the average diameter and the chart will give you the exact trip currents. Conclusion There are many application aspects of faulted-circuit indicators. This article addresses three of the more frequently asked questions. The proper application and operation of existing designs along with the introduction of the new Chance LCD and Directional designs have brought faulted-circuit indicators a long way and your customers have spent much less time in the dark. ❐ & TiPS NEWS Reprinted from October 1992 Figure 5 ©Copyright 4 2000 Hubbell • 210 North Allen Street • Centralia, MO 65240 Bulletin 16-9202