VOLTAGE SAG COMPENSATION OF POINT OF COMMON COUPLING (PCC) USING FAULT CURRENT LIMITER IN THREE PHASE LINES 1 P.ANUSHA & 2K. SWARNASRI Department of Electrical & Electronics Engineering, R.V.R &J.C.College of Engineering, Chowdavaram, Guntur, A.P, India. E-mail: peram00@gmail.com, : swarnasrik@gmail.com Abstract-This paper presents a new component called Fault Current Limiter (FCL) in three phase lines. Voltage sag compensation is provided on both sides of the Point of Common Coupling (PCC) by using FACTS Devices (STATCOM, APF, DSTATCOM, DVR, UPFC) and FCL. The FACTS devices provide compensation on input side and FCL provides compensation on output side. A sensitive load is considered at output side of PCC. The main objective of the designed component is to protect the sensitive load from the shunt faults. The compensation is being provided at output side of PCC. Load voltage reduces upon the occurrence of shunt fault. This results in unbalance of the system voltages and phase angle jump. The foremost purpose of the FCL would be to limit the voltage sag and the phase angle change of the substation point of common coupling. IGBT based FCL is designed in this paper instead of Thyristor based FCL. When IGBT is used as switching device, FCL will have reduced ac side losses and increased speed of operation. DC side reactor value can be reduced to a lower value. Lowered Total Harmonic Distortion (THD) and improved voltage wave form at PCC shows the effective ness of the designed FCL. The analysis and design is carried out in MATLAB with SIMULIN K simulation package. Index Terms— Fault Current Limiter (FCL),Point of Common Coupling (PCC), Total Harmonic Distortion (THD), Power Quality (PQ). coil in the FCL. The non conducting coil exhibits power loss which is negligible as compared with the total power provided by the radial feeders. In this paper IGBT based FCL is proposed for voltage sag and phase angle jump mitigation of the substation PCC. I. INTRODUCTION Now a dayβs power system network becomes very complex due to rapid changes in development. There is a great desire for improving power quality because of growing demand of electrical energy. There are so many power quality problems i.e. malfunctioning of the control systems and voltage sag etc. that are affected on the power transmittable capacity of the transmission system. The voltage sag problem rises due to increasing the sensitive load demand. The voltage sag problems are mostly appears in buses which are connected to radial feeders [1]-[6]; results loss of voltage quality. The dynamic voltage restorer (DVR) is most commonly used for voltage sag compensation which will inject the compensated voltage with magnitude and phase angle in series with the distribution feeders [7],[8]. During the fault the voltage sag is proportional to the short circuit current level. The levels of fault current in different places have often exceeded the withstand capacity of existing power system equipment due to this the stability and reliability of the power system will be reduces[9]. Thus, the fault current of the power system is limiting to a safe level can greatly reduce the risk of failure to the power system equipment due to high fault current flowing through the system. II. VOLTAGE SAG IN POWER SYSTEM Fig.1 shows the single-line diagram of the three phase power system. This figure shows a substation with six feeders (F1,F2,F3,F4,F5,F6). For an easy analysis of the three phase lines we are consider only one phase instead of three phases. PCC F1 BUS BAR Sensitive load FCL F2 F3 Sensitive load FCL F4 F5 AC AC AC TRANSFORMER Sensitive load FCL F6 Figure 1. Single-line diagram of the three phase power system The levels of fault current are controlled by super conducting fault current limiter (SFCL) due to their variable impedance characteristics but the cost of super conductors is high. Therefore, the super conducting coil is replaced with non superconducting The below figure shows the single line diagram of the power system, here we are considering only one phase which is having two feeders F1 and F2. Feeder F1 supplies a sensitive load and F2 is faulted. International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 106 Voltage SAG compensation of point of common coupling (PCC) using fault current limiter in three phase lines BUS BAR PCC F1 Sensitive load π- Phasorof the load impedance at the F2. In the normal state ZK(N),is larger than|ππ + ππ‘ | . So the PCC voltage is approximately equal to the source voltage. In the fault condition in the F2, the voltage and phase angle of substation PCC can be expressed as follows: FCL F2 TRANSFORMER AC Fault Figure 2. Single-line diagram of the power system πππΆπΆ(πΉ) = Fig.3. shows the positive-sequence equivalent circuit of the case study system in the fault condition. To calculate the voltage sag, the simple voltage divider method is introduced in [10]. ΦππΆπΆ BUS BAR Zs πππΆπΆ PCC Zl1 Zsl Zl2 Z Sensitive load Where VPCC(F) during fault ΦPCC(F) during π PCC(F) fault ZF Figure3.Positive-sequence equivalent circuit of the case study system in the fault condition. In the normal operating condition, the voltage magnitude and its phase angle in the substation PCC can be expressed as follows: ππ +ππ‘ +π πΎ (π ) ΦππΆπΆ π = π πΎ (π ) = πππ tan π πΎ (π ) π πΎ (π ) (5) ππ (6) πΉ πΉ π πΎ πΉ +π π +ππ‘ π πΎ πΉ +π π +π π‘ (7) - Voltage magnitude of the PCC -Phase angle of voltage of the PCC the fault -voltage phasor of the PCC during - Fault impedance. Equivalent impedance of parallel feeders during fault is ππ π π +ππ‘ +ππΎ (π ) −1 ππΎ π πΎ ππ ππΎ(πΉ) = π πΎ(πΉ) + πππΎ(πΉ) (1) π = tan−1 F2 Fault π πΎ (π ) π πΎ (πΉ) π π +ππ‘ +ππΎ (πΉ) − tan Zt Zf πππΆπΆ πΉ = F1 AC πππΆπΆ(π) = πΉ π πΎ (πΉ) ππ +ππ‘ +π πΎ (πΉ) ππΎ(πΉ) = ππΏ1 + πππΏ (8) ππ − πππ tan ππΏ2 + ππΉ (2) In the three-phase fault condition i.e.symmetrical fault condition, the fault impedance (ZF)isapproximately equal to zero and according to equation (8) the magnitude of πK(F)will be small. During the faultthe voltage sag and phase angle jump of the sensitive load is comparatively worse. To prevent voltage sag and phase angle jump during a fault, a new component is introducing between the substation PCC and the fault location for providing large limiting impedance. A new component is known as FCL. π πΎ (π ) +π π +ππ‘ π πΎ (π ) +π π +π π‘ (3) Where VPCC(N)-Voltage magnitude of the PCC in normal state. π PCC(N) - Voltage phasor of the PCC in normal state. ΦPCC(N) - Phase angle of voltage of the PCC in normal state. Where the phase angle of π s is considered to be zero ππ‘ -Phasor of transformer impedance. ππΎ(π) = π πΎ(π) + πππΎ(π) - Equivalent impedance of parallel feeders in normal state. πS -Phasor of source voltage. ππ = π π + πππ - Phasor of source impedance. II. FCL CONFIGURATION AND ITS OPERATION The Fault Current Limiter (FCL) is defined as “it is a variable impedance device connected in series with a circuit to limit the currentunder fault conditions [4]”. During normalcondition the „FCLβ should have very low impedance and under fault condition it should have high impedance [5,6]. FCL has potential to reduce fault level on the electricity power networks and may ultimately lead to lower rated components being used or to increased capacity πK(N) =( πL1+πSL )β₯(πL2+π) (4) International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 107 Voltage SAG compensation of point of common coupling (PCC) using fault current limiter in three phase lines onexisting systems[4]. FCL limits the circuitcurrent to an acceptable level[7,8]. short VSWF - Forward voltage drop on the semiconductor switch Iave - Average of diodes current in each cycle that is equalto Ipeak/π Fig.4 shows Fault Current Limiter (FCL) circuit topology which is formed by composing of two individual parts. Considering (9) the power loss FCL becomes a very small percentage of the feederβs transmitted power. In the fault condition, the PCC voltage drops on the shunt impedance. Therefore, the line current will bypass through the shunt resistor (Rsh). As a result, power loss on the Rsh depends on its value. Note that the fault condition is more than a few cycles and it is a small time interval. 1) Bridge part that includes a diode rectifier bridge, a small dc limiting reactor (Ldc) .resistance (Rdc), a semiconductor switch (IGBT or GTO),and a freewheeling diode(D5) . 2) Shunt branch as a compensator that includes a resistor and an inductor (Rsh + jωLsh). III. CONTROL STRATEGY Fig.5 shows the control circuit of the FCL. In the normal operating condition of the power system, IGBT is turned ON and the line current (i L) flows through “D1, Ldc, IGBT, D4” and “D3, Ldc, IGBT, D2” in positive and negative alternatives, respectively. So, Ldc is charged to the peak of the line current and behaves as a short circuit. Using semiconductor devices and a small dc reactor cause a negligible voltage drop on the FCL. During fault condition, Idc become greater than the maximum permissible current I m. The control circuit detects it and turns the semiconductor switch off. So the bridge retreats from the feeder, and the shunt impedance enters the faulted line and limits the fault current. At this moment, the freewheeling diode discharges Ldc. In fact, the freewheeling diode is used to provide a free route for the dc reactor current when the semiconductor switch is OFF. Figure 4. Fault Current Limiter (FCL) circuit topology. Previously thyristor based FCL is used instead of one semiconductor device (IGBT) at bridge arms for reducing the levels of the fault current.Thyrister based FCLposses two limitations first, they have more complicated control system. Second, considerable voltage drop on the FCL and the ac power loss on the shunt branch impedance, dc reactor power loss in the normal operating condition. In the proposed topology IGBT based FCL is used to reduce the voltage drop and power losses, increase the speed of operation. It is possible to choose a small value for Ldc to prevent severe rate of change of current at the beginning of the fault occurrence. In the normal operating condition the FCL has the power losses on the rectifier bridge diodes, IGBT, Rdc.Therefore,the power loss of this FCL can be calculated as Figure 5. Control circuit of the proposed FCL After the fault is removed, while the semiconductor switch is OFF, shunt impedance will be connected in series with the load impedance. Therefore, line current will be reduced instantaneously. To detect this instantaneous reduction of line current, iLis compared fault current (If) with that can be calculated from ππππ π = ππ + ππ· + πππ 2 = π ππ πΌππ + 4ππ·πΉ πΌππ£π + ππππΉ πΌππ where Idc VDF (9) - dc side current which is equal to the peak of line current -Forward voltage drops on each diode Iπ = π ππΆπΆ π π β + ππ πΏπ β (10) International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 108 Voltage SAG compensation of point of common coupling (PCC) using fault current limiter in three phase lines When the difference of line current (iL) and fault current(If)becomelarger than as the fault removal sign, the control circuit turns the semiconductor switch ON. So, the power system proceeds to the normal state. The value of k can be calculated from as k= π ππΆπΆ ππ β − π ππΆπΆ ππ β + ππΏ,πππ However, it is difficult to equate these impedances exactly because of the load variation on distribution feeders. So it is difficult to estimate the suitable value for Lsh and Rsh. From a practical point of view, parameters of the shunt branch can be resolute by using the history of load measurements at the protected distributed feeder. It is obviously the power and current flowing through the feeders is change. For the calculation of Lsh and(3.11) Rsh values, average impedance of the protected feeder is calculated. So Lshand Rshare chosen to be equal to its inductance and resistance. The horizontal axis of this Fig.6(a) shows the magnitude of load impedance in per unit where the base value is its impedance of the ideal case. The dashed line represents the existence of the ideal case. The ratio of reactance to resistance of shunt branch is kept constant in this figure. The parameter of this figure is the magnitude of source impedance. This figure shows that for a large range of load magnitude variations (0.5 to 2 p.u. with a fixed shunt branch impedance), the voltage magnitude of PCC for the post fault condition changes in an acceptable range especially for low values of ππ . Fig.6(b) shows the phase-angle deviation of the PCC from its base value that is the phase-angle deviation of pre fault PCC voltage. The horizontal axis of this figure is the ratio of reactance to resistance of shunt branch in per unit where the base value is obtained from the ideal condition. This figure shows that it is possible to decrease the resistance of the shunt branch (without changing the magnitude of itsimpedance) in a large range without any considerable phase-angle jump during fault. Decreasing Rsh reduces the power loss of the shunt branch during the short-circuit interval. So its design becomes simpler. (11) whereZsh is the shunt impedance, and ZL,min is the minimum impedance of load on the protected feeder. By the use of diodes,IGBTs and small dc reactor there is a voltage drop on FCL.This results harmonic distortion on load voltage and power loss in shunt branch in normal operating conditions.the voltage drop on power electronic devices is compensated by considering a dc source in the proposed FCL. So it reduces the total harmonic distortion (THD) of voltage waveform. Benefits of the FCL: FCLs offer numerous benefits to electric utilities. For instance, utilities spend millions of dollars each year to maintain and protect the grid from potentially destructive fault currents. These large currents can damage or degrade circuit breakers and other expensive T&D system components. Utilities can reduce or eliminate these replacement costs by installing FCLs. Other benefits include: 1. Enhanced system safety, stability, and efficiency of the power delivery systems. 2. Reduced or eliminated wide-area blackouts, reduced localized disruptions, and increased recovery time when disruptions do occur. 3. Reduced maintenance costs by protecting expensive downstream T&D system equipment from constant electrical surges that degrade equipment and require costly replacement. 4. Improved system reliability when renewable and DG are added to the electric grid. 5. Elimination of split buses and opening bustie breakers. 6. Reduced voltage dips caused by high resistive system components. 7. Single to multiple shot (fault) protection plus automatic resetting Figure 6(a) Magnitude of the PCC voltage. III. DESIGN CONSIDERATIONS For designing shunt branch parameters, it is possible to consider the following conditions. 1. 2. In the ideal case, shunt branch impedance is equal to load impedance. When a fault occurs in the protected feeder, the voltage sag at the PCC will be zero. International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 109 Voltage SAG compensation of point of common coupling (PCC) using fault current limiter in three phase lines Figure 6(b) Phase angle deviation of the PCC. Figure7. Simulation model of three phase system without FCL Three single phase sources are taken for simulation and the combined voltage wave form at PCC during the three phase fault created at t=0.1 sec to t=0.2 sec is plotted in Fig.8, Fig.9 shows the instantaneous power in first phase of the system at PCC with fault condition. IV. SIMULINK MODELING AND RESULTS OF FCL This FCL topology has been implemented on three phase system and the results are presented in this section. Three phase system is considered for the analysis and simulation because it would be more practical to carry out the analysis on the widely used three phase sensitive loads in industries. During the three phase balanced fault condition, without using the FCL, the voltage sag appears severely at PCC.when FCL is used it will reduces the fault current as well as the voltages of the other feeders are restores to the normal value. The FCL improves the system reliability and voltage quality. The system parameters are in Table I. The simulations are obtained using the MATLAB/SIMULINK software. Figure 8.Three phase voltages at PCC without FCL. Table I: System parameters Power 20kv,50Hz,X/R ratio:5 source Total Impedance:1.608β¦ Source Side Data Transform 20kv/6.6kv,10MVA,0.1 er pu Feeder F1 j0.314β¦ Distributi on Feeders Feeder F2 J0.157β¦ Data Ldc=0.01H,Rdc=0.03β¦ VDF=3V,VSWF=3V,Im=0. DC Side 6kA FCL Data Switch type: IGBT Shunt Lsh=0.08H,Rsh=5β¦ Branch Sensitive 10+j15.7β¦ load Load Data Load Of 15+j31.3β¦ F2 Figure9.Power Waveform at PCC for one phase Fig. 10.Sshows simulation model of three phase system with FCL.when the fault is occurs the FCL inserts large impedance in to the faulted line and prevents the voltage sag and phase angle jump at the substation PCC. I1 Goto2 + v - r v1 + l3 i3 V1 Goto1 i - AC Voltage Source l3 i3 l1 Goto2 + v - v1 l1 I1 V1 Goto1 i - + 1 Measurements 2 tf1 r +v e AC Voltage Source 1 l2 + i - + -v e Measurements 2 c Pulse Generator + i - + i - I2 v2 Breaker i - + I2 l7 i5 l5 V2 Goto3 Goto4 + v - 2 1 Breaker V2 Goto3 c Pulse Generator l4 2 1 l4 i i1 l2 i - i i1 FCL tf1 Goto4 + v - v2 + r1 i - l7 i5 l5 AC Voltage Source1 1 2 tf2 r1 AC Voltage Source1 1 2 +v e l6 i - + i - + -v e c c Pulse Generator1 I3 2 1 2 1 Breaker1 l8 i2 i4 l6 Pulse Generator1 i - + i + - Goto5 Breaker1 V3 + v - Discrete, Ts = 5e-005 s. Goto6 powergui v3 I3 Goto5 + V3 + v - Discrete, Ts = 5e-005 s. Goto6 + i8 i - l9 i - l11 i8 powergui v3 l9 l8 i2 i4 FCL1 tf2 r2 l11 AC Voltage Source2 1 2 r2 tf3 AC Voltage Source2 1 2 +v e tf3 l10 + l10 + i - l12 i6 i7 c Pulse Generator2 1 -v e FCL2 + + i - i - l12 i6 i7 c i - Pulse Generator2 1 2 Breaker2 2 Breaker2 Figure10. Simulation model of three phase system with FCL International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 110 Voltage SAG compensation of point of common coupling (PCC) using fault current limiter in three phase lines V. CONCLUSION In this paper, voltage sag compensation, phaseangle jump mitigation, and fault current limiting operation were analyzed. The designed FCL is capable of mitigating voltage sag and phase-angle jump to acceptable levels. By using the semiconductor switch in the dc current path instead of two numbers of Thyristors at the bridge branches, the FCL will have high speed and consequently, the dc reactor value is reduced to a lower value.In addition, the dc voltage source placed in the FCL structure reduces its THD and ac losses in normal operation. In general, this type of FCL, with the simple control circuit and low cost, is useful for the voltage-quality improvement because of voltage sag and phase-angle jump mitigating and low harmonic distortion in distribution systems. In addition to that three phase power systems are developed with and without the FCL as well as their behaviors are also observed. Figure 11.Three phase voltages at PCC with FCL. REFERENCES Figure 12.Voltage drop across FCL. [1] J. V. Milanovicand y. Zhang, “Modeling of Facts devices for voltage sag mitigation studies in large power systems,” IEEE Trans. Power del., vol. 25, no. 4, pp. 3044–3052, oct. 2010. [2] T. J. Browne and G. T. Heydt, “Power quality as an educational opportunity,”IEEE Trans. Power Del., vol. 23, no. 2, pp. 814–815, May2008. [3] N. Ertugrul, A. M. Gargoom, and W. L. Soong, “Automatic classificationand characterization of power quality events,” IEEE Trans. PowerDel., vol. 23, no. 4, pp. 2417–2425, Oct. 2008. [4] M. Abapour, S. H. Hosseini, and M. T. Hagh, “Power quality improvementby use of a new topology of fault current limiter,” in Proc. ECTICON,2007, pp. 305–308. Figure 13.Shunt Current. [5] M. Brenna, R. Faranda, and E. Tironi, “A new proposal for powerquality and custom power improvement: Open UPQC,” IEEE Trans.Power Del., vol. 24, no. 4, pp. 2107– 2116, Oct. 2009. [6] W. M. Fei, Y. Zhang, and Z. Lü, “Novel bridge-type FCL based on selfturnoffdevices for three-phase power systems,” IEEE Trans. PowerDel., vol. 23, no. 4, pp. 2068–2078, Oct. 2008. [7] E. Babaei, M. F. Kangarlu, and M. Sabahi, “Mitigation of voltage disturbancesusing dynamic voltage restorer based on direct converters,”IEEE Trans. Power Del., vol. 25, no. 4, pp. 2676–2683, Oct. 2010. Figure 14.DC Side Current. [8] M. Moradlou and H. R. Karshenas, “Design strategy for optimum ratingselectionof interline DVR,” IEEE Trans. Power Del., vol. 26, no. 1,pp. 242–249, Jan. 2011. [9] Fabio, Tosto; “Voltage Sag mitigation on Distribution Utilities”, ETEP- European Transaction on Electric power, Vol. 11(1), pp. 17-21, January/February 2001. . [10] L. E. Conrad, “Proposed chapter 9 for predicting voltage sags (dips) inrevision to IEEE std. 493, the gold book,” IEEE Trans. Ind. Appl., vol.30, no. 3, pp. 805–821, May/Jun. 1994. *** Figure 15.Three phase power. International Conference on Electrical Electronics and Computer Science-EECS-9th Feb 2014-ISBN-978-93-81693-54-2 111