CONFIDENTIAL INFORMATION BASLER ELECTRIC, Publication: INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: APR 63-5 of Basler Electric, Highland, IL. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric. BOX 269, 9 1687 00 991 © 1997-2000, Basler Electric, Highland, IL 62249 First Printing November 1986 Revision E ECO: 9609 HIGHLAND, IL 62249 PHONE 618/654-2341 INTRODUCTION Basler Electric Highland, Illinois COM 200 SOLID-STATE VOLTAGE REGULATOR 50 HZ Sensing: 240, 480 Vac Power: 190-277 Vac 650VA Output: 63 Vdc 5A Oper. Freq. 50/60 Hz 4.75 (121) CB- CB+ R F- Model: APR 63-5 5.66 (144) F+ FREQ 4 Regulation is provided by sensing the generator output voltage, converting it to a dc signal and comparing the signal to a reference voltage signal. An error signal is developed and used to control the dc field power in order to maintain a constant generator output. 6 STAB 7 240 480 0.45 (12) D2717-07 11-18-97 1.58 (40) 1.68 (43) 0.625 (15.88) Voltage Adjust Range (Internal):170 to 264 Vac (240 V tap) or 340 to 528 Vac (480 V tap). External Voltage Adjust Rheostat: 1,000 ohms, 2 W (supplied as an optional item). Voltage Build-Up: Internal and automatic from generator residual voltage (6 Vac minimum). Overexcitation Shutdown: Output power removed under the following conditions: Exciter field voltage exceeds 100 ±5 Vdc for a time inversely proportional to voltage magnitude, or instantaneously if voltage exceeds 135 ±5 Vdc. 0.375 (9.53) Storage Temperature: –65°C (–85°F) to +85°C (+185°F) FUSES Install 5 A, 250 V, high interrupting capacity, fast-blowing fuses in lines 3 and 4. See interconnection diagrams. MOUNTING The regulator may be mounted in any position. Refer to the outline drawing for dimensions. The regulator may be mounted directly on the generator set using ¼” hardware. Select the proper hardware to withstand any expected shipping or transportation conditions. 0.125 (3.18) 0.81 (20.64) 120 100 110 120 130 FIELD VOLTS (dc) 140 150 135 5+- a. Set generator RPM to desired frequency roll-off. b. Adjust FREQ control until voltage starts to drop off. c. Speed up generator to rated speed. Voltage should be at nominal. "CORNER FREQUENCY" STAB CONTROL 100 50 HZ 80 This control allows the generator response time (and thus voltage stability) to be adjusted. Use an oscilloscope or other voltage recording device to set this control. 60 60 HZ 40 a. Rotation of STAB control CW will slow voltage response time. b. Rotation of STAB control CCW will speed response time. If rotated too far, generator voltage will hunt (oscillate). c. Rotate STAB control CW just past point where voltage oscillation occurs. 20 0 90 This control prevents generator and regulator damage by dropping the generator output voltage when the generator frequency drops. NOTE: ALL DIMENSIONS ARE IN INCHES (MILLIMETERS) External Voltage Adjust Potentiometer (Optional), Basler P/N 17727 Operating Temperature: –40°C (–40°F) to +60°C (+140°F). 80 FREQ CONTROL 1.094 (27.78) D2717-08.vsd 06-06-00 70 Typical Inverse Time Delay Characteristic Curves 0.53 (13.49) 0.25 (6.35) GENERATOR OUTPUT (% FROM NOMINAL) AC Sensing Input: 190 to 240 Vac (240 V tap), 380 to 480 Vac (480 V tap), single-phase, 50/60 Hz. Burden: 5 VA maximum. D2717-06 11-18-97 REGULATOR CONTROLS 0.625 (15.88) Exciter Field DC Resistance: 12.6 ohms minimum, 100 ohms maximum. 10 8 6 5 4 3 1 3.16 (80) APR 63-5 Outline Diagram DC Output Power: 5.0 Adc @ 63 Vdc (315 W) maximum continuous, 8.5 Adc @ 105 Vdc (893 W) one minute forcing. 20 0.90 (23) NOTE: ALL DIMENSIONS ARE IN INCHES (MILLIMETERS) Certification: UL Listed, CSA Certified 100 80 60 50 40 30 2 1.35 (34) SPECIFICATIONS AC Input Power: 190 to 277 Vac ±10%, singlephase, 50/60 Hz. Burden: 650 VA. 3 VOLT TIME DELAY (SECONDS) R FAX 618/654-2351 500 400 300 60 HZ The Basler APR 63-5 Voltage Regulator is a CSA/UL approved unit contained in an encapsulated plastic case. The regulator controls the dc exciter field power of conventional, 50 or 60 hertz brushless generators that have a 63 Vdc field to regulate the output voltage. June 2000 0 10 20 30 40 50 60 D2717-05 11-18-97 FREQUENCY (HZ.) Frequency Compensation Curves OVEREXCITATION SHUTDOWN If the exciter field voltage exceeds 100 ±5 Vdc, the regulator automatically removes the field current after a time delay. The time delay is inversely proportional to the magnitude of the detected overvoltage condition. At approximately 135 ±5 Vdc, the field voltage is removed instantaneously. Refer to the following figure. Upon detection of overexcitation and the resulting field voltage shutdown, the regulator will not reset or return to an operational condition until the generator output drops to less than 6 Vac for 10 seconds minimum. VOLT CONTROL Rotation of VOLT control CW will increase generator output voltage. Removing jumper (terminals 6 and 7) and connecting external potentiometer (1,000 ohms, 2 watts) allows a ±10% adjustment of voltage range with nominal set by VOLT control. INTERCONNECTION Refer to the following interconnection diagrams. a. Connect the jumper from COM to either the 50 Hz or 60 Hz terminal depending upon the generator frequency. b. Remove the jumper and connect terminals CB– and CB+ to the CBS 305 inputs (if used). If the CBS 305 is not being used, leave the jumper in place. c. A B GEN C FIELD ISOLATION TRANSFORMER If an external voltage adjust control is being used, connect the potentiometer to terminals 6 and 7 as shown. If not, connect a jumper between terminals 6 and 7. Connect the input power to the generator stator to provide power to terminals 3 and 4. Fuse both leads. Install the optional shutdown switch, if desired. f. Connect the sensing input to either 240 or 480 depending on voltage. The sensing should be connected line-to-line. Parallel Compensation - APM2000 and Current Transformer E1 Current Boost System - CBS305 and Current Transformer SHUTDOWN SWITCH EXTERNAL VOLTAGE ADJUST Connect the exciter field to terminals F+ and F–. Be sure to observe polarity. e. Power Isolation Transformer - BE 18674 001 Manual Voltage Control - MVC-300 4 3 TO CBS 305 (OPTIONAL) 1 OPERATIONAL TEST CW } d. 2 2 ACCESSORY EQUIPMENT a. Connect the test setup as shown below and apply 240 Vac as shown. b. Adjust the VOLT control fully CCW. Observe that the lamp is not lit. c. Adjust the VOLT control fully CW. Observe that the lamp is lit. d. Adjust the VOLT control until the lamp just goes out. 4 3 60 HZ COM 50 HZ CB- CB+ F- F+ 4 6 APR 63-5 VOLTAGE REGULATOR 7 3 240 480 D2717-11 11-18-97 1 JUMPER FOR 60HZ OR 50HZ. 2 250V, 5A, FAST BLOW, HIGH INTERRUPTING CAPACITY FUSES. 3 REMOVE JUMPER IF CBS 305 IS USED. 4 IF EXTERNAL ADJUST RHEOSTAT IS NOT BEING USED, JUMPER TERMINAL 6 TO TERMINAL 7. Isolation Transformer Interconnection Diagram A B GEN C FIELD OPERATION 60 HZ The following system operation procedures provide instructions for adjusting the APR 635 Voltage Regulator. R J1 Basler Electric Highland, Illinois COM SOLID-STATE VOLTAGE REGULATOR 50 HZ Sensing: 240, 480 Vac Power: 190-277 Vac 650VA Output: 63 Vdc 5A Oper. Freq. 50/60 Hz CB- J3 CB+ 10 OHMS R 2 2 F- CAUTION EXTERNAL VOLTAGE ADJUST CB- CB+ F- F+ 4 6 7 3 240 To prevent damage to the regulator, complete the following steps before proceeding with system startup. 480 D2717-09 11-18-97 1 JUMPER FOR 60HZ OR 50HZ. 2 250V, 5A, FAST BLOWING, HIGH INTERRUPTING CAPACITY FUSES. 3 REMOVE JUMPER IF CBS 305 IS USED. 4 IF EXTERNAL ADJUST RHEOSTAT IS NOT BEING USED, JUMPER TERMINAL 6 TO TERMINAL 7. a. Verify that the voltage regulator specification conforms with the generator system requirements. b. Ensure that the regulator is correctly connected to the generator. See interconnection diagram. c. Install fuses per FUSES paragraph. 240 Vac, 1-Phase Interconnection Diagram A B 480V GEN C N FIELD a. TO CBS 305 (OPTIONAL) Slowly adjust VOLT control until voltage reaches nominal value. If used, adjust remote voltage adjust to set generator output to exact value desired. c. Apply and remove load to check stability. Adjust per STAB CONTROL paragraph if voltge is unstable. d. Reduce generator frequency (speed) to 55 Hz (on 60 Hz systems) or 45 Hz (on 50Hz systems). Check that generator output decreases from this point. If it does not, adjust per FREQ CONTROL paragraph. } CW 4 3 CB- CB+ Start the prime mover and bring it up to rated speed. Voltage should build up. If a minimum residual of 6 Vac is not present, perform field flashing. b. EXTERNAL VOLTAGE ADJUST 50 HZ 240 VAC 3 F- F+ 4 6 7 3 APR 63-5 VOLTAGE REGULATOR 240 480 D2717-10 11-18-97 1 JUMPER FOR 60HZ OR 50HZ. 2 250V, 5A, FAST BLOWING, HIGH INTERRUPTING CAPACITY FUSES. 3 REMOVE JUMPER IF CBS 305 IS USED. 4 IF EXTERNAL ADJUST RHEOSTAT IS NOT BEING USED, JUMPER TERMINAL 6 TO TERMINAL 7. 480 Vac Interconnection Diagram Operational Test Setup FIELD FLASHING When the regulator is operated with the generator for the first time, the polarity of residual magnetism may not be correct or the magnitude may not be enough. If the generator does not build up, shut down the prime mover and proceed as follows. a. With the prime mover at rest, apply a dc source (not grounded) of not more than 48 Vdc to terminals F+ and F– in series with a limiting resistor. Use 1 ohm of resistance for each volt from the dc source with a power rating of at least 1 watt per volt. b. Allow approximately 30 seconds before removing the dc source. c. Start the prime mover and measure the voltage at the regulator leads 3 and 4. If the voltage is greater than 6 Vac, voltage buildup should occur. Repeat flashing if less than 6 Vac residual is measured. SYSTEM STARTUP SHUTDOWN SWITCH COM VOLT During periods of prime mover idling, use the excitation shutdown switch. 2 2 60 HZ J2 7 PRELIMINARY SETUP APR 63-5 VOLTAGE REGULATOR 1 6 240 CW } 50 HZ 4 STAB D2717-12 11-18-97 4 COM 100 W LIGHT BULB 480 TO CBS 305 (OPTIONAL) 3 60 HZ 10 W F+ FREQ Meggers and high potential test equipment must not be used. Incorrect use of such equipment could damage the semiconductors contained in the regulator. SHUTDOWN SWITCH 1 Model: APR 63-5