VL Circuit Breaker – NG 1200A frame Breaker type Defined by the 3rd character of the catalog number G – Global (UL, CSA, NOM, IEC, CE), interchangeable X – Global, non-interchangeable Y – Global, 100% rated, non-interchangeable Trip unit type Defined by the 5th character of the catalog number B – Thermal-magnetic, model 525 N– LI, electronic, model 545 P – LSI, electronic, model 545 X – LIG, electronic, model 545 U – LSIG, electronic, model 545 D – LSI, electronic with LCD, model 576 E – LSIG, electronic with LCD, model 576 R – LI, electronic, Model 555 T – LSI, electronic, Model 555 W – LIG, electronic, Model 555 V – LSIG, electronic, Model 555 A – LSI, electronic with LCD, Model 586 G – LSIG, electronic with LCD, Model 586 K – LSI + GF alarm, electronic with LCD, Model 586 For DC applications, use thermal magnetic trip unit only. For reverse-feed applications, select non-interchangeable trip breakers only. HACR rated. Interrupting ratings Interrupting Class Breaker Type N H L NNG HNG LNG UL / CSA / NOM 40ºC 50/60Hz RMS symmetrical amperes (kA) UL 489 Volts AC 240 480 600 65 100 200 IEC 40ºC 50/60Hz 35 65 100 25 35 65 Trip Unit Model 525 Thermal magnetic trip units, model 525 In – Trip unit rating Ii – Nominal instantaneous trip (amps) adjustable range (amps) 800 4000 4800 5600 6400 900 5000 6000 7000 8000 1000 5000 6000 7000 8000 1200 7000 8000 9000 10000 IEC 60947-2 Volts AC 240 Icu/Ics 65 / 35 100 / 50 200 / 100 415 Icu/Ics 50 / 25 70 / 35 100 / 50 690 Icu/Ics 20 / 10 30 / 15 35 / 17 UL or IEC Volts DCa 250 500 600b 22 25 42 35 50 65 – 65 – a For DC applications and wiring diagrams, see p. 5 of VL Information Guide. b Special version, Type HNGD. See Speedfax catalog for more information. Ii M4-PAN-TORX M4-PAN-TORX I n = 600A 3850 7200 9000 9000 11000 8000 10000 10000 12000 3300 4400 40 C 4950 2750 TM ~ 5500 Trip Unit/Disparador 525 Trip unit model 525 Trip Unit Model 545 Electronic trip units, Model 545 with LI (Trip unit type N) or LIG (Trip unit type X) Trip Functions In – Trip unit rating (amps) Switch 1 800 1000 1200 Ir – Continuous amp switch settings (amps) 300 300 315 350 400 400 400 500 400 400 500 600 In – Trip unit Switch 2 rating (amps) 800, 1000, 1200 Switch 3 In – Trip unit rating (amps) 800 1000 1200 Fixed settings (LIG only) In – Trip unit rating (amps) 800 1000 1200 500 630 700 600 700 800 630 800 900 700 900 1000 800 1000 1200 tr – Long time delay switch settings (seconds) Pt @ 6 x Ir 2.5 4 6 8 10 14 17 20 25 30 Ii – Nominal instantaneous trip switch settings (amps) 1000 1200 1600 2400 3200 1205 1500 2000 3000 4000 1500 1800 2400 3600 4800 4000 5000 6000 4800 6000 7200 6400 8000 9600 8000 10000 12000 8800 11000 12000 Ig – Ground fault pickup (amps) 480 600 720 tg – Ground fault delay .25 sec .32 sec .32 sec 400 600 630 Switch 1 Switch 2 Switch 3 Trip unit model 545 VL Circuit Breakers Information Guide 39 Trip Unit Model 545 (continued) Switch 1 Switch 2 Switch 3 Electronic trip units, Model 545 with LSI (Trip unit type P) or LSIG (Trip unit type U) Trip Functions Switch 1 In – Trip unit rating (amps) 800 1000 1200 Ir – Continuous amp switch settings (amps) 300 300 315 350 400 400 400 500 400 400 500 600 400 600 630 500 630 700 600 700 800 630 800 900 700 900 1000 800 1000 1200 In – Trip unit Switch 2 rating (amps) 800, 1000, 1200 Isd – Short time pick-up switch settings (amps) x Ir 1.5 2 2.5 3 4 5 6 7 8 10 In – Trip unit Switch 3 rating (amps) 800, 1000, 1200 tsd – Short time delay switch settings (seconds) @ 8xlr 0 0.1, I2t OFF 0.2, I2t OFF 0.3, I2t OFF 0.4, I2t OFF 0.5, I2t OFF 0.1, I2t ON 0.2, I2t ON 0.3, I2t ON 0.4, I2t ON Fixed settings In – Trip unit rating (amps) 800 1000 1200 tr – Long time delay 10 sec. (I2t @ 6 x Ir) Ii – Nominal instantaneous trip 8000A 10000A 12000A Ig – Ground fault pick-up (LSIG only) 480A 600A 720A tg – Ground fault delay (LSIG only) .25 sec. .32 sec .32 sec Trip Unit Model 555 Switch 1 Switch 2 Switch 3 Switch 4 Electronic trip units, Model 555 with LI (Trip unit type R) or LIG (Trip unit type W) Trip Functions In – Trip unit rating (amps) Switch 1 800 1000 1200 Ir – Continuous amp switch settings (amps) 300 315 350 400 400 450 500 550 400 450 500 600 In – Trip unit Switch 2 rating (amps) 800, 1000, 1200 Switch 3 In - Trip unit rating (amps) 800 1000 1200 In – Trip unit rating (amps) 800 1000 Switch 4 1200 (LIG Only) In – Trip unit rating (amps) 800 1000, 1200 40 500 630 700 600 700 800 630 800 900 700 900 1000 800 1000 1200 tr – Long time delay switch settings (seconds) I2t @ 6 x Ir 2.5 4 6 8 10 14 17 20 25 30 Ii - Nominal instantaneous trip switch settings (amps) 1000 1200 1600 2400 3200 1250 1500 2000 3000 4000 1500 1800 2400 3600 4800 4000 5000 6000 4800 6000 7200 6400 8000 9600 8000 10000 12000 8800 11000 12000 Ig - Ground fault pick-up switch settings (amps) 480 320 320 320 480 600 400 400 400 600 720 480 480 480 720 480 600 720 480 600 720 800 1000 1200 800 1000 1200 800 1000 1200 tg – Ground fault delay switch settings (seconds) 0.25 0.10 0.20 0.30 0.10 0.32 0.10 0.20 0.30 0.10 0.20 0.20 0.30 0.30 0.10 0.10 0.20 0.20 0.30 0.30 VL Circuit Breakers Information Guide 450 600 630 Trip Unit Model 555 (continued) Switch 1 Switch 2 Switch 3 Switch 4 Electronic trip unit, Model 555 with LSI (Trip unit type T) Trip Functions In – Trip unit rating (amps) 800 1000 Switch 1 1200 Ir – Continuous amp switch settings (amps) 400 500 600 700 600 700 800 900 700 800 900 1000 400 600 700 500 700 800 600 800 900 700 900 1000 800 1000 1200 tr – Long time delay switch settings (seconds) I2t @ 6 x Ir 10 10 10 10 10 20 20 20 20 20 In – Trip unit Switch 2 rating (amps) 800, 1000, 1200 Isd – Short time pick-up switch settings (amps) x Ir 1.5 2 2.5 3 4 5 6 7 8 10 In – Trip unit Switch 3 rating (amps) 800, 1000, 1200 tsd – Short time delay switch settings (seconds) 0 0.1, I2t OFF 0.2, I2t OFF 0.3, I2t OFF 0.4, I2t OFF 0.5, I2t OFF 0.1, I2t ON 0.2, I2t ON 0.3, I2t ON 0.4, I2t ON In – Trip unit rating (amps) Switch 4 800 1000 1200 Ii – Nominal instantaneous trip switch settings (amps) 1000 1200 1600 2400 3200 1250 1500 2000 3000 4000 1500 1800 2400 3600 4800 4000 5000 6000 4800 6000 7200 6400 8000 9600 8000 10000 12000 8800 11000 12000 400 600 700 500 700 800 600 800 900 700 900 1000 800 1000 1200 In – Trip unit rating (amps) 800, 1000, 1200 800 1000 1200 Electronic trip unit, Model 555 with LSIG (Trip unit type V) Trip Functions In – Trip unit rating (amps) 800 1000 Switch 1 1200 Ir – Continuous amp switch settings (amps) 400 500 600 700 600 700 800 900 700 800 900 1000 800 1000 1200 In – Trip unit rating (amps) 800, 1000, 1200 tr – Long time delay switch settings (seconds) I2t @ 6 x Ir 10 10 10 10 10 20 20 20 20 20 In – Trip unit rating (amps) 800, 1000, 1200 Isd – Short time pick-up switch settings (amps) x lr 1.5 2 2.5 3 4 5 6 7 8 10 In – Trip unit rating (amps) 800, 1000 1200 Ii – Nominal instantaneous trip switch settings (amps) x ln 5 5 5 5 5 11 5 5 5 5 5 10 11 10 11 10 11 10 11 10 In – Trip unit Switch 3 rating (amps) 800, 1000, 1200 tsd – Short time delay switch settings (seconds) 0 0.1, I2t OFF 0.2, I2t OFF 0.3, I2t OFF 0.4, I2t OFF 0.5, I2t OFF 0.1, I2t ON 0.2, I2t ON 0.3, I2t ON 0.4, I2t ON In – Trip unit rating (amps) 800 1000 Switch 4 1200 Ig – Ground fault pick-up switch settings (amps) 480 320 320 320 480 600 400 400 400 600 720 480 480 480 720 480 600 720 480 600 720 800 1000 1200 800 1000 1200 800 1000 1200 In – Trip unit rating (amps) 800 1000, 1200 tg – Ground fault delay switch settings (seconds) 0.25 0.10 0.20 0.30 0.10 0.32 0.10 0.20 0.30 0.10 0.20 0.20 0.30 0.30 0.10 0.10 0.20 0.20 0.30 0.30 Switch 2 VL Circuit Breakers Information Guide 41 Trip Unit Model 576 and 586 ESC X3 440JM Trip unit model 576 Trip unit model 586 Electronic trip units with LCD Model 576 (Trip unit type D and E) or Model 586 (Trip unit type A, G and K) In – Trip tr – Long time delay Isd – Short time tsd – Short time Ir – Continuous unit rating settings (I2t @ 6 x Ir) pick-up range delay settings amps rangea (amps) 800 300 - 800 1.25 - 10 x Ir (8,000 A max.) 2.5, 4, 6, 8, 10, 14, 0.1, 0.2, 0.3, 0.4, 0.5 sec. 1000 400 - 1000 1.25 - 10 x Ir (10,000 A max.) 17, 20, 25, 30 sec. (I2t off) or I2t @ 8 x Ir (I2t on) 1200 400 - 1200 1.25 - 10 x Ir (10,800 A max.) Ig – Ground fault pick-up rangea 320 - 800A 400 - 1000A 480 - 1200A In – Trip unit rating (amps) 800 1000 1200 Ii – Nominal instantaneous trip rangeab 1000 - 8800A 1250 - 11000A 1500 - 12000A tg – Ground fault delay Pre-alarm indication 0.1, 0.2, 0.3, 0.4, 0.5 sec. (I2t off) or I2t @ .5 x In (I2t on) 80 - 100% x Ir (Amps) a Current settings are adjustable in 1-amp increments. b Model 586, can turn function OFF. Instantaneous trip override function will be enabled to ensure self protection of circuit breaker. Motor circuit protectors Amp rating 1200 Ii – Nominal instantaneous trip adjustable range (amps)a 7000 – 12000 a Settings adjustable in increments of 1000 amps. 600 V DC circuit breakers Amp rating 800, 900, 1000, 1200 42 Short-circuit rating 600 V DC 65 kA VL Circuit Breakers Information Guide Molded case switch Amp rating 1200 1200 Self-protective instantaneous override 12000A 12000A Short-circuit current rating 480 V ACa 65 kA 100 kA a Max. available current when protected by an appropriate overcurrent protective device. Terminal Connectors Wire range Cables per connectors Wire size Torque Ib-in. (Nm) Catalog number 1/0 – 500 kcmil 4 (Cu / Al) 1/0 - 500 375 (42.37) 3TA4NG500 ab 500 – 750 kcmil 3 (Cu / Au) 500 - 750 375 (42.37) 3TA3NG750 b 1/0 – 500 kcmil 4 (Cu / Al) 1/0 - 500 375 (42.37) 3TA4NG500Hbc 1/0 – 500 kcmil 4 (Cu / Al) 1/0 - 500 375 (42.37) 3TC4NG500bc Compression connector kits 1/0 - 500 kcmil 12CLN500d 4 (Cu / Al) a Standard connector when an “L” suffix is used on an assembled breaker catalog number. b Packaged as 3 connectors. c For 100% rated NG applications. Requires 90ºC cable sized at 75ºC ampacity. d Packaged as 12 connectors (4 connectors per phrase). Internal accessories Auxiliary and alarm switch kits Description Auxiliary / Alarm switches only (requires a base) Mounting pocket Catalog number 2 Aux + 2 Alarm switches (2NO + 2NC + 1 base) Left ASKP3 4 Aux. switches (2NO + 2NC + 1 base) Left, right ASKP4 Auxiliary and alarm switch mounting base only Description Mounting pocket Catalog number For 2 Aux + 2 Alarm Left AMBP2 For 4 Aux Left, right AMBP1 Shunt trip Control voltage Catalog number 48 – 60 VAC STRPM60 110 – 127 VAC STRPN120 208 – 277 VAC STRPS277 380 –600 VAC STRPV600 24 VDC STRPB24DC 48 –60 VDC STRPC60DC 110 – 127 VDC STRPD125DC 220 – 250 VDC STRPE250DC Description Catalog number 1 NO (normally open contact) ASWPA 1 NC (normally closed contact) ASWPB (A) Normally open contacts are open when the breaker contacts are open. (B) Normally closed contacts are closed when the breaker contacts are open. Undervoltage release Control voltage Catalog number 110 – 127 VAC UVRPN120 220 –250 VAC UVRPR240 208 VAC UVRPP208 277 VAC UVRPS277 380 – 425 VAC UVRPT415 440 – 480 VAC UVRPU480 12 VDC UVRPA12DC 24 VDC UVRPB24DC 48 VDC UVRPC48DC 60 VDC UVRPG60DC 110 – 127 VDC UVRPD125DC 220 – 250 VDC UVRPE250DC Shunt trips or UVR’s may be mounted in the Right Pocket only. Internal accessory locations Left accessory pocket Right accessory pocket Up to 4 auxiliary switchesa Shunt trip or UVR or up to 4 auxiliary switchesa Up to 2 auxiliary switchesb + 2 alarm switches Shunt trip or UVR or up to 4 auxiliary switchesa Maximum of 8 switches total. Maximum of 2 alarm switches, Left Pocket only. Maximum of 4 switches in Left Pocket. a Max load is 5A per switch when 4 switches are mounted. b Max load is 10A per switch. VL Circuit Breakers Information Guide 43 Dimensions (complete breaker) 13.12 [333.3] Z 8.22 [208.9] 3.00 [76.2] 6.86 [174] I O OFF X 7.86 [199.6] Y X 7.50 [190.5] 13.06 [331.8] I X 1.46 [37.3] 4.68 [119.1] 8.74 [221.9] 16.00 [406.4] ON 1.50 [38.1] (3P) 6.18 [157.2] 14.24 [361.9] Y HANDLE EXTENSION 1.48 [37.3] NFT00827 9.00 [228.6] (3P) 1.50 [38.1] (3P) 4X ø.28 [ø 7.1] 3.82 [97] 1.90 [48.5] Y w Shipping weight, lbs. (kg) PolesFrame Trip unit 2,3 46.3 (21.0) 8.8 (4.0) Z Complete breaker 55.1 (25.0) SCALE: 1/8 (.125) FROM ORIGINAL 44 VL Circuit Breakers Information Guide Permissible mounting positions 30° 90° 90° 30°