Per Unit Analysis The per unit method of power system analysis eliminates the need for conversion of voltages, currents and impedances across every transformer in the circuit. In addition, the need to transform from 3-phase to 1-phase equivalent and vice versa is avoided with the use of per unit quantities. Single-Phase systems In the per unit system, any electrical quantity may be expressed in per unit as the ratio of the actual quantity and the chosen base value for that quantity. per unit value = actual value base value Four base quantities must be considered, that are: apparent power, voltage, current and impedance. In single-phase systems, the relationships among the base quantities are: S base = Vbase I base Vbase = I base Z base With only two equations relating the four quantities, it is necessary to specify two base values. The apparent power and the voltage bases are usually chosen equal to the rated values and the other two base values are computed accordingly. I base = S base Vbase (V ) (kVbase ) V = base = base = I base S base MVAbase 2 Z base 2 The specified power base is applicable to all parts of the power system. However, the voltage base varies across a transformer and so does the current and impedance bases. Note that the actual voltage, current and impedances change across the transformer. However, because the bases also change across the transformer, the per unit values are the same on both sides of the transformer. 31 Example A generator supplies a load through a feeder whose impedance is Z f = 1 + j 2Ω . The load impedance is Z L = 8 + j 6Ω . The voltage across the load is 120V. Find the real power and reactive power supplied by the generator. Take the load voltage as the reference phasor for per unit analysis. Assume that the generator has zero impedance and that S base = 1500VA & Vbase = 120V . Solution Ig ZF VL Eg The base current is: I base = IL ZL S base 1500 = = 12.5 A Vbase 120 The base impedance is: Z base 2 2 Vbase ) ( 120 ) ( = = S base 1500 = 9 .6 Ω The per unit values are computed as follows: VL = 120∠0 = 1∠0 pu 120 ZL = 10∠36.9 = 1.04∠36.9 pu 9 .6 IL = 1.0∠0 = 0.96∠ − 36.9 pu 1.04∠36.9 ZF = 2.24∠63.4 = 0.233∠63.4 pu 9 .6 32 The generator voltage in per unit is: E g = VL + I L Z F E g = 1∠0 + (0.96∠ − 36.9 )(0.233∠63.4 ) = 1.204∠4.8 pu E g = 1.204∠4.8 × 120∠0 = 144.5∠4.8 V The complex power is: S g = E g I g* S g = (1.204∠4.8)(0.96∠36.9 ) = 1.156∠41.7 = 0.863 + j 0.769 pu Pg = 0.863 × 1500 = 1295 Watt Qg = 0.769 × 1500 = 1154 VAR Three-Phase systems In three-phase systems, the base power is the total three-phase power and the base voltage is the lineto-line voltage. With the Star connection assumed, the base line current is equal to the base phase current. The base impedance is per phase. The three-phase base quantities are related to the single phase bases as follows: Base Power, S base 3−φ = 3S base 1−φ Base Voltage, VL base = 3V phase base = Base Current, I L Base Impedance, Z base S total = base 3VL (V = base base S phase base V phase base ) = (V = I phase S total base ) 2 2 L base base phase base S phase base 33 The impedance characteristic of electrical equipment is usually expressed as a percentage based on its ratings. When such a device is connected in a power system in which the selected base values are different from the machine ratings, the per-unit quantities have to be expressed in terms of the system bases. The per unit values of any impedance may be converted to the new base as follows: Z pu new = Z pu æ S base new öæ Vbase old ö ç ÷ç ÷ old ç S ÷ ç ÷ V è base old øè base new ø 2 Example A three-phase, 60 Hz, 30 MVA, 13.8kV, wye connected synchronous generator has an armature resistance Ra = 2Ω per phase and a synchronous reactance X s = 10Ω per phase. a) Express the machine impedance in per unit based on the machine ratings. b) Using the results in part (a), find the per unit impedance based on S base = 50MVA and Vbase = 34.5kV . Solution a) Z base 2 13.8) ( = 30 = 6.35Ω Z s = Ra + jX s = 2 + j10 = 10.2∠78.7Ω Zs pu = Zs 10.2∠78.7 = = 1.606∠78.7 pu Z base 6.35 2 b) Z s pu − new Zs pu − new æ 50 öæ 13.8 ö = 1.606∠78.7ç ÷ç ÷ = 0.428∠78.7 pu è 35 øè 34.5 ø = 0.084 + j 0.42 pu 34 NOTE In large power systems, the power base is usually chosen to be the rating of one of the major equipment. The power base is the same for all parts of the power system. The voltage bases are normally chosen as the nominal voltages in the various parts of the system or are selected to be the voltage ratings of the transformer windings. The current and impedance bases are computed based on the previously selected values of the power and voltage bases. Example A transformer of 30MVA, 60Hz, 15/138kV has equivalent impedance referred to the primary side of Z = 0.75 Ω . Calculate the Pu impedance of the transformer referred to both primary and secondary windings, taking the power base as 30MVA. Solution From the primary side Vbase 1 = 15kV and S base = 30MVA S base 30,000 = = 2,000 A Vbase 15 I base 1 = Z base 1 = Z pu = 1 (Vbase )2 = (15)2 S base Z1 Z base 1 30 = = 7 .5 Ω 0.75 = 0.1 pu 7.5 35 From the secondary side 2 æN ö æ 138 ö Z = Z1 çç 2 ÷÷ = 0.75ç ÷ = 0.75 × 84.64 = 63.48 Ω è 15 ø è N1 ø 2 \ 1 Vbase 2 = 138kV and S base = 30MVA I base 2 = Z base 2 2 2 Vbase ) ( ( 138) = = Z pu = 2 S base 30,000 = = 217.39 A Vbase 138 S base Z2 Z base ∴ Z pu 1 = Z pu 30 = 2 2 = 634.8 Ω 63.48 = 0.1 pu 634.8 = Z pu = 0.1 pu Example The one-line diagram of a three-phase power system is shown in the figure below. Select a common base of 100MVA and 22kV on the generation side and draw the impedance diagram with all impedances including the load impedance in per unit. The manufacturer data for each device is given in the table below. The three-phase load at bus #4 absorbs 57MVA, 0.6 power factor lagging at 10.45kV. Lines 1 and 2 have reactances of 48.4 and 65.43 ohms, respectively. Device Power (MVA) Voltage (kV) Reactance (%) G1 90 22 18.0 T1 50 22/220 10.0 T2 40 220/11 6.0 T3 40 22/110 6.4 T4 40 110/11 8.0 M 66.5 10.45 18.5 36 1 T1 T2 2 Line #1 220 kV 3 4 G M T3 5 Line #2 110 kV 6 T4 Load #1 Solution Vbase 1 (Low voltage of T1 ) = 22kV Vbase 2 (High voltage of T1 ) = 22æç 220 ö÷ = 220kV Vbase 3 (High voltage of T2 ) = 220kV Vbase 4 (Low voltage of T2 ) = 220æç è 22 ø 11 ö ÷ = 11kV è 220 ø æ 110 ö Vbase 5 = Vbase 6 = 22ç ÷ = 110kV è 22 ø The new per unit values for the reactances of G, T1, T2, T3 and T4 are: (Note: there is no change in the voltage base) æ 100 ö G: X = 0.18ç ÷ = 0.2 pu è 90 ø æ 100 ö T1: X = 0.10ç ÷ = 0.2 pu è 50 ø æ 100 ö T2: X = 0.06ç ÷ = 0.15 pu è 40 ø æ 100 ö T3: X = 0.064ç ÷ = 0.16 pu è 40 ø æ 100 ö T4: X = 0.08ç ÷ = 0.2 pu è 40 ø 37 The new per unit reactance for the motor M is: 2 æ 100 öæ 10.45 ö M: X = 0.185ç ÷ç ÷ = 0.25 pu è 66.5 øè 11 ø Z base Z base 2 2 2 ( Vbase ) ( 220 ) = = = 484 Ω , Line #1: X = 48.4 = 0.1 pu 484 5 2 2 Vbase ) ( ( 110 ) = = = 121Ω , Line #2: X = 65.43 = 0.54 pu 121 100 S base S base 100 The load impedance Z L = ∴ZL = V phase I phase Since S L ∴ZL = 3−φ = S L* ∴ZL pu 3(V phase ) = S L* 3−φ = 3V * phase phase I ÞI * phase = SL 3−φ 3V phase Þ I phase = S L* 3−φ * 3V phase 2 ( VLine ) = Ω 3−φ S L* 3−φ = 57∠ cos −1 0.6 = 57∠53.13 MVA = Z base 4 = = Ω , but S L 2 * 3V phase 3−φ 57∠ − 53.13 base I phase V phase (10.45)2 ∴ZL V phase = 1.1495 + j1.53267Ω (11)2 100 = 1.21Ω 1.1495 + j1.53267 = 0.95 + j1.2667 pu 1.21 The per unit impedance diagram can be drawn as shown in the figure below: J0.2 J0.1 J0.15 J0.16 J0.54 J0.2 J0.2 J0.25 0.95 G M J1.2667 38