CHAPTER 2 UPFC WITHOUT DC LINK CAPACITOR 2.1 INTRODUCTION The unified power flow controller, which has been recognized as one of the best featured FACTS devices [20, 38, 40], is capable of providing simultaneous active and reactive power flow control, as well as voltage magnitude control. The UPFC is a combination of static synchronous compensator and static synchronous series compensator which is connected via a common dc link, to allow bi-directional flow of real power between series output terminals of SSSC and the shunt terminals of the STATCOM, and is allowed to provide concurrent real and reactive power compensation. The UPFC comprises of two voltage source inverters, operated from a common dc link provided by a dc storage capacitor. The dc link capacitor should be properly designed so as to substantially reduce the ripple present in the dc voltage [57]. The ratings of this dc link capacitor bank pose a significant impact on the cost and physical size of the UPFC. Besides, this capacitor has shorter life when compared to ac capacitor of same rating. This in turn limits the life and reliability of the voltage source inverter [50]. Therefore efforts have to be taken to eliminate the need of the dc link capacitor and still obtain more or less the same performance. It is in this pretext two different schemes of UPFC without dc link capacitor have been proposed. In the first method the dc link capacitor present in the UPFC is eliminated and suitable modulation techniques [85, 86] are employed in the converter configurations so as to operate the UPFC without degrading its performances. The 15 front end converter is operated through a relatively new PWM scheme that enables to regulate the dc link voltage, minimize the ripples and improve the shape of the dc link current. Space vector modulation (SVM) strategy is used to fire the switches in the VSI. In the second method a matrix converter is employed in UPFC whereby the classical ac/dc and dc/ac converter structure with dc link capacitor is replaced by a matrix converter. The indirect space vector modulation technique is used to control the matrix converter present in the UPFC. The ISVM algorithm for the matrix converter has the inherent capability of controlling simultaneously both the output voltage vector and the instantaneous input current displacement angle [87]. The scope includes evaluating the performance of the proposed schemes of UPFC on a sample power system, in its different operating modes through MATLAB based simulation and highlights its ability as a powerful voltage regulator and a power controller. 2.2 POWER SYSTEM WITH THE EXISTING SCHEME OF UPFC The scheme of UPFC connected with a simple power system is shown in the Fig. 2.1. UPFC is placed between two sections B2 and B3 of the transmission line. The feeding network is represented by a Thevenin’s equivalent circuit [88, 89] at bus B1 where the voltage source is a 230 kV with a short circuit power level of 10,000 MVA and an X/R = 8. The system parameters are given in APPENDIX-A. The STATCOM model in the UPFC is connected in shunt with the transmission line using a step-down transformer having leakage reactance XT and a three phase IGBT based current source rectifier. The ac voltage difference across this transformer leakage reactance produces reactive power exchange between the STATCOM and the power system at the point of interface. The voltage can be regulated to improve the voltage profile of the interconnected power system. Thus the main function of STATCOM is to regulate the bus voltage magnitude either by absorbing or generating reactive power to the ac grid network. The SSSC which is 16 connected in series with the transmission line through a series transformer enhances the power flow over the line by emulating a series capacitance. The capacitance effect in series with the line is brought by injecting a voltage which is lagging the line current by 90°. Fig. 2.1 Power system embedded with a conventional scheme of UPFC 2.3 PROPOSED SCHEME OF UPFC WITHOUT DC LINK CAPACITOR The elimination of dc link capacitor results in considerable ripple in the dc link voltage and current distortions in the ac side. To overcome such problems three capacitors of much smaller rating and lower cost are used in the STATCOM side. The first converter present in the STATCOM side is operated as a current source rectifier (CSR) with a suitable pulse width modulation (PWM) technique. The objectives of this rectifier are to maintain a fixed dc voltage on the dc link without the dc link capacitor and to regulate the bus voltage. This CSR is connected in shunt with the transmission line through a coupling transformer. The converter present in the SSSC is connected in series with the transmission line through a series insertion transformer. It is controlled using space vector modulation technique to 17 enable it to generate synchronous ac voltage of controllable magnitude and phase angle with reduced harmonics. The scheme of ac-dc-ac conversion without dc link capacitor is shown in Fig.2.2. The filter components R, Lf and Cf present at the input side of the first converter have a significant role in maintaining the dc link current constant and reducing the distortions at the transformer and CSR interface. The switching functions of the current source rectifier and voltage source inverter are adjusted to maintain the average dc side voltage and current constant [45]. Fig. 2.2 Scheme of ac-dc-ac conversion without dc link capacitor 2.3.1 Modulation Techniques It is assumed that the ac input voltages to the current source rectifier after the step down shunt transformer are the three-phase balanced sinusoidal voltages. The expected line currents in the STATCOM side and the fundamental component of the line voltages injected into the transmission line in the SSSC side are described as i a = I m cos ( ωi t - ψin ) 2π ⎞ ⎛ i b = I m cos ⎜ ωi t - ψin ⎟ 3 ⎠ ⎝ 2π ⎞ ⎛ i c = I m cos ⎜ ωi t - ψin + ⎟ 3 ⎠ ⎝ (2.1) 18 where ψin is the STATCOM side power factor angle vsu = Vom cosθ Tu 2π ⎞ ⎛ vsv = Vom cosθ Tv = Vom cos ⎜ θ Tu ⎟ 3 ⎠ ⎝ 2π ⎞ ⎛ vsw = Vom cosθ Tw = Vom cos ⎜ θ Tu + ⎟ 3 ⎠ ⎝ (2.2) where θTu, θTv and θTw are the angle of the expected output voltage vectors. A Modified PWM Strategy for the CSR The dc side voltage of UPFC is essentially decided by the switching function of the first converter present in the STATCOM and the ac input voltage. In one full cycle of the ac input there are six switching intervals, during which one of the line or phase voltages will have the maximum absolute value. For example, in the interval 1, Vsa has the largest absolute voltage and in the interval 2, Vsc has the largest absolute voltage and so forth in all the intervals of the three phase sinusoidal voltage of a cycle. Each switching interval is divided into two portions. During the interval 1, when Vsa has the largest absolute voltage, T1 is held ON with T6 for the first 30o conduction period and all other rectifier switches remain in the OFF state. The dc side voltage is Vdc = Vsa-Vsb. In portion 2, for the next 30o conduction period T1 is held ON with T2 and all other rectifier switches are OFF. The dc side voltage is Vdc = Vsa-Vsc. The above sequence is applicable for all other intervals. By providing this switching sequence, dc voltage at the dc link can be maintained with a constant value. Table 2.1 shows the states of the rectifier switches and the dc voltage of each portion for all the six intervals. Fig.2.3a) and Fig.2.3b) depict the carrier waveform and the PWM scheme applied to the front end converter using sinusoidal pulse width modulation (SPWM) technique respectively. The carrier which is initially triangular in nature slowly changes into ramp and serves to reduce the line side THD. Fig. 2.3c) clearly depicts the switching pulses applied to the switches present in the converter 1. 19 Table 2.1 Switch state and the dc voltage in each interval Interval Portion 1 Portion 2 ON switch Vdc ON switch Vdc 1 T1 , T6 Vsa- Vsb T1, T2 Vsa - Vsc 2 T2 , T1 Vsa - Vsc T2, T3 Vsb - Vsc 3 T3 , T2 Vsb - Vsc T3 , T4 Vsb - Vsa 4 T4 , T3 Vsb - Vsa T4, T5 Vsc - Vsa 5 T5 , T4 Vsc - Vsa T5 , T6 Vsc - Vsb 6 T6 , T5 Vsc- Vsb T6 , T1 Vsa - Vsb Fig. 2.3 a) Carrier signal Fig. 2.3b) PWM scheme for the first converter 20 Fig. 2.3c) Switching pulses for the first converter The first converter switches commutate only at the transition between adjacent portions. The switches are made to commutate with zero current by setting zero voltage vector of the inverter to occur at both the beginning and ending of each portion. A separate synchronizing circuit is required [48] to ensure the occurrence of zero voltage vector of the second converter during the commutation of the first converter switches when conventional sinusoidal pulse width modulation technique is employed. However this need for synchronizing circuit can be eliminated if space vector modulation technique is employed instead of sinusoidal pulse width modulation for the second converter. SVM Strategy for the VSI Space vector modulation is essentially an averaging technique that takes into consideration that a three-phase inverter has only eight switch states. Each leg has two switch states. Therefore, 23 states can be obtained for the three independent legs of the inverter. The desired three phase voltages at the output of the inverter, operated in the 180° mode can be represented by an equivalent vector Vo rotating in the counter clockwise direction in a two dimensional (d, q) plane as shown in Fig. 2.4. For example, when the desired line to line output voltage vector Vo is in sector 1, it could be synthesized by the pulse-width modulation of the adjacent state space vectors V4(100) and V6(110). The duty cycle of each being d4 and d6 respectively, with the zero vectors V0(000) or V7(111) of duty cycle d0. 21 d 4 V4 +d 6 V6 = M a 3Vm cos ψin θ Tu (2.3) 2 d0 = 1-d4-d6 where Ma is the modulation index and 0<Ma <0.866 Using the same theory, analogous vectors and respective duty cycles can be derived when the system operates in other sectors. The SVM train of pulses applied to the inverter is as shown in Fig.2.5. Fig. 2.4 Space vector diagram Fig. 2.5 SVM pulses applied to the inverter 22 2.3.2 Modes of Operation of the Proposed Scheme of UPFC Automatic Voltage Control Mode for STATCOM The controller seen in Fig.2.6 is an integral part of the converter present in STATCOM to operate it in the automatic voltage control mode. Its function is to maintain a fixed dc voltage in the dc link without the storage capacitor and ensure unity power factor in the supply side. Fig. 2.6 Control block diagram of STATCOM The reference waveform for the pulse width modulator is derived from the direct and quadrature components Vd,av and Vq,av respectively. The real power reference is derived from a dc bus voltage controller and the reactive power is directly controlled treating iq* as zero, in order to achieve unity power factor operation [90]. The decoupled control system ensures that a change in the real power reference can be envisaged without any transient in the reactive power reference and vice versa. The parameters of the PI controllers used are given in the Table 2.2. Automatic Power Flow Control Mode for SSSC The main function of the static synchronous series compensator is to control the power flow over the transmission line. The control scheme [43] shown in the 23 Fig.2.7 operates the SSSC in the automatic power flow control mode. The reference inputs (Pref and Qref) are chosen accordingly. Fig. 2.7 Control block diagram of SSSC A phase locked loop (PLL) is used to determine the instantaneous angle θ of the three-phase line voltage Vabc sensed at bus B2 of Fig.2.6. The active and reactive power flows over the transmission line are determined from the actual line currents and voltages. Separate PI controllers with optimal values seen in Table 2.2, are used in the feedback path to regulate the active power and reactive power. The modulation index Ma to the PWM modulator is derived as M a = ΔM a + M a,se (2.4) K ⎞ ⎛ where ΔM a = ⎜ K p + i ⎟ ( Pref -Pact ) s ⎠ ⎝ The reference angle θT to the PWM modulator is generated as θT = θ - β (2.5) K ⎞ ⎛ where β = ⎜ K p + i ⎟ ( Q ref -Qact ) s ⎠ ⎝ The desired compensation is obtained by either adding or subtracting π/2 with β depending upon whether it is inductive or capacitive. The modulation index Ma and the phase angle θT are applied to the PWM modulator to generate the SSSC compensating voltage. 24 Table 2.2 PI controller parameters of the proposed UPFC scheme PI controllers STATCOM SSSC Kp Ki PI1 0.015 1.6 PI2 0.1 40 PI3 0.1 40 PI1 20 2 PI2 16 25 2.3.3 Performance Evaluation of the Proposed Scheme of UPFC Automatic Voltage Control Mode The proposed model of UPFC is simulated using MATLAB/Simulink. Fig.2.8 shows the bus voltage and current in the STATCOM side, which are found to be almost in phase with each other. This explains that the UPFC performs the role of shunt compensator by either absorbing or supplying the reactive power with the transmission line. There exists a small phase difference between the bus voltage and current so as to absorb power from the ac system in order to replenish the operating losses of the converter. The THD response of the line current and line voltage in the STATCOM side given in Figs.2.9 a) and 2.9 b) respectively are found to be very low through a proper choice of filter components. The dc link voltage and current waveforms of the proposed scheme of UPFC are compared with that of the existing scheme in Fig.2.10. Fig.2.11a) shows the distorted dc link current waveform when the dc link as well as ac capacitors are not present. The steady dc current obtained at the dc link depicted in Fig.2.11b) emphasizes the necessity of using capacitors on the ac side. 25 Fig. 2.8 Transmission line voltage and current with UPFC Fig. 2.9a) Line current THD in the STATCOM side Fig. 2.9b) Line voltage THD in the STATCOM side 26 a) Existing scheme of UPFC b) Proposed scheme of UPFC Fig. 2.10 Comparison of dc link voltage and current 27 a) without AC capacitor b) with AC capacitor Fig. 2.11 DC link current of the proposed UPFC scheme Automatic Power Flow Control Mode The UPFC is operated with the most powerful control mode namely the automatic power flow control mode in which the UPFC can directly control the active and reactive power by controlling the magnitude and angle of the series injected voltage. The VSI output voltage of the series converter is shown in the Fig.2.12. This voltage, which is injected in series with the transmission line, lags the line current almost by 90˚ as seen in Fig.2.13. This reveals that the SSSC operates in the capacitive mode. The occurrence of a very small deviation of the injected voltage with respect to the line current is due to the real power losses of the coupling transformer and the switches in the VSI. 28 Fig.2.12 VSI output voltages with SVM technique Fig. 2.13 Series injected voltage with respect to transmission line current 29 The transient performance of the system is evaluated by suddenly changing the load at time t = 0.1 s from an initial value of 300 MW, 220 MVAR to a new value of 270 MW, 220 MVAR. The variation of P and Q over the line is found to track almost their reference set values irrespective of load variations as depicted in Fig.2.14 because of the voltage injected in series at an appropriate angle. Fig. 2.14 Real and reactive power flow over the transmission line with UPFC A three-phase fault of 50 ms duration is introduced in the transmission line at t = 0.2 s and is allowed to be cleared at t = 0.25 s. The voltage across the STATCOM bus suddenly goes to zero as shown in Fig.2.15a). This results in a corresponding reduction in dc voltage and current magnitudes and the output of the VSI present in the SSSC side as depicted in Figs 2.15b) and 2.15c) respectively. However P and Q of the transmission line settles to their reference values within a small interval of time once the fault is cleared as seen in Fig. 2.15d). 30 a) Line voltage and current in the STATCOM side b) DC link voltage and current 31 c) VSI output voltages in the SSSC side d) Real and reactive power flow over the transmission line Fig. 2.15 Transient responses for a three-phase fault with UPFC 32 2.4 UPFC USING MATRIX CONVERTER Though the proposed scheme of UPFC without dc link capacitor perform similar to the existing scheme of UPFC a noisy dc link performance is observed due to the lack of dc capacitor. To overcome this limitation, a matrix converter is employed in UPFC as shown in Fig.2.16 whereby the classical ac/dc and dc/ac converter structure with dc link capacitor is replaced by a matrix converter [91]. Matrix converters which have an array of nine bidirectional switches are found to be more reliable and potential enough to have much longer life, because of the absence of the dc link capacitor. Besides, it has several advantages such as single stage conversion, bidirectional power flow, less number of switches and guarantees input and output sinusoidal voltages and currents with reduced THD [92-95]. The indirect space vector modulation technique has been used to control the matrix converter present in the UPFC [94, 95]. The ISVM algorithm for the matrix converters has the inherent capability of controlling simultaneously both the output voltage vector and the instantaneous input current displacement angle. Fig. 2.16 Proposed scheme of UPFC with matrix converter 33 2.4.1 Switching Algorithm In matrix converter, each output phase is connected to each input phase depending on the state of the switches. Considering that each bidirectional switch is either in the ON or OFF condition, (29 = 512) different states of the matrix converter can be defined. For safe operation of the matrix converter input phases should never be short circuited and output phases should never be opened at any switching time. Hence the number of allowable switching combination is reduced to 27. Out of these 27 switching combinations 18 active switching vectors and three zero vectors are used. The MC switching combination is given in the APPENDIX-B. In the indirect space vector modulation technique, the matrix converter is considered as a two stage transformation converter: a rectification stage to provide a constant imaginary dc link voltage per switching period and an inverter stage to produce three phase output voltages. However it is only the same nine switches that perform both rectification and inversion. Input Current SVM The SVM uses a combination of two adjacent vectors and a zero vector to produce the reference current vector as depicted in Fig. 2.17. The input currents can be considered constant during a short switching interval Ts. Then, for the switching combination from groups II and III in Appendix-B, the input phase current space vector is defined as ii = 2 ia + ib e j120 + ic e − j120 ) ( 3 (2.6) It is assumed that there are only seven discrete positions in the complex plane, called the input current switching state vectors (SSVs), as shown in Fig.2.17. For example, if the switching combination 1 from the sub group II-A in the (APPENDIX–B) is used, the input phase currents are Ia = IA, Ib = 0 and Ic = -IA, producing the SSV I1 if IA > 0 and I4 if IA < 0 switching combination 4 34 produces the same SSVs but for the opposite polarity of IA. The remaining four SSVs are produced in a similar manner. All the SSVs have the same magnitude, which from Fig.2.17 is Ik = 2 I om 3 kє{1,…6} (2.7) where Iom = i A is the maximum output current Fig. 2.17 Input current SVM The desired reference current vector is defined as iin = Iim e j(ωi t-ψin ) (2.8) where Iim is the maximum input current ψin is the STATCOM side power factor angle The input current iin can be approximated by adjacent two switching state vectors, Iγ and Iδ as shown in Fig.2.18. Fig. 2.18 Current vector in sector 1 35 The switching combinations from subgroups II-B and II-C produce SSVs in same positions but with different magnitudes, given by equation (2.7) and by Iom = ׀iB ׀and Iom = ׀iC ׀respectively. The switching combinations from group III result in the zero input current SSV I0. The duty cycles of the SSVs are Tγ dγ = ⎛π ⎞ = M ai sin ⎜ - θsi ⎟ TS ⎝3 ⎠ dδ = Tδ = M ai sinθsi TS d zi = (2.9) (2.10) Tzi = 1 - d γ - dδ TS (2.11) where Mai is the modulation index of the virtual rectifier stage. 0 ≤ M ai ≤ 1 M ai = 2Iim 3Iom cosφL where φL is the displacement angle between the output voltage and current Output Voltage SVM The output line voltage space vector is defined as Vo = 2 ( VAB + VBC e j120 + VCA e− j120 ) 3 (2.12) which assumes seven discrete positions in the complex plane, as shown in Fig. 2.19. Fig. 2.19 Output voltage SVM 36 The reference voltage vector is defined as vo = 3 Vom e ( j θT + 30° ) (2.13) This vo can be approximated by two adjacent switching state vectors, Vα and Vβ and the zero voltage vector Vz using PWM technique as shown in Fig.2.20. Vo = Tβ Tα T Vα + Vβ + zv Vz = d α Vα + dβ Vβ + d zv Vz TS TS TS (2.14) where Vo is the sampled value of vo at an instant within the switching cycle TS. The duty cycle of the active switching vectors for the inversion stage Vα and Vβ are calculated as ⎛π ⎞ d α = M a sin ⎜ - θsv ⎟ ⎝3 ⎠ (2.15) dβ = M a sinθsv (2.16) where Ma is the modulation index of the inversion stage 0 ≤ M a ≤ 1 Ma = 2 Vom 3Vim cosψin where Vom is the maximum output voltage Vim is the maximum input voltage Fig 2.20 Voltage vector in sector 1 37 A proper balance between the input currents and the output voltages is obtained in the same switching period. Each switching pattern of the inversion stage should include both the active sequence of the rectification stage as shown in Fig.2.21. In the first active portion of the inversion stage, the durations of the rectification stage active switching vectors are obtained by the following product: dαγ = dαdγ dαδ = dα dδ In second active portion these durations are calculated as follows: dβγ = dβ dγ dβδ = dβdδ Each duty cycle sequence is a result of the product of the rectification and inversion stage duty cycles. One switching sequence is completed by the zero vectors with a duty ratio of d z = 1- ( d αγ + d αδ + dβγ + dβδ ) (2.17) The duration of each sequence is found by multiplying the corresponding duty cycle to the switching period. Fig. 2.21 ISVM switching pattern Thus in the ISVM method, the four active states and the zero state to be applied in each PWM period are determined according to the sector in which the space vectors of output voltage and input current lie. In order to reduce harmonic distortion, duty cycles are symmetrically distributed round the zero state duty cycle 38 as shown in this figure. The train of pulses obtained using ISVM is shown in Fig.2.22. Fig. 2.22 ISVM pulses applied to the matrix converter 2.4.2 Control Scheme of MC based UPFC The closed loop control scheme shown in Fig.2.23 is an integral part of the matrix converter present in the UPFC to operate the STATCOM part of the UPFC in improving the power factor and SSSC part to enhance the power flow over the line. A single closed control strategy has been used for controlling both the input current displacement angle as well as the series injected voltage, thereby controlling the power flow. The references derived separately from the STATCOM and SSSC parts of the UPFC are combined in the ISVM pulse generator. The ISVM pulse generator in turn generates appropriate control pulses for the matrix converter switches. The SSSC control is similar to that described in section 2.3.2. The parameters of the PI controllers are given in Table 2.3. In the shunt control, in order to achieve unity power factor the real and reactive power components of the current must be controlled independently. The real and reactive current references 39 are derived from the instantaneous real and reactive power flow over the line. The instantaneous real and reactive power can be written in terms of d-q quantities as P= 3 ( Vd Id + Vq Iq ) 2 (2.18) Q= 3 ( Vd Iq - Vq Id ) 2 (2.19) From equations (2.18 and 2.19) the real and reactive current references are derived as follows I*d = 2 ⎛ Pref Vd + Q ref Vq ⎜ 3 ⎜⎝ Vd2 + Vq2 ⎞ ⎟⎟ ⎠ (2.20) I*q = 2 ⎛ Pref Vq + Q ref Vd ⎜ 3 ⎜⎝ Vd2 + Vq2 ⎞ ⎟⎟ ⎠ (2.21) where Pref is the real power reference Qref is the reactive power reference Fig. 2.23 Closed loop control scheme of UPFC with MC The reactive power reference Qref is set to 0 in order to achieve unity power factor. The derived two phase current commands are converted into three phase quantities using dq-abc transformation. These three phase current references are fed as control signals to the rectifier SVM pulse generator. Similarly the voltage 40 references derived from series control part are fed to the inverter SVM pulse generator. The MC pulse generator uses the control signals from the rectifier and inverter pulse generators for generating appropriate control signals to the matrix converter switches. Table 2.3 PI controller parameters of the MC based UPFC PI Controllers Kp Ki PI1 20 2 PI2 16 25 2.4.3 Performance Evaluation of the MC based UPFC The performance of the matrix converter based UPFC is analyzed through MATLAB/Simulink based simulation. The matrix converter output phase and line voltages along with their fundamental components are shown in Figs. 2.24 and 2.25 respectively. Fig. 2.24 MC output phase voltage with its fundamental 41 Fig. 2.25 MC output line voltage with its fundamental The initial load in the system with the ratings of 600 MW, 150 MVAR connected at load bus B5 through the circuit breaker CB1 is disconnected at time t = 0.15 s and a second load with ratings of 650 MW, 200 MVAR is connected to the system. The transmission line current lags the transmission line voltage as shown in Fig.2.26 in the absence of UPFC. The STATCOM part of the UPFC maintains the line current almost in phase with the voltage as depicted in Fig.2.27. This shows that the UPFC performs the role of shunt compensator by either absorbing or supplying the reactive power for any load variations. The magnitude of the quadrature voltage injected by the SSSC depending on the load variations varies as depicted in the Fig.2.28 in order to maintain the real and reactive power flow over the line to follow the set reference values as shown in Fig.2.29. 42 Fig. 2.26 Transmission line current and voltage before compensation Fig. 2.27 Transmission line current and voltage with shunt compensation 43 Fig. 2.28 Series injected voltage and transmission line current Fig. 2.29 Real and reactive power flow over the transmission line with MC based UPFC 44 2.5 SUMMARY The contribution of this chapter is to propose a novel structure of UPFC to be connected into the transmission line. Since the cost and space occupied by the dc link capacitor in the existing UPFC structure are quite large the proposed schemes eliminate the dc link capacitor. With the proposed scheme 1 a noisy dc link performance is obtained in the dc link, which is due to the lack of dc capacitor. To reduce this problem space vector modulation technique is employed for the voltage source inverter present in the SSSC side. Also another scheme of UPFC is proposed whereby the classical ac/dc and dc/ac converter structure with dc link capacitor is replaced by a matrix converter. The indirect space vector modulation technique effectively used to generate the control pulses for the matrix converter switches. The performance of the proposed schemes has been analyzed with MATLAB/Simulink assuming that the UPFC is connected with the 230 kV transmission line of sample power system. The STATCOM offers a good voltage regulation and the SSSC controls the magnitude and angle of the injected voltage so as to maintain the real and reactive power flow over the transmission line to follow the set reference values in spite of variations in the load and the operating conditions. The proposed schemes of UPFC interfaced in the sample power system accomplish a similar performance as that of a traditional system. 45