KVA/KW AMP CHART 3 - Phase 0.8 POWER FACTOR (LAG) 50 Hertz COMMON VOLTAGE RATINGS AMPS PER TERMINAL KVA KW 3 2.4 6 L-L L-N 200V 115V 208V 120V 220V --- 230V --- 240V --- 380V 220V 400V 230V 415V 240V 8.7 8.3 7.9 7.5 7.2 4.6 4.3 4.2 4.9 17.3 16.7 15.8 15.1 14.5 9.1 8.7 8.4 10 8 29 28 26 25 24 15 14 14 12 9.6 35 33 32 30 29 18 17 17 15 12 43 42 39 38 36 23 22 21 18 14 52 50 47 45 43 27 26 25 20 16 58 56 53 50 48 30 29 28 26 21 75 72 68 65 63 40 38 36 30 24 87 83 79 75 72 46 43 42 39 31 113 108 102 98 94 59 56 54 45 36 130 125 118 113 108 68 65 63 52 42 150 145 137 131 125 79 75 72 60 48 173 167 158 151 145 91 87 84 75 60 217 208 197 188 181 114 108 104 90 72 260 250 236 226 217 137 130 125 120 96 347 333 315 302 289 183 173 167 125 100 361 347 328 314 301 190 181 174 150 120 434 417 394 377 361 228 217 209 200 160 578 556 525 503 482 304 289 279 Chart Notes: L-L and L-N identifies voltage levels as measured from Line to Line or Line to Neutral respectively. Power Factor PF = KW / KVA, and is the ratio of True Power to Apparent Power. Power Factor Rating: Amps shown above are at 0.8PF rating. Actual load PF may differ. Abbreviations: KVA : Kilo Volt Amperes; KW: Kilowatts; PF: Power Factor; L-L: Line to Line; L-N: Line to Neutral Chart Instructions: Find KVA & KW Rating To find the KVA or KW rating (at 0.8PF) for your application, select the 50HZ three phase L-L (line to line) voltage level being utilized. Scan down this column to the current needed for your application (select the next higher current rating for more margin). Scan the row to the left and find the KVA and KW rating needed. Find Current Rating To find the phase current rating if the 50HZ load KW or KVA is known, select the known KVA or KW rating on the chart above. Scan across the row to the right until the three phase L-L (line to line) voltage being utilized column is reached. Useful Electrical Formulas KVA = Volts x Amps x 1.732 1,000 KW = KVA x Power Factor (PF) Amps (When KVA is Known) = KVA x 1,000 Volts x 1.732 Amps (When KW is Known) = __________KW x 1,000_______ Volts x Power Factor (PF) x 1.732 Disclaimer: The content herein is provided for informational purposes only. For technical assistance with your specific 50HZ needs, contact AP&C application engineers. FREQUENCY CONVERTER RENTAL Powered By Advanced Power & Controls, LLC Power for the Planet® | Engineered Power Solutions 605 E Alton Ave Ste A, Santa Ana, CA 92705 Tel 714-540-9010 ● Fax 714-540-5313 www.FrequencyConverterRental.com