3 - Phase KVA/KW AMP CHART 50 Hertz

advertisement
KVA/KW
AMP CHART
3 - Phase
0.8 POWER FACTOR (LAG)
50 Hertz
COMMON VOLTAGE RATINGS
AMPS PER TERMINAL
KVA
KW
3
2.4
6
L-L
L-N
200V
115V
208V
120V
220V
---
230V
---
240V
---
380V
220V
400V
230V
415V
240V
8.7
8.3
7.9
7.5
7.2
4.6
4.3
4.2
4.9
17.3
16.7
15.8
15.1
14.5
9.1
8.7
8.4
10
8
29
28
26
25
24
15
14
14
12
9.6
35
33
32
30
29
18
17
17
15
12
43
42
39
38
36
23
22
21
18
14
52
50
47
45
43
27
26
25
20
16
58
56
53
50
48
30
29
28
26
21
75
72
68
65
63
40
38
36
30
24
87
83
79
75
72
46
43
42
39
31
113
108
102
98
94
59
56
54
45
36
130
125
118
113
108
68
65
63
52
42
150
145
137
131
125
79
75
72
60
48
173
167
158
151
145
91
87
84
75
60
217
208
197
188
181
114
108
104
90
72
260
250
236
226
217
137
130
125
120
96
347
333
315
302
289
183
173
167
125
100
361
347
328
314
301
190
181
174
150
120
434
417
394
377
361
228
217
209
200
160
578
556
525
503
482
304
289
279
Chart Notes:
L-L and L-N identifies voltage levels as measured from Line to Line or Line to Neutral respectively.
Power Factor PF = KW / KVA, and is the ratio of True Power to Apparent Power.
Power Factor Rating: Amps shown above are at 0.8PF rating. Actual load PF may differ.
Abbreviations: KVA : Kilo Volt Amperes; KW: Kilowatts; PF: Power Factor; L-L: Line to Line; L-N: Line to Neutral
Chart Instructions:
Find KVA & KW Rating
To find the KVA or KW rating (at 0.8PF) for your application, select the 50HZ three phase L-L (line to line) voltage level being utilized.
Scan down this column to the current needed for your application (select the next higher current rating for more margin). Scan the
row to the left and find the KVA and KW rating needed.
Find Current Rating
To find the phase current rating if the 50HZ load KW or KVA is known, select the known KVA or KW rating on the chart above. Scan
across the row to the right until the three phase L-L (line to line) voltage being utilized column is reached.
Useful Electrical Formulas
KVA = Volts x Amps x 1.732
1,000
KW = KVA x Power Factor (PF)
Amps (When KVA is Known) = KVA x 1,000
Volts x 1.732
Amps (When KW is Known) = __________KW x 1,000_______
Volts x Power Factor (PF) x 1.732
Disclaimer: The content herein is provided for informational purposes only. For technical assistance with your specific 50HZ needs, contact AP&C application engineers.
FREQUENCY CONVERTER RENTAL
Powered By Advanced Power & Controls, LLC
Power for the Planet® | Engineered Power Solutions
605 E Alton Ave Ste A, Santa Ana, CA 92705
Tel 714-540-9010 ● Fax 714-540-5313
www.FrequencyConverterRental.com
Download