2014 Ninth International Conference on Ecological Vehicles and Renewable Energies (EVER) Analysis of Synchronous and Stationary Reference Frame Control Strategies to Fulfill LVRT Requirements in Wind Energy Conversion Systems Matías Díaz Roberto Cárdenas University of Chile Av. Tupper #2007 Santiago, PC PC 8370451 , Chile Email: matias.diaz@ing.uchile.cl Abstract—In order to avoid stability problems, LVRT requirements (Low Voltage Ride Through) demand Wind Energy Conversion Systems (WECS) to remain connected to the grid in the presence of grid voltages dips. Because 88% of the grid failures are asymmetrical, positive and negative sequence components have to be controlled to fulfill LVRT requirements. This paper present a comparison between synchronous and stationary reference frame control strategies for an active frontend converter of a grid connected WECS working under grid fault conditions. The mathematical analysis and design procedure of both control system are presented in this work. Experimental results obtained from a 3kW prototype are fully discussed in this paper. The experimental implementation is realized using a novel implementation of a voltage sag generator which is based on a 3x4 Matrix Converter University of Chile Av. Tupper #2007 Santiago, PC PC 8370451 , Chile Email: rcd@ieee.org To support voltage regulation in the power system. This is accomplished through the consumption/injection of reactive power by the grid side converter (see Fig. 3). Typically only 12% of the grid-faults are symmetrical; therefore, LVRT control system has to be able to deal with positive and negative sequence currents and voltages. Several Control systems for LVRT operation have already been Index Terms—Low Voltage Ride Through, Resonant Controllers, Wind Energy Conversion Systems, Voltage Sag Generators. I. INTRODUCTION W ENERGY has become one of the industries with the greatest and fastest growth in the renewable energy sector [1]. The wind energy production capacity for the whole world in 2012 was 282-GW [1]. Moreover, the penetration of wind energy is steadily increasing. A good example is Spain, where the average wind energy penetration has been 11%, 13.8%, and 16% in 2008, 2009, and 2010, respectively [x]– [x]. Therefore, some rather strict grid codes are enforced in countries with relatively high penetration of wind energy, in order to regulate the connection of large wind energy parks to generation and transmission systems. In these grid-codes, Low-Voltage Ride-Through (LVRT) requirements demand wind-power plants to remain connected in the presence of grid-voltage dips, contributing to keep grid voltage and frequency stable. According with [2], [3], [4], in the presence of a grid-voltage dip, the requirements of the LVRT control strategy are: To maintain the WECS connected to the grid, when the line voltage is inside the boundaries specified in Fig. 1(a). a) IND a) b) Fig. 1. LVRT Requirements of the Spanish grid code. (a) Limit of the grid voltage dip. (b) Demanded Reactive Current in function of grid-voltage dip. presented in [5], [6], [7], [8]. In most of these papers the controllers are based on revolving synchronous rotating d-q axe where the negative and positive sequences are transformed into dc signals and controlled using standard PI regulators. Resonant controllers (RC) are well suited to manage positive and negative sequence components of grid voltage [9], [10], but no attention has been paid to stationary axis based control systems under grid fault condition, in order to study WECS LVRT requirements fulfillment. This paper is focused on the comparison of synchronous and stationary reference frame based control strategies to fulfill the LVRT requirements for a system similar to Fig. 1(a). The system is composed of a wind turbine connected to the grid through a low voltage two level Back to Back converter. Low voltage two-level voltage-source converters are the most used topology in WECS [11], [12], [13], [14]. In this work it is assumed that the dc-link voltage is fairly constant, both in steady state and under grid fault conditions [2]. Therefore, grid-side and generator-side operations are decoupled and only the control of the grid-side converter is considered. extraction is included in some advanced 3-phase PLL structures, such as the 3-phase enhanced PLL (EPLL), double second order integrator PLL (DSOGI-PLL), decoupled double synchronous reference frame PLL (DDSRF-PLL), delayed signal cancellation PLL (DSC-PLL) [20]. Fig. 3. Delay Signal Cancellation Method. Delayed-signal-cancellation (DSC) is probably the best suited method to separate sequences [21], [22]. This method presents an intrinsic delay of T/4 and is described in the Fig. 3. Regarding DSC, the PLL is employed to synchronize the active Front-End converter to positive sequence of the grid voltage at the Point of Common Coupling (PCC) [23], [24] and [25]. Fig. 2. (a) Wind generator connected to the grid through a Back-to-Back converter. (b) Grid-Connected Front-End Converter. II. CONTROL STRATEGY When a grid-voltage dip appears, the power injected to the grid is decreased as a function of the voltage reduction, therefore is not possible to supply to the grid all the power produced by the machine. An active power surplus is stored in the dc-link, resulting in an unacceptable dc-link voltage increase that can be dangerous to the Back-to-Back converter. Furthermore, the unbalance between the power generated and the power supplied to the grid induces an increase in the speed of the generator due to the mismatch between the mechanical input power and electrical output power [2], [15], [16]. To avoid this, Back-to-Back power converters are usually equipped with a dc-link-voltage limiter unit (Crow-Bar, Braking Chopper) [13], [14]. Therefore, generator side converter and/or dc-link Crow Bar regulate the active power surplus through grid-voltage dips, and the assumption of decoupled generator-grid side converter is realistic [2], [17]. For asymmetrical grid-voltage dip conditions, a separation sequence method is required to guarantees correct grid frequency detection due to the second harmonics produced by the negative sequence is reflected in the grid-frequency estimation [18], [19]. To improve the performance of the PLL, positive sequence III. CURRENTS REFERENCES CALCULATION The apparent power at grid terminal, calculated considering three-leg unbalanced system with positive -and negativesequence components, is show in (7): ̅ (̅ ̅ )( ̅ ̅ ) (1) The superscripts (c), (p), and (n) are used to denote the complex conjugate of the current vector, positive-sequence component and negative-sequence component, respectively. Developing the previous equation and separating real and imaginary parts: (2) (3) and are the grid average active and reactive power. Furthermore, and as it is well known, an unbalanced gridvoltage dip produces double frequency components in both active power as reactive power, represented by , , . A. Synchronous Reference Frame Current Reference Calculation According to [26], (11)-(12) could be expressed in function of sequence components voltages/currents in d-q frame as follow: ( ) (4) ( ) ( (5) ( ) ( ) (19) ) (20) (6) (7) Where is the average active power dissipated in the filter, and are the double frequency active power components. It is also important to note that the system described by (11)-(16) has four degrees of freedom ( ) to control six variables ( . In this case, reactive power oscillations ( ) are not controlled again. Two different current references methods are presented. The first one, considers that the Front-End converter supplies the oscillating active power to the filter, which results in zero oscillating active power components on the grid side, i.e. . (8) (9) The system described by (4) - (9) has four degrees of freedom ( ) to control six variables ( , , . Therefore it is necessary to make a choice of variables according to the control objectives. Mainly, the reference currents are setting to regulate average active and reactive power and to eliminate the double frequency oscillations in the active power ( ). Reactive power oscillations ( , ) are not controlled in any case. Therefore, it is possible to write (4)-(7) in matrix notation: [ ( [ [ ] [ ] (10) ] B. Stationary Reference Frame Current Reference Calculation Follow the same procedure, it is possible to demonstrate that (2)-(3) can be represented by sequence component voltages/currents in the natural frame: [ ] [ ] (21) ] In the second case, the oscillating powers flow from the grid into the filter, therefore oscillating active power components are regulated to zero at the Front-End terminals, and . (22) (11) (13) IV. SYNCHRONOUS REFERENCE FRAME CONTROL (SYN-RFC) (14) This strategy is based in [6], [8]. Implementations for LVRT fulfillment can be found in recent literature [27], [28] and [29]. Positive and negative-sequence components are regulated by independent rotational frame PI controllers. “Positive sequence current controller” rotates ̂ , that correspond to the angle of the positive sequence voltage component, founded by DSC-PLL. “Negative sequence current controller” rotates with - ̂ . A schematic of the d-q control is represented in Fig. 4. Proportional Integral (PI) controllers are used since they have correct behavior controlling dc variables. For improving the performance of the PI controller, crosscoupling terms and voltage feedforward are considering. (16) The apparent power at Front-End converter terminal follows the same structure than (2) and (3), and the next expression gives the power balance at the Front-End terminals (see Fig. 8): (17) is the apparent power dissipated in the filter. It contains average active and reactive power terms and cosine and sine component oscillating with double grid frequency. The active powers dissipated in the filter are obtained from [21], [27]. ( ) (18) ] ] [ ] (15) [ [ (12) V. STATIONARY REFERENCE FRAME CONTROL (ST-RFC) Mainly, all strategies used in LVRT are based on conventional d-q frame control systems explained in previous section. Instead synchronous reference frame, the use of stationary reference frame current controllers based on RC is presented and development in this section. Positive Sequence Current Controller + + + PI - + + + PI dq αβ dq + αβ αβ + DSC Negative Sequence Current Controller + - PI + PI abc αβ abc DSC + + + αβ dq abc αβ - ~ ~ ~ dq αβ PLL dq αβ Current References Calculation dq αβ DSC DSC Fig.4: Synchronous Reference Frame Control Strategy. A RC have a couple of purely imaginary poles, with a resonant frequency of , found by the DSC-PLL. In the zplane, a RC controller has the follow transfer function [9], [10]: ̂ ( ( ̂ ̂ ) ( ) ( ̂ ) ) (23) Where: represents the distance between the pole and zero; represent the sampling time; is the controller gain. A schematic of the proposed control is represented in Fig. 5 Positive and negative-sequence components are regulated by the same RC. Each RC regulate line current get the current reference calculated according to the method explain in previous section. In this strategy, line current and voltages are measured and trigonometric functions required to transform from - to d-q coordinates (and vice versa) are not used for the implementation. RCs are designed using root locus in the z-plane. The controllers should have an appropriate dynamic response during grid-voltage dips, therefore, a second order lead lag network is added for improvement of dynamic behavior [10]. The expression for the controller considering RC and lead lag network is presented in (24): (24) The controller presented in (25) has been designed considering: =500µs, closed loop poles damping coefficientof 0.35, =100π rads-1, =5 , =0.5 . The root locus of the proposed control system is shown in Fig. 7: (25) Fig.5: Stationary Reference Frame Control Strategy If the frequency at the PCC “ ̂ ” is proportioned for the DSC-PLL, (25) represents a Self Tuning Discrete Resonant Controller that can be easily implemented in a digital signal processor. VI. EXPERIMENTAL IMPLEMENTATION The experimental system attempts to emulate the WECS presented in Fig. 1(b) through the implementation of a low power grid-connected Front-End converter. The SVM algorithm, d-q based controllers, RC and all control structures were implemented using a DSP based board and a FPGA –to generate signal IGBT drivers, IGBT’s dead time, hardware protection–. The DSP board used in this application is based on a TMS320C67 processor. For data acquisition purposes a board with ten analogue to digital channels and 1conversion time is interfaced to DSP. Open-Loop Bode for (6) Root Locus for (6) 1 6.28e3 5.03e3 0.1 3.77e3 0.2 0.3 0.6 Zoom Root Locus for (6) 2.51e3 0.4 0.1 0.5 0.6 0.4 0.7 1.26e3 0.8 -100 -200 G.M.: 3.33 dB 0.05 0 Freq: 8.35e+003 rad/s Stable loop -300 x 0 Plant -0.2 o x 0.95 1 -0.4 0.85 2.51e3 -0.6 LL Zero 3.77e3 -0.8 0 -0.05 1.26e3 0.9 RC Zero RC Pole -100 -200 -300 -400 P.M.: 41.6 deg 5.03e3 -1 -1 0 0.9 Phase (deg) Imag Axis 0.2 Magnitude (dB) 100 0.8 Freq: 6.8e+003 rad/s 6.28e3 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1 0 10 Real Axis 1 10 2 10 3 10 4 10 Fig.6: Root locus for controller shown in (25). A 3-kW grid-connected two-level Front-End converter is used. The switching frequency is set to 2-kHz. Discrete RC’s and PI regulators have been calculated for 500-us sample time. Three Hall-Effect voltage transducers are used to measure the grid and dc-link voltages. Also, two Hall-Effect current transducers are used to measure the grid currents. The FrontEnd converter is connected to the grid using a first order filter of 20-mH 0.5-Ω. The grid-voltage dips have been produced a using a novel 3-kVA Matrix Converter Voltage Sag Generator, implemented on a DSP board based on a high performance TI TMS320C67 processor, capable of a performance of 1350MFLOPS. For data acquisition purposes an external board, with ten Analogue to Digital (ADC) channels of 14bits, 1-μs conversion time each, is interfaced to the DSP. VII. EXPERIMENTAL RESULTS This section presents experimental results for the system shown in Fig.7. This Experimental Rig has been tested under grid-voltage dip type B and C conditions [30]. Different tests are carried out to validate the proposal strategy and to compare it with the traditional d-q control scheme presented in Fig.4. In all the cases, active power, line current and reactive power responses are presented. The sag conditions have duration of 140-ms and are produced by the Matrix Converter based VSG. In state steady, the voltage in the PCC is controlled to 110-V (rms value), the active power is set to 1-kW and the reactive power reference is controlled to 0kVA, in order to work with unitary power factor. Test 1: 35% Grid-voltage dip type B. Fig. 8 shows that Syn-RFC strategy is able to keep the control through the grid-voltage dip. There is not presence of double-frequency oscillations in active power (calculations presented in (22) are also valid for synchronous reference frame), but reactive power presents double frequency oscillations that flows between the grid and the filter. At the fault time appearance, the active power delivered to the grid is 0-kW, and the Front-End starts to support to the grid voltage through reactive power injection. When the fault is over, the systems come back to state steady references. Fig. 7. Experimental System. 5 10 Frequency (rad/s) The same behaviour is observed in waveforms presented in Fig.9. In this case, St-RFC strategy is utilised. During the grid-voltage sag condition, the active power delivered to the grid is 0-kW and the Front-End to support to the grid voltage through reactive power injection. For both strategies, line currents are slightly distorted and unbalance during the sag, mainly due to the control objective is to regulate the power and not the current. Fig. 8: Syn-RFC responses for 50% Grid-Voltage Dip Type B. Up: Grid Voltage. Medium: Grid Currents. Lower: Active and Reactive Power. Fig.9: St-RFC responses for 50% Grid-Voltage Dip Type B. Up: Grid Voltage. Medium: Grid Currents. Lower: Active and Reactive Power. Fig. 10: Syn-RFC responses for 30% Grid-Voltage Dip Type C. Up: Grid Voltage. Medium: Grid Currents. Lower: Active and Reactive Power. Fig. 11: St-RFC responses for 30% Grid-Voltage Dip Type C. Up: Grid Voltage. Medium: Grid Currents. Lower: Active and Reactive Power. The responses using Syn-RFC are presented in Fig. 10. In this case, a grid-voltage dip type C is tested. At the beginning of the sag, phases A and C drop from 110 to the 35 . In order to fulfil LVRT, the reference to reactive power injection through the grid-voltage dip is 0.5 kVA. However, when a fault appears, inaccurate values are feeding to the control systems during of the period. An amplified view of the line current is shown in Fig.12. Fig.11 presents the performance of St-RFC to the same grid-voltage sag condition. Both strategies to allow grid voltage support by reactive injection while the grid-voltage dip is present. However, St-RFC presents slightly better dynamic behaviour. At the appearance/clearance fault time using Syn-RFC- line current reaches 14 A, almost 3 times the rated value. With St-RFC line current overshoot is lower, reaching 9 A at the clearance fault time. An amplified view of the line current is presented in Fig.13. The time required by the DSC method to separate the positive and negative sequences is very short, and it is included within the sampling time (500 us) of the DSP controller. Hence, this calculation time does not affect the control dynamics. Fig. 12: St-RFC responses for 30% Grid-Voltage Dip Type C. Left: Current response at fault appearance time. Right: Current response at fault clearance time. VIII. CONCLUSIONS A comparison between Syn-RFC and a novel control strategy, dealing with sequence components under unbalanced voltage conditions, have been presented in this paper. Proposed control strategy (St-RFC) is based on the use of Resonant Controllers to regulate line currents in stationary frame and is able to fulfill LVRT requirements. According to experimental results, both strategies present correct performance under unbalance grid-voltage conditions. This fault conditions have been generated by a Matrix Converter based VSG. In all the cases, the voltage sags generated do not present peaks, transient effects or low reliability. Therefore, the good performance of the novel VSG has been ratified to test LVRT capability in grid-connected systems. Syn-RFC and St-RFC strategies are able to keep the system grid-connected and to support grid-voltage through reactive power injection when grid-voltage sag appears. Therefore, both strategies meet LVRT requirements. However, St-RFC strategy has slightly better dynamic behavior. St-RFC is more stable and faster than Syn-RFC, mainly due to the lead lead network, added to the RC in order to increase the dynamic behaviour and stability. Also, St-RFC is simpler than SynRFC. A single RC could be used to regulate the positive and negative sequence current and no transform from d-q to α-β are needed. Additionally, for LVRT control, orientation along any of the voltage or current vectors is not required and a PLL is implemented only to obtain the grid-frequency which is used to tune the resonant controller. DSC presents a delay of T/4, which does not affect under steady-state operation, but makes an inexact sequence separation during the firts 5-ms (T=20-ms) after the appearance of any grid-voltage dip. During this 5-ms, inaccurate values are fed back to the control system. The result of these inaccuracies can be observed in all responses (currents and power), and explain the presence of non-desired values during the 5-ms after at the appearance and clearance fault time. Despite of the inaccuracies produced by DSC method and the Voltage Sag Generator System, the results obtained are acceptable for all the tests. [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] IX. REFERENCES [1] The Wind Power Database. (2011) [Online]. http://www.thewindpower.ne [2] S. Alepuz, S. Busquets-Monge, J. Bordonau, J.A. MartinezVelasco, C. Silva, J. Pontt, J. Rodriguez, "Control Strategies Based on Symmetrical Components for Grid-Connected Converters Under Voltage Dips," IEEE Transactions on Industrial Electronics, vol.56, no.6, pp.2162-2173, June 2009. [3] 12.3, Red Eléctrica. Procedimiento de operación P.O. (España, 2006) Requisitos de respuesta frente a huecos de tensión de las instalaciones de producción en régimen especial. [Online]. www.ree.es [4] Grid Code. , "High and extra high voltage. E.ON Netz," August 2003. [online] www.eon-netz.com. Germany. [5] S. Alepuz, S. Busquets, J. Bordonau, J. Pontt, C. Silva, J. Rodríguez, "Fast on-line symmetrical components separation method for synchronization and control purposes in three phase [16] [17] [18] [19] distributed power generation systems," in Proc. 12th Eur. Conf. Power Electron. Appl. EPE, Aalborg,Denmark, Sep. 2–5, 2007, pp. 1–10. Miret, J.; Camacho, A.; Castilla, M.; de Vicuna, L.G.; Matas, J., "Control Scheme With Voltage Support Capability for Distributed Generation Inverters Under Voltage Sags," IEEE Transactions on Power Electronics, vol.28, no.11, pp.5252,5262, Nov. 2013. Alepuz, S.; Busquets-Monge, S.; Bordonau, J.; Cortes, P.; Kouro, S., Control Methods for Low Voltage Ride-Through Compliance in Grid-Connected NPC Converter Based Wind Power Systems Using Predictive Control., Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE , vol., no., pp.363,369, 20-24 Sept. 2009. Hojoon Shin; Hyun-Sam Jung; Seung-Ki Sul, Low Voltage Ride Through(LVRT) control strategy of grid-connected variable speed Wind Turbine Generator System., 2011 IEEE 8th International Conference on Power Electronics and ECCE Asia (ICPE & ECCE), vol., no., pp.96,101, May 30 2011-June 3 2011. R. Cardenas, R. Peña, P. Wheeler, J. Clare, "Resonant Controllers for 4-leg Matrix Converters," Proceeding of International Symposium on Industrial Electronics, Bari Italy, 2010, pp. 1027-1032.. R. Cárdenas, C. Juri, R. Peña, P. Wheeler, J. Clare, "The Application of Resonant Controllers to 4-Leg Matrix Converters Feeding Unbalanced or Non-Linear Loads ," IEEE Proceeding. L. Xu and P. Cartwright, Direct active and reactive power control of DFIG for wind energy generation., IEEE Transactions on Energy Conversion, Vol. 21, No. 3, pp. 750–758, Sep. 2006. J. Yao et al., "An improved control strategy of limiting the DClink voltage fluctuation for a doubly fed induction wind generator," IEEE Trans. on Power Electron., Vol. 23, No. 3, pp. 1205–1213, May 2008. M. Chinchilla, S. Arnaltes, J.C. Burgos, "Control of Permanentmagnet Generators Applied to Variable-Speed Wind-Energy Systems Connected to the Grid," IEEE Trans. on Energy Conversion, Vol. 21, No. 1, Mar. 2006. J. F. Conroy, R. Watson , "Low-Voltage Ride-Through of a Full Converter Wind Turbine with Permanent Magnet Generator," IET Renewable Power Generation, Vol. 1, No. 3, pp. 182 – 189, Sept. 2007. J. Li, D. Li, L. Hong, C. Xie, G. Chen, "A novel power-flow balance LVRT control strategy for low-speed direct-drive PMSG wind generation system," IECON 2010 - 36th Annual Conference on IEEE Industrial Electronics Society , vol., no., pp.748-753, 7-10 Nov. 2010. G. Michalke, A.D. Hansen, "Multi-pole permanent magnet synchronous generator wind turbines grid support capability in uninterrupted operation during grid faults," Renewable Power Generation, IET , vol.3, no.3, pp.333-348, Sept. 2009. M. Fatu, C. Lascu, G. D. Andreescu, R. Teodorescu, F. Blaabjerg, and I. Boldea, "Voltage sags ride-through of motion sensorless controlled PMSG for wind turbines," Conf. Rec. IEEE IAS Annu. Meeting Sep. 23–27, 2007, vol. 1, pp. 171–178. F. Blaabjerg, R. Teodorescu, M. Liserre, and A.V. Timbus, "Overview of Control and Grid Synchronization for Distributed Power Generation Systems," Industrial Electronics, IEEE Transactions on, vol. 53, no. 5, pp. 1398-1409, 2006. L.N. Arruda, S.M. Silva, and B. J C Filho, "PLL structures for utility connected systems," in Industry Applications Conference, 2001. Thirty-Sixth IAS Annual Meeting. Conference Record of the 2001 IEEE, vol. 4, 2001, pp. 2655-2660 vol.4. [20] Siyu Gao and Mike Barnes, "Phase-locked loop for AC systems: Analyses and comparisons," in Power Electronics, Machines and Drives (PEMD 2012), 6th IET International Conference on, 2012, pp. 1-6. [21] G. Saccomando and J Svensson, "Transient operation of gridconnected voltage source converter under unbalanced voltage conditions," Industry Applications Conference, 2001. ThirtySixth IAS Annual Meeting. Conference Record of the 2001 IEEE , vol.4, no., pp.2419-2424 vol.4, 30 Sep-4 Oct 2001. [22] S. Alepuz et al., "Fast on-line symmetrical components separation method for synchronization and control purposes in three phase distributed power generation systems.," in Power Electronics and Applications, 2007 European Conference on, 2007, pp. 1-10. [23] S. M. Silva, B. Filho L. N. Arruda, "PLL structures for utility connected systems," Industry Applications Conference, 2001. Thirty-Sixth IAS Annual Meeting. Conference Record of the 2001 IEEE , vol.4, no., pp.2655-2660 vol.4, 30 Sep-4 Oct 2001. [24] V. Kaura, V. Blasko, "Operation of a Phase Locked Loop System Under Distorted Utility Conditions," IEEE Transaction on Industry Applications, Vol. 33, NO 1, February 1997. [25] J.C. Alfonso-Gil, J.J. Vague-Cardona, S. Orts-Grau, F.J. Gimeno-Sales, and S. Segui-Chilet, "Enhanced Grid Fundamental Positive-Sequence Digital Synchronization Structure," Power Delivery, IEEE Transactions on, vol. 28, no. 1, pp. 226-234, 2013. [26] S. Hong-Seok, N. Kwanghee, "Dual current control scheme for PWM converter under unbalanced input voltage conditions," Industrial Electronics, IEEE Transactions on , vol.46, no.5, pp.953-959, Oct 1999. [27] F. Magueed, A. Sannino, and J. Svensson, Transient operation of grid voltage source converter under unbalanced voltage dips., Proc. IEEE PESC, Jun. 20–25, 2004, vol. 2, pp. 1163–1168. [28] Hong-Seok Song and Kwanghee Nam, "Dual current control scheme for PWM converter under unbalanced input voltage conditions," Industrial Electronics, IEEE Transactions on, vol. 46, no. 5, pp. 953-959, 1999. [29] M. Díaz, P. Jara, R. Cárdenas, "A Control Strategy To Fulfill LVRT Requirements in Wind Energy Conversion Systems," Seventh International Conference and Exhibition on Ecological Vehicles and Renewable Energies EVER’12, March 22-25, 2012, Monte-Carlo, Monaco. [30] M.H.J. Bollen, "Characterisation of voltage sags experienced by three-phase adjustable-speed drives," IEEE Trans. Power Delivery, vol. 12, pp. 1666-1671, Oct. 1997.