281300S01 ACCESS CONTROL-Security And Key Access Systems

advertisement
281300S01 ACCESS CONTROL-Security And Key Access Systems
1.
SECURITY SYSTEM
Location/Building
1.
Security Control Panels with Remote Down line Loading Capability
1.
1
MDC-16CETX Morse 16 Zone Control Panel /no programmer required and equipped
with digital communicator and downloading capability.
MDC-16CCS Morse MDC-16CD in UL listed heavy duty box.
MPC-32DL Morse keypad and personal control with 32 digit LCD display.
MDC series software for remote computer (Not required if remote programming and
downloading is not required)
Gel Cell Rechargeable Battery
1
MA3000 NAPCO 8 zone control panel with digital communicator
H1518 UL commercial locking metal cabinet
RP3000LCD Designer Backlite Alphanumeric Display keypad
PCD3000 software for remote computer (not required if remote programming and
downloading is not required), requires PCI MINI interface
Maintenance-Free Rechargeable Battery 12 VDC 6.5 AH
2.
Note:
2.
Manufacturers part numbers in this specification are provided for clarification only and do not
exclude equivalent part numbers of acceptable manufacturers.
Features all systems must have:
Uninterruptible Battery Backup, nonvolatile memory, built in digital dialer, autotest timer,
programmable, UL Listing
3.
Guarantee
All systems must be guaranteed in accordance with UK Standard 01740S01.
2.
DETECTORS
1.
Combination Infrared/Microwave
Qty.
D-100ST NAPCO with walk test (Default)
C-100STLRE with walk test (compact model)
DS-702 Detection Systems with walk test
2.
Break Glass
BGE-9100SM Blue Grass Dual Switch Glass Break Detector
Magnetic Reed Switch
Steel Door Jam Internal: Sentrol/United Security 1078C-1 w/ 1" press fit, 1/2" gap, 6"
22awg leads, N.C., self-locking mount
Steel Door Jam Internal: Sentrol/United Security 1072 w/ 3/8" flange for screw mounting,
1/2" gap, 6" 22awg leads, N.C.,
Wood Door Jam Internal Wide Gap: GRI/Telemark Corp. 20-12 3/8" diameter, 1/2",1",&
1-1/2" gap (specify), 6" 22awg leads, N.C., press fit mount
Wood Door Jam Internal: Sentrol/United Security 1075B 3/8" diameter, 1/2" gap, 6"
22awg leads, N.C., press fit mount
3.
281300S01- ACCESS CONTROL-Security And Key Access Systems
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 1 of 5
281300S01 ACCESS CONTROL-Security And Key Access Systems
Door and Window Surface Mtd.: Sentrol/United Security 1087T 1 1/4" max gap, terminal
screws, spacer, cover
4.
Radio Frequency Receiver
D2R Linear 2 RF channel, 2 SPDT contact outputs
ADV-52 (includes 2 D-21A's) 1 RF channel, siren driver, ?delay
5.
Radio Frequency Transmitter
Linear D-22A single channel, 256 code
Linear D-22C 2 channel, 256 codes per channel
Linear ET-1A single channel, Pendant, 2 button, 256 codes
Linear ET-2 single channel, Key chain, 1 button, 256 codes
Linear D-21A open circuit transmitter
6.
Temperature, AC Power, Monitors and Alarms
United Security model TA1 with high/low limits
United Security model TA2HL with high/low limits, low profile
United Security model DTA1 with high/low limits, remote probe, digital readout
United Security model PS110 contact closure on loss of AC for 3-6 minutes
7.
Digital Dialers
5104 Silent Knight, 4 zone, low batt, 24 hr test, 2 phone line, surge (lightning) protection, line
seizure, and UL,FM,CFM,NFPA listed
8.
Miscellaneous Hardware
Phone Jack model RJ31x
Phone Plug model
Electric Door Strike, Von Duprin Type 99, with lockdown keyed to UK Best or Yale master
system
Electric Door Strike, with lactone keyed to UK Best or Yale master system
3.
INSTALLATION AND WIRING
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
All wiring shall be in 3/4" or larger conduit. Exposed raceway in finished areas shall be in 750
or larger wiremold.
All conduit must be concealed in occupied spaces.
All conduit wiremold and junction boxes must be painted to match existing surface except in
mechanical rooms.
Exterior conduit must be rigid galvanized metal conduit with threaded fittings.
Underground conduit must be rigid galvanized metal conduit with threaded fittings and
asphaltum coating or rigid PVC Conduit encased in 3" reinforced concrete with dye
identification.
Use metallic anchors only.
All equipment shall be UL listed.
Provide guarantee in accordance with UK Standard 01740-01.
To assure satisfaction of the owner, installer of the system shall put the features and sequence
of operation of the system in writing and get the sequence of operation signed by the owner
before installation of the system begins.
All equipment and devices provided to meet this spec shall meet all FCC requirements and
restrictions for the application.
Provider of equipment or system to meet this spec must meet this regardless of any other
approvals the provider obtains either verbally or in writing.
Install system in accordance with local regulations and the State regulations of the Department
of Housing, Buildings, and Construction.
281300S01- ACCESS CONTROL-Security And Key Access Systems
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 2 of 5
281300S01 ACCESS CONTROL-Security And Key Access Systems
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
Provide detailed interconnecting wiring diagrams, operating manuals, programming manuals,
part list with manufacturer part numbers, and schematics of all circuits provided.
If an interruption in service of existing facilities or equipment is required, advanced notice shall
be given and a mutually agreeable time for the installer and the University will have to be
selected. This interruption duration will have to be limited to mutually agreeable intervals.
Delivery and Storage shall be the responsibility of the system provider. No space is available at
work site for storage of materials.
Clean-up shall be done daily and when project is complete. Clean-up must be thorough.
During construction, cover all equipment subject to mechanical damage or contamination in any
way.
All wiring shall be 98% copper and all 120 volt power runs shall be 12 awg minimum.
Provide an isolated run of conduit from the 120 VAC power source to the system. Use
emergency power panel if building is equipped.
Final connections of the control panel and start-up shall be made under direct supervision of a
representative of the manufacturer.
Conduit Location, Appearance and Support - All conduit shall be concealed except in University
of Kentucky designated mechanical rooms or unless otherwise specified and shown on
drawings approved by the designated UK Project Manager. Conduits that are not concealed
must have written approval of the designated UK Project Manager prior to installation and shall
be surface metal raceway (wiremold) unless otherwise noted in the approval. Conduit or tubing
shall have supports installed and spaced in accordance with the NEC. Conduit shall be
installed with runs parallel or perpendicular to walls, structural members on intersections of
vertical planes and ceilings, with right angle turns consisting of cast metal fittings or symmetrical
bends. Bends or offsets shall be avoided where possible but where necessary shall be made
with approved conduit bending machine. Conduit or tubing which has been crushed or
deformed in any way shall not be installed.
Install mechanical identification to properly identify the system and its components.
Arrange and pay for the inspections, examinations and tests required by the Department of
Housing, Buildings, and Construction as necessary to obtain complete and final acceptance of
the Automated Fuel Dispensing System. Deliver certificates of such inspections to the
University before final inspection and testing.
Complete system shall be functionally tested in the presence of the UK Project Manager and all
functions including system operation and interface must be in operation for at least 10 days
without problems prior to the final acceptance test.
Training Requirements: - Prior to final acceptance, provide operator training to each shift of the
owner's personnel and a group of up to five (5) of the owners maintenance persons. Each
training session shall include emergency procedures, manual operation, system control panel
operation, trouble procedures, programming and safety requirements. Each session shall
include a complete demonstration of the system. Dates and times of the training period shall be
coordinated through the owner not less than two weeks prior to session.
Firestop all penetrations in accordance with the current edition of the National Electric Code.
Installer shall coordinate and program the Remote Station connection with the designated UK
Security Administrator. Operation of this programming shall have approval of the owner, the UK
Security Administrator.
Conduit shall be EMT, Rigid or wiremold. Written exception to use PVC conduit in corrosive
environments must be obtained from the designated UK Project Manager.
Provide programming to be compatible with the UK Security Office. Contact UK Security Office
for a copy of the programming form to be completed. This form includes the phone numbers
and associated alarm transmission format, and associated monthly departmental cost for nonFire Alarm Point connections.
281300S01- ACCESS CONTROL-Security And Key Access Systems
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 3 of 5
281300S01 ACCESS CONTROL-Security And Key Access Systems
COGEBEC ALARM #
ACCOUNT NUMBER
ACCOUNT NAME
ADDRESS
PHONE NUMBER
DEPARTMENT
CONTACT PERSON
SYSTEM ON-LINE DATE
BUILDING KEY #
TYPE OF ALARM
SYSTEM NAME
HOOK #
PANEL LOCATION
COMMUNICATOR LOCATION
EQUIPMENT
CODE
ZONE
OR
LOCATION
SPECIAL NOTES
281300S01- ACCESS CONTROL-Security And Key Access Systems
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 4 of 5
281300S01 ACCESS CONTROL-Security And Key Access Systems
*Emergency Call list located on reverse side.
SAMPLE
SAMPLE
COGEBEC ALARM #
SAMPLE
ACCOUNT NUMBER
01-0111
ACCOUNT NAME Sample Name Here
ADDRESS 123 South Main Street
DEPARTMENT
PHONE NUMBER 123-4567
CONTACT PERSON John Doe
SYSTEM ON-LINE DATE 10-31-88 BUILDING KEY #
TYPE OF ALARM Fire/Trouble
HOOK # 123-4567
SYSTEM NAME Firelite c24
PANEL LOCATION Mechanical Room in basement
COMMUNICATOR LOCATION Mechanical Room in basement
EQUIPMENT DD3 Digital Dialer
CODE
ZONE
OR
LOCATION
02
Fire alarm (Building)
04
Trouble on fire alarm panel
74
Trouble restore
30
24 Hour self test
60
Low battery
SPECIAL NOTES This building fire alarm is not zoned. Check smoke detector located in
hallways and rooms.
*Emergency Call list located on reverse side.
281300S01- ACCESS CONTROL-Security And Key Access Systems
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 5 of 5