281300S01 ACCESS CONTROL-Security And Key Access Systems 1. SECURITY SYSTEM Location/Building 1. Security Control Panels with Remote Down line Loading Capability 1. 1 MDC-16CETX Morse 16 Zone Control Panel /no programmer required and equipped with digital communicator and downloading capability. MDC-16CCS Morse MDC-16CD in UL listed heavy duty box. MPC-32DL Morse keypad and personal control with 32 digit LCD display. MDC series software for remote computer (Not required if remote programming and downloading is not required) Gel Cell Rechargeable Battery 1 MA3000 NAPCO 8 zone control panel with digital communicator H1518 UL commercial locking metal cabinet RP3000LCD Designer Backlite Alphanumeric Display keypad PCD3000 software for remote computer (not required if remote programming and downloading is not required), requires PCI MINI interface Maintenance-Free Rechargeable Battery 12 VDC 6.5 AH 2. Note: 2. Manufacturers part numbers in this specification are provided for clarification only and do not exclude equivalent part numbers of acceptable manufacturers. Features all systems must have: Uninterruptible Battery Backup, nonvolatile memory, built in digital dialer, autotest timer, programmable, UL Listing 3. Guarantee All systems must be guaranteed in accordance with UK Standard 01740S01. 2. DETECTORS 1. Combination Infrared/Microwave Qty. D-100ST NAPCO with walk test (Default) C-100STLRE with walk test (compact model) DS-702 Detection Systems with walk test 2. Break Glass BGE-9100SM Blue Grass Dual Switch Glass Break Detector Magnetic Reed Switch Steel Door Jam Internal: Sentrol/United Security 1078C-1 w/ 1" press fit, 1/2" gap, 6" 22awg leads, N.C., self-locking mount Steel Door Jam Internal: Sentrol/United Security 1072 w/ 3/8" flange for screw mounting, 1/2" gap, 6" 22awg leads, N.C., Wood Door Jam Internal Wide Gap: GRI/Telemark Corp. 20-12 3/8" diameter, 1/2",1",& 1-1/2" gap (specify), 6" 22awg leads, N.C., press fit mount Wood Door Jam Internal: Sentrol/United Security 1075B 3/8" diameter, 1/2" gap, 6" 22awg leads, N.C., press fit mount 3. 281300S01- ACCESS CONTROL-Security And Key Access Systems Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 1 of 5 281300S01 ACCESS CONTROL-Security And Key Access Systems Door and Window Surface Mtd.: Sentrol/United Security 1087T 1 1/4" max gap, terminal screws, spacer, cover 4. Radio Frequency Receiver D2R Linear 2 RF channel, 2 SPDT contact outputs ADV-52 (includes 2 D-21A's) 1 RF channel, siren driver, ?delay 5. Radio Frequency Transmitter Linear D-22A single channel, 256 code Linear D-22C 2 channel, 256 codes per channel Linear ET-1A single channel, Pendant, 2 button, 256 codes Linear ET-2 single channel, Key chain, 1 button, 256 codes Linear D-21A open circuit transmitter 6. Temperature, AC Power, Monitors and Alarms United Security model TA1 with high/low limits United Security model TA2HL with high/low limits, low profile United Security model DTA1 with high/low limits, remote probe, digital readout United Security model PS110 contact closure on loss of AC for 3-6 minutes 7. Digital Dialers 5104 Silent Knight, 4 zone, low batt, 24 hr test, 2 phone line, surge (lightning) protection, line seizure, and UL,FM,CFM,NFPA listed 8. Miscellaneous Hardware Phone Jack model RJ31x Phone Plug model Electric Door Strike, Von Duprin Type 99, with lockdown keyed to UK Best or Yale master system Electric Door Strike, with lactone keyed to UK Best or Yale master system 3. INSTALLATION AND WIRING 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. All wiring shall be in 3/4" or larger conduit. Exposed raceway in finished areas shall be in 750 or larger wiremold. All conduit must be concealed in occupied spaces. All conduit wiremold and junction boxes must be painted to match existing surface except in mechanical rooms. Exterior conduit must be rigid galvanized metal conduit with threaded fittings. Underground conduit must be rigid galvanized metal conduit with threaded fittings and asphaltum coating or rigid PVC Conduit encased in 3" reinforced concrete with dye identification. Use metallic anchors only. All equipment shall be UL listed. Provide guarantee in accordance with UK Standard 01740-01. To assure satisfaction of the owner, installer of the system shall put the features and sequence of operation of the system in writing and get the sequence of operation signed by the owner before installation of the system begins. All equipment and devices provided to meet this spec shall meet all FCC requirements and restrictions for the application. Provider of equipment or system to meet this spec must meet this regardless of any other approvals the provider obtains either verbally or in writing. Install system in accordance with local regulations and the State regulations of the Department of Housing, Buildings, and Construction. 281300S01- ACCESS CONTROL-Security And Key Access Systems Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 2 of 5 281300S01 ACCESS CONTROL-Security And Key Access Systems 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. Provide detailed interconnecting wiring diagrams, operating manuals, programming manuals, part list with manufacturer part numbers, and schematics of all circuits provided. If an interruption in service of existing facilities or equipment is required, advanced notice shall be given and a mutually agreeable time for the installer and the University will have to be selected. This interruption duration will have to be limited to mutually agreeable intervals. Delivery and Storage shall be the responsibility of the system provider. No space is available at work site for storage of materials. Clean-up shall be done daily and when project is complete. Clean-up must be thorough. During construction, cover all equipment subject to mechanical damage or contamination in any way. All wiring shall be 98% copper and all 120 volt power runs shall be 12 awg minimum. Provide an isolated run of conduit from the 120 VAC power source to the system. Use emergency power panel if building is equipped. Final connections of the control panel and start-up shall be made under direct supervision of a representative of the manufacturer. Conduit Location, Appearance and Support - All conduit shall be concealed except in University of Kentucky designated mechanical rooms or unless otherwise specified and shown on drawings approved by the designated UK Project Manager. Conduits that are not concealed must have written approval of the designated UK Project Manager prior to installation and shall be surface metal raceway (wiremold) unless otherwise noted in the approval. Conduit or tubing shall have supports installed and spaced in accordance with the NEC. Conduit shall be installed with runs parallel or perpendicular to walls, structural members on intersections of vertical planes and ceilings, with right angle turns consisting of cast metal fittings or symmetrical bends. Bends or offsets shall be avoided where possible but where necessary shall be made with approved conduit bending machine. Conduit or tubing which has been crushed or deformed in any way shall not be installed. Install mechanical identification to properly identify the system and its components. Arrange and pay for the inspections, examinations and tests required by the Department of Housing, Buildings, and Construction as necessary to obtain complete and final acceptance of the Automated Fuel Dispensing System. Deliver certificates of such inspections to the University before final inspection and testing. Complete system shall be functionally tested in the presence of the UK Project Manager and all functions including system operation and interface must be in operation for at least 10 days without problems prior to the final acceptance test. Training Requirements: - Prior to final acceptance, provide operator training to each shift of the owner's personnel and a group of up to five (5) of the owners maintenance persons. Each training session shall include emergency procedures, manual operation, system control panel operation, trouble procedures, programming and safety requirements. Each session shall include a complete demonstration of the system. Dates and times of the training period shall be coordinated through the owner not less than two weeks prior to session. Firestop all penetrations in accordance with the current edition of the National Electric Code. Installer shall coordinate and program the Remote Station connection with the designated UK Security Administrator. Operation of this programming shall have approval of the owner, the UK Security Administrator. Conduit shall be EMT, Rigid or wiremold. Written exception to use PVC conduit in corrosive environments must be obtained from the designated UK Project Manager. Provide programming to be compatible with the UK Security Office. Contact UK Security Office for a copy of the programming form to be completed. This form includes the phone numbers and associated alarm transmission format, and associated monthly departmental cost for nonFire Alarm Point connections. 281300S01- ACCESS CONTROL-Security And Key Access Systems Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 3 of 5 281300S01 ACCESS CONTROL-Security And Key Access Systems COGEBEC ALARM # ACCOUNT NUMBER ACCOUNT NAME ADDRESS PHONE NUMBER DEPARTMENT CONTACT PERSON SYSTEM ON-LINE DATE BUILDING KEY # TYPE OF ALARM SYSTEM NAME HOOK # PANEL LOCATION COMMUNICATOR LOCATION EQUIPMENT CODE ZONE OR LOCATION SPECIAL NOTES 281300S01- ACCESS CONTROL-Security And Key Access Systems Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 4 of 5 281300S01 ACCESS CONTROL-Security And Key Access Systems *Emergency Call list located on reverse side. SAMPLE SAMPLE COGEBEC ALARM # SAMPLE ACCOUNT NUMBER 01-0111 ACCOUNT NAME Sample Name Here ADDRESS 123 South Main Street DEPARTMENT PHONE NUMBER 123-4567 CONTACT PERSON John Doe SYSTEM ON-LINE DATE 10-31-88 BUILDING KEY # TYPE OF ALARM Fire/Trouble HOOK # 123-4567 SYSTEM NAME Firelite c24 PANEL LOCATION Mechanical Room in basement COMMUNICATOR LOCATION Mechanical Room in basement EQUIPMENT DD3 Digital Dialer CODE ZONE OR LOCATION 02 Fire alarm (Building) 04 Trouble on fire alarm panel 74 Trouble restore 30 24 Hour self test 60 Low battery SPECIAL NOTES This building fire alarm is not zoned. Check smoke detector located in hallways and rooms. *Emergency Call list located on reverse side. 281300S01- ACCESS CONTROL-Security And Key Access Systems Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 5 of 5