Matt Gudorf Campus Energy Manager Identify building operation metrics, and how they are affected by lab practices. Understand how UCI uses sub metering and dash boarding to compile data at the building, floor, and zone level. How to use data analysis to reduce operating cost and ensure continuous commissioning. Agenda 1. Smart Lab vs. Previous Best Practice 2. Metering and Monitoring Installed 3. Lab Energy Use, 2001 vs. 2010 4. Smart Continuous Commissioning Air-handler/filtration airspeeds Total system (supply + exhaust) pressure-drop Duct noise attenuators Occupied lab air-changes/hr. (ACH) Night air-change setback (unoccupied) 2001 Best Practice 400 ft/min. max 6 in. w.g. Few 6 ACH No setback Gross Hall 2010 Smart Lab 350 ft/min. max <5 in. w.g. (incl. dirty filter allow.) None 4 ACH w/contaminant sensing 2 ACH w/occupancy + contaminant sensing Fume hood face-velocities 100 FPM 100 FPM Fume hood face-velocities (unoccupied) 100 FPM 60 FPM (Zone Presence Sensors) ~3,500 FPM ~2,100 FPM Wind Tunnel Modeled Exhaust stack discharge velocity Lab illumination power-density 0.9 watt/SF 0.6 watt/SF w/LED task lighting Fixtures near windows on daylight sensors No Yes Energy Star freezers & refrigerators No Yes 20-25% 50% Out-perform CA Title 24 Lab Efficiency Cycle UCI’s Goal is to reduce lab energy consumption by 50% Verify savings and use added tools to constantly commission labs Set Goals & Targets Measurement & Verification Analysis & Development Energy Improvement Measures Implement Smart Labs CDCV, ESDVR, Day Lighting and Lighting Controls, Low Pressure Drop Filters, Remove Duct Noise Attenuators, Static Pressure Reset Review data, Labs21 Toolkit, Scope out energy project Total Energy Use Building Electric and Gas Meter EMS, Sub Metering Building System Use Zone Level Use EMS Boiler, Water Heater HVAC, Pumps, Chillers EMS, CDCV Fume Hood Use, IAQ, Thermal Demand Sub Metering CDCV, EMS Lighting, Plug Load Reheat Meter Specs 12 Channels Per Board Meter accuracy: +/- 0.5% (0.25% Typ.) V, I, Active Energy, Reactive Energy, Power Factor Current Transformer Specs Sensor Accuracy: +/- 1% CT’s 60-400 Amps Clamp on installation d an ger h igh vol t age 10 KWH 00 1406 mel r ok C o r p o r a t i on Individual 12 Channel Meters d an ger h igh vol t age 10 KWH 00 1406 mel r ok C o r p o r a t i on EnerACQ User Interface Acquisition SW SQL Express DB User PC Multiple Users EnerACQ User Interface Database Server User PC Air Change Rates IAQ Sash position of each fume hood Occupancy Relative Humidity Temperature Total Supply Total Exhaust • Fume hood• usage range Change in average sash position from the month prior • This hood shows between • Redusage indicates poorer average green indicates 0% open and improved 65% open.average sash management Smart Labs are not just controls and sensors. Smart Labs provide real time feedback as well as monthly reporting data that is actionable. Return on investment is directly affected by lab practices. Designed in 2001 Designed in 2009 Exceeded Title 24 by 23.7% Biomedical research Lighting upgrade in 2009 Exhaust Stack Discharge Velocity Reduction in 2009 Re-Commissioned in 2010 76,905 Square Feet Exceeded Title 24 by 50.4% Biomedical Research Submitted to USGBC for LEED Platinum certification 94,705 Square Feet Percent Occupied by Building (7 days) 100% 90% 80% 70% 60% 50% 40% 30% 58% 27% 20% 10% 0% Gross Hall Hewitt Hall Time of Day 23:30 22:45 22:00 21:15 20:30 19:45 19:00 18:15 17:30 16:45 16:00 15:15 14:30 13:45 13:00 12:15 11:30 10:45 10:00 9:15 8:30 7:45 7:00 6:15 5:30 4:45 4:00 3:15 2:30 1:45 1:00 0:15 Watts per Square Foot Watts / Gross Square Foot 6.00 5.00 4.00 3.00 Hewitt Hall Gross Hall 2.00 1.00 It is easy to see how campus labs compare to each other but what about across the country? http://labs21benchmarking.lbl.gov/CompareData.php Peak W/gsf (elec) 10 9 8 7 6 5 4 3 2 1 Facilities Hewitt Gross 20166 20322 20043 20047 20053 20180 0 20008 Hewitt is right at the average Gross Hall beats the most efficient lab benchmarked by 18% Watts per Square Foot 8/30/11 5:59 8/29/11 21:57 1.20 8/29/11 13:57 1.80 8/29/11 5:57 8/28/11 21:56 8/28/11 13:56 8/28/11 5:55 8/27/11 21:53 8/27/11 13:53 8/27/11 5:53 8/26/11 21:52 8/26/11 13:52 8/26/11 5:52 8/25/11 21:50 8/25/11 13:50 8/25/11 5:50 8/24/11 21:49 8/24/11 13:49 8/24/11 5:49 8/23/11 21:48 8/23/11 13:48 8/23/11 5:48 8/22/11 21:46 8/22/11 13:46 8/22/11 5:46 8/21/11 21:44 8/21/11 13:44 8/21/11 5:44 8/20/11 21:42 8/20/11 13:42 8/20/11 5:42 8/19/11 21:41 8/19/11 13:41 8/19/11 5:41 8/18/11 21:41 8/18/11 13:41 8/18/11 5:41 8/17/11 21:41 8/17/11 13:41 CFM/ Sq. Ft. The HVAC savings of 1 CFM/ft2 at $4-5 per CFM can reduce operational significantly. A 1 CFM reduction at Hewitt Hall in just the open lab bays would reduce operational cost by $83,250 per year CFM / Square Foot Comparison Gross Hall vs. Hewitt Hall 1.53 CFM/ ft2 average. 1.60 1.40 0.52 CFM/ ft2 average. 1.00 0.80 0.60 Gross CFM/ Sq. Ft. Hewitt CFM / Sq. Ft. 0.40 0.20 0.00 0:15 0:45 1:15 1:45 2:15 2:45 3:15 3:45 4:15 4:45 5:15 5:45 6:15 6:45 7:15 7:45 8:15 8:45 9:15 9:45 10:15 10:45 11:15 11:45 12:15 12:45 13:15 13:45 14:15 14:45 15:15 15:45 16:15 16:45 17:15 17:45 18:15 18:45 19:15 19:45 20:15 20:45 21:15 21:45 22:15 22:45 23:15 23:45 Watts per Square foot 6 5 4 3 2 1 0 Hewitt Hall Gross Hall Gross Total Building Hewitt Hall Total Building BTU/h Per Square Foot 45 40 BTU/h Per Square Foot 35 30 25 20 15 10 5 0 08/27/2011 08/27/2011 08/27/2011 08/26/2011 08/26/2011 08/26/2011 08/25/2011 08/25/2011 08/25/2011 08/24/2011 08/24/2011 08/24/2011 11:59:00 PM 03:39:00 PM 07:19:00 AM 10:59:00 PM 02:39:00 PM 06:19:00 AM 09:59:00 PM 01:39:00 PM 04:51:00 AM 08:31:00 PM 12:11:00 PM 03:51:00 AM Hewitt Hall Gross Hall Previous Best Practice 0.9 watts/sqft 0.49 watts/sqft Offices 1.1 watts/sqft 0.66 watts/sqft Labs Overall Conditioned Space 24 Hour Actual Watts Per SQFT Watts Per Square Foot 20 18 16 14 12 10 8 6 4 2 0 0:15 1:15 2:15 3:15 4:15 5:15 6:15 7:15 8:15 9:15 10:15 11:15 12:15 13:15 14:15 15:15 16:15 17:15 18:15 19:15 20:15 21:15 22:15 23:15 kW 24 Hour Demand Curves Hewitt Hall 2nd Floor Lighting Demand Gross Hall 2nd Floor Lighting Demand 0.61 watts/sqft 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0:15 1:30 2:45 4:00 5:15 6:30 7:45 9:00 10:15 11:30 12:45 14:00 15:15 16:30 17:45 19:00 20:15 21:30 22:45 0:00 1 watts/sqft Gross Hall Space Type Hewitt Hall Watts Per Sqft Gross Hall Watts Per Sqft • • • 6 Air changes per hour minimum No set back during unoccupied periods Zone presence sensors on fume hoods Lab 2501 • • • • 4 Air changes per hour minimum occupied 2 Air Changes per hour minimum unoccupied Zone presence sensors on fume hoods Centralized Demand Controlled Ventilation system adjusting ACH for indoor air quality. Lab 2200 Hewitt Hall Lab 2501 Air change rates are dynamic responding to occupancy, IAQ, sash position, and thermal demands Lab 2200 averages 4 air changes per hour Air change rates are dependent on sash position and thermal demand. Lab 2501 averages 8 air changes per hour Gross Hall Lab 2200 Continuous Commissioning Meaningful Analysis and Reports Actionable information Verification of Actions Taken Physical and Behavioral CDCV Find failed lab air control valves Review of fume hood sash management Ensure safe lab air quality Find excessive air flows due to point sources of heat Sub Metering Monitoring of fans, pumps, and lighting control systems Verification of energy retrofits Reduce demand charges by modifying operations BMS Locate simultaneous heating and cooling Reset of static pressure to minimum required Control run times of office areas Autoclave In Gross Hall 60 kW peak HDP1 is a distribution board on the 1st Floor. It is responsible for feeding several equipment loads, autoclave units EQ2, EQ3, and EQ4. HDP1 is fed directly from the main switchboard at 480/277 volts. The board maximum current rating is 225 amps. The largest load on HDP1 is the medium autoclave EQ2, which is rated at 75kVA. Autoclave EQ2 Did running the Autoclave on peak just cost you $600 in demand charges? Gross Hall average site demand ranges from a baseline of 148kW to an average peak of 205 kW Researcher connects 4 tanks of CO2 to the lab distribution system and within 8 hours they are empty. To find the leak the research staff could have spent hours soaping lines and connections and wasting additional gas listening for the leak. Suspected location of CO2 leak It was quickly located and repaired The Knowledge Center has been used to locate lab equipment placed too close or under thermostats Commissioning Cx, Rx, MBCx is approximately $2 per SqFt Hewitt Hall MBCx $131,309 Net present value for 10 years (MBCx every 5 years) Hewitt Hall $113,590 Cumulative Cash Flow MBCx Project $250,000.00 MBCx $200,000.00 $150,000.00 $100,000.00 $50,000.00 $1 2 3 4 5 6 7 $(50,000.00) $(100,000.00) MBCx Cumulative Cash Flow MBCx Net Savings 8 9 10 11 Sub metering and monitoring your lab can be very competitive with the cost of a single commissioning effort. CDCV ~$3.12 per SqFt Sub metering $0.20 per SqFt Hewitt Hall Sub Metering and CDCV $302,888 Net present value for Hewitt Hall continuous commissioning (10 years) $665,903 Cumulative Cash Flow $1,400,000.00 $1,200,000.00 $1,000,000.00 $800,000.00 $600,000.00 $400,000.00 $200,000.00 $$(200,000.00) 1 2 3 4 5 Smart CCx Cumulative Cash Flow 6 7 Smart CCx Net Savings 8 9 10 11 Smart CCx although a larger initial investment provides for greater long term savings as well as strategic analysis, monitoring, and savings that can not be accomplished with traditional MBCx Cumulative Cash Flow MBCx vs. SMART CCx $1,400,000.00 $1,200,000.00 $1,000,000.00 $800,000.00 $600,000.00 $400,000.00 $200,000.00 $1 2 3 4 5 6 7 8 9 10 $(200,000.00) Smart CCx Cumulative Cash Flow Smart CCx Net Savings MBCx Cumulative Cash Flow MBCx Net Savings 11