Using Pinch Analysis to Optimize the Heat Exchanger Network of a Regenerative Rankine Cycle for an Existing Modern Chemical Power Plant by Stephanie Barnes A Project Submitted to the Graduate Faculty of Rensselaer Polytechnic Institute in Partial Fulfillment of the Requirements for the degree of MASTER OF ENGINEERING Major Subject: MECHANICAL ENGINEERING Approved: _________________________________________ Professor Ernesto Gutierrez-Miravete, Project Adviser Rensselaer Polytechnic Institute Hartford, Connecticut December, 2013 i © Copyright 2013 by Stephanie Barnes All Rights Reserved ii CONTENTS LIST OF TABLES ............................................................................................................ vi LIST OF FIGURES ......................................................................................................... vii DEFINITIONS ............................................................................................................... viii ACRONYMS .................................................................................................................... ix NOMENCLATURE .......................................................................................................... x ACKNOWLEDGMENT .................................................................................................. xi ABSTRACT .................................................................................................................... xii 1. Introduction.................................................................................................................. 1 1.1 Background ......................................................................................................... 1 1.2 Regenerative Rankine Cycle............................................................................... 1 1.2.1 Millstone III Unit Overview .................................................................. 1 1.3 Pinch Analysis .................................................................................................... 3 1.4 Problem Statement .............................................................................................. 3 1.5 Previous Work .................................................................................................... 4 2. Theory .......................................................................................................................... 5 2.1 Second Law of Thermodynamics ....................................................................... 5 2.2 Enthalpy Discussion?? ........................................................................................ 5 2.3 Problem Table Analysis ...................................................................................... 5 2.4 Composite Curves ............................................................................................... 6 2.4.1 Shifted Composite Curve ....................................................................... 7 2.5 Grand Composite Curve ..................................................................................... 8 2.6 ΔTmin ............................................................................................................... 10 2.7 Targeting for Multiple Utilities ........................................................................ 10 2.8 Trade Offs ......................................................................................................... 11 2.9 Design of the Heat Exchanger Network ........................................................... 13 3. Methodology .............................................................................................................. 14 iii 3.1 Overview........................................................................................................... 14 3.2 Assumptions ..................................................................................................... 14 3.3 Data Extraction ................................................................................................. 14 3.4 Problem Table ................................................................................................... 17 3.4.1 Heat Cascades ...................................................................................... 17 3.5 Composite Curves ............................................................................................. 18 3.6 Grid Diagram .................................................................................................... 18 3.7 HEN design ....................................................................................................... 19 3.8 3.7.1 Area of Heat Exchangers ..................................................................... 19 3.7.2 Cost?..................................................................................................... 19 How to use design for utilities .......................................................................... 19 4. Results and Discussion .............................................................................................. 20 4.1 Problem Table ................................................................................................... 20 4.2 Heat Cascade .................................................................................................... 21 4.3 Pinch Points and Utility .................................................................................... 22 4.4 Composite Curves ............................................................................................. 22 4.5 Grand Composite Curve ................................................................................... 23 4.6 Retrofit Heat Exchanger Network .................................................................... 24 4.6.1 Splitting the Cross Pinch Heat Exchanger ........................................... 25 4.6.2 Utility Design ....................................................................................... 25 5. Conclusion ................................................................................................................. 26 6. References.................................................................................................................. 27 6.1 Works Cited ...................................................................................................... 27 6.2 Additional References Consulted ..................................................................... 28 7. Appendices ................................................................................................................ 29 7.1 Guide to Excel File ........................................................................................... 29 7.2 Raw Data and Intermediate Steps ..................................................................... 29 iv 7.3 Millstone Unit III Heat and Mass Balance ....................................................... 31 v LIST OF TABLES Table 1 Millstone Unit III Heat Exchanger Network ...................................................... 15 Table 2 Input Stream Data ............................................................................................... 16 Table 3: Problem Table ................................................................................................... 20 Table 4: Heat Cascade ..................................................................................................... 21 Table 5: Raw Data from Millstone Unit III Heat and Mass Balance .............................. 29 Table 6: Combined Data for HEN used in Analysis........................................................ 30 vi LIST OF FIGURES Figure 1: Millstone Unit III Power Plant Schematic [Dominion] ..................................... 2 Figure 2 Hot and Cold Composite Curves ......................................................................... 7 Figure 3 Shifted Composite Curves .................................................................................. 8 Figure 4 Pg 10 March – Construction of the Grand Composite Curve ............................ 9 Figure 5 Grand Composite Curve Example....................................................................... 9 Figure 6 Multiple Utility Targeting March pg 11 ............................................................ 11 Figure 7: Grid Diagram Example [Bi] ............................................................................. 18 Figure 8: Grid Diagram with Cross Pinch Heat Transfer Example {Bi] ......................... 19 Figure 9: Hot and Cold Composite Curves...................................................................... 22 Figure 10: Shifted Hot and Cold Composite Curves ....................................................... 23 Figure 11: Grand Composite Curve ................................................................................. 24 Figure 12: Grid Diagram ................................................................................................. 25 Figure 13: Millstone Unit III Heat and Mass Balance ..................................................... 31 vii DEFINITIONS viii ACRONYMS The following is a list of acronyms and abbreviations that are used throughout this paper. Acronym Definition GCC Grand Composite Curve SCC Shifted Composite Curve HEN Heat Exchanger Network SG Stream Generator LP Low Pressure HP High Pressure ix NOMENCLATURE The following is a list of nomenclature used throughout this paper: Symbol Description Unit mCp Heat Capacity Flowrate MBtu/hr/F dH Heat Load MBtu/hr Tmin Minimum Temperature Difference Between Hot and Cold F Composite Curves TS Supply Temperature F TT Target Temperature F TSS Shifted Supply Temperature F TTS Shifted Target Temperature F M dot Mass flow rate lb/hr H Enthalpy Btu/lb x ACKNOWLEDGMENT Type the text of your acknowledgment here. xi ABSTRACT Type the text of your abstract here. xii 1. Introduction 1.1 Background Vapor power systems are commonly used to generate electricity. In nuclear power plants, a controlled nuclear reaction generates heat energy, which is released to a working fluid (i.e. reactor coolant) to transform feedwater into steam, via a steam generator. The steam flows through a secondary plant to power a turbine that generates electricity. The steam leaves the turbine and is sent through a condenser and feedwater is pumped back in the steam generator. The Rankine cycle is an ideal vapor power cycle without irreversibilities that are present in real power plants. Real power plants encounter losses (expansion through the turbine, work input to pumps, frictional losses through pipes, etc.) and modifications to the Rankine cycle are made to improve plant performance. 1.2 Regenerative Rankine Cycle The Regenerative Rankine cycle has features that improve the thermal efficiency of the power plant when compared with the Rankine cycle. The Regenerative Rankine cycle preheats the feedwater from the condenser, using the waste heat/steam from the turbines, before it enters the steam generator. Modern power plants use open or closed feedwater heaters to increase the average temperature of the feedwater without using an external heat source. Regenerative rankine cycles are common in modern power plants because they increase the thermal efficiency and power generation of the plant, while reducing cost. 1.2.1 Millstone III Unit Overview Figure 1 shows a simplified version of the Millstone III unit nuclear power plant. The unit uses a pressurized water reactor, which prevents boiling in the reactor, to transfer heat to a steam generator, which produces steam that flows through a high pressure and three low pressure turbines to turn a turbine generator shaft to generate 1290 MW of power. The steam exits the high pressure turbine, enters a moisture separator steam 1 reheater that separates “approximately 10% of the moisture from the steam.” (Dominion). The steam gets reheated and is dry enough to flow through three low pressure turbines. After exiting each low pressure turbine, the steam enters a condenser below each low pressure turbine that condenses the steam into water. The condensate and feed system transfers the water from the exit of the condenser back to the steam generator. The feedwater is reheated prior to entering the steam generator by six closed feedwater heaters. QuickTime™ and a decompressor are needed to see this picture. Figure 1: Millstone Unit III Power Plant Schematic [Dominion] Excess steam from the turbines is used as a heating element in six closed feedwater heaters. Excess steam from the three low pressure turbines and the high pressure turbine enters four closed feedwater heaters (#3-6) and two closed feedwater heaters (#1-2), respectively. The closed feedwater heaters are used to heat the working fluid (water) before it enters the steam generator, which significantly increases plant efficiency. The closed feedwater heaters contain U-shaped tubes inside a shell and do not allow the steam and water to mix. The temperature of the feedwater is increased after going 2 through each fclosed eedwater heater. Feedwater pumps “enable the feedwater to overcome the steam pressure in the boiling device.” The smaller the temperature difference between the input and output of the steam generator, the less external heating work is that must be done by the reactor. (Dominon) 1.3 Pinch Analysis Optimizing the thermal efficiency and overall cost of a power plant can be determined by pinch analysis. Linnhoff & Flower developed pinch analysis, at the ETH Zurich & Leeds University, in 1978. Pinch analysis is a means of optimizing a chemical power plant by using the heat energy from the streams, instead of using external heating and cooling methods (heat exchanger, furnace, cooler, etc.), to increase the thermal efficiency of the plant and minimize energy costs. Streams are any flow paths that do not change in chemical composition. Pinch analysis can be used for designing new, or retrofitting existing, power plants. Pinch analysis utilizes energy targets, which “are absolute thermodynamic targets, showing what the process is inherently capable of achieving if the heat recovery, heating and cooling systems are correctly designed” (Kemp pg 2). “The principle is to predict what should be achieved (targeting), and to then set out to achieve it (design)” (Linnhoff & Tjoe). 1.4 Problem Statement This project will analyze a Regenerative Rankine cycle, based on the Millstone Unit III nuclear power plant, using pinch analysis. The thermal efficiency of the heat exchanger network will be evaluated and a recommendation for retrofitting the components of the power plant or improvements to increase efficiency and reduce cost will be made. 3 1.5 Previous Work Linnhoff / march paper Pinch analysis has been used to optimize new heat exchanger networks in power plants as well as retrofit existing HENs. (Singh and Crosbie sized and integrated a heat exchanger into an existing HEN at a gas processing plant). Energy pinch, water pinch, hydrogen pinch (READ PINCH GUIDE ON WEBSITE Pg 38) 4 2. Theory 2.1 Second Law of Thermodynamics Pinch analysis is based on the second law of thermodynamics. The second law of thermodynamics describes the spontaneous processes that exist in irreversible (nonideal) cycles. The Clausius Statement of the second law of thermodynamics states: “it is impossible for any system to operate in such a way that the sole result would be an energy transfer by heat from a cooler to a hotter body.” [Moran pg 216] A hot stream cannot be used to heat a cold stream to a temperature hotter than the hot stream. The Kelvin-Planck Statement of the second law states: “it is impossible for any system to operate in a thermodynamic cycle and deliver a new amount of energy by work to its surroundings while receiving energy by heat transfer from a single thermal reservoir.” [Moran pg 217] The hot streams cannot transfer all of their energy to heat the cold stream. There must be some waste heat as a result of the heat transfer process. 2.2 Enthalpy Discussion?? Steam data is plotted on a temperature-enthalpy diagram. The plot can be shifted because we only care about the change in enthalpy. CP=heat capacity flowrate = mass flow x specific heat The heat available in the interval is (CPa+CPb)*(T2-T1) Heat Load Q=dH=MCp x (Ts-Tt) amount of enthalpy change in the process stream MORE 2.3 Problem Table Analysis The problem table method is developed to “allow for the maximum possible amount of heat exchange within each temperature interval (Pg 21, Kemp).” Shifted temperatures (1/2 ΔTmin below hot stream and above cold stream) are used to ensure that Tmin exists between all hot and cold streams. (See table 2.3 Kemp) 5 The heat cascade uses the surplus heat from one hot utility and moves it into the next interval. The minimum utility requirements are determined from the heat cascade diagram. “The total heat recovered by heat exchange is found by adding the heat loads for all the hot streams and all the cold streams. Subtracting the cold and hot utility targets from these values gives the total heat recovery by two separate routes (Pg 24, Kemp).” Rules: Don’t transfer heat across the pinch, don’t use cold utilities above the pinch, don’t use hot utilities below the pinch. If you were to transfer heat across the pinch, you would have to “replace this cross-pinch heat with an equivalent amount of hot utility above the pinch, and we would increase our consumption of cold utility below the pinch (air, cooling water, etc.) by the same amount” (Pinch Analysis Guide pg 26). 2.4 Composite Curves The composite curve is a way to incorporate all of the hot and cold streams onto a temperature-enthalpy (or heat content H) diagram. The heat flow is determined by multiplying the mass flow rate (lb/hr) by the change in enthalpy (Btu(IT)/lb). The hot and cold composite curves are plotted separately and “the overlap between the composite curves represents the maximum amount of heat recovery possible within the process. The “overshoot” at the bottom of the hot composite represents the minimum amount of external cooling required and the “overshoot” at the top of the cold composite represents the minimum amount of external heating (Pg 20 Kemp).” The hot and cold composite curves are separated by ΔTmin. The location of the minimum temperature difference between the curves is the pinch point. The complete overlap of the curves (overlaps for the same range of heat flow) represents the maximum heat recovery possible. The extension of the cold composite curve on the upper right represents the minimum hot utility requirement and the extension of the hot composite 6 curve on the lower left represents the minimum cold utility requirement for the given ΔTmin (March pg 7). The slope of the T-H diagram is mCp. (Hint Online slides) QuickTime™ and a decompressor are needed to see this picture. Figure 2 Hot and Cold Composite Curves “The temperature difference between cold and hot streams, in any heat exchanger of the process, is close to the ΔTmin value when the composite curves are almost parallel.” (Pinch Analysis Guide pg 27) 2.4.1 Shifted Composite Curve The composite curves are also plotted using the shifted temperatures. The shifted composite curves touch at the pinch point. The problem is divided on either side of the pinch point. Above the pinch point the cold flow is greater than the hot flow and the hot utilities must be supplied to make up the difference. The opposite is true for below the pinch. Moving a composite curve horizontally does not change the stream data because the x-axis represents a change in enthalpy. 7 QuickTime™ and a decompressor are needed to see this picture. Figure 3 Shifted Composite Curves 2.5 Grand Composite Curve The grand composite curve (GCC) is a graph of the net heat flow (utility requirement) versus the shifted temperature. The GCC is used for “setting multiple utility targets” (March pg 10). The shifted composite curves ensure that ΔTmin is maintained (by using ΔTmin /2 less than hot temps & ΔTmin /2 greater than cold temps) at all points. The composite curves touch at the pinch in the shifted composite curve (SCC). The x-axis of the GCC shows the utility heat or cooling required. 8 QuickTime™ and a decompressor are needed to see this picture. Figure 4 Pg 10 March – Construction of the Grand Composite Curve QuickTime™ and a decompressor are needed to see this picture. Figure 5 Grand Composite Curve Example The pinch point is the location where the new heat flow is 0. “The values of net heat flow at the top and bottom end are the heat supplied to and removed from the cascade, and thus tell us the hot and cold utility targets (Pg 26 Kemp).” The curve also tells us the temperatures at which heating and cooling are required. When the pinch occurs at one end of the curve, it is referred to as a threshold problem. 9 2.6 ΔTmin “Only the heat exchangers at the pinch need to operate at delta T values down to delta T min (Pg 20, Kemp)”. “A zero temperature difference would require an infinitely large heat exchanger (Pg 18 Kemp).” The surface area required for heat exchange is given by A=Q/U*deltaTLM. U is the overall heat transfer coefficient, delta TLM is the log mean temperature difference, Q is the heat transferred in the exchanger, and A is the surface area. Text assumes a value of 0.1 kW/m^2 K for U) Delta TLM = (see pg 36 of Kemp) The heat exchanger area is roughly inversely proportional to the temperature difference. Low values of ΔTmin can result in large and costly heat exchangers. QuickTime™ and a decompressor are needed to see this picture. 2.7 Targeting for Multiple Utilities Using the grand composite curve to target for multiple utilities helps reduce utility costs. For example, in Figure b, MP and cooling water are used to reduce the amount of HP 10 steam and refrigeration required. In this figure b, a horizontal line is drawn from the yaxis at the temperature of MP steam until it hits the GCC. This is the MP steam target. The remaining heating utility is satisfied by HP steam. The points where MP, HP, CW, and Ref touch the GCC are called utility pinches. “Heat transfer across a utility pinch represents inefficiency. For the process pinch, the inefficiency is an increase in overall energy use above the target value. For a utility pinch, the inefficiency is a shift in heat load from a cheaper utility level to a more expensive one.” (Pinch Guide pg 32). QuickTime™ and a decompressor are needed to see this picture. Figure 6 Multiple Utility Targeting March pg 11 “The general objective is to maximize the use of cheaper utility levels and minimize the use of the expensive utility levels. (March pg 9).” “It is preferable to use LP steam instead of HP steam, and cooling water instead of refrigeration” (March pg 9). LP steam use can replace part of the HP steam use for heating purposes until the ΔTmin is difference between the hot composite curve and the cold composite curve is reached. Each time a new utility is added, the composite curve will change shape. 2.8 Trade Offs There is a trade off between the capital costs and energy costs. The optimum ΔTmin can be selected by the intersection of the capital cost and the energy cost graphs to determine the minimum cost in new designs. If the energy cost and the heat exchanger cost (surface area), the optimal ΔTmin can be determined (Pinch Analysis Guide pg 27). 11 “There is a correlation between the value of ΔTmin in the exchanger and the total utility load on the system (Pg 18, Kemp).” As ΔTmin is increased, the difference between the hot and cold composite curves increases, which increases the heat required by external utilities, as shown in Figure 3.7. QuickTime™ and a decompressor are needed to see this picture. Pg 14 of March 12 QuickTime™ and a decompressor are needed to see this picture. Pg 27 Pinch Analysis Guide 2.9 Design of the Heat Exchanger Network 13 3. Methodology 3.1 Overview The pinch analysis performed for this project is divided into four major steps: (1) extraction of steam data (temperature, flow, and heat capacity data) from the Millstone Unit III heat and mass balance, (2) selection of Tmin and calculation of the pinch point and minimum utility requirements, (3) determining areas of cross-pinch heat transfer and modifying the heat exchanger network, (4) designing the hot and cold utility systems and modifying the heat exchanger network as necessary. [Kemp] An excel spreadsheet, developed by Gabriel Norwood (Kemp) was used for the first two steps of the analysis. The user enters Tmin, the supply and target temperatures, the mass flow rate, and the change in enthalpy. Typical ΔTmin values for different types of plants can be found in various texts. ΔTmin for chemical plants ranges from 10-20 deg C. (Linhoff, Kemp, Pinch Guide). The program calculates the heat load, whether the stream is hot or cold, and the shifted temperatures based on the supplied Tmin. The problem was evaluated as two systems, one above the pinch and one below the pinch. The analysis was also verified by hand calculations. 3.2 Assumptions In the analysis, it is assumed that the flow from the condenser is that which enters the 6th point heater. A weighted average supply and target temperatures, enthalpy, and flowrates are used when streams are combined. The HEN consisting of six feedwater heaters was evaluated. The main condenser is considered a permanent utility because of the cooling water from the Long Island Sound. 3.3 Data Extraction Data is extracted from the heat and mass balance in Appendix 7.3 for all areas of the plant that need heating or cooling. In this analysis, the HEN consisting of six feedwater heaters was evaluated for simplicity. A ΔTmin of 50 F was used for this analysis. 14 In the input stage, the heating and cooling demands of the streams are included without any reference to the existing heat exchangers (March pg 5). “The assumption in the data extraction flow-sheet is that any process cooling duty is available to match against any heating duty in the process.” (March pg 5). This analysis “does not consider matching constraints between specific hot and cold streams” (March pg 14). The effective stream temperatures are more important than the actual stream temperatures in the data extraction phase (March pg 50). For an existing plant, the heat exchangers and the plant layout should not be used at first. Utility streams (cooling water, steam, etc.) are not to be included in the data extraction phase unless they cannot be replaced. [Kemp] The original heat exchanger network design parameters are presented in Table 1. Table 1 Millstone Unit III Heat Exchanger Network Hot Stream Heat Exchanger Cold Stream Number Ts (F) Tt (F) Ts (F) Tt (F) 1st Point 491 380 369 442.8 2nd Point 379 334 326.7 365.6 3rd Point 346 292 282 297.9 4th Point 297 266 222.9 288.1 5th Point 231 174 158.3 222.9 6th Point 163 158 101 158.3 The 1st through 4th point heaters have a combination of streams that flow through the exchanger to heat the feedwater stream. The input streams are combined to simplify the analysis. The supply temperatures for the 1st through 4th point heaters are weighted averages based on the mass flow rates. For example, the supply temperature for the 1 st point heater (stream 2 of Table 2) was determined by the following: 15 m m m Ý Ý Ý Ts TW W TV V THP1 HP1 ÝTot ÝTot ÝTot m m m (Equation 1) 73,748lbm /hr 1,540,778lbm /hr 1,247,218lbm /hr Ts 525F 525F 448F 491F 2,861,744lbm /hr 2,861,744lbm /hr 2,861,744lbm /hr The same procedure was followed to determine the enthalpy the combined streams. Table 2 Input Stream Data Stream Name Supply Target Temperature Temperature dT Min Contrib Mass Flowrate Enthalpy Change °F °F °F lb/h Btu(IT)/lb 1 98 442.8 25 10085320.000 202 2 491 380 25 2861744.000 455 3 379 334 25 3444389.000 173 4 432 292 25 3983700.000 171 5 297 266 25 4566511.000 146 6 231 174 25 675020.000 968 7 163 158 25 571554.000 928 The shifted temperatures are then calculated by adding half of Tmin to the cold stream supply and target temperatures. The shifted supply temperature for stream 2 of Table 2 is calculated as follows. TSS TS Tmin 50F 491F 466F 2 2 (Equation 2) The supply shift temperature for the cold stream (stream 1 of Table 2) is calculated by addinghalf of Tmin to the supply temperature as follows. TSS TS Tmin 50F 98F 123F 2 2 (Equation 3) The analysis was done using one cold stream (from the condenser to the SG (stream 1 of Table 2)) and six hot streams (one stream for each closed feedwater heater (streams 2 through 7 of Table 2)). The mass flowrates for streams 2 through 5 of Table 2 are a 16 combined sum of the individual stream flowrates that enter the feedwater heater (See Table 6 of Appendix 7.2 for intermediate steps and details). 3.4 Problem Table To make the problem table, the shifted temperatures are ranked in decreasing order, starting from the highest temperature. The heat capacity flowrate (mCp) and the heat load (dH) are calculated for all of the temperature intervals. The calculations for the first interval (between shifted temperatures 467.8F and 466F) are provided below. The following conversion factors are used in the heat capacity flowrate equation. 1 kJ/kg = 0.42992261 Btu/lb 1 kJ = 0.94781742 Btu T(R) = 1.8T(K) 1 kg/s = 7936.64144 lb/hr Ý m h 7936.64144 0.42992261 0.94781742 mCp 1.8 TSS TTS (Equation 4) 10085320lb /hr 202Btu /lb 7936.64144 0.42992261 0.94781742 911.7986MBtu /hr /F mCp 1.8 123F 467.8F dH mCpTTS TSS (Equation 5) dH 911.7986MBtu /hr /F 467.8 466 1641.2375MBtu /hr 3.4.1 Heat Cascades Starting from a zero heat input at the highest temperature in the Problem Table, the net heat change (dH) is added to each temperature interval to form a “heat cascade.” The heat cascade is typically evaluated and determined to be infeasible because the cascade contains negative heat flows. The minimum heat flow (largest negative value) from the infeasible heat cascade is now added to the hot utility in a new cascade. “All the net heat flows in the cascade now 17 increase by this amount and the minimum value becomes zero.” The minimum value (should be zero) is the pinch point. The heat added to the first interval is the hot utility requirement and the heat removed from the final interval is the cold utility target. [Kemp] 3.5 Composite Curves The composite curve is a graph of temperature versus heat flow. The shifted composite curve is then made using the shifted temperatures for both the hot and cold streams. To generate the GCC, the net heat flow (right side of the feasible heat cascade –not the boxed numbers) is plotted on the horizontal axis and the shifted temperature is plotted on the vertical axis. 3.6 Grid Diagram The grid diagram is another way to visualize the streams in the analysis. The grid diagram “represents the countercurrent nature of the heat exchange” [section 2.3.2 Kemp]. As shown in Figure 7, streams 1 and 2 (boxes) are hot streams and streams 3 and 4 are cold streams. The circled numbers represent current heat exchangers between two streams. The circles with “H” and “C” represent external heating and cooling utilities. QuickTime™ and a decompressor are needed to see this picture. Figure 7: Grid Diagram Example [Bi] For a retrofit analysis, the current streams and heat exchangers are depicted on the grid diagram. The location of the pinch is drawn, as shown in Figure 8. If there is a current 18 heat exchanger that transfers heat across the pinch, the heat exchanger is split into two (one above the pinch and one below the pinch as shown by the green circles in Figure 8). QuickTime™ and a decompressor are needed to see this picture. Figure 8: Grid Diagram with Cross Pinch Heat Transfer Example {Bi] The heat exchangers that were split are then combined with another heat exchanger on the same side of the pinch or a new heat exchanger is created. 3.7 HEN design 3.7.1 Area of Heat Exchangers 3.7.2 Cost? 3.8 How to use design for utilities Selecting the minimum number of heat exchanger units can be determined by Umin = N1 where N is the total number of process and utility streams in the HEN (March pg 13). Process improvements for reducing the hot utility target include increasing the hot stream above the pinch and decreasing the cold stream above the pinch. The cold utility is reduced by the opposite. This is called the plus-minus principle for process modifications (Pinch Guide pg 37). 19 4. Results and Discussion 4.1 Problem Table The problem table is provided in Table 3. The heat capacity flowrate and the heat load are calculated for each interval, using Equations 4 and 5. Table 3: Problem Table Shift Temperature °F 467.8 Interval T(i+1)-Ti mCpnet dH °F MBtu(IT)/hr/°F MBtu(IT)/hr 1 1.8 -911.7986 -1641.2375 demand 2 59 898.4755 53010.0519 surplus 3 52 1649.3715 85767.3194 surplus 4 1 -160.9025 -160.9025 demand 5 45 1882.5799 84716.0964 surplus 6 37 -160.9025 -5953.394 demand 7 5 3158.0482 15790.2408 surplus 8 26 2407.1521 62585.9543 surplus 9 35 -911.7986 -31912.9514 demand 10 57 857.2602 48863.832 surplus 11 11 -911.7986 -10029.7847 demand 12 5 15458.6421 77293.2106 surplus 13 10 -911.7986 -9117.9861 demand 466 407 355 354 309 272 267 241 206 149 138 133 123 20 4.2 Heat Cascade The heat cascade is drawn from the problem table. The heat loads are in the boxes of Table 4 and the heat load for each interval is added to that of the previous interval. The heat cascade on the left hand side of Table 4 is infeasible because there is a negative net heat load. The minimum heat flow (largest negative value) from the infeasible heat cascade is now added to the hot utility in a new cascade. The feasible heat cascade does not include any negative heat flows. The temperature with no heat flow is the pinch. Table 4: Heat Cascade Infeasible Cascade ▼ PINCH -1641.2375 ▼ 53010.05195 ▼ 85767.31943 ▼ 160.9025404 ▼ 84716.09638 ▼ 5953.393995 ▼ 15790.2408 ▼ 62585.95432 ▼ 31912.95139 ▼ 48863.83203 ▼ 10029.78472 ▼ 77293.21059 ▼ -9117.98611 ▼ Feasible Cascade ▼ 0 378328.4354 -1641.2375 ▼ 53010.05195 ▼ 85767.31943 ▼ 160.9025404 ▼ 84716.09638 ▼ 5953.393995 ▼ 15790.2408 ▼ 62585.95432 ▼ 31912.95139 ▼ 48863.83203 ▼ 10029.78472 ▼ 77293.21059 ▼ 369210.4492 -9117.98611 ▼ -1641.2375 51368.81445 137136.1339 136975.2313 221691.3277 215737.9337 231528.1745 294114.1288 262201.1775 311065.0095 301035.2248 21 1641.2375 0 53010.05195 138777.3714 138616.4688 223332.5652 217379.1712 233169.412 295755.3663 263842.415 312706.247 302676.4623 379969.6729 370851.6867 4.3 Pinch Points and Utility The pinch temperature (shifted) is 466F and is highlighted in yellow in Table 3. The hot pinch his 491F and the cold pinch is 441F and is calculated using Equations 2 and 3. The minimum hot and cold utility requirements are 1641.24 MBtu/hr and 370,851.69 MBtu/hr, respectively. 4.4 Composite Curves The pinch point is also determined graphically by using the shifted composite curve. The hot and cold composite curves are shown in Figure 9. Hot and Cold Composite Curves 600 Actual Temperature (ЎF) 500 400 300 200 100 0 0 100000 200000 300000 400000 500000 600000 700000 800000 Heat Flow (Mbtu(IT)/hr) Figure 9: Hot and Cold Composite Curves The shifted hot and cold composite curves are shown in Figure 10. The point where the hot and cold shifted composite curves touch is the pinch point. 22 Shifted Hot and Cold Composite Curves 500 450 Shifted Temperature (ЎF) 400 350 300 250 200 150 100 50 0 0 100000 200000 300000 400000 500000 600000 700000 800000 Heat Flow (Mbtu(IT)/hr) Figure 10: Shifted Hot and Cold Composite Curves 4.5 Grand Composite Curve The grand composite curve is shown in Figure 11. The utility requirements can be obtained from the grand composite curve. 23 Grand Composite 500 450 400 Shifted Temperature (ЎF) 350 300 250 200 150 100 50 0 0 50000 100000 150000 200000 250000 300000 350000 400000 Net Heat Flow (Mbtu(IT)/hr) Figure 11: Grand Composite Curve 4.6 Retrofit Heat Exchanger Network The grid diagram is shown in Figure 12. The current heat exchangers, with their corresponding cold and hot streams, are depicted by black circles with arrows between the streams. The 1st point heat crosses the pinch point and must be evaluated using the method described in Section 3.6. 24 QuickTime™ and a decompressor are needed to see this picture. Figure 12: Grid Diagram 4.6.1 Splitting the Cross Pinch Heat Exchanger 4.6.2 Utility Design 25 5. Conclusion 26 6. References 6.1 Works Cited Bi, Bao-Hong, and Chuei-Tin Chang. "Retrofitting Heat Exchanger Networks Based on Simple Pinch Analysis." Ind. Eng. Chem. Res. 49 (2010): 3967-971. Web. Dominion. Nuclear Media Guide, Information on Millstone Power Station. Waterford: Dominion, 2012. Dominion, 2012. Web. 19 Aug. 2013. Kemp, Ian E. Pinch Analysis and Process Integration - A User Guide on Process Integration for the Efficient Use of Energy. 2nd ed. Oxford: Elsevier, 2007. Print. March, Linnhoff. Introduction to Pinch Technology. 1998. Targeting House Gadbrook Park, England. Moran, Michael J., and Howard N. Shapiro. Fundamentals of Engineering Thermodynamics. New York: Wiley, 2008. Print. Pinch Analysis: For the Efficient Use of Energy, Water, and Hydrogen. N.p.: Canada, 2003. Print. Singh, Kamel, and Raymond Crosbie. "Use of Pinch Analysis in Sizing and Integrating a Heat Exchanger into an Existing Exchanger Network at a Gas Processing Plant." The Journal of the Association of Professional Engineers of Trinidad and Tobago 40.2 (2011): 43-48. Print. 27 6.2 Additional References Consulted Bakhtiari, Bahador, and Serge Bedard. "Retrofitting Heat Exchanger Networks Using a Modified Network Pinch Approach." Applied Thermal Engineering 51 (2012): 973-979. Science Direct. Web. 17 Aug. 2013. Linnhoff, B., and E. Hindmarsh. "The Pinch Design Method for Heat Exchanger Networks." Chemical Engineering Science 38.5 (1983): 745-63. Print. Rossiter, Alan P. Using Spreadsheets for Pinch Analysis. Tech. no. 96D. N.p.: Unpublished, 2004. Print. Tjoe, T. N., and Bodo Linnhoff. "Using Pinch Technology for Process Retrofit." Chemical Engineering 28 (1986): 47-60. Web. Zebian, Hussam, and Alexander Mitsos. "A Double-pinch Criterion for Regenerative Rankine Cycles." Energy 40.2 (2012): 258-70. Print. 28 7. Appendices 7.1 Guide to Excel File The following tabs in the excel file: TARGETS – Problem table, energy targets, pinch temperature and type of problem (pinch, threshold, multiple pinch, or pinch region) CC – Hot and cold composite curves SCC – Shifted composite curves GCC – Grand composite curves GRID – Network grid diagram, shifted temperatures AS – Stream data plot, actual temperatures SS – Stream data plot, shifted temperatures AT – Interval tables (heat loads and temperatures), actual temperatures ST – Interval tables (heat loads and temperatures), shifted temperatures DTMIN – Variation of hot and cold utility targets and pinch temperature with ∆Тmin. 7.2 Raw Data and Intermediate Steps Table 5: Raw Data from Millstone Unit III Heat and Mass Balance Stream Description from LP 1 from LP 2 from LP 3 from LP 4 HP 1 HP 2 W to 1st pt V to 1st pt A to 2nd pt waste from 1st pt waste from 2nd pt waste from Input H (Btu/lb) 1241 1200 1110 1054 1146 1089 1198 518 1192 Output H (Btu/lb( 261 235 142 126 354 305 354 354 305 Change H (Btu/lb) 980 965 968 928 792 784 844 164 887 Supply Temp (F) 426 335 231 163 448 373 525 525 538 Target Temp (F) 292 266 174 158 380 334 380 380 334 Flow (lb/hr) 539308 582815 675020 571554 1247218 570935 73748 1540778 11711 354 305 49 380 334 2861743 305 261 261 235 44 26 334 292 292 266 3444392 3983696 29 3rd pt waste from 5th pt waste from 6th pt 142 56 86 174 98 675021 126 56 70 158 98 785742 Table 6: Combined Data for HEN used in Analysis Stream Description Condenser to SG 1 Total W+V+HP1 flow 2 Total A + 2nd pt + waste from 1st pt 3 Total 3rd pt (LP1)+ 2nd pt waste 4 Total waste from 3rd pt + LP2 5 From LP 3 6 7 From LP 4 Output H (Btu/lb ) Change H (Btu/lb) 56 258.1 809 Supply Temp (F) Target Temp (F) 202.1 98 442.8 354 455 491 380 479 305 174 379 432 261 171 381 235 1110 1054 Input H (Btu/lb) Supply Shift (F) Target Shift (F) Cold 123 467.8 2861744 Hot 466 355 334 3444389 Hot 354 309 346 292 3983700 Hot 407 267 146 297 266 4566511 Hot 272 241 142 968 231 174 675020 Hot 206 149 126 928 163 158 571554 Hot 138 133 30 Flow (lb/hr) 10085320 Stream Type 7.3 Millstone Unit III Heat and Mass Balance QuickTime™ and a decompressor are needed to see this picture. Figure 13: Millstone Unit III Heat and Mass Balance 31