University of Manitoba STANDBY GENERATOR Section 16613

advertisement
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
1.1
Page 1
RELATED WORK
.1
Concrete Formwork
.2
Mechanical Specification
.3
Electrical General Provisions
.4
Conduit
.5
Wire and Cable
.6
Circuit Breakers
Section 03100
Section 15000
Section 16050
Section 16111
Section 16120
Section 16182
1.2
SYSTEM DESCRIPTION
.1
Generator set consists of:
.1
diesel engine
.2
generator
.3
engine/generator control panel
.4
closed transition automatic transfer equipment and controls
.5
battery charger and batteries
.6
cooling system
.7
fuel supply system
.8
exhausts system
.9
structural steel mounting base
.2
Set designed to operate automatically as emergency standby source.
1.3
SUBMITTALS
.1
Submit shop drawings in accordance with Section 16050.
.2
Include:
.1
Engine: make and model, with specification data.
.2
Generator: make and model, with specification data.
.3
Battery: make, type and capacity.
.4
Battery charger: Make type and model.
.5
Prototype testing data.
.6
Automatic transfer switch: make, model and type.
.7
Engine/generator control panel: make and type of meters and controls.
.8
Governor: type and model.
.9
Radiator: type, model and capacities.
.3
Submit dimensioned drawings showing complete generating set mounted on steel base,
including interconnect points for fuel system, exhaust system, cooling system, and load leads.
.4
Submit performance characteristics based on SAE J134Q standard conditions of 100 KPA
and 25°C (77°F).
.5
Submit wiring diagrams showing interconnection points of all electrical components.
.6
Submit description of set operation including:
.1
Automatic starting and transfer to load and back to normal power, including time in
seconds from start of cranking until unit reaches rated voltage and frequency.
.2
Manual starting.
.3
Automatic shut down.
.7
.8
1.4
Submit prototype test certificate.
Submit factory test results to Consultant upon request.
OPERATION AND MAINTENANCE DATA
.1
Provide Operation and Parts Manual, as listed below, for incorporation into Maintenance
Manuals specified in Section 16050.
.1
Operation instructions - with description and illustration of all switchgear controls and
indicators and engine and generator controls.
.2
Parts book - that illustrate and list all assemblies, sub-assemblies and components, except
standard fastening hardware (nuts, bolts, washers, etc.).
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Req. #
Section 16613
Page 2
.3
.4
.5
.6
Preventative maintenance instructions - on the complete system that covers daily, weekly,
monthly, bi-annual and annual maintenance requirements and includes a complete lubrication
chart.
Troubleshooting chart - covering the complete generator set showing description of trouble,
probable cause, and suggested remedy.
Recommended spare parts list - showing all consumables anticipated shall be required during
routine maintenance and test.
Wiring diagrams and schematics - showing function of all electrical components.
1.5
MAINTENANCE MANUALS
.1
Provide maintenance materials and turn over to Owner.
.2
Include:
.1
2 fuel filter replacement elements.
.2
6 lube oil filter replacement elements.
.3
2 air cleaner filter elements.
.4
1 set of fuses for control panel.
.5
one battery hydrometer.
1.6
PROTOTYPE TESTING
.1
The power system consisting of prime mover, generator and all necessary controls shall be
tested as complete systems on representative engineering prototype models. The tests,
being potentially damaging to the equipment tested, shall not be performed on equipment
sold, but on separate prototype models. A certificate certifying that this prototype testing has
been performed shall be submitted along with submittal data for approval. These tests shall
have included, but not have been limited to:
.1
Maximum power level (maximum kW).
.2
Maximum motor starting capacity (maximum kVA).
.3
Structural soundness.
.4
Torsigraph analysis per MIL-STD 705B, Method 504.2. A torsional analysis shall be
calculated using data from actual tests by the engine-generator set manufacturer to
verify freedom from torsional stresses with ±10% of rated speed. Results shall be
made available to Consultant upon request. Actual torsional fatigue test shall be
performed on the complete prototype generator-set. Calculations based on engine
and generator data separately are not acceptable.
.5
Engine-alternator cooling air flow.
.6
Transient response and steady-state governing.
.7
Alternator temperature rise by imbedded thermocouples and by resistance method
per NEMA MG1-22.40.
.8
Harmonic analysis and voltage wave form deviation per MIL-STD-05B, Method 601.4.
.9
Three-phase short-circuit test for mechanical and electrical strength. With system
operating at rated volts, amps, power factor, and speed, the generator terminals shall
be short circuited ten times on all three phases for a duration of thirty seconds.
Generator set shall build up and perform normally without manual interventions of any
kind such as re-setting of circuit breakers or other tripping devices when the short
circuit is removed.
.10
Failure mode test for voltage regulator. With generator set operating at no load, rated
speed and voltage, the AC sensing circuit to the regulator shall be disconnected for a
period of at least one hour. The generator set shall be fully operative after the test,
and without evidence of any kind of damage.
.11
Endurance testing at rated load and speed is required without significant damage or
failures of electrical or mechanical components.
1.7
FACTORY TESTING
.1
Before shipment of equipment, factory test generator set including engine, alternator,
Date revised November 30, 2012
University of Manitoba
Req. #
Section 16613
Page 3
.2
.3
.4
.5
.6
1.8
STANDBY GENERATOR
control panels, transfer equipment and accessories for performance and proper
functioning of control and interfacing circuits.
Test procedures shall include:
.1
Load test at rated load and power factor for a continuous 2 hour time period
to observe engine blow by, slobber, combustion gas leaks, inlet air leaks,
excessive vibration and unusual noise.
.2
Single step load pickup per NFPA 76A.
Transient response and steady state governing.
Alternator temperature rise by resistance method.
Functional compatibility between generator set controls and transfer switch controls
(start, transfer, retransfer, stop, with all time delays).
Fuel consumption.
FIELD TESTING
.1
Prior to the official field test, the following related items shall be completed and operational:
.1
The ventilation system and related damper controls for the generator room.
.2
The fuel tank, float sensors and related pumps.
.3
The insulation on the exhaust system.
.4
The remote radiator, related piping and electric fan with controls.
.5
The door to the generator room shall be in place, complete with hardware.
.6
Sealing of the generator room from the other rooms in the building.
.7
The complete standby power system shall be initially started and checked out for
operational compliance by factory-trained representatives of the manufacturer of the
generator set. The initial start-up shall be performed at least two days in advance of
the Field Test to allow the factory representative time to correct any part of the system
which may not be functioning properly.
.2
Upon completion of the above items the standby power system shall be ready for a Field Test
which shall be performed by the generator set supplier and witnessed by the Consultant.
.3
Notify the Consultant 6 working days in advance of the Field Test.
.4
Test procedure:
.1
Prepare blank forms and check sheet with spaces to record data. At top of first sheet
record:
.1
date
.2
generator set serial number
.3
engine make, model, serial number
.4
alternator make, model, serial number
.5
voltage regulator make and model
.6
rating of generator set kW, kVA, V, A, RPM, Hz.
.2
Mark check sheet and record data on forms in duplicate as test proceeds.
.3
Submit test results with the Maintenance Manuals.
.5
With a portable resistive load bank at 100% rated load of generator, operate set for 6 hours,
taking readings at 30 minute intervals, and 110% rated load for 1 hour and record following:
.1
time of reading
.2
running time
.3
ambient temperature in °C (°F)
.4
lube oil pressure in kPa
.5
lube oil temperature in °C (°F)
.6
engine coolant temperature in °C (°F)
.7
exhaust stack temperature in °C (°F)
.8
alternator voltage, Phase A, B, C, AN, BN, CN
.9
alternator current, Phase A, B and C
.10
power in kW
.11
frequency in Hz
.12
power factor
Date revised November 30, 2012
University of Manitoba
Req. #
STANDBY GENERATOR
Section 16613
Page 4
.6
.7
.8
.9
.10
.11
.12
.13
.13
battery charger current in A
.14
battery voltage
.15
alternator stator temperature in °C (°F)
Disconnect load bank and reconnect generator to the building distribution.
Demonstrate automatic starting of set and automatic transfer of load on failure of normal
power and transfer on resumption of normal power.
Demonstrate operation of manual bypass switch in both directions.
Demonstrate automatic cool down and shut down of engine on resumption of normal power.
Demonstrate that battery charger reverts to high rate charge after cranking. Demonstrate two
minute total cranking capacity and recharge cycle.
Demonstrate low oil pressure and high engine temperature shutdowns.
Simulate loss of normal power by de-energizing main distribution feeder breaker. Allow
generator to operate with building loads. R-energize main distribution feeder breaker. Note
operation of transfer switch and controls during the simulated power failure test.
All testing shall conform to C282-M89 Clause 9 - total of 6 hours.
1.9
GUARANTEE
.1
After the site testing is completed and all systems are operating satisfactorily, the system
supplier shall submit a certification report and letter stating that the complete standby
generator installation complies with the requirements of the manufacturer.
.2
The standby generator equipment, as supplied and installed, shall be guaranteed for a period
of two years from date of acceptance and turnover to the Owner.
1.10
ON-SITE INSTRUCTION
.1
The generator set supplier shall provide on-site instruction to familiarize personnel with the
operational techniques and preventative maintenance procedures for the system.
2.1
SYSTEM DESCRIPTION
.1
The standby diesel electric generating system shall include, but not necessarily be limited to,
the following:
.1
diesel engine - generator set as described herein
.2
starting batteries exhaust silencer and manifold, flexible fuel lines, etc.
.3
engine/generator control and console and output disconnect breaker
.4
transfer switch arrangement shall transfer the load from normal supply to emergency
supply.
.5
all necessary controls and devices to provide a complete operable automatic standby
power system.
2.2
SYSTEM OPERATION
.1
Upon failure of the normal power supply the engine-generator set shall automatically start.
Once generator voltage and frequency are within acceptable limits, the transfer switch shall
operate to allow emergency power to be supplied to the emergency loads. Upon return of the
normal power the load shall be retransferred to the normal power supply and the enginegenerator set shall cool down and stop.
.2
Engines shall start, achieve rated voltage and frequency, and transfer to the load within ten
seconds of loss of normal power.
2.3
ENGINE
.1
Diesel engine: to British Standard Specification BS649-1958.
.2
Prime mover: full diesel 4 cycle, turbo charged, synchronous speed, 1800 rpm. Engine shall
be capable of recovery from 0% to 100% instantaneous step load with maximum transient
speed deviation of 10% (6 Hz) and recover to rated speed within 5 seconds.
.3
Capacity: engine shall be capable of driving the specified generator on a continuous standby
Date revised November 30, 2012
University of Manitoba
Req. #
Section 16613
Page 5
.4
.5
.6
.7
.8
.9
.10
.11
.12
.13
.14
2.4
STANDBY GENERATOR
basis for duration of normal utility source interruptions for ambient conditions of 30°C (86°F),
101 kpa barometric pressure and 300 ft. elevation.
Cooling system: engine shall be liquid cooled via engine mounted radiator, engine driven fan
and engine driven water pump. Provide a 50% ethylene glycol antifreeze/water coolant.
Cooling system shall maintain manufacturer’s recommended engine temperature range at
10% continuous overload in ambient temperature of 38°C (100°F).
Engine coolant heaters: engine mounted, jacket water heater type, thermostatically
controlled, 120V AC, single phase power liquid coolant heaters shall allow engine to start in
room ambient temperature of 0°C (32°F).
Fuel system: solid injection, mechanical fuel transfer pump with hand primer, replaceable
element fuel filters, fuel rack solenoid energized when engine running, fuel rail line check
valve and fuel return line check valve. Fuel system shall be complete with all necessary
valves, restrictors, check valves, seals, etc., as required and recommended by the supplier to
suit the actual site fuel system. Engine shall operate on Number 2 diesel fuel.
Governor: Electronic to provide isochronous regulation.
Lubrication system: pressure lubricated by engine driven oil pump with pressure regulation
valve, replaceable element lube oil filter, lube oil cooler and engine sump drain valve. Engine
shall have an oil level indicator, oil pressure gauge and low oil pressure shutdown switch.
Air cleaners: large capacity replaceable dry element type.
Starting system:
.1
Positive shift, gear engaging stator 24V DC.
.2
Cranking limiter to provide 3 cranking periods of 10s duration, each separated by 5s
rest.
.3
Lead acid, 24V heavy duty batteries with sufficient capacity to crank engine for 3
minutes at 0°C (32°F) without using more than 25% of ampere hour capacity.
Provide corrosion resistant mounting rack.
.4
Battery charger: constant voltage, solid state, two stage from trickle charge at
standby to boost charge after use.
Regulation: +1% output for +10% input variation. Equipped with DC voltmeter, DC ammeter
and ON-OFF switch.
Engine instrument panel: shall include lube oil pressure gauge, lube oil temperature gauge,
coolant temperature gauge, running time meter.
Guards shall be integrally mounted on unit to protect personnel from hot and moving parts.
Drip tray.
Engine shall have water jacketed exhaust manifolds.
GENERATOR
.1
Standard: to CSA C22.2 No. 100 and NEMA MGL.
.2
Rating: 347/600V, 3 phase, 4 wire, 60 Hz, at 0.8 pf with 105°C (221°F) temperature rise, 1800
RPM. Output capacity shall be as indicated on the drawings.
.3
Generator: single-bearing, four-pole, drip-proof construction, synchronous type, revolving
field, with direct drive centrifugal blower for cooling and minimum noise. Stator shall be
skewed design and twice impregnated with high-temperature polyester varnish.
Generator shall be directly connected to engine flywheel housing. Rotor shall be driven
through a flexible coupling to insure permanent alignment. Rotor shall have amortisseur
windings, and be vacuum impregnated with 100% solid epoxy resin, and shall be dynamically
balanced.
.4
Exciter: shall include a DC stator field with three-phase rotor, full wave, rectified, with heavyduty encapsulated silicon diodes mounted on the common rotor shaft and sized for maximum
motor starting.
.5
Insulation: EEMAC Class F.
.6
Voltage regulator: temperature compensated solid state, silicon controlled rectifiers with
phase controlled sensing circuit:
.1
Frequency regulation ±3% no load to full load.
Date revised November 30, 2012
University of Manitoba
Req. #
Section 16613
Page 6
.7
.8
2.5
STANDBY GENERATOR
.2
Steady state voltage regulation ±1% no load to full load.
Voltage waveform deviation factor and telephone influence factor shall meet NEMA
standards. Total harmonic content of the output waveform shall not exceed 5%.
A permanent magnet generator shall provide excitation power to the AVR to provide immunity
from voltage distortion from non-linear loads.
CONTROL PANEL
.1
Provide a unit mounted control console that is factory built, wired, tested and shock-mounted
by the unit manufacturer. Control console shall be a rigid, ‘sprinkler proof’, metal enclosure,
mounted on the generator end of the set, containing all devices as specified herein, and as
required for described functions. Control console shall include a control section and control
panel with required access to all components. Control wire shall have termination
identification on each wire for ease of tracing. Control wires which run between generator set
controls and automatic transfer switches shall have identical termination identification on both
ends. Lamacoid nameplates shall be provided to identify each device or function.
.2
Instruments:
.1
Analogue indicating type 2% accuracy, rectangular scale, flush panel mounting:
.1
voltmeter: AC, scale 0 to 600V
.2
ammeter: AC, scale 0 to 600 amps
.3
frequency meter: scale 55 to 65 Hz.
.2
Voltmeter selector switch, rotary, panel mounting, round notched handle, four
position, labeled “OFF-AB-BC-CA”.
.3
Ammeter selector switch, rotary, maintained contacts, panel mounting, designed to
prevent opening of current circuits, round notched handle, four position labeled “OFF, APhase, B-Phase, C-Phase”.
.4
Fuses for indicating instruments: miniature, glass, fast acting.
.5
Oil pressure gauge.
.6
Coolant temperature gauge.
.7
Running time (hour) meter.
.3
Controls:
.1
Engine run-stop-auto switch.
.2
Engine emergency stop button plus provision for remote emergency stop button.
.3
Lamp test switch and reset switch.
.4
Voltage adjusting control.
.5
Frequency adjusting control.
.4
Automatic shut-down lights and alarms:
.1
Engine over crank (shutdown after 3 cranking attempts).
.2
Engine over speed shutdown at 115%).
.3
High engine temperature (shutdown at 120%).
.4
Engine - low lube oil pressure (shutdown at 40%).
.5
Short circuit and over current.
.6
Low battery voltage continuously monitored even when engine not running. Auto
reset alarm.
.7
Alternator over voltage and under voltage (shutdown at 115% and 85% sustained for
5 seconds).
.8
Low fuel level (alarm: connect to the building management system and remote
annunciator).
.9
Low coolant temperature (alarm at 20°C to 30°C) (68°F to 86°F).
.10
Auxiliary contact for “not in auto” (alarm).
.11
No battery voltage: provide a separate relay audible device and 120V AC power
source.
.12
Common alarm contacts (connect to the building management system and remote
annunciator).
.5
Remote annunciator:
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 7
.1
.6
2.6
Provide a remote annunciator with common alarm signal, low fuel alarm signal and
silence switches. Locate in Engineer’s office, unless otherwise indicated.
.2
Wire and connect the following signals to Fire Alarm System Annunciator via Remote
Addressable Monitoring Modules:
.1
Low Fuel Alarm
.2
Generator Running
.3
Common Alarm
Auxiliary contacts:
.1
Three sets of N/O and N/C contacts for remote annunciator connection and control of
mechanical ventilation within the generator room.
AUTOMATIC TRANSFER SWITCH
.1
To be ASCO 7000 Series closed transition transfer.
.2
Include two-single, 4-pole contactors mounted on common frame, in double throw
arrangement, mechanically and electrically interlocked. Three switch positions shall be
provided: normal, emergency and neutral.
.3
Rated: [347/600V], 60 Hz. Current rating as indicated.
.4
.5
.6
.7
.8
.9
.10
.11
Main contacts: silver surfaced, blow on construction protected by arc disruption means
including separate arcing contacts, arc splitters and blow out coils for load current.
Switch and relay contacts, coils, spring and control elements accessible for inspection and
maintenance from front of panel without removal of switch panel or disconnection of drive
linkages and power conductors.
Auxiliary contacts: to initiate emergency generator start-up upon failure of normal power.
Fault withstand rating: 42 kA symmetrical.
Selector switch - three position “Test”, “Auto”, “Manual”.
.1
Test position - normal power failure simulated. Engine starts and automatic transfer
takes place. Return switch to “Auto” to retransfer and stop the engine as per the
control sequence.
.2
Auto position - allows automatic operation of transfer switch to emergency upon
failure of normal power; retransfers on return of normal power and shuts down
engine, as per the control sequence.
.3
Manual position - transfer switch may be operated by manual handle but transfer
switch will not operate automatically and engine will not start.
Control transformers: dry type with a fused 24V secondary to isolate control circuits from:
.1
Normal power supply.
.2
Emergency power supply.
Relays: continuous duty, industrial control type, with wiping action contacts rated 10A
minimum:
.1
Voltage sensing, one per phase, solid state type: adjustable drop out (75%) and
pickup (95%) close differential, 2V minimum under voltage, over voltage protection.
.2
Time delay on engine starting to override momentary power outages or dips:
adjustable from 1 to 6s; set at 3 seconds.
.3
Time delay to initiate signal to transfer from standby to normal power, once normal
power is available: adjustable 5 minutes to 30 minutes; set at 10 minutes.
.4
Time delay on transfer from the neutral position to normal power to allow the residual
voltage on motor loads to decay to a safe level before retransfer: adjustable 0.5
seconds to 5 seconds; set at 1.0 seconds (ASCO switches shall be provided with an
in-phase monitor for retransfer operation).
.5
Time delay for engine cool-off shall permit standby set to run unloaded after
retransfer to normal power: adjustable 5 minutes to 30 minutes. Set at 5 minutes.
.6
Frequency sensing, shall prevent transfer from normal power supply until frequency
of standby unit reaches preset value.
Pilot light shall indicate switch position, green for normal, red for emergency.
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Req. #
Page 8
.12
.13
2.7
Section 16613
Three normally open and three normally closed auxiliary contacts.
Sheet steel “sprinkler proof” enclosure.
BYPASS ISOLATION SWITCH
.1
As shown on the drawings, specified transfer switches shall be included in a factory assembly
with bypass-isolation switch equipment. The bypass-isolation switch shall provide a safe
means for manually bypassing the transfer switch from either source (Normal or Emergency)
to the load, while under load if necessary, and isolating the transfer switch from both sources
for maintenance or repair. Two source bypass is a requirement of NFPA 110. Designs which
bypass to only one source are not acceptable under this specification.
.2
By-pass isolation switch equipment shall be UL listed per Standard 1008 CSA Certified with
continuous current rating, voltage and frequency ratings, and withstand and closing ratings
equal to the transfer switch ratings at the specified conditions of ambient temperature,
humidity and altitude.
.3
Bypass switch shall be a fully rated, manually operated switch, rated for the same loads as
the automatic transfer switch.
.4
Positive mechanical interlocks shall prevent all possible source to source connections.
Designs depending on electrical interlocks to prevent source to source connections, or which
intentionally interconnect the sources are not acceptable.
.5
Isolating contacts in the draw out isolation mechanism shall allow the automatic transfer
switch to be separated electrically and mechanically. The isolation mechanism shall be
interlocked so that either the transfer switch must be bypassed or the transfer switch must be
open before the mechanism shall permit transfer switch isolation.
The draw out mechanism shall provide for three-position operation; CONNECTED, TEST and
ISOLATED. These positions shall be shown on the draw out position indicator. In the CONNECTED
position isolation contacts shall be fully engaged and closed with the automatic transfer switch control
cable connected.
In the TEST position isolation contacts shall be open, with the transfer switch control cable connected.
The TEST position shall allow operational testing of the automatic transfer switch and the controls
without power disruption to the load.
In the ISOLATED position the automatic transfer switch and the control shall be completely isolated
from all power sources. In this position safety shutters shall close to cover bypass power terminals for
operator safety.
Once isolated, the automatic transfer switch shall be capable of being completely withdrawn from the
cabinet for inspection or service without disconnection of power cables.
When re-installing the transfer switch from the isolated position, the isolation mechanism shall not
permit connection of the transfer switch unless it is in the open position, and shall automatically open
the transfer switch if necessary regardless of the availability of electrical power. When the transfer
switch is fully connected and locked in place, the mechanism shall move the transfer switch from the
open position to the closed position on the same source as the bypass switch.
.6
2.8
The free-standing enclosure shall be a UL listed Type 1 (NEMA 1) welded construction
sprinklerproof steel cabinet. Wire bend space shall comply with Canadian Electrical Code for
the maximum size and number of conductors the terminal lugs will accept. A key locking
handle shall be provided. Front panel mounted controls shall require use of a key.
GENERATOR OUTPUT DISCONNECT
.1
Provide a [600V] output circuit breaker, complete with shunt trip as indicated, to disconnect
the output circuit of the generator.
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 9
2.9
CHARGER AND BATTERIES
.1
Provide solid state, duel rate, automatic battery charger with voltmeter and ammeter.
.2
Provide a battery rack and 24V DC lead acid battery and cables.
2.10
STRUCTURAL STEEL MOUNTING BASE
.1
Complete generating set mounted on structural steel base of sufficient strength and rigidity to
maintain proper alignment between components during transportation, installation and under
operating conditions. Include vibration isolators to isolate moving parts from the steel base.
Steel spring isolators shall be provided on the base to provide suitable mounting to a level
surface.
2.11
EXHAUST SYSTEM
.1
Include heavy duty, critical type, horizontally mounted exhaust silencer, with condensate drain,
plug and flanged couplings.
.2
Include suitable length of heavy duty flexible exhaust hose with flanged couplings for
connection between exhaust manifold and exhaust line.
2.12
FUEL SYSTEM
.1
Include flexible connections for connecting fuel lines to engine. Include auxiliary float
controlled fuel reservoir on engine to accommodate mounting of the main fuel tank above line
of injectors (if applicable).
.2
Provide a day tank with float switch of minimum capacity as recommended by generator set
manufacturer. Tank shall be new and unused and shall not be galvanized.
.3
A 200 gallon main fuel tank, complete with rack, shall be provided by Division 15. The tank
shall be provided with a float switch for low level alarm indication (set float at point where 3/4
hour of fuel is left). The low level alarm shall be connected to an audible and visual indicator
on the engine control panel and remote annunciator. The audible indicator at the remote
annunciator shall have a silence switch. The tank shall also be provided with an exterior
weatherproof high level alarm, complete with weatherproof silence switch, activated by a high
level float switch for filling purposes.
.4
Fuel transfer pumps that may be required shall be provided by Division 15. Pumps shall be of
sufficient lift and capacity to deliver fuel in excess of maximum fuel consumption rate of the
engine from the main storage tank to the day tank. Day tank float switch shall cycle pumps to
control fuel level in day tank.
2.13
COOLING SYSTEM
.1
Remote mounted industrial radiator, complete with electric fan. Assemble unit on steel frame.
Include vibration isolators. Size of radiator, fan and motor shall be compatible with cooling
capacity required.
.2
Provide an LCL sensor to shutdown the engine in the event of a total loss of coolant.
2.14
ACCEPTABLE MANUFACTURERS
.1
Caterpillar.
.2
Onan.
.3
Midwest Detroit Diesel.
.4
Kohler.
2.15
EQUIPMENT IDENTIFICATION
.1
Provide equipment identification in accordance with Section 16050.
.2
Control panel and transfer switch:
.1
Size 5 nameplates for controls.
.2
Size 5 nameplates for meters, alarms, indicating lights.
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 10
2.16
FABRICATION
.1
Shop assemble generating unit including:
.1
base
.2
engine
.3
generator
.4
control panel
.5
remote radiator.
2.17
FLUIDS
.1
Provide lube oil and antifreeze.
.2
Provide Number 2 diesel fuel, as recommended by the manufacturer.
3.1
INSTALLATION
.1
Locate generating unit, remote radiator and all associated equipment and install as indicated.
.2
Wire and connect all equipment and controls.
.3
Installation of exhaust fan, ventilating air duct system, motorized dampers on air intake and
discharge grilles, and room temperature controls by Division 15.
.4
Installation of main fuel tank, pumps and supply, vent and fill lines by Division 15. Wire and
connection of float controls by Division 16.
.5
Installation of silencer, exhaust piping and high temperature insulation by Division 15.
Silencer shall be mounted such that its weight is not supported by the engine. Condensate
drain on the silencer shall be connected to the nearest floor drain by Division 15.
.6
Provide branch circuit wiring for block heaters, battery charger, fuel transfer pumps and
remote radiator fan.
.7
Provide all required fuel for testing. Top up fuel tank upon completion of testing.
.8
Install, wire and connect remote annunciator.
.9
Installation shall meet the requirements of CSA Standard C282-M89 and CSA Standard
B139.
.10
Coordinate with the General Contractor to mount the generator set on a 4" (100 mm) high
concrete housekeeping pad.
.11
Coordinate installation with site conditions. Disassemble and reassemble as required to place
genset as indicated.
3.2 TESTING
.1
.2
Furnish all necessary equipment, labor, instruments, etc. as needed to perform testing as
outlined in Section 1.8.
Verification Report.
EMERGENCY ELECTRICAL POWER SUPPLY
FOR BUILDINGS
CSA - C282 - M91
VERIFICATION REPORTS
(This form shall be completed by the manufacturer/supplier of the equipment required under the scope of this
standard.)
Building Address:
_________________________________________________
Emergency Power System Supplier/Manufacturer:
Company Name:
___________________________________________________
Company Address:
_______________________________________________
Name of the person conducting the test: _________________________
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 11
Telephone: ___________________
Date:
Signature:
______________________
____________________________________________________________
Generator Data:
__________________________________________________
__________KW, __________ V, __________ Phase, __________ Wire
Summery (every line shall have the appropriate marking in the space provided).
YES
____
NO
____
Emergency Generator is now fully functional in
conformance with M282-M91 applicable clauses.
____
____
All relevant features of the suppliers’ equipment and respective wiring and
installation have been checked and tested in accordance with attached checklist/test record.
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 12
EMERGENCY ELECTRICAL POWER SUPPLY
CSA-C282-M91-VERIFICATION REPORT
CHECKLIST/TEST RECORD
(Every line shall have the appropriate marking in the space provided.)
STATUS
EQUIPMENT, WIRING & INSTALLATION COMPONENTS Shall be CHECKED
OR TESTED
CLAUSE
NO.
Conformances with NFPA Standard 37-1984 “Installation and use of stationary
combustion engines and gas turbines”
4.3
Conformance of installation, wiring, protection and grounding of the electrical
equipment with CSA Standard C22.1, Canadian Electrical Code, Part 1
4.4
Conformance with CSA B139-1976 “Installation Code for Oil Burning Equipment”
4.5
Location of generator set in conformance with the Manitoba Building Code
5.2
Vibration
5.6
Ventilation
5.7
Temperature
5.8
Unit Equipment for emergency lighting
5.11
Control Sequence
5.12
Engine horsepower rating
6.1-6.2
Fuel supply
6.4
Engine control panel
6.5
Cranking cycle
6.6
Storage batteries
6.7.1
Compressed air pressure
6.7.2
Generator construction in conformance with CSA Standard C22.2 #100
7.1
Generator performance
7.2
Exciter
7.4
Voltage regulator
7.5
YES NO
Date revised November 30, 2012
University of Manitoba
STANDBY GENERATOR
Section 16613
Req. #
Page 13
Voltage build-up
7.6
Overcurrent protection
7.7
Generator controls
7.8
Transfer switch RE: CSA Standard C22.2 No. 178
8.1-8.4
Manual by-pass switch
8.5
Initial installation performance test
9.0
Above checklist shall be completed before Letter of Acceptance will be issued for project.
Date revised November 30, 2012
Download