M1115NL Radios – Checking AI1 and AI2 inputs. 1) Select the IP address of the radio. It’s written on the side. Such as 192.168.0.171. It will ask for user name and password. The defaults are “user” and “user”. 2) Select I/O Configuration. Enter in Register = 30001, Count = 2, and Select READ. 3) The number that is returned will be a number between 0 and 49,152. The value is based on the chart below. mA Input #1 (38001) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Example Values Span Zero M1115NL Results (30001) 2048 8192 8192 2048 8192 10240 2048 8192 12288 2048 8192 14336 2048 8192 16384 2048 8192 18432 2048 8192 20480 2048 8192 22528 2048 8192 24576 2048 8192 26624 2048 8192 28672 2048 8192 30720 2048 8192 32768 2048 8192 34816 2048 8192 36864 2048 8192 38912 2048 8192 40960 2048 8192 43008 2048 8192 45056 2048 8192 47104 2048 8192 49152 2048 8192 51200 4) You can read the digital values for all (8) Di’s. Input Register = 10001, Count = 8, and Select READ.