123 Alpha Drive Pittsburgh, Pennsylvania https://www.google.com/maps/place/150+Gamma+Dr/@40.4997521,79.8681269,18z/data=!4m2!3m1!1s0x8834ecdbc348bd5f:0xd10a14f6b42509 a0 Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Pittsburgh, Pennsylvania 123 Alpha Drive Background Location: Pittsburgh, Pennsylvania Introduction Building Use: Existing Mechanical System • Warehouse Storage • Laboratory Space • Offices Variable Refrigerant Flow System Cost Analysis Emissions Analysis Footprint: 74,900 square feet Acoustical Design Ceiling Height: • Offices: 9’ • Warehouse: 22’ 6” Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado https://www.google.com/maps/place/150+Gamma+Dr/@40.4997521,79.8681269,18z/data=!4m2!3m1!1s0x8834ecdbc348bd5f:0xd10a14f6b42509 a0 Renovated: 2012 Design Conditions Pittsburgh, Pennsylvania 123 Alpha Drive Outdoor Design Conditions Introduction Indoor Design Conditions Existing Mechanical System Offices & Lab Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado OA Dry Bulb (°F) OA Wet Bulb (°F) Summer Design Cooling Winter Design Heating 89 °F 2.0 °F 72 °F .3 °F Warehouse & Storage & Packaging Maintenance Cooling Set Point 70 °F 85 °F 95 °F Heating Set Point 55 °F 55 °F 60 °F Relative Humidity 45% - - Pittsburgh, Pennsylvania 123 Alpha Drive Office/Lab Space Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Existing Mechanical System Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Warehouse and Storage - 6 single zone CAV rooftop units (RTUs) - Primarily electric resistance heat - CO2 preheat conditioning option available - 8 air handling units (AHUs) - CO2 radiant floor cooling and heating - Makeup air handling unit Annual Load Simulation Pittsburgh, Pennsylvania 123 Alpha Drive Monthly Energy Consumption 350000 Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Energy Consumed (kWh) Introduction 300000 250000 Advisor: Dr. Stephen Treado HVAC 18% 200000 150000 100000 50000 0 Mechanical Option | Spring 2014 Energy Consumption By Use Lighting 46% Electrical Equipment 36% Annual Load Simulation Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Annual Energy Consumption By Use Energy Consumption By Use Existing Mechanical System Variable Refrigerant Flow System HVAC: 595,045 kWh Lighting: Cost Analysis Emissions Analysis 2,657,011 kWh Electrical Equipment: 3,252,057 kWh Acoustical Design Total Annual Energy Consumption: Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado HVAC 18% 6,5041,143 kWh Lighting 46% Electrical Equipment 36% Energy Cost and Consumption Pittsburgh, Pennsylvania 123 Alpha Drive Electrical Cost by Use Introduction $40,000 Annual Cost per Unit Floor Area $35,000 Existing Mechanical System $25,000 Lighting: Cost Analysis Emissions Analysis $30,000 $0.96/ft2 Cost Variable Refrigerant Flow System HVAC: $2.04/ft2 Electrical Equipment: $1.89/ft2 Acoustical Design Total Annual Energy Cost: $366,744 Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado $20,000 $15,000 $10,000 $5,000 $0 Electrical Equipment Lighting HVAC Pittsburgh, Pennsylvania 123 Alpha Drive Variable Refrigerant Flow System System Components Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Advantages • • Outdoor/Indoor Condensing Unit 3 pipe system (suction, liquid, discharge gas) • Mode Change Unit (MCU) • 2 pipe system from MCU to fan coil unit • • Lower energy costs • Lower CO2e emissions • Simultaneous heating and cooling • Precise and occupant control capabilities Disadvantages Indoor fan coil units • Expensive first costs • Requires DOAS system Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado http://y.asi.ph/note/commissioning-daikin-vrv-systems/ VRF System Layout Pittsburgh, Pennsylvania 123 Alpha Drive Introduction System Layout Restrictions Existing Mechanical System Variable Refrigerant Flow System • Piping Length – 656 feet maximum Key VRF System 1 Cost Analysis • External Static Pressure – 1” maximum VRF System 2 Emissions Analysis • Condensing Unit Elevation – 360 feet maximum VRF System 3 Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 123 Alpha Drive Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Condensing Unit Quantity Pittsburgh, Pennsylvania Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Samsung DVM S Series Condensing Unit Requirements Number of Condensing Units Needed One Size (tons) 6-12 Two 14-24 VRF System 1 2 3 Size (tons) 11.5 17.2 12.5 Number of Condensing Units Needed One Two Two Three 26-36 Indoor Fan Coil Unit Selection Pittsburgh, Pennsylvania 123 Alpha Drive 1-Way Cassette Terminal Unit Introduction • Located at edges of room ceiling Existing Mechanical System Variable Refrigerant Flow System Cost Analysis • Diffuses in one direction 4-Way Cassette Terminal Unit • Located in central area of ceiling 1 Way Cassette Terminal Unit Source: Samsung DVM S Series Catalog Emissions Analysis Acoustical Design Conclusion Alexander Radkoff 4 Way Cassette Terminal Unit Source: Samsung DVM S Series Catalog • Distributes air in four directions High Static Pressure Duct Unit • Up to .99 in wg. external static pressure Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado • Can condition multiple spaces at a time High Static Pressure (HSP) Duct Unit Source: Samsung DVM S Series Catalog VRF System Selection Pittsburgh, Pennsylvania 123 Alpha Drive VRF System 1 Introduction Existing Mechanical System 12 ton Outdoor Condensing Unit (1) Variable Refrigerant Flow System Cost Analysis CU-1 Mode Change Units (3) Emissions Analysis Acoustical Design 4 Way Cassette FCU (6) Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 1 Way Cassette FCU (9) Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Existing Mechanical System VRF System Selection VRF System 2 6 ton Outdoor Condensing Unit (1) 10 ton Outdoor Condensing Unit (1) Variable Refrigerant Flow System Cost Analysis Mode Change Units (4) Emissions Analysis Acoustical Design 4 Way Cassette FCU (12) Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 1 Way Cassette FCU (7) Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Existing Mechanical System VRF System Selection VRF System 3 6 ton Outdoor Condensing Unit (1) 10 ton Outdoor Condensing Unit (1) Variable Refrigerant Flow System Cost Analysis Mode Change Units (3) Emissions Analysis Acoustical Design 4 Way Cassette FCU (3) Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 1 Way Cassette FCU (4) High Static Pressure Unit (2) Dedicated Outside Air System Pittsburgh, Pennsylvania 123 Alpha Drive Semco FV-2000 Fresh Air Preconditioner Design Conditions: Cooling Season Introduction Existing Mechanical System Variable Refrigerant Flow System • 3 Angstrom Total Energy Wheel Outdoor Airstream • Parallel system to VRF system • Manages humidification and de-humidification Cost Analysis Emissions Analysis Airflow (cfm) Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Supply Airstream Ext. Static Motor Brake Pressure (in Horsepower wg.) Fan Speed (RPM) Supply Air 1,250 1.50 1.00 1723 Exhaust Air 1,175 .75 .64 1413 Dry Bulb (°F) : Wet Bulb (°F): Enthalpy (BTU/lb): Dry Bulb (°F) : 80.2 Wet Bulb (°F): 65.7 Enthalpy (BTU/lb): 30.5 Airflow (CFM): 1,250 95.0 75.0 38.4 Exhaust Airstream Dry Bulb (°F) : Wet Bulb (°F): Enthalpy (BTU/lb): Return Airstream Dry Bulb (°F) : 75.0 Wet Bulb (°F): 62.0 Enthalpy (BTU/lb): 27.8 Airflow (CFM): 1,175 90.8 72.5 36.1 Advisor: Dr. Stephen Treado Source: Semco FV 2000 Catalog Dedicated Outside Air System Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Existing Mechanical System Variable Refrigerant Flow System Outdoor Airstream Sensible Supply Efficiency: 74% Cost Analysis Latent Supply Efficiency: 74% Emissions Analysis Supply Air Pressure Loss: .36 Acoustical Design Conclusion Alexander Radkoff Design Conditions: Cooling Season Efficiency and Static Pressure Loss Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Exhaust Air Pressure Loss: .33 Dry Bulb (°F) : Wet Bulb (°F): Enthalpy (BTU/lb): 95.0 75.0 38.4 Exhaust Airstream Dry Bulb (°F) : Wet Bulb (°F): Enthalpy (BTU/lb): 90.8 72.5 36.1 Supply Airstream Dry Bulb (°F) : 80.2 Wet Bulb (°F): 65.7 Enthalpy (BTU/lb): 30.5 Airflow (CFM): 1,250 Return Airstream Dry Bulb (°F) : 75.0 Wet Bulb (°F): 62.0 Enthalpy (BTU/lb): 27.8 Airflow (CFM): 1,175 Controls Pittsburgh, Pennsylvania 123 Alpha Drive BACnet Gateway Building Management System Occupant Controls Introduction • Can connect up to 256 indoor units/16 outdoor units • MWR-WE10N Wired Remote Controller Variable Refrigerant Flow System • Weekly/Daily Scheduling • Can control up to 16 indoor units and ERV Cost Analysis • Temperature limitations • Operation mode • ERV operation mode and fan speed • Temperature setting (limited by BACnet) • Zone Management • ERV operation and fan speed (limited by BACnet) Existing Mechanical System Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Cost Analysis Pittsburgh, Pennsylvania 123 Alpha Drive VRF System Monthly HVAC Energy Consumption Introduction Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Energy Consumption (kWh) 7000 Existing Mechanical System Alexander Radkoff VRF Zone Annual Energy Consumption By Use 6000 5000 4000 3000 2000 1000 0 Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado HVAC 9% Lighting 51% Electrical Equipment 40% Cost Analysis Pittsburgh, Pennsylvania 123 Alpha Drive VRF System Zones Electrical Cost by Use Introduction Annual HVAC Cost Per Unit Area: $4,500 $4,000 Existing Mechanical System $0.71/ft2 Cost Analysis Emissions Analysis Total Annual HVAC Energy Cost: $9,001 Conclusion Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado $2,500 $2,000 $1,500 $1,000 Acoustical Design Alexander Radkoff $3,000 Cost Variable Refrigerant Flow System $3,500 $500 $0 Electrical Equipment Lighting HVAC Energy Consumption Comparison Pittsburgh, Pennsylvania 123 Alpha Drive Original Design Annual HVAC Energy Consumption: 14,000 Existing Mechanical System 85,148 kWh Variable Refrigerant Flow System Cost Analysis Emissions Analysis VRF System Annual HVAC Energy Consumption: Acoustical Design 72,316 kWh Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Monthly HVAC Energy Consumption Energy Consumption (kWh) Introduction 12,000 10,000 8,000 6,000 4,000 2,000 0 Difference: 12,832 kWh Original VRF System Energy Cost Comparison Pittsburgh, Pennsylvania 123 Alpha Drive Original Design Annual HVAC Energy Cost: Monthly HVAC Energy Cost Introduction 2,500 $16,416 Existing Mechanical System VRF System Annual HVAC Energy Cost: Cost Analysis $9,001 Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Advisor: Dr. Stephen Treado 1,500 1,000 500 Difference: $7,415 Mechanical Option | Spring 2014 Cost ($) Variable Refrigerant Flow System 2,000 0 Original VRF System Mechanical First Costs Comparison Pittsburgh, Pennsylvania 123 Alpha Drive Original HVAC vs. VRF System First Costs Introduction Existing Mechanical System Materials Labor Total Original HVAC System $144,663.88 $79,733.00 $222,396.88 Emissions Analysis VRF System $327,702.26 $20,690.81 $348,393.07 Acoustical Design Difference -$178,038.38 $59,042.19 -$118,996.19 Variable Refrigerant Flow System Cost Analysis Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Materials Difference: +118% Labor Difference: -74% Total First Cost Difference: +51.8% Payback Period Pittsburgh, Pennsylvania 123 Alpha Drive Variables Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis FCO= First Cost of Original HVAC System AECO= Annual Energy Cost of Original HVAC System FCVRF= First Cost of Original VRF System Equation FCO + (AECO * X) = FCVRF + (AECVRF * X) $229,396 + ($16,416*X) = $348,393.07 + (9001 * X) $118996 = $7415 * X Emissions Analysis Acoustical Design Payback Period X= Payback Period in years Conclusion Alexander Radkoff AECVRF= Annual Energy Cost of VRF HVAC System X= 16.04 years Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Emissions Comparison Pittsburgh, Pennsylvania 123 Alpha Drive Acoustical Breadth Investigation Recommended Noise Criterion - NC Introduction KEY Existing Mechanical System Recommended NC Rating Equivalent Sound Level dBA Open-Plan Offices 35-40 45-50 Private Offices 30-35 Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conference Rooms Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 25-30 40-45 35-40 Private Offices Conference Rooms Open Plan Offices Pittsburgh, Pennsylvania 123 Alpha Drive Acoustical Breadth Investigation Existing Mechanical NC Rating Existing Mechanical Conditions Introduction Existing Mechanical System Variable Refrigerant Flow System • 5 Ton Carrier 50TCD06 Rooftop Unit NC-46 ~ 48 dBA • 1” Fiberglass Insulation • Room Dimensions : 34’x26’x8’ Cost Analysis Emissions Analysis • Measure SPL to nearest diffuser Acoustical Design Sound Power Level, dB (re 10^-12 W) Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Octave Band Frequency, HZ 63 125 250 500 1000 2000 4000 Discharge 85.8 84.3 80.5 78.7 76.4 72.7 68.3 Pittsburgh, Pennsylvania 123 Alpha Drive Acoustical Breadth Investigation Recommended Noise Criterion - NC Introduction Existing Mechanical System Recommended NC Rating Equivalent Sound Level dBA Open-Plan Offices 35-40 45-50 Private Offices 30-35 40-45 Conference Rooms 25-30 35-40 Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Existing Mechanical NC Rating NC-46 ~ 48 dBA Acoustical Breadth Investigation Pittsburgh, Pennsylvania 123 Alpha Drive Proposed Mechanical Conditions Introduction Recommended Noise Criterion - NC • Samsung DMV AM024FN4dCH/AA 4 Way Cassette Fan Coil Units Existing Mechanical System NC-25 ~ 32 dBA Variable Refrigerant Flow System Cost Analysis • Room Dimensions : 34’x26’x8’ Emissions Analysis Acoustical Design Sound Power Level, dB (re 10^-12 W) Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Octave Band Frequency, HZ 63 125 250 500 1000 2000 4000 Discharge 40.1 37.2 36.4 33.0 29.7 27.3 22.6 Acoustical Breadth Investigation Pittsburgh, Pennsylvania 123 Alpha Drive Recommended Noise Criterion - NC Introduction Existing Mechanical System Recommended NC Rating Equivalent Sound Level dBA Open-Plan Offices 35-40 45-50 Private Offices 30-35 40-45 Conference Rooms 25-30 35-40 Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado Recommended Noise Criterion - NC NC-25 ~ 32 dBA Conclusion Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Variable Refrigerant Flow System Acoustical Invesitgation Existing Mechanical System Variable Refrigerant Flow System • First Costs – 51% more expensive than original • Annual Costs – 45% cheaper than original system Cost Analysis • Original Design – did not meet recommended NC Ratings for office spaces Emissions Analysis • Payback Period – 16 years (uneconomical) • Potential for rumbly HVAC noise Acoustical Design • Emissions – 13% less annually than original • VRF Design – met all recommended NC Rating Conclusion Alexander Radkoff • Improve occupant comfort Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado and dBA values Pittsburgh, Pennsylvania 123 Alpha Drive Acknowledgements Introduction Existing Mechanical System Variable Refrigerant Flow System Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado AE Staff and Faculty Marc Portnoff Jonathan Iams Joel Butler Dan Gardner My friends and family Pittsburgh, Pennsylvania 123 Alpha Drive Introduction Existing Mechanical System Variable Refrigerant Flow System Questions? Cost Analysis Emissions Analysis Acoustical Design Conclusion Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado