FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Holy Cross Hospital – North Addition Philip Mackey The Pennsylvania State University Architectural Engineering L/E Option FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Project Background Location: Silver Spring, MD Owner: Holy Cross Hospital Architect: SmithGroup Engineers: Leach Wallace Assoc. (MEP) CM/GC: Bovis Lend Lease Size: 124,000 s.f. Completion Date: July 2005 Final Cost: $21.9 million $7.8 million MEP * North Addition part of a global renovation plan for the facility totaling 260,000 s.f. and costing $69 million. FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Topics of Discussion Lighting of Registration Space Lighting of Main Lobby Electrical Depth Final Conclusions Acknowledgements Covered in Final Report CM Breadth Mechanical Breadth Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Topics of Discussion Lighting of Registration Space Lighting of Main Lobby Electrical Depth Final Conclusions Acknowledgements Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Registration Space Architectural Features: Curved wooden south façade Frosted glass north façade Open to concourse/lobby on east and west walls Metal partitions separate each workstation Design Goals: Accent architectural features Limit spill light into admin. Offices Provide ample task illuminance 30 fc horizontal (reading) 10 fc horizontal (corridor) Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Lighting Depth – Registration Space 4” (18TRT) DownlightsRecessed (13Q) 2x2Open Direct/Indirect Basket Lighting Fixture Schedule Type A B1 B2 B3 D1 F3 Description 2' X 2' DIRECT/INDIRECT RECESSED, MICROPERFORATED MESH DIFFUSER, CENTER BASKET, WHITE FINISH, GRID CEILING 4" OPEN DOWNLIGHT, VERTICAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 4" OPEN DOWNLIGHT, VERTICAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 6" OPEN DOWNLIGHT, HORIZONTAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM ADJUSTABLE TABLE LAMP, SILVER FINISH, BLUE GLASS REFLECTOR 6" COLOR CHANGING LED COVE STRIP, COLOR ADJUSTING CAPABILITIES, VENTED PLASTIC HOUSING Lamps CCT (2) 40WTT5 3500K (1) CFL13Q 3500K (1) CFL18TRT 3500K (1) CFL26TRT 3500K (1) 35W GY6.35 3000K INCLUDED 100010000K HC FINAL REPORT Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Registration Space Computer Analysis Results: (AGI32) Calc Grids Registration Plane Height Average (ft) (fc) Pseudo-corridor 0 18 Desktops 2.5 36 * Max value correlates to point under task lamp Description Power Density Calcs Fixture A B1 B2 D1 F3 Ballast Quantity Watts/Fixture 81 4 16 12 20 5 35 5 6.9 24 Total Watts: Power Density (W/ft2): Total 324 192 100 175 166 957 1.15 Allowable Power Density: 1.3 W/ft2 Maximum (fc) 30 *72 Minimum (fc) 5 15 Max/Min (fc) 6.0 4.8 FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Registration Space Final Solution: Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Topics of Discussion Building Background Lighting of Registration Space Lighting of Main Lobby Electrical Depth Final Conclusions Acknowledgements Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Main Lobby Architectural Features: Information Kiosk central to space Reading area in SW corner Art wall adjacent to entrance Wood-paneled north facade Design Goals: Bring attention to info kiosk Accent architectural features Provide ample task illuminance at kiosk and reading space Accent back wall to limit depth of space 10 fc horizontal, 3 fc vertical (corridor) 50 fc horizontal (info kiosk) 30 fc horizontal (reading space) Phil Mackey FINAL REPORT HC Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Main Lobby 6” LED Cove Cove Fixture FixtureIn Column Lighting Fixture Schedule Type B3 B4 C1 C2 D2 D3 F1 F2 Description 6" OPEN DOWNLIGHT, HORIZONTAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 6" OPEN DOWNLIGHT, HORIZONTAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 2' RECESSED LINEAR WALLWASH, 2" APERTURE, BLACK METAL DIFFUSER, GRID CEILING 4' RECESSED LINEAR WALLWASH, 2" APERTURE, BLACK METAL DIFFUSER, GRID CEILING 4" RECESSED ADJUSTABLE SPOT, BLACK POWDER-COAT FINISH, WHITE TRIM ADJUSTABLE WALLWASH SPOT, TRACK/CEILING MOUNTED, WHITE FINISH, INTEGRATED ELECTRONIC TRANSFORMER 6" COLOR CHANGING LED COVE STRIP, COLOR ADJUSTING CAPABILITIES, VENTED PLASTIC HOUSING 6" COLOR CHANGING LED COVE STRIP, COLOR ADJUSTING CAPABILITIES, VENTED PLASTIC HOUSING Lamps CCT (1) CFL26TRT 3500K (1) CFL42TRT 3500K (1) F24T5HO 3500K (1) F28T5 3500K (1) 50W GY6.35 3000K (1) 75W GY6.35 3000K INCLUDED 100010000K INCLUDED 100010000K FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Lighting Depth – Main Lobby Dimmed 6” Ceiling Recessed Mounted 6” Recessed Downlights Photosensor Downlights (42TRT) (42TRT) Lighting Fixture Schedule Type B3 B4 C1 C2 D2 D3 F1 F2 Description 6" OPEN DOWNLIGHT, HORIZONTAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 6" OPEN DOWNLIGHT, HORIZONTAL LAMP, ALUMINUM REFLECTOR AND SELFFLANGED TRIM 2' RECESSED LINEAR WALLWASH, 2" APERTURE, BLACK METAL DIFFUSER, GRID CEILING 4' RECESSED LINEAR WALLWASH, 2" APERTURE, BLACK METAL DIFFUSER, GRID CEILING 4" RECESSED ADJUSTABLE SPOT, BLACK POWDER-COAT FINISH, WHITE TRIM ADJUSTABLE WALLWASH SPOT, TRACK/CEILING MOUNTED, WHITE FINISH, INTEGRATED ELECTRONIC TRANSFORMER 6" COLOR CHANGING LED COVE STRIP, COLOR ADJUSTING CAPABILITIES, VENTED PLASTIC HOUSING 6" COLOR CHANGING LED COVE STRIP, COLOR ADJUSTING CAPABILITIES, VENTED PLASTIC HOUSING Lamps CCT (1) CFL26TRT 3500K (1) CFL42TRT 3500K (1) F24T5HO 3500K (1) F28T5 3500K (1) 50W GY6.35 3000K (1) 75W GY6.35 3000K INCLUDED 100010000K INCLUDED 100010000K FINAL REPORT HC Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Main Lobby Daylight Study Results: Annual Energy Savings fixture shut-off below BF=.05 Annual Energy - kW No ControlsConsumption All Dim Selective Dim . KWh Payback Cost KWh Cost KWh Cost Period fixture shut-off below BF = .05 474.3 $45.54 435.1 $41.78 390.8 $37.52 January Number Payback Cloudy February 1-21Overcast 306.0Type$29.38 Partly 280.7 $26.95 Dimming Selective Period Month No22-28 Selective$14.10 No February 124.4 All Dim 146.9 All Dim $11.94 Ballasts (yrs) Controls Dim $54.65 Controls 483.5 Dim March 569.2 $46.42 All Dim (shut-off) 34 17.7 Oct. 22 - Feb. 21 April 1-21 385.6 $37.02 324.3 $31.14 Selective Dim (shut-off) 23 7.8 (Jan 21 analysis April 22-30 979.2 967.7 927.9 443.7 142.5 371.1$13.68 297.3 All Dim (no shut-off) 34 17.7 192.8 $18.51 Feb. 22 - April 21 Selective Dim (no shut-off) 492.2 23 7.1 May 664.0 $63.76 $47.26 Aug. 22 - Oct. 21 June 642.6 $53.55 465.9 $38.83 (Mar. 21 analysisJuly 991.4 939.8 664.0 868.0$55.33 624.2 480.0 456.0$40.00 301.3 April 22 - Aug. 21 August 1-21 449.8 $37.48 324.7 $27.06 (May 21 analysisAugust1071.0 963.0 885.0 921.1 552.4 378.8 22-31 183.6 $15.30 151.2 $12.60 Totals:September 3041.6 2870.6 550.8 2680.9$45.90 1989.0 455.2 1379.5$37.93 977.4 October 1-21 449.8 $37.48 318.0 $26.50 October 22-31 153.0 $12.75 136.8 $11.40 November 459.0 $44.07 417.7 $40.10 December 474.3 $45.54 435.1 $41.78 Total Cost: $610.38 $495.37 Savings: $115.01 Clear 252.3 $24.23 No Selective 102.2 $9.82 All Dim Controls Dim 398.8 $38.29 264.4 $25.39 443.7$11.19 366.5 300.5 116.5 403.4 $38.74 376.0 $31.33 605.9 460.7 333.4 386.5 $32.21 261.2 $21.76 621.2 370.2 279.8 119.9 $10.00 1670.8$30.30 1197.5 913.7 363.6 253.7 $21.14 119.8 $9.99 372.0 $35.72 390.8 $37.52 $415.14 $195.24 HC FINAL REPORT Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Main Lobby Computer Analysis Results: (AGI32) Calc Grids Main Lobby Description Circulation Floor Reading Area Kiosk Desktop Art Wall (vertical) Plane Height (ft) 0 2.5 2.5 - Average (fc) 15 31 61 34 Maximum (fc) 44 40 100 64 Power Density Calcs Power Density Calcs Circulation Spaces Reading Space Fixture B3 C1 C2 D2 D3 F1 F2 Ballast Quantity Watts/Fixture 29 54 27 11 63 9 50 21 50 2 6.9 52 6.9 12 Total Watts: Power Density (W/ft2): Total Fixture 1566 297 567 1050 100 359 83 4022 0.84 B4 Ballast Quantity Watts/Fixture 45 34 Total Watts: Power Density (W/ft2): Allowable Power Density: 1.3 W/ft2 (lobby) 1.2 W/ft2 (reading) Total 1530 1530 0.97 Minimum (fc) 7.3 14 35 8 Max/Min (fc) 6.0 2.9 2.9 8.0 FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Lighting Depth – Main Lobby Final Solution: Phil Mackey HC FINAL REPORT Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Electrical Depth – Alternate 1 Schematic: Existing Normal Proposed NormalPower PowerDistribution Distribution - denotes 480Y/277V panel - denotes 208Y/120V panel Panel Panel MDP-N MDP-N Panel LP-1N XFMR T-1 Panel PP-1N XFMR T-9 Panel PP-2N Panel PP-1N1 XFMR T-11 Panel PP-2N Panel HCK XFMR T-L Panel LP-2N Panel MDP-L Panel LP-3N Panel LP-4N XFMR T-2 Panel PP-2N Panel PP-2N XFMR T-3 Panel PP-2N Panel PP-3N XFMR T-4 Panel PP-4N HC FINAL REPORT HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Electrical Depth – Alternate 1 Summary: - Feeder upsized due to voltage drop Electrical Equipment Normal System Components (Existing) Voltage-- Deleted DropNormal Calculations - Alt. 1 (Proposed) Electrical Equipment Added System Components Feeder Panelboard Panelboard Equipment Type TRANSFORMER TRANSFORMER PANEL TRANSFORMER FEEDER TRANSFORMER TRANSFORMER FEEDER TRANSFORMER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER CIRCUIT BREAKER FEEDER CIRCUIT BREAKER FEEDER CIRCUIT BREAKER FEEDER CIRCUIT BREAKER FEEDER CIRCUIT BREAKER FEEDER CIRCUIT BREAKER CIRCUIT CIRCUIT BREAKER BREAKER CIRCUIT CIRCUIT BREAKER BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER Name Name MDP-L Load Load Rating Rating Connected Connected (A) (A) (A) (A) 644 800 Size VL-N Amperage Length Factor Vdrop % Vdrop Feeder Transformer Feeder Transformer Protection Conduit Primary Secondary Protection Conduit Primary Secondary (2)Voltage #1/0 277 16 Impact 0.127 0.10 Alternate ##1H Name Size Rating (A) Ground Length (ft) kVA # Poles Poles Spaces Spaces Voltage Name Size 140 Rating1 (A) Cost Ground Length (ft) Name Name 0.283 kVA (A) Size Voltage (A) Size Voltage Voltage Voltage (3) #300 45 480∆ 208Y/120 225 480∆ 0.20 208Y/120 #1L 120 215 20 0.0545T-1T-L 0.234 T-2 45 480∆ 208Y/120 3 24 MCM 208Y/120 800 T-3 45 480∆ 208Y/120 2 SETS Credits: $40,439.34 #1H 300 #6 1 1/2" 16 45 480∆ 208Y/120 #1N #1/0 120 168 6 0.127 T-4 0.128 0.11 (3) #1/0 T-9 45 480∆ 208Y/120 3 SETS 855 #2 152 2 1/2" 20 #1N1 #3/0 120#1LCosts: 160 0.0865 2.104 1.75 T-11 75 480∆ 208Y/120 (4) #300 $79,769.75 #5 (3) 85 #8 146 #1N (4) #4 #1/0 150 #6 11"1/2" #2N #1/0 120#1N1 148 12 0.127 0.226 0.19 #6 (4) 150 #6 1 11/2" 10 (4)#1/0 #1/0 150 #6 1/2" 152 Total Costs: $39,330.41 (3) #4 85 #8 1512 #2N (4) #1/0 150 #6 24 11"1/2" #3N #1/0 120#11 160 0.127 0.488 0.41 #12 (4) #1/0 150 #6 1 1/2" 12 #3N (4) #1/0 150 #6 1 1/2" 24 (3) #8 2236 #4N (4) #4 #1/032 85 150 #6 36 11"1/2" #4N #1/0 120#17 0.127 0.146 0.12 #18 (4) 150 #6 1 11/2" 1288 #1HCK (4)#1/0 #4/0 230 #4 1/2" #1HCK #4/0 120#25 0.0695 0.342 0.29 (3) #4 56 85 #8 88 1" 15 #26 #32 #33 #34 #44 (4) #1/0 (3) #4 (4) #1/0 (4) #4/0 (3) #1 150 85 150 230 130 #6 #8 #6 #4 #8 1 1/2" 1" 1 1/2" 1 1/2" 1 1/2" 12 20 152 88 16 CircuitBreaker Breaker Circuit Type Type Feeding (A)(A) Phase Feeding Size Size Phase Voltage Voltage DRY DRY DRY DRY DRY DRY DRY T-L MDP-L PP-1N PP-1N1 HCK PP-2N PP-1N PP-3N PP-1N1 PP-4N HCK PP-2N PP-3N PP-4N 300 800 150 150 200 150 70150 70150 100 70 70 70 3 3 3 3 3 3 3 3 3 3 3 3 3 3 480Y/277 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 208Y/120 HC FINAL REPORT HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Electrical Depth – Alternate 2 Schematic: ProposedStandby Existing StandbyPower PowerDistribution Distribution - denotes 480Y/277V panel - denotes automatic transfer switch EX. EMERGENCY ISOLATED EMERGENCY GENERATOR SETS GENERATOR SUBSTATION SUBSTATIONDD - denotes switchgear with secondary voltage 480Y/277V ATS-1 ATS-1 ATS-3 ATS-2 ATS-4 NORMAL BRANCH LIFE SAFETY BRANCH CRITICAL BRANCH EQUIPMENT BRANCH EMERGENCY BRANCHES NORMAL BRANCH HC FINAL REPORT Phil Mackey HOLY CROSS HOSPITAL – NORTH ADDITION Electrical Depth – Alternate 2 Summary: - Feeder upsized due to voltage drop Drop Calculations - Alt. 2(Proposed) ElectricalVoltage Cost Analysis - Added System Components Panelboard Equipment Type Name PANEL FEEDER FEEDER EMDP Load Connected (A) 828 FEEDER Equipment Type FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER PARALLELING SWITCHGEAR Name Load Connected (A) Rating (A) Feeder # Poles Spaces Size Voltage VL-N Protection (A) Name Feeder Amperage Size Rating (A) Length Ground Conduit Size Automatic Transfer Switch Factor Length (ft) Vdrop Name Rating (A) Circuit Breaker % Vdrop Priority Voltage Phase ATS-1 #1 277 59 500 0.156 4.602 1.66 3 24 480Y/277 1000 Electrical Cost Analysis Deleted System Components (Existing) ATS-1 (4) #1 130 #8 1 1/2" 500 ATS-2 #2 277 52.5 500 0.196 5.145 1.86 ATS-2 (4) #2 115 #8 1 1/4" 500 ATS-3 #300 MCM 277 205 500 0.0545 5.586 2.02 (4) #300 ATS-3 285 #2 2 1/2" 500 MCM Panelboard Automatic Transfer Switch Alternate 2Feeder Cost Impact (3) #350 3 SETS (4) ATS-4 855 (3) #2 2 1/2" 0.047 500 241 500(3) 5.664 2.04 Rating ATS-4 Protection277 Conduit Rating MCM # Poles Spaces MCM Voltage Name #300 Size Rating (A) Ground Length (ft) Name Priority Voltage Phase (A) (A) (A) EATS-1 (4) #3 100 #8 1Size 1/4" 20 EATS-2 (4) #3 100 #8 1 1/4" 35 3 SETS (4) EATS-1 #3 277 59 1005 (3) #1/0 20 (3) 3$73,232.22 0.294 0.11 #1 1/2" 0.2495 500 Credits: (4) #250 EATS-3 #400 MCM #2 2 1/2" 20 MCM EATS-2 #3 277 52.5 255 0.2495 0.458 0.17 #2 (4) #1/0 150 #4 35 2" 500 3 SETS #3 (4) #4(4) 85 1$426,547.64 1/4" 500 EATS-4 855 (3)#6#2 (3) 2 1/2" 20 Costs: EATS-3 #250 MCM 277 205 20 0.062 0.254 0.09 #300 MCM (4) #350 #35 310 #1 3" 500 4 SETS MCM (4) EMDP 1340 (3) #1/0 (3) 3 1/2" 500 (3) #300 #400 MCM Total #36 Costs: (3) #2/0 #6 20 2" 40 $353,315.42 EATS-4 277 241 175 0.0545 0.263 0.09 E6ATS (E) (3) #2/0 175 #6 2" 40 MCM E6ATS (N) (3) #2/0 175 #6 2" 40 ATS-1 100 1 480Y/277 3 (4) #400 100 2 480Y/277 3 EMDP 277 259 500 0.043 ATS-2 5.563 2.01 ATS-3 250 3 480Y/277 3 MCM Feeding Size (A) Phase Voltage 1200 ATS-4 800 4 480Y/277 E6ATS(E) #2/0 277 50.5 40 0.104 0.210 0.08 E6ATS(N) #2/0 277 50.5 40 0.104 0.210 0.08 Circuit Breaker Feeding Size (A) Phase Voltage EMDP 1200 3 480Y/277 3 FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Topics of Discussion Building Background Lighting of Registration Space Lighting of Main Lobby Electrical Depth Final Conclusions Acknowledgements Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Phil Mackey Final Conclusions Lighting Depth – Registration Space – complimented architectural elements while keeping fixtures minimally obtrusive to the space, provided sufficient illuminance levels under ASHRAE 90.1 Power Density recommendations Main Lobby – utilized light as a means to call attention to particular functions and artistic features within the space, created a more inviting space by washing the back wall, provided sufficient illuminance levels for various tasks under ASHRAE 90.1 Power Density recommendations Electrical Depth – investigated cost impact of centralizing normal branch step- down transformers, provided alternative emergency back-up power generation system and assessed the feasibility of proposed implementation FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Acknowledgements Professional Leach Wallace and Associates, Inc. Reese Engineering, Inc. Faculty Dr. Richard Mistrick Dr. Martin Moeck Prof. M. Kevin Parfitt Personal Family Friends/ Roommates Fellow AE Students Phil Mackey FINAL REPORT HC HOLY CROSS HOSPITAL – NORTH ADDITION Questions? Comments Phil Mackey