Circulating Current – load switch open I circulating E A EB Z A ZB Circulating Current load switch closed Icirculating adds to the load current in one transformer and subtracts from the load current in the other transformer. At rated load, the transformer with the higher secondary voltage will be overloaded! Example 3.4 • Two 100 kVA single-phase transformers A and B are to be operated in parallel. The respective no-load voltage ratios and respective impedances are obtained from the nameplates as – Transformer A • 2300 – 460 V %R = 1.36 %X = 3.50 %R = 1.40 %X = 3.32 – Transformer B • 2300 – 450 Example 3.4 continued • Determine – the circulating current in the paralleled secondaries – the circulating current as a percent of the rated current in transformer A – the percent difference in secondary voltage that caused the circulating current. The rated low-side currents are 100kVA IA 217.39 A 460V 100kVA IB 222.22 A 450V The equivalent resistance and reactance of each transformer referred to the low side RPU I rated Req Vrated 0.0136 0.0140 X PU 217.39 RAeq 460 222.22 RBeq 450 I rated X eq 0.0350 0.0332 RAeq 0.0288 RBeq 0.0284 Vrated 217.39 X Aeq 460 222.22 X Beq 450 X Aeq 0.0741 X Beq 0.0672 The impedance of the closed loop formed by the two secondaries Z loop Z A Z B Z loop 0.0288 j 0.0741 0.0284 j 0.0672 Z loop 0.0572 j 0.1413 Z loop 0.152467.97 The circulating current I circulating I circulating I circulating E A EB Z A ZB 4600 4500 0.15467.97 65.6 68 A The circulating current as a percent of the rated current in transformer A I circulating I Arated 65.62 0.302 30.2% 217.39 The percent difference in secondary voltage that caused the circulating current VA VB 460 450 0.022 2.2% VB 450