Cintas Center - Courtside Club Xavier University 1624 Herald Avenue Cincinnati, OH 45207 ISSUED FOR CONSTRUCTION - 08/05/2015 XAVIER UNIVERSITY 3800 VICTORY PARKWAY CINCINNATI, OH 45207 (T): 513-745-3000 STRUCTURAL ENGINEER: MSA Architects 316 W. FOURTH STREET CINCINNATI, OH 45202 (T): 513 241-5666 www.msaarch.com MEP ENGINEER SCHAEFER 10411 MEDALLION DR CINCINNATI, OH 45241 (T): 513-542-3300 MOTZ 316 W. FOURTH STREET CINCINNATI, OH 45202 (T):513-621-5400 GENERAL NOTES GENERAL NOTES GENERAL NOTES CODE INFORMATION CONTRACTOR SHALL COMPLY WITH ALL CODES, LAWS, ORDINACES RULES AND INDUSTRY REGULATIONS BEARING ON THE INSTALLATION OF THE WORK SHOWN HEREIN. ALL WORK IS TO BE INSTALLED TO MEET CURRENT CODE REQUIREMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFYING REQUIREMENTS PRIOR TO INSTALLING WORK. MAINTAIN ACCESS TO ALL REQUIRED EXITS FROM ALL AREAS. THE CONTRACTOR IS RESPONSIBLE FOR ALL SECURITY OF HIS MATERIALS, EQUIPMENT AND TOOLS. CONTRACTOR IS TO PROTECT ALL FINISHED SURFACES FROM DIRT AND DAMAGE UNTIL FINAL ACCEPTANCE BY OWNER. MATERIALS DAMAGED DURING CONSTRUCTION ARE TO BE REPAIRED/REPLACED AT CONTRACTOR'S COST TO THE SATISFACTION OF THE OWNER. CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL UTILITIES AND SHALL PROTECT AND SUPPORT THEM AS REQUIRED. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, NECESSARY TOOLS, EXPENDABLE EQUIPMENT, UTILITY AND TRANSPORTATION SERVICES, DELIVERY MATERIAL HANDLING, STORAGE, TESTING, INSPECTIONS AND SUPERVISION. CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES. CONTRACTOR SHALL ALSO COORDINATE WITH WORK BY THE TENANT/OWNER AND OTHER CONTRACTS BY TENANT/OWNER (E.G., IF APPLICABLE, SECURITY SYSTEM, DATA SYSTEM, TELEPHONE SYSTEM.) THE TENANT/OWNER SHALL SECURE AND PAY FOR THE ZONING PERMIT, GENERAL BUILDING PERMIT, THE MECHANICAL (HVAC ONLY) PERMIT AND ASSOCIATED PLANS EXAMINATIONS. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL OTHER APPLICABLE PERMITS, FEES, LICENSES, INSPECTIONS, CERTIFICATIONS AND TAXES AS MAY BE REQUIRED BY AUTHORITIES HAVING JURISDICTION. IN ADDITION TO THESE REQUIREMENTS, THE TENANT/OWNER SHALL EMPLOY AN INDEPENDENT CONSULTANT FOR TESTING OF SOIL BEARING, PROPERTIES OF CAST CONCRETE, AND STEEL WELDING/CONNECTIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OTHER TESTING, FEES, AND CERTIFICATIONS, INCLUDING RECORD DRAWINGS, SURVEYS, OR PLATS AS MAY BE REQUIRED BY AUTHORITIES HAVING JURISDICTION. DEFINITION OF TERMS "FURNISH" MEANS "PROCURE AND DELIVER TO PROJECT SITE". "PROVIDE" MEANS "FURNISH, INSTALL AND MAKE READY FOR USE". "AS SELECTED" OR "AS DIRECTED" IMPLIES "BY OWNER OR ARCHITECT". "TENANT" MEANS THE BUILDING OWNER. "OWNER" MEANS THE BUILDING OWNER OR LANDLORD. GENERAL THE FOLLOWING OUTLINES THE GENERAL QUALITIES OF THE WORK EXPECTED. ALL MATERIALS USED ARE REQUIRED TO BE GOOD QUALITY AND MEET OR EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIC PRODUCTS OR MANUFACTURERS ARE NOT NOTED, THE CONTRACTOR IS REQUIRED TO NOTIFY ARCHITECT TO OBTAIN A STANDARD OF QUALITY. EXIT ALL WORK IS TO BE DONE WITH THE APPROPRIATE TOOLS AND MATERIALS. THE ARCHITECT HAS THE RIGHT TO REJECT ANY WORK NOT DONE APPROPRIATELY. ALL CUTTING, PATCHING, REFINISHING AND REPAINTING OF ALL WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR ALL SECURITY OF HIS MATERIALS, EQUIPMENT AND TOOLS. EGRESS PATH EXISTING MECHANICAL EXISTING OFFICE EXISTING OFFICE EXISTING DOCK DOOR ALL MATERIALS, PRODUCTS AND SYSTEMS SHALL BE FABRICATED AND INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S/FABRICATOR'S INSTRUCTIONS, RECOMMENDATIONS AND SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO THE USE OF ATTACHMENTS, ACCESSORIES, PRIMERS, SEALERS, CONTROL JOINTS, ETC., UNLESS OTHERWISE SPECIFICALLY NOTED IN THESE DRAWINGS. CONTRACTOR (OR THE INSTALLER, FABRICATOR, MANUFACTURER OR SUPPLIER OF SUCH ITEM) SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN THE PRODUCT INSTALLATION REQUIREMENTS AND THE DRAWINGS. PERFORMING WORK MEANS ACCEPTANCE OF EXISTING CONDITIONS AND SUBSTRATE WORK. DO NO WORK UNTIL CONDITIONS ARE ACCEPTABLE. SHOULD DISCREPANCIES EXIST BETWEEN THE INFORMATION SHOWN IN THESE DRAWINGS/NOTES AND THE MANUFACTURER’S INFORMATION, THE ARCHITECT SHALL BE NOTIFIED PRIOR TO COMMENCEMENT OF THE WORK IN QUESTION FOR REVIEW AND COORDINATION. DN 43' EXIT AUX GYM COURTSIDE CLUB 100 973 SF THE CONTRACTOR MAY ELECT TO OFFER OPINIONS, ADVICE OR ALTERNATE MATERIALS OR DETAILS. ALL WILL BE REVIEWED AND DISCUSSED WITH THE CONTRACTOR TO DETERMINE MERITS. ANY SAVINGS OF MATERIALS OR DETAILS WILL BE CREDITED TO THE TENANT/OWNER, WHILE ANY ADDITIONS SHALL BE BILLED TO THE TENANT/OWNER. A CHANGE ORDER FORM MUST BE COMPLETED IN ORDER TO ALTER CONSTRUCTION BID. SUBSTITUTIONS OF SPECIFIED MATERIALS ARE TO BE APPROVED IN WRITING PRIOR TO EXECUTING WORK. SUBSTITUTIONS INSTALLED PRIOR TO RECEIVING APPROVAL ARE PERFORMED AT THE CONTRACTOR'S RISK. STORAGE 101 572 SF 65 AREA OF WORK 2 EXISTING RESTROOM C:\Users\nschoeppner\Documents\Revit Local\CINTAS_CENTRAL-HOST_v14_nschoeppner.rvt 86' CINTAS CENTER KEY PLAN 2 G0.0a 1" = 40'-0" COURTSIDE CLUB LIFE SAFETY PLAN 1 G0.0a 1" = 10'-0" CODE NOTES VICINITY PLAN PROJECT SCOPE: THIS PROJECT IS THE CONSTRUCTION OF A GATHERING SPACE WITHIN THE EXISTING DOCK AREA OF THE CINTAS CENTER. THE COURTSIDE CLUB WILL BE EXCLUSIVE TO CURRENT SEASON TICKET HOLDERS AND THUS THE OVERALL OCCUPANT LOAD OF THE BUILDING WILL NOT CHANGE. THE PROJECT WILL ALSO INCLUDE A STORAGE ROOM TO SERVE THE DOCK AREA. APPLICABLE BUILDING CODE: OHIO BUILDING CODE, 2011 USE CLASSIFICATION (BUILDING) - NO CHANGE: A-4 ASSEMBLY (ARENA) S-2 LOW HAZARD STORAGE CONSTRUCTION CLASSIFICATION: ACTUAL CONSTRUCTION TYPE: TYPE 1B HEIGHT AND AREA LIMITATIONS: ALLOWABLE HEIGHT: ACTUAL HEIGHT: UNLIMITED (NO CHANGE) INTERIOR RENOVATION ALLOWABLE AREA: ACTUAL AREA: UNLIMITED (NO CHANGE) 1,505 SF TOTAL OCCUPANTS 9/17/2015 3:58:02 PM EGRESS PATH COURTYARD CLUB: (PER OBC TABLE 1004.1.1) 972 / 15 = 65 STORAGE ROOM: (PER OBC TABLE 1004.1.1) 533 / 300 = 2 MEANS OF EGRESS: ALLOWED TRAVEL DISTANCE TO AN EXIT: ACTUAL TRAVEL DISTANCE TO AN EXIT: ALLOWED COMMON PATH OF EGRESS TRAVEL: ACTUAL COMMON PATH OF EGRESS TRAVEL: ALLOWED DISTANCE FOR DEAD ENDS IN CORRIDOR: ACTUAL DISTANCE FOR DEAD ENDS IN CORRIDOR: REQUIRED NUMBER OF EXITS: ACTUAL NUMBER OF EXITS: REMOTENESS OF EXITS: FIRE RESISTANT ASSEMBLIES: FLOOR BEAMS: FLOOR DECKS: ROOF BEAMS: ROOF DECK: *ROOF BEAMS: *ROOF DECK STEEL COLUMNS: 250 FT FOR ALL SPACES 112 FT OR LESS FOR ALL SPACES 75 FT FOR ALL SPACES 75 FT OR LESS FOR ALL SPACES 20 FT 20 FT OR LESS 2 (PER 1021.1) 3 1/3 THE DIAGONAL RULE U.L. DESIGN RATING 2 HR (NO CHANGE) 2 HR (NO CHANGE) 2 HR (NO CHANGE) 2 HR (NO CHANGE) 1 HR (NO CHANGE) 1 HR (NO CHANGE) 2 & 3 HR (NO CHANGE) * INDICATES OVER 15' IN HEIGHT BULIDING IS FULLY SPRINKLERED WITH THE EXCEPTION OF THE ARENA ROOF OVER THE SEATING BOWL WHERE FIRE SPRINKLERS ARE NOT REQUIRED. SHEET INDEX SHEET NO. SHEET NAME GENERAL G0.0a COVER SHEET ARCHITECTURE A1.0a COURTSIDE CLUB DESIGN PROJECT LOCATION: CINTAS CENTER XAVIER UNIVERSITY 1624 HERALD AVENUE CINCINNATI, OH 45207 MECHANICAL M2.1 M5.1 ELECTRICAL E2.1 HVAC FLOOR PLAN HVAC DETAILS ELECTRIC LIGHTING FLOOR PLAN E3.1 ELECTRIC POWER FLOOR PLAN E5.1 ELECTRIC DETAILS E5.2 ELECTRIC DETAILS CONTRACTOR IS TO PROTECT ALL FINISHED SURFACES FROM DIRT AND DAMAGE UNTIL FINAL ACCEPTANCE BY TENANT/OWNER. MATERIALS DAMAGED DURING CONSTRUCTION ARE TO BE REPAIRED/REPLACED AT CONTRACTOR'S COST TO THE SATISFACTION OF THE TENANT/OWNER. REQUIRED FORMS (USE CURRENT EDITION): 1. CONTRACT: AIA, A101, "STANDARD FORM OF AGREEMENT BETWEEN OWNER AND CONTRACTOR". 2. GENERAL CONDITIONS: AIA A201, "GENERAL CONDITONS OF THE CONTRACTOR FOR CONSTRUCTION". 3. CHANGE ORDER: AIA G701, "CHANGE ORDER". UPON ACCEPTANCE OF THE CONTRACT, THE CONTRACTOR IS TO PREPARE A DETAILED SCHEDULE FOR THE PROPOSED WORK, INCLUDING ALL PHASING, WORK AFTER HOURS, AND MOVE/OCCUPANCY DATES. THIS SCHEDULE MUST BE REVIEWED AND ACCEPTED BY THE TENANT/OWNER AND ARCHITECT. ALL LONG ORDER ITEMS MUST BE CALLED TO OWNER’S ATTENTION AS SOON AS POSSIBLE. TENANT/OWNER WILL PREPARE AND FILE NOTICE OF COMMENCEMENT. APPLICATIONS FOR PAYMENT ARE TO BE SUBMITTED TO ARCHITECT IN FIRST WEEK OF MONTH FOLLOWING PERIOD FOR WHICH WORK WAS PERFORMED. RETAINAGE WILL BE 10% FOR THE ENTIRE PROJECT AND WILL BE REDUCED APPROPRIATELY AT SUBSTANTIAL COMPLETION.. ARCHITECT WILL FORWARD CERTIFICATE FOR PAYMENT TO TENANT/OWNER FOR PAYMENT. USE STANDARD AIA FORMS G702 AND G703. SUBMIT SCHEDULE OF VALUES WITH FIRST APPLICATION FOR PAYMENT. PRIOR TO ISSUANCE OF THE CERTIFICATE FOR FINAL PAYMENT, THE CONTRACTOR SHALL SUBMIT COPIES OF CERTIFICATES OF INSPECTION FOR ALL WORK ISSUED BY PROPER AGENCIES AND DOCUMENTATION OF ALL FIELD CHANGES ON THE RECORD DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND MAINTAINING LIABILITY INSURANCE AND WORKER'S COMPENSATION. CONTRACTOR SHALL PROVIDE PROOF OF INSURANCE FOR A MINIMUM $1,000,000.00 "UMBRELLA" LIABILITY POLICY. CONTRACTOR'S LIABILITY POLICIES SHALL BE ENDORSED TO INCLUDE THE TENANT/OWNER, ARCHITECT AND ARCHITECT'S CONSULTANTS AS ADDITIONAL NAMED INSUREDS. ALL WORK SHALL BE WARRANTED FOR A MINIMUM PERIOD OF ONE YEAR, BEGINNING NO SOONER THAN THE CERTIFIED DATE OF SUBSTANTIAL COMPLETION. PROVIDE LONGER WARRANTIES WHERE SPECIFIED FOR INDIVIDUAL COMPONENTS OR WHERE PROVIDED BY MANUFACTURER’S STANDARD WARRANTY. SUBMIT ALL WRITTEN WARRANTIES/GUARANTEES ALONG WITH ALL OPERATING MANUALS, INSTRUCTIONS, ETC. FOR ALL EQUIPMENT, SYSTEMS, ETC. AT PROJECT COMPLETION AND PRIOR TO RELEASE OF FINAL PAYMENT. CONTRACTOR SHALL MAINTAIN RECORD DOCUMENTS THROUGHOUT THE COURSE OF THE WORK. NOTE ALL CHANGES AND SHOW ALL UNDERGROUND OR CONCEALED UTILITIES. SUBMIT RECORD DRAWINGS AT PROJECT COMPLETION. SUBMIT SHOP DRAWINGS, SAMPLES, PRODUCT DATA, ETC. IN A TIMELY MANNER SO AS NOT TO IMPEDE UPON THE CONSTRUCTION SCHEDULE. SUBMIT TWO ADDITIONAL SET OF SUBMITTALS FOR ARCHITECT'S AND TENANT’S/OWNER’S RECORDS IN ADDITION TO QUANTITIES AS REQUIRED BY THE CONTRACTOR. HERE PRODUCTS AND/OR SYSTEMS OF THE MECHANICAL, ELECTRICAL OR PLUMBING ARE INVOLVED, SUBMIT ONE ADDITIONAL SET OF SUBMITTALS FOR ENGINEER'S RECORDS IN ADDITION TO QUANTITIES AS REQUIRED BY THE ARCHITECT, TENANT/OWNER AND THE CONTRACTOR. SUBSTITUTIONS OF SPECIFIED MATERIALS ARE TO BE APPROVED IN WRITING PRIOR TO EXECUTING WORK. SUBSTITUTIONS INSTALLED PRIOR TO RECEIVING APPROVAL ARE PERFORMED AT THE CONTRACTOR'S RISK. CONSTRUCTION AND SAFETY CONTRACTOR AND/OR CONTRACTOR'S AGENT(S) SHALL VERIFY ALL DIMENSIONS AND INFORMATION IN THESE DRAWINGS. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS. ANY ERRORS, INCONSISTENCIES OR OMISSIONS SHALL BE REPORTED TO THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK. ANY CHANGES FROM THESE DOCUMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR. THESE DRAWINGS ARE NOT TO BE SCALED. WHENEVER POSSIBLE, CONDITIONS WHICH ARE SUBJECT TO MODIFICATION OR CHANGE ARE SHOWN AS EXISTING. CONTRACTORS SHALL INSPECT THE EXISTING CONDITIONS AND PROVIDE MODIFICATIONS TO MEET GOVERNING CODES AND PERFORMANCE SPECIFICATIONS, WHETHER OR NOT SPECIFICALLY INDICATED IN THE DRAWINGS. IF INSUFFICIENT INFORMATION EXISTS, CONTACT THE ARCHITECT / ENGINEER FOR CLARIFICATION. IF, IN THE CONTRACTOR'S OPINION, ANY WORK IS INDICATED ON THE DRAWINGS OR IS SPECIFIED IN SUCH A MANNER AS WILL MAKE IT IMPOSSIBLE TO PRODUCE FIRST CLASS WORK, OR IF THE WORK OF A PREVIOUS TRADE SHOULD MAKE FIRST CLASS WORK IMPOSSIBLE FOR ANOTHER TRADE, THE CONTRACTOR SHALL REFER THE PROBLEM TO THE ARCHITECT FOR INTERPRETATION BEFORE PROCEEDING WITH THE WORK. ALL DIMENSIONS ON THE DRAWINGS ARE TO BE CONFIRMED BY THE CONTRACTOR. ANY DISCREPANCIES ARE TO BE RESOLVED BY ARCHITECT PRIOR TO EXECUTION OF WORK. THE ARCHITECT / ENGINEER SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES OF CONSTRUCTION SELECTED BY THE CONTRACTOR. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. WHEN ON SITE, THE ARCHITECT / ENGINEER SHALL BE RESPONSIBLE FOR HIS/HER OWN SAFETY BUT HAS NO RESPONSIBILITY FOR THE SAFETY OF OTHER PERSONNEL OR SAFETY CONDITIONS AT THE SITE. ALL CUTTING, PATCHING, REFINISHING AND REPAINTING OF ALL WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. FIRE BLOCKING AND DRAFT STOPPING SHALL BE INSTALLED IN ALL LOCATIONS REQUIRED BY OBC SECTION 712. MAINTAIN ALL FIRE RATINGS IN NEW AND EXISTING CONSTRUCTION. COMPLETED WORK SHALL BE STRUCTURALLY SOUND, FULLY OPERATIONAL, INSTALLED PLUMB, LEVEL AND SQUARE, SHALL BE FINISHED, CLEANED, POLISHED AND READY FOR OCCUPANCY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY AND ALL DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES. CONTRACTOR IS TO COORDINATE WITH THE TENANT/OWNER FOR SECURITY CLEARANCES AND HOURS OF OPERATION. COORDINATE WORK AFTER HOURS (EVENINGS AND WEEKENDS) WITH THE OWNER TO PREVENT SETTING OFF FIRE ALARMS. COORDINATE SCHEDULING OF ALL WORK WITH THE TENANT/OWNER. CONTRACTOR AND ALL ASSOCIATED PERSONNEL SHALL NOT ENGAGE IN DISRUPTIVE CONSTRUCTION ACTIVITIES DURING TENANT’S/OWNERS/OTHER BUILDING TENANTS’ NORMAL BUSINESS HOURS. WORK TO BE PERFORMED IN AREAS AFFECTING THE OTHER BUILDING TENANTS SHALL BE COORDINATED WITH THE OWNER AND THE OTHER BUILDING TENANTS. CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY CLEAN UP FOLLOWING WORK PERFORMED IN OCCUPIED AREAS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING CONSTRUCTION AND FOR DAILY CLEAN UP FOLLOWING WORK PERFORMED IN OCCUPIED AREAS. PERFORM FINAL CLEANING AT THE END OF EACH PHASE OF WORK. REMOVE ALL TRASH AND DEBRIS FROM THE SITE. WASH ALL TILE, LAMINATE AND GLASS SURFACES, PLUMBING FIXTURES, ETC. DUST AND SWEEP TO REMOVE ALL DIRT. REMOVE ALL TEMPORARY LABELS. PROJECT IS TO BE COMPLETED, CLEAN AND IN MOVE IN CONDITION. REMOVE ALL UNUSED MATERIALS, TRASH DEBRIS, TOOLS AND EQUIPMENT FROM THE SITE. CONTRACTORS SHALL BE RESPONSIBLE FOR REPAIR OF ANY DAMAGE TO ALL TENANT AND BUILDING SPACES CAUSED BY THEIR ACTIONS OR NEGLECT. STREETS, DRIVEWAYS, UNDERGROUND SERVICES, ETC. DAMAGE IN ANY WAY ATTRIBUTABLE TO CONSTRUCTION SHALL BE RESTORED BY THE CONTRACTOR TO THEIR ORIGINAL CONDITIONS. CONTRACTOR SHALL COORDINATE THE USE OF BUILDING LOADING AREAS, DELIVERY TIMES AND LOCATIONS, WORK ON UTILITIES AND ANY OTHER WORK WHICH MAY DISRUPT THE NORMAL FLOW AND OPERATION OF THE BUILDING OR CONCURRENT CONSTRUCTION ACTIVITIES WITH THE OWNER. DIMENSION NOTES: A. ALL EXTERIOR DIMENSIONS ARE TO FACE OF FOUNDATION AND/OR FACE OF EXTERIOR SHEATHING. B. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS UNLESS NOTED OTHERWISE. CONTRACTOR SHALL SUBMIT MSDS SHEETS FOR ALL MATERIALS USED IN CONSTRUCTION TO THE TENANT AND THE OWNER AND SHALL KEEP COPIES OF ALL MSDS SHEETS ON SITE AT ALL TIMES. SMOKING IS PROHIBITED IN THE CONSTRUCTION AREA FOR SAFETY PURPOSES. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE AND MAINTAIN ALL NECESSARY TEMPORARY BARRICADES, SHORING AND LIGHTING. CONTRACTOR IS TO ERECT DUST BARRICADES TO PROTECT OCCUPIED AREAS OF THE BUILDING DURING DEMOLITION AND CONSTRUCTION. COORDINATE WITH OWNER FOR APPROVAL OF BARRIER LOCATIONS PRIOR TO ERECTION OF BARRIERS. THE CONTRACTOR SHALL PROVIDE AND INSTALL BARRICADES AND TEMPORARY SIGNAGE, AS REQUIRED TO DIRECT OCCUPANT FLOW AS REQUIRED AND TO ESTABLISH ROUTES OF EGRESS FOR EMPLOYEES. CONTRACTOR SHALL EMPLOY OTHER MEANS AS SITE CONDITIONS MAY REQUIRE. TEMPORARY DUST BARRIERS, UNLESS EQUIVALENT BARRIERS CAN BE PROVIDED, SHALL BE SEALED, FULLY TAPED, DOUBLE LAYERS OF 4 MIL MINIMUM PLASTIC SHEET WITH STAGGERED JOINTS ON TEMPORARY FRAMING. ALL EARTHWORK, EXCAVATION, BACKFILLING AND EROSION CONTROL OPERATIONS SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE GEOTECHNICAL REPORT FOR THIS PROJECT. BUILDING ENVELOPE THERMAL PERFORMANCE AND ALL MECHANICAL, ELECTRICAL AND PLUMBING DESIGN SHALL COMPLY WITH ASHRAE 90.1-04. DEMOLITION UNLESS NOTED OTHERWISE, REMOVE ALL EXISTING TENANT AND OWNER IMPROVEMENTS AS REQUIRED TO CLEAR SPACE FOR NEW IMPROVEMENTS AS SHOWN ON THE DRAWINGS AND AS DESCRIBED BELOW: DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, ALL FLOOR COVERINGS, BASE, RESIDUAL ADHESIVE, STAPLES AND NAILS IN FLOOR, WALL COVERINGS, HARDWARE, DOORS, FRAMES, CASEWORK, ABANDONED SUPPORTS, FASTENERS, TRIM, INTERIOR PARTITIONS, ACOUSTIC CEILING PANELS, T-BAR CEILING GRIDS, FLOOR DEVICES AND ANY OTHER ITEMS AS NOTED ON DRAWINGS. REMOVE ALL PLUMBING, HVAC AND ELECTRICAL COMPONENTS THAT ARE ASSOCIATED WITH DEMOLISHED WALLS, CEILINGS AND AS NOTED. ALL CEILINGS ARE TO BE REMOVED TO THE DECK UNLESS OTHERWISE SPECIFIED. ALL ITEMS NOT SHOWN OR NOTED TO BE REMOVED ARE TO REMAIN UNLESS IN DIRECT CONFLICT WITH NEW WORK. REMOVE ALL DEMOLITION DEBRIS FROM SITE AND DISPOSE OF LEGALLY. Xavier University 1624 Herald Avenue Cincinnati, OH 45207 ARCHITECT: Cintas Center - Courtside Club OWNER: THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects DATE 08/05/2015 NO. DATE ISSUED FOR CONSTRUCTION REVISION PLUMBING DEMOLITION: REMOVE ALL PIPING ASSOCIATED WITH FIXTURES/DEVICES THAT ARE TO BE REMOVED. REMOVE BACK TO NEAREST JUNCTION AND CAP. ALL TERMINATIONS SHALL BE CONCEALED BEHIND WALLS OR CEILINGS. REMOVE ALL OLD PLUGGED OR CAPPED PIPES BACK BEHIND FINISHED WALL SURFACE. WHERE PIPING BRANCHES ARE COMPLETELY ELIMINATED, REMOVE BACK TO MAIN DISTRIBUTION. ELECTRICAL DEMOLITION: REMOVE CONDUIT AND WIRE ASSOCIATED WITH DEMOLISHED ELECTRICAL DEVICES BACK TO NEXT ACTIVE DEVICE OR PANELBOARD IF THE CIRCUIT IS COMPLETELY UNLOADED. WIRING SHALL REMAIN WHERE CIRCUITS ARE REQUIRED TO SERVE NEW LOADS OR ELECTRICAL ITEMS THAT ARE REPLACED. THE TENANT/OWNER MAY REQUEST SOME ITEMS TO BE SALVAGED AND STOCK PILED. COORDINATE WITH TENANT’S/OWNER'S REPRESENTATIVE. PROVIDE SUFFICIENT BRACING AS REQUIRED TO PROTECT EXISTING SPACES AND FINISHES. REBUILD EXISTING STRUCTURES THAT ARE TO REMAIN IF THEY WOULD OTHERWISE BECOME UNSTABLE DURING DEMOLITION. PATCH PENETRATIONS IN FLOOR AND WALLS RESULTING FROM DEMOLITION. RESTORE DAMAGE TO FIRE RATED SYSTEMS INCLUDING FIREPROOFING. RE-LAMINATE ALL WALLS AS REQUIRED. REMOVE COMBUSTIBLE MATERIALS FROM CEILING PLENUM OR ENCASE AS ACCEPTED BY BUILDING INSPECTOR. COVER "GLUE SPOTS" WITH FIRE-RETARDANT PAINT. ANY WINDOW GLASS BROKEN DURING DEMOLITION IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST BE REPLACED BEFORE THE JOB IS COMPLETED. CUTTING AND PATCHING ALL CUTTING AND PATCHING FOR HVAC, PLUMBING, AND ELECTRICAL ARE TO BE PERFORMED BY OR COORDINATED WITH THE GENERAL CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR PROVIDING AN ACCEPTABLE FINAL FINISH AND APPEARANCE OF AFFECTED AREAS. PROJECT NO. 00000.00 DRAWING TITLE COVER SHEET G0.0a 8" BOND BEAM 8' - 0" - TYP EXISTING BULKHEAD AND CEILING ASSEMBLY ALL EXISTING STORAGE UNITS, FRAMING AND METAL PANELS TO BE REMOVED WITHIN THE FOOTPRINT OF NEW WORK L2 ACCENT LIGHT TO BE DETERMINED L3 VERTICAL REINFORCEMENT VERTICAL REINFORCEMENT 5/8" GYP. BOARD 7/8" FURRING HAT CHANNEL 1/2" STAINLESS STEEL DRINK RAIL CLADDING ON TOP OF PLYWOOD SUPPORT ADHESIVE DOWEL INTO STRUCTURAL SLAB ON GRADE 5/8" GYP. BOARD 7/8" FURRING HAT CHANNEL 1/2" FURRING WOOD SHIM ADHESIVE DOWEL INTO STRUCTURAL SLAB ON GRADE 1.MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM TO ALL REQUIREMENTS OF "SPECIFICATIONS FOR MASONRY STRUCTURES” (ACI 530.1-08/ASCE 6-08/TMS 602-08) EXCEPT AS MODIFIED BY THE REQUIREMENTS OF THESE CONTRACT DOCUMENTS. VERTICAL REINFORCEMENT 2.CONCRETE MASONRY UNITS: ASTM C90 TYPE I (LIGHTWEIGHT), 1900 PSI UNIT STRENGTH. 3.VERTICAL REINFORCEMENT SHALL BE #5 @ 24”oc PLACED AT THE CENTER OF WALL. VERTICAL DOWELS SHALL MATCH VERTICAL REINFORCEMENT SIZE, SPACING, AND LOCATION. PROVIDE 45-INCH LAP TO VERTICAL REINFORCEMENT AND 6-INCH EMBEDMENT INTO STRUCTURAL SLAB ON GRADE. HILTI HIT-RE 500-SD EPOXY SHALL BE USED. ADHESIVE DOWEL INTO STRUCTURAL SLAB ON GRADE ADHESIVE DOWEL INTO STRUCTURAL SLAB ON GRADE 4.PROVIDE CONTINUOUS BOND BEAMS AT THE TOP OF WALL AND AT WALL MID-HEIGHT (8’0” ABOVE EXISTING FLOOR). REINFORCE WITH (2) #4 CONTINUOUS. 1/2" 2 1/2" 1/2" FURRING WOOD SHIM VERTICAL REINFORCEMENT CMU CONSTRUCTION NOTES 8" LIGHTWEIGHT CMU BLOCK WALL 9' - 4" UNCONNECTED HEIGHT 2 3/4" 4' - 0" TYP 8" BOND BEAM 8" LIGHTWEIGHT CMU BLOCK WALL 8" LIGHTWEIGHT CMU BLOCK WALL 9' - 4" UNCONNECTED HEIGHT 16' UNCONNECTED HEIGHT 8" LIGHTWEIGHT CMU BLOCK WALL 16' UNCONNECTED HEIGHT 2 3/4" 8" BOND BEAM L1 DEMO NOTES 2" CLEAR 8" BOND BEAM 2" CLEAR LIGHTING LEGEND EXISTING BULKHEAD AND CEILING ASSEMBLY 5.MORTAR: ASTM C270, TYPE S (2) 1/2" PLYWOOD SUPPORT WELD SUPPORT CONNECTION @ STEEL DRINK RAIL SUPPORT TYPE 1 TYPE 2 TYPE 3 6.GROUT: ASTM C476. SLUMP 8” TO 11”. MINIMUM COMPRESSIVE STRENGTH = 2000 PSI AT 28 DAYS. TYPE 4 WALL TYPES 6 A1.0a 7.REINFORCING STEEL: ASTM A615, ASTM A706, OR ASTM A996, 60 KSI YIELD. 3/4" = 1'-0" STEEL DRINK RAIL SUPPORT @ EACH VERTICAL GUARDRAIL, PAINTED BLACK 8.HORIZONTAL JOINT REINFORCING FOR SINGLE WYTHE CONCRETE MASONRY: ASTM A951 9 GAGE LADDER TYPE. HOT DIPPED GALVANIZED PER ASTM A153 CLASS B. PLACE HORIZONTAL JOINT REINFORCING AT 16" CENTERS VERTICALLY FOR CONCRETE MASONRY. LAP HORIZONTAL JOINT REINFORCING 6” MINIMUM. HORIZONTAL JOINT REINFORCING SHALL BE DISCONTINUOUS ACROSS MOVEMENT JOINTS. STEEL WIRE HANGER ATTACHED TO EXISTING DECKING ABOVE, TYP. 1-5/8" METAL SUPPORTS. REFER TO MANUFACTURER NOTES STAINLESS STEEL HSS 2x2x0.25 SUPPORT, PAINTED BLACK CEILING @ 12'-0" AFF 9.PROVIDE PREFABRICATED “L” AND ”T” SHAPED HORIZONTAL JOINT REINFORCING AT WALL INTERSECTIONS. 3/8" PLASTIC EGG CRATE CEILING, BLACK. REFER TO MANUFACTURER NOTES 10.RUNNING BOND PATTERN SHALL BE USED FOR ALL MASONRY WORK UNLESS OTHERWISE NOTED. ATTACH RAIL TO DECK w/ (4) 1/8" BOLTS FINISH SCHEDULE SUSPENDED LINEAR LIGHT - SEE RCP FOR SIZE AND LOCATION Name EXISTING CONCRETE SLAB STORAGE COURTSIDE CLUB DRINK RAIL 101 100 Wall Finish Wall Finish Wall Finish Wall Finish North East South West PT-1 GRAPHIC PT-1 GRAPHIC PT-1 OPEN PT-1 OPEN Ceiling Finish 12.ALL REINFORCING STEEL SHALL BE SUPPORTED AND FASTENED TO APPROVED POSITIONERS LOCATED AT 192 BAR DIAMETERS MAXIMUM SPACING AND WITH A MINIMUM OF TWO POSITIONERS PER GROUT POUR (ONE NEAR THE BOTTOM AND ONE NEAR THE TOP) TO PREVENT DISPLACEMENT DURING THE PLACEMENT OF GROUT. OPEN 2x2 EGG CRATE CEILING CONNECTION DETAIL 3/4" = 1'-0" EXISTING OFFICE EXISTING DOCK DOOR EXISTING MECHANICAL EXISTING OFFICE EXISTING OFFICE 4' - 0" EXISTING CORRIDOR 4 2 1 TV TO BE PROVIDED BY OWNER 3 HATCH REPRESENTS EGG CRATE MATERIAL OF CEILING L2 LINE OF BULKHEAD ABOVE 12' - 0" 6' - 0" ALIGN L1 4 L1 A1.0a CORRIDOR EXISTING COLUMN TO REMAIN EXISTING COLUMN TO REMAIN 2 Sim 9/17/2015 3:57:54 PM NEW DRINK RAIL STORAGE 101 572 SF 2' x 2' SYSTEM - EGG CRATE PANEL 12' - 0" A.F.F. EXISTING DOCK AREA L1 THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects EXISTING BULKHEAD @ 9'-6" AFF 20' - 0" C:\Users\nschoeppner\Documents\Revit Local\CINTAS_CENTRAL-HOST_v14_nschoeppner.rvt 26' - 0" A1.0a L2 36' - 0" COURTSIDE CLUB 100 973 SF 3 L1 EXISTING COLUMN TO REMAIN TV TO BE PROVIDED BY OWNER EXISTING COLUMN TO REMAIN EXISTING DOCK DOOR Xavier University 1624 Herald Avenue Cincinnati, OH 45207 EXISTING OFFICE 9' - 6" EXISTING MECHANICAL Cintas Center - Courtside Club 1 1/2" = 1'-0" 4' - 0" 3 A1.0a 4 A1.0a Number 11.PROVIDE MOVEMENT (CONTROL AND EXPANSION) JOINTS IN WALLS WHERE INDICATED. BOND BEAMS SHALL BE DISCONTINUOUS ACROSS MOVEMENT JOINTS UNLESS NOTED OTHERWISE. DATE EXISTING CEILING GRID TO REMAIN 08/05/2015 L2 ISSUED FOR CONSTRUCTION L1 1 1 L1 ALIGN +/- 11'-0" 24' - 0" 6' - 0" REVISION --- 1 NEW DRINK RAIL A1.0a NO. DATE L1 - 3 18' - 0" 10' - 11 5/8" 48' - 0" L2 EXISTING CORRIDOR L1 PROJECT NO. 00000.00 DRAWING TITLE COURTSIDE CLUB DESIGN 1 A1.0a COURTSIDE CLUB FLOOR PLAN 1/4" = 1'-0" 2 A1.0a COURTSIDE CLUB RCP 1/4" = 1'-0" A1.0a GENERAL NOTES MECHANICAL CONTRACTOR SHALL CAREFULLY COORDINATE DUCTWORK AND OUTLET LOCATIONS WITH ALL OTHER TRADES BEFORE FABRICATING ANY DUCTWORK. ALL DUCTWORK SHALL BE INSTALLED AS TIGHT TO THE STRUCTURE AS POSSIBLE. ALL CONNECTIONS TO CEILING OUTLETS SHALL BE SAME SIZE DUCTWORK AS OUTLET NECK SIZE. CONNECTIONS TO CEILING OUTLETS SHALL BE MADE WITH FLEX. DUCTWORK (MIN. LENGTH 9"; MAX. LENGTH 72"). IF AN ELBOW IS INSTALLED DIRECTLY AT A CEILING OUTLET IT SHALL BE A SHEET METAL ELBOW. ALL CONDITIONS SHALL BE FIELD VERIFIED BEFORE ORDERING EQUIPMENT OR FABRICATING MATERIAL. REFER TO SPECIFICATIONS FOR COORDINATION. 3. ST O EXIST 8"Ø CD 252 CFM E F 4. FOR ADDITIONAL INFORMATION CONCERNING FAN COIL UNIT, SEE SCHEDULE AND DETAILS. 5. ALL SQUARE THROATED ELBOWS SHALL HAVE AIRFOIL TURNING VANES AND SHALL ONLY BE USED WHEN RADIUS ELBOWS WILL NOT FIT. 6. THE MECHANICAL CONTRACTOR SHALL VISIT THE JOB SITE AND CHECK AND VERIFY ALL EXISTING CONDITIONS BEFORE BIDDING. ANY DISCREPANCIES DISCOVERED BETWEEN EXISTING CONDITIONS AT THE SITE AND THOSE SHOWN ON THE DRAWING SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER, IN WRITING. 7. ALL ROUND DUCTWORK TO BE UNITED MCGILL OR EQUAL DOUBLE WALL INSULATED SPIRAL DUCTWORK - 2" PRESSURE CLASS. 8. ALL SUPPLY DIFFUSERS TO BE TITUS OMNI OR EQUIVALENT. E OF OH I O DAVID WAHOFF E-59973 PR INSTALL A MANUAL DAMPER IN ALL BRANCH DUCTS, INCLUDING CONNECTIONS TO ALL CEILING OUTLETS. ALL ROUND CONNECTIONS TO MAIN AND TRUNK DUCTS SHALL BE MADE WITH CONICAL FITTINGS. AT SS RE G I S T ERED I ON L A EN R 2. EE UNLESS OTHERWISE NOTED, ALL DUCTWORK SHOWN IS NEW. REMOVE ALL EXISTING DUCTWORK NOT USED IN FINAL ARRANGEMENT. N 1. G I DATE: Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 MEP Design Security Commissioning Sustainable Design Design/Build EXIST 8"Ø CD 252 CFM EXIST EHC-2 EXIST EHC-3 100 CFM EXIST 8" X 4" DUCT EXIST 12" X 8" DUCT EXIST 16" X 8" DUCT EXIST 31 34" X 13" DNTO UNIT FCU-24 EXIST 18" X 14" DUCT EXIST FLEX EXIST 18" X 12" DUCT DIM-LF-1A OA-14"Ø S8L4-175 M.D. 48X14 EGG CRATE R.G. R-777 CFM OA-14" Ø DN. S8L4-200 M.D. FCU-26 S8L4-200 S8L4-175 S-14"Ø 2' x 2' SYSTEM - EGG CRATE PANEL 12' - 0" A.F.F. S-16"Ø S-14"Ø Xavier University 1624 Herald Avenue Cincinnati, OH 45207 Cintas Center - Courtside Club EXIST 12" X 8" S8L4-200 THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects S8L4-175 DATE 09/22/15 ISSUED FOR PERMIT S-12"Ø S8L4-200 8/14/2015 1:24:18 PM C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt S8L4-175 NO. DATE REVISION S8L4-100 PROJECT NO. XU.2014.08 N DRAWING TITLE HVAC FLOOR PLAN FLOOR PLAN SCALE: 1/4" = 1'-0" W E S M2.1 ST E OF OH I O F SS G I S T ERED I ON L A EN EE RE N O E R DAVID WAHOFF E-59973 PR VENTILATION AIR SCHEDULE AT G I DATE: Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 MEP Design Security Commissioning Sustainable Design Design/Build FAN COIL UNIT SCHEDULE DETAIL - FAN COIL PIPING TAP FROM BOTTOM OF DUCT TAP FROM SIDE OF DUCT DETAIL - OUTLET CONNECTION SCALE: NOT TO SCALE Xavier University 1624 Herald Avenue Cincinnati, OH 45207 LEGEND Cintas Center - Courtside Club NOT TO SCALE THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects DATE 8/14/2015 1:24:18 PM C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt 09/22/15 ISSUED FOR PERMIT NO. DATE REVISION PROJECT NO. XU.2014.08 DRAWING TITLE HVAC DETAILS M5.1 GENERAL NOTES: A. ALL CONDUITS SHALL BE 3/4" UNLESS OTHERWISE NOTED. HOMERUNS: LESS THAN 50' - No. 12 CONDUCTOR 50' TO 100' - No. 10 CONDUCTOR 100' OR MORE - No. 8 CONDUCTOR ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE LATEST EDITIONS OF CODES AND STANDARDS AS FOLLOWS. ELECTRIC WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA NATIONAL ELECTRIC CODE, NBS NATIONAL ELECTRIC SAFETY CODE, NFPA STANDARDS. ELECTRIC MATERIALS SHALL BE U.L. LISTED AND COMPLY WITH NEMA STANDARDS. O ALL BRANCH CIRCUIT WIRING IN CHANNELS, WIREWAYS, FIXTURES OR CONDUITS SHALL BE TYPE THHN STRANDED AND FACTORY COLOR CODED. F. CONDUIT CONCEALED ABOVE CEILINGS OR IN WALLS SHALL BE EMT TYPE UNLESS OTHERWISE NOTED - SEE SPECS. G. THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND CHECK AND VERIFY ALL EXISTING CONDITIONS BEFORE BIDDING. ANY DISCREPANCIES DISCOVERED BETWEEN EXISTING CONDITIONS AT THE SITE AND THOSE SHOWN ON THE DRAWING SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER, IN WRITING. H. ELECTRIC CONTRACTOR SHALL BE LICENSED AND CERTIFIED IN THE STATE OF OHIO. I. WHERE ANY NEW CONDUIT PASSES THROUGH EXISTING WALLS, ELECTRIC CONTRACTOR SHALL PROVIDE ALL CUTTING, PATCHING OF WALLS AND PROTECT OPENING WITH THROUGH-PENETRATION FIRESTOP SYSTEM. J. THE CONTRACTOR SHALL EXERCISE ADEQUATE PROTECTIVE AND SAFETY MEASURES FOR ALL PERSONS AND PROPERTY AND SHALL BE RESPONSIBLE FOR ANY DAMAGES OR INJURIES ARISING FROM THE EXECUTION OF THIS WORK. E F E. METAL CONDUITS, WIREWAYS, AND EQUIPMENT ENCLOSURES SHALL NOT BE USED AS EQUIPMENT GROUND CONDUCTORS. AT E OF OH I O DAVID WAHOFF E-59973 PR D. ST SS RE G I S T ERED I ON L A EN R C. EE ALL CONDUCTORS INCLUDING BRANCH CIRCUIT CONDUCTORS AND CONTROL WIRING SHALL BE INDIVIDUALLY IDENTIFIED AT BOTH ENDS AND AT EACH TERMINATION. N B. G I DATE: Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 MEP Design Security Commissioning Sustainable Design Design/Build SCOPE OF WORK DIM-LF-1A LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) LF-1A (LP-A-41a) 2' x 2' SYSTEM - EGG CRATE PANEL 12' - 0" A.F.F. LF-1A (LP-A-41a) LF-1A (LP-A-41a) Xavier University 1624 Herald Avenue Cincinnati, OH 45207 Cintas Center - Courtside Club 1. INSTALL 20 NEW LIGHT FIXTURES AND 2 NEW SWITCHES. THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects LF-1A (LP-A-41b) DATE LF-1A (LP-A-41b) LF-1A (LP-A-41b) 09/22/15 ISSUED FOR PERMIT 8/14/2015 1:24:18 PM C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt DIM-LF-1B LF-1A (LP-A-41b) LF-1A (LP-A-41b) NO. DATE REVISION LF-1A (LP-A-41b) LF-1A (LP-A-41b) LF-1A (LP-A-41b) LF-1A (LP-A-41b) LF-1A (LP-A-41b) PROJECT NO. XU.2014.08 N FLOOR PLAN SCALE: 1/4" = 1'-0" W DRAWING TITLE E S ELECTRIC LIGHTING FLOOR PLAN E2.1 GENERAL NOTES: A. ALL CONDUITS SHALL BE 3/4" UNLESS OTHERWISE NOTED. HOMERUNS: LESS THAN 50' - No. 12 CONDUCTOR 50' TO 100' - No. 10 CONDUCTOR 100' OR MORE - No. 8 CONDUCTOR ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE LATEST EDITIONS OF CODES AND STANDARDS AS FOLLOWS. ELECTRIC WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA NATIONAL ELECTRIC CODE, NBS NATIONAL ELECTRIC SAFETY CODE, NFPA STANDARDS. ELECTRIC MATERIALS SHALL BE U.L. LISTED AND COMPLY WITH NEMA STANDARDS. O ALL BRANCH CIRCUIT WIRING IN CHANNELS, WIREWAYS, FIXTURES OR CONDUITS SHALL BE TYPE THHN STRANDED AND FACTORY COLOR CODED. F. CONDUIT CONCEALED ABOVE CEILINGS OR IN WALLS SHALL BE EMT TYPE UNLESS OTHERWISE NOTED - SEE SPECS. G. THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND CHECK AND VERIFY ALL EXISTING CONDITIONS BEFORE BIDDING. ANY DISCREPANCIES DISCOVERED BETWEEN EXISTING CONDITIONS AT THE SITE AND THOSE SHOWN ON THE DRAWING SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER, IN WRITING. H. ELECTRIC CONTRACTOR SHALL BE LICENSED AND CERTIFIED IN THE STATE OF OHIO. I. WHERE ANY NEW CONDUIT PASSES THROUGH EXISTING WALLS, ELECTRIC CONTRACTOR SHALL PROVIDE ALL CUTTING, PATCHING OF WALLS AND PROTECT OPENING WITH THROUGH-PENETRATION FIRESTOP SYSTEM. J. THE CONTRACTOR SHALL EXERCISE ADEQUATE PROTECTIVE AND SAFETY MEASURES FOR ALL PERSONS AND PROPERTY AND SHALL BE RESPONSIBLE FOR ANY DAMAGES OR INJURIES ARISING FROM THE EXECUTION OF THIS WORK. E F E. METAL CONDUITS, WIREWAYS, AND EQUIPMENT ENCLOSURES SHALL NOT BE USED AS EQUIPMENT GROUND CONDUCTORS. AT E OF OH I O DAVID WAHOFF E-59973 PR D. ST SS RE G I S T ERED I ON L A EN R C. EE ALL CONDUCTORS INCLUDING BRANCH CIRCUIT CONDUCTORS AND CONTROL WIRING SHALL BE INDIVIDUALLY IDENTIFIED AT BOTH ENDS AND AT EACH TERMINATION. N B. G I DATE: Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 MEP Design Security Commissioning Sustainable Design Design/Build SCOPE OF WORK D TV 96" AFF (RP-A-20) (RP-A-20) 2 1 3 D TV 96" AFF (RP-A-26) PROVIDE NEW 208V, 1PH CONNECTION TO NEW FCU-26 FED FROM EXISTING PANEL RP-A. 12' - 0" 6' - 0" (RP-A-26) FCU-26 (RP-A-22,24) 2 36' - 0" MAKE CONNECTION TO EXISTING FIRE ALARM CONTROL PANEL. COURTSIDE CLUB 100 973 SF STORAGE 101 572 SF 26' - 0" (RP-A-26) (RP-A-26) THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects 20' - 0" D TV 96" AFF (RP-A-26) Xavier University 1624 Herald Avenue Cincinnati, OH 45207 4 4D (RP-A-20) D TV 96" AFF (RP-A-20) (RP-A-20) 4' - 0" 4' - 0" 9' - 6" 2. INSTALL96 NEW DUPLEX OUTLETS, 4 NEW DATA JACKS FOR TVS, 1 QUAD OUTLET WITH 4 DATA FOR MOBILE BAR USE, AND 1 HORN STROBE. EXTEND POWER FROM EXISTING PANEL RP-A TO SERVE NEW FCU-26. Cintas Center - Courtside Club 1. DATE 1 09/22/15 1 ISSUED FOR PERMIT 8/14/2015 1:24:18 PM NO. DATE +/- 11'-0" 24' - 0" 6' - 0" REVISION 18' - 0" 48' - 0" 10' - 11 5/8" C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt 1 PROJECT NO. XU.2014.08 N FLOOR PLAN SCALE: 1/4" = 1'-0" W DRAWING TITLE E S ELECTRIC POWER FLOOR PLAN E3.1 LUMINAIRE SCHEDULE SYMBOL DESIGNATION MANUFACTURER MODEL NO. NOMINAL DIMENSIONS W X L LAMP/ BULB TYPE CONFIGURATION LAMPS WATTS LCS4-35HL-EDU-GLR-CSWG4 4" x 48" x 2"HIGH LED SUSPENDED 3500K 55W MANUFACTURER LF-1A COLUMBIA LIGHTING LEGEND LENS/ REFLECTOR SYMBOL DESCRIPTION WIREGUARD DESCRIPTION LIGHT FIXTURE - NEW LED STRIPLIGHT GROUNDING TYPE DUPLEX RECEPTACLE - WALL MOUNTED DATA RECEPTACLE WALL MOUNTED - NUMBER INDICATES NO. OF DATA JACKS 75cd SHADED LUMINAIRES INDICATE NIGHT LIGHTS, FED FROM A CENTRAL INVERTER FOR EMERGENCY ST FIRE ALARM HORN/STROBE - 75cd INDICATES CANDELA RATING ELECTRIC PANEL EVLA-L CIRCUIT No. 27 TO PANEL EVLA-L PR (EVLA-L-27) O S3W-EVLA-R1-17a SINGLE-GANG SWITCH DOUBLE-GANG SWITCH E F SINGLE POLE SWITCH - PANEL EVLA-L - CIRCUIT 27a S-EVLA-L-27a THREE WAY SWITCH - PANEL EVLA-R1 - CIRCUIT 17a E OF OH I O DAVID WAHOFF E-59973 NOT TO SCALE N.T.S. AT SS RE G I S T ERED I ON L A EN R DIM - 0-10VDC DIMMING EE 2D LED- LIGHT EMITTING DIODE N LEGEND: G I DATE: THREE-GANG, TWO SWITCHES, ONE DIMMER Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 MEP Design Security Commissioning USB CHARGING DUPLEX RECEPTACLE DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE Sustainable Design Design/Build DOUBLE-GANG, ONE SWITCH ONE DUPLEX RECEPTACLE. NOTE: WHERE PRACTICAL, ALIGN SWITCHES AND RECEPTACLES. TYPICAL RECEPTACLE AND SWITCH PLATE DETAIL NOT TO SCALE EXISTING PANEL No. LP-A ACC CCT LTG - 01A05, 6, 7, 10, 25 AMP 20 POLE 1 NO 1 LTG - 01A04, 20, 21, 23 20 1 3 LTG - 01A24 HID 20 1 5 LTG - 01A24 HID 20 1 7 LTG - 01B02, 3, 4, 5, 6 20 1 9 TERM. BOX B15-6 (01A05) 20 1 11 PEC 20 1 13 AMPERE A 3.7 4.0 15 3 UH-1 (01A24) 15 3 FCU-24 (01A24) 20 3 UH-2 (01A24) 15 3 LTG - 01A01, 2 20 1 39 LTG - COURTSIDE CLUB 20 1 41 1 20 10 1 20 3 14 1.7 2.0 20 16 1.7 2.0 1 20 1 POLE 1 NO 1 RECP 20 1 3 RECP 20 1 5 RECP - OFFICE/COMMISSARY 20 1 7 RECP - FIRE COMMAND 20 1 9 RECP - CONTROL ROOM 20 1 11 RECP - GREEN ROOM 20 1 13 RECP - T.R. 01A30, 31 20 1 15 RECP - LOUNGE (01A60) 20 1 17 SPARE 20 1 19 CP-3 (1/12 HP) 20 1 21 EWC - 01A04 20 1 23 SUMP PUMP - ELEV PIT #1 20 1 25 LTG/RECP - ELEV PIT #1 20 1 27 LTG/RECP - ELEV PIT #2 20 1 29 SUMP PUMP - ELEV PIT #2 20 1 31 RECIRC PUMPS 20 1 33 SPARE 20 1 35 SPARE 20 1 37 SPARE 20 1 39 SEAT LIGHTS 20 1 41 A 0.9 1.2 B 20 1.7 2.7 15 3 0.7 0.7 0.9 1.3 0.7 0.9 0.9 0.9 0.0 1.1 0.2 41 26 3.5 2.0 15 3 TERM. BOX CVB17-6 (01A53) 30 3.5 1.7 20 1 TERM. BOXES B12-6, B21-6, B27-6 32 2.5 1.7 34 2.5 2.4 15 3 0.5 0.0 0.5 0.0 1.0 0.0 0.5 0.0 TERM. BOX CVB22-6 (01A06) 0.0 0.0 36 2.5 1.7 38 0.7 2.4 40 4.0 1.7 42 15 3 0.0 0.0 0.0 0.0 TERM. BOX B13-6 (01A06) MAINS : 225 AMP M.L.O. 25% OF CONTINUOUS LOAD 9.03 8.08 9.73 VOLTAGE RATING : 480Y/277V, 3PH, 4W 0 0 0 SHORT CIRCUIT RATING : 42,000 AMPS AIC 1.0 1.0 1.0 PANEL MOUNTING : SURFACE - - - FEEDER SIZE : (4) #2/0 CU 45.13 40.38 48.63 MAIN O. C. P. D. : 175A CB IN PP-1 SUBTOTAL : CONTINUOUS LOAD 3 SEAT MOTORS (4) 8 20 1 PRACTICE GYM RECEPTACLES 10 20 1 PRACTICE GYM RECEPTACLES 12 20 1 PRACTICE GYM RECEPTACLES 14 20 1 PRACTICE GYM RECEPTACLES 16 20 1 PRACTICE GYM CLG FANS 18 20 1 PRACTICE GYM CLG FANS 20 20 1 COURTSIDE CLUB RECP NORTH WALL 100 2 FCU-26 26 20 1 COURTSIDE CLUB RECP EAST WALL 28 20 1 SPARE 30 20 1 SPARE 32 20 1 SPARE 34 20 1 SPARE 36 20 1 SPARE 38 20 1 SPACE 40 20 1 SPACE 0.5 0.0 42 20 1 SPACE 7.0 45.9 47.4 MAINS : 150 AMP 1.75 11.5 11.9 VOLTAGE RATING : 208Y/120V, 3PH, 4W NON-CONTINUOUS LOAD 2.0 1.2 1.2 SHORT CIRCUIT RATING : 10,000 AMPS AIC DEMAND FACTOR 1.9 1.0 1.0 PANEL MOUNTING : SURFACE - - - FEEDER SIZE : (4) #1/0 CU 10.7 58.6 60.5 MAIN O. C. P. D. : 150A MCB 25% OF CONTINUOUS LOAD DERATED NON-CONTINUOUS LOAD TOTAL NEC LOAD PANEL LOAD SUMMARY EXISTING MAXIMUM kW DEMAND PER UTILITY = 103.3 kW EXISTING LOADS BEING REMOVED = 0 kW EXISTING MAXIMUM kW DEMAND PER UTILITY = 20.7 kW EXISTING LOADS BEING REMOVED = 0 kW NEW LOADS BEING ADDED = 4.2 kW NEW LOADS BEING ADDED = 30.24 kW TOTAL LOAD BEING INCREASED BY = 4.2 kW TOTAL LOAD BEING INCREASED BY = 30.24 kW NEW TOTAL EXISTING AND NEW LOADS ON EXISTING SERVICE = 103.3 kW +4.2 kW = 107.5 kW New Calculated load = EXISTING 225A, 480Y/277V,3PH,4W SERVICE AND EQUIPMENT ARE ADEQUATE FOR NEW LOADS 129.4 Amps ACC 24 1.0 .9 28 3.5 2.7 20 22 1.0 41 24 2.4 2.0 POLE 6 0.9 0.5 EC-1 (T.R. , QUAD A) CIRCUIT DESCRIPTION AMP 4 0.9 0.7 22 1.7 2.7 NO 0.7 1.2 CUH-1 (2 IN 01A02) TERM. BOX CVB16-6 (01A63) C C/B 2 LTG - QUAD A SOUTHEAST EHC-2 (01A20), EHC-3 (01A21) CCT 0.7 1.2 18 2.4 2.0 PANEL LOAD SUMMARY C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt AMP 20 AMPERE LTG - QUAD A NORTHEAST 38.9 TOTAL NEC LOAD CCT LTG - QUAD A WEST 32.3 DERATED NON-CONTINUOUS LOAD C/B ACC 36.1 DEMAND FACTOR 8/14/2015 1:24:18 PM ACC SUBTOTAL : CONTINUOUS LOAD NON-CONTINUOUS LOAD CIRCUIT DESCRIPTION 12 0.2 4.0 35 37 CIRCUIT DESCRIPTION 8 4.6 3.4 33 1 20 6 1.9 3.3 29 31 POLE 20 4 2.7 3.3 27 AMP 2 23 25 NO 3.6 2.4 21 C/B RECP - CORR 17 19 C 2.6 3.6 15 TERM. BOX B14-6 (01A10) B CCT NEW TOTAL EXISTING AND NEW LOADS ON EXISTING SERVICE = 20.7 kW +30.24 kW = New Calculated load = Xavier University 1624 Herald Avenue Cincinnati, OH 45207 C/B Cintas Center - Courtside Club CIRCUIT DESCRIPTION EXISTING PANEL No. RP-A THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects DATE 09/22/15 ISSUED FOR PERMIT 50.94 kW 141.5 Amps EXISTING 150A, 208Y/120V,3PH,4W SERVICE AND EQUIPMENT ARE ADEQUATE FOR NEW LOADS NO. DATE REVISION PROJECT NO. XU.2014.08 DRAWING TITLE ELECTRIC DETAILS E5.1 ST AT E OF OH I O F SS RE G I S T ERED I ON L A EN R EE O E N PR DAVID WAHOFF E-59973 G I DATE: Motz Engineering 300 West 4th Street, Suite 300 Cincinnati, OH 45202-2666 T: 513.621.5400 F: 513.621.5407 Sustainable Design Design/Build Xavier University 1624 Herald Avenue Cincinnati, OH 45207 WORK FOR THIS PROJECT Cintas Center - Courtside Club MEP Design Security Commissioning THIS DRAWING AND THE DESIGN CONCEPTS REPRESENTED, AS INSTRUMENTS OF SERVICE, ARE THE SOLE PROPERTY OF MICHAEL SCHUSTER ASSOCIATES INC., AND MAY NOT BE USED, REPRODUCED, OR COPIED IN WHOLE OR PART, FOR ANY PURPOSE WITHOUT PRIOR WRITTEN AUTHORIZATION OF MICHAEL SCHUSTER ASSOCIATES INC. Copyright Michael Schuster Associates, Inc. dba MSA Architects All Rights Reserved MSA Sport is a division of MSA Architects DATE 8/14/2015 1:24:18 PM C:\Users\lpetrakis\Documents\CINTAS_CENTRAL-HOST_v14_lpetrakis.rvt 09/22/15 NO. DATE ISSUED FOR PERMIT REVISION PROJECT NO. XU.2014.08 DRAWING TITLE ELECTRIC DETAILS E5.2