IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 IAQ Check List Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False N/A 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed to keep vents clear at all times. Record locations here: 2. Ground Level Outdoor Inspection (weather permitting) a. Univent air intakes are free of obstructions. If false, record locations here: b. Filters i. Medium efficiency filters are installed in all univents. If false, list locations and create work orders to initiate corrective action. ii. High efficiency filters are installed in the air handling units. If false, list locations and create work orders to initiate correction action. iii. Filters are being changed every six months and the installed date is written on the outer filter casing. If filter is older than 6 months, list locations and create work orders to initiate corrective action. c. Insects, bird nests, or droppings are not evident near outdoor air intakes. If false, indicate locations here: d. Trash dumpsters are located away from doors, windows, and outdoor air intakes. e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) f. Trucks and buses are not allowed to keep their engines idling near the building. Page 1 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False g. No evidence of drainage problems exist. Water drains away from the building including roof downspouts. N/A h. Sprinklers do not spray directly toward the building or into outdoor air intakes. i. Grass clippings from mowers are directed away from the building air intakes. j. Clean walk-off mats are present at exterior entrances. 3. Roof (Inspections conducted weather permitting) a. Roofing consultant has not found any issues requiring immediate repair. Most recent roofing inspection date/company: 5-year roofing plan completed 5/25/2010 with C. E. Crowley & Associates. This winter we had a total of 5 leaks identified in the high school. The cafeteria, the CAD room, the kitchen, C125 and the weight room. Our contractor was contacted and addressed these issues. Our roofing contractor is All American Exterior Solutions. b. There is no evidence of water ponding on the roof. c. Intake ventilation units are operating properly and free of debris. d. All exhaust fans are operating properly and free of debris. The exhaust system for the "B" Wing, classrooms 101 - 109 was off because of relay switches shutting the system down. This has been rectified. e. Air intake dampers are set to allow air flow even at minimum setting. There is a control problem which requires manual adjustment. We are setting these units to draw outside air at the correct levels while investigating with Johnson Controls on how to remedy these problems. f. Insects, birds, animal nests or droppings are not evident near outdoor air intakes. g. Plumbing stacks and exhaust vents are located away from air intakes. Page 2 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 IAQ Check List Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False N/A 4. Attic a. There is no evidence of roof or plumbing leaks. No Attic b. There is no evidence in attic of insects, birds, animals, or nests. No Attic 5. General Considerations a. Classrooms, offices and/or common areas appear recently cleaned. If examples of poor housekeeping are found, record locations below: b. Only vacuums with HEPA filters are being used. c. All supply and exhaust ventilation units are working properly. The exhaust system for the "B" Wing, classrooms 101 - 109 was off because of relay switches shutting the system down. this has been rectified. d. Occupied space temperatures and relative humidity levels are within the standards listed below. i. Temperature range: Winter temperatures 70-73 degrees. Summer temperatures 74-80 in air-conditioned spaces and 74-85 in non-air-conditioned spaces. Outdoor air temperature: 36.3; 34.8; 26.6 degrees. Highest temperature – Location: B106; A106; A133; Reading of 75.7; 75; 72.7 degrees. Lowest temperature – Location: 138; Admin 145; B105; Reading of 68.6; 69.3; 68.8 degrees. ii. Relative humidity range is 30% to 60%. Non-air-conditioned spaces may be higher on rainy or humid summer humid days. All spaces may be less than 30% when the out-door air temperature is less than 32 degrees. Outdoor relative humidity: 45.7; 44.7; 65.1% Page 3 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False Highest relative humidity – Location: B110; C112; D223; Reading of 34.5; 32.8; 30.9% Lowest relative humidity – Location: PA114; Field House; C106A;Reading of 26.2; 23.1; 23.8% N/A Readings not within acceptable standards will result in the creation of a work order, requesting maintenance to address. (Readings are noted on the attached test data sheet) e. Occupied space readings of carbon monoxide (CO) levels are less than 9.0 PPM. Outdoor Air CO Reading: .7; 0; 0 Highest CO Location: B138; D221; A119 Reading: .9; .6; .5 Lowest CO Location: Several Rooms Reading: 0 If the CO level is greater than 9.0 PPM in any space as measured with a handheld device or “leave-in” monitor, the space must be cleared of all occupants and steps taken to correct the problem. The issue will be immediately addressed by maintenance and the Fire Department. (Readings are noted on the attached test data sheet) f. CO2 levels in any occupied space are below threshold limits. i. Perform CO2 check with Gray Wolf or other portable device. Measure four times yearly or more often if needed. Measure only in fully occupied rooms. Reading should be less than 700 PPM plus outside air CO2 PPM. 700 PPM + 350 PPM = 1050 PPM Assume outside CO2 is 350 if temperature is below 41 degrees and air is not stagnant with no- wind. Record all occupied space CO2 levels on forms provided. Provide the outdoor CO2 level as well as the high and low CO2 extremes below: Outdoor reading: 376; 386; 382 PPM Highest CO2 reading – Location: B105; D223; B121; Reading of 1510; 1096; 1040 PPM Lowest CO2 reading – Location: F103; Field House; B107; Reading of 539; 497; 575 PPM Page 4 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False Work orders were written to respond to high readings above the base line. In the B Wing the exhaust was shut off that pulled air out of the hallways and classrooms. These were turned back on. The third test readings are the retesting of those rooms with high CO2 readings. All are below the baseline. N/A ii. If reading is above threshold, check univent and air handling dampers to ensure a value is set to provide at least 15 cfm of fresh air intake per student based on average space occupancies. If reading is consistently elevated, then use data logging to monitor CO2 concentrations over time and look for other sources of problems. iii. CO2 levels were checked three months ago. iv. CO2 levels on “leave-in” devices, where present, where checked. No leave-in devices g. Offensive odors are not apparent. If false, list problem areas: h. Water damage is not evident. Check for roof leaks, pipe leaks, spills, stained ceiling tiles, etc, visually and with moisture meter. Look for the source of any water leaks and schedule repairs. Discard porous items such as ceiling tiles if wet for more than 24 hours. For carpeting, if less than 9 square feet of wet area, shampoo with germicide and fan dry. For areas greater than 9 square feet, replace carpet with tile in reasonable timeframe. If carpet is over ACM tile, replace during next unoccupied break time (winter break, spring break, summer). If false, record findings and locations here: Please be aware that roof leaks did occur in the past 3 months but these were identified and addressed. Page 5 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 i. j. IAQ Check List Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False N/A Mold or mildew growth is not evident. If false, record findings and locations here: All pest management issues are being handled by Integrated Pest Management. k. No other unresolved concerns or complaints by building personnel are known. If false, list any pending issues not previously mentioned in this report here: l. There are no incomplete HVAC preventative maintenance (PM) work requests. If false, list any incomplete HVAC work request here: We began the process with Johnson Controls to get 6 systems back under our control. This work is on-going but progress is being made. 6. Bathrooms and General Plumbing a. All locker or restroom exhaust fans are working. Inoperable or malfunctioning fans are listed as follows: Location: Problem: b. All of the following drain-trap maintenance procedures are being conducted according to the frequency indicated. If false, indicate all deviations and locations: i. Water is poured into floor drains once per week (approximately 1 quart of water) or water and a teaspoon of cooking oil poured into the drain once a month. Two drains gave evidence of not being treated - the dance room bathroom and the IDF room in the C wing. These have been addressed. ii. Water is poured into sinks at least once per week (about 2 cups of water). iii. Toilets are flushed at least once per week. 7. Lab Chemicals & Maintenance Supplies a. Lab chemicals are used with exhaust fans turned on. Page 6 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False b. Lab chemical storage areas have been inspected yearly by ROE and Fire Department. Record last inspection dates below: ROE: 11/2011 LZFD: 11/2011 N/A c. Flammables are not stored with igniters. d. All chemicals that may react or produce toxic or explosive by-products are separated and maintained in approved containers stored in approved storage. (e.g. lockable, with appropriate ventilation). e. Chemical disposal records for all lab chemicals are available for review. f. All cleaning products used in building contain no/low VOC. List any exceptions: g. Increased ventilation is considered when installing new carpets, cleaning upholstered furniture, shampooing carpets, etc. h. Exhaust ventilation systems in chemical and trash storage areas are turned on and functioning properly. i. Portable fuel containers are properly closed. j. Power equipment, like snow blowers and lawn mowers, have been serviced and maintained according to manufacturers’ guidelines. k. Oil based paints are stored in approved storage cabinets. No oil based paints are allowed in the district. l. Green Cleaning products and processes are used in this building. Page 7 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 8. IAQ Check List Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False N/A Combustion Appliances a. Combustion analysis is performed at the start of the heating season on all boilers. Adjustments are made to the burners to correct any abnormalities and improve efficiency. b. In rooms that contain combustion appliances, there is no evidence of combustion gas or fuel odors. If false, record locations here: c. No leaks, disconnections, and/or deterioration were found on exhaust hoods. d. Flue components are clean and free of soot. e. All combustion appliances have flues or exhaust hoods and vent NO2. i. If false, inspect cooking hoods, chemical hoods. Assure that cooking stoves and appliances are correctly installed, used, and maintained according to manufacturers’ specifications. ii. If not vented, ensure that “leave-in” CO monitors are placed in room. Record locations here: NONE iii. CO levels in rooms with combustion appliances are measured and recorded with an IAQ monitor. CO readings outside of normal CO range will result in an immediate response by maintenance to reduce CO level or vacating the room/building, if necessary. Record locations here: 9. Other a. Paint No peeling and/or flaking paint found. If planned building renovation will damage paint or if peeling paint is discovered, lead testing may be necessary. If peeling paint is found, send email to the building Principal and the Facilities Director alerting them of the problem. Staff and teachers need to pick up any flakes of paint to prevent children from being exposed. The Facilities Director will advise the Facilities Coordinator (a Certified Lead Paint Renovator) to test the paint for lead. Lead paint was discontinued in 1978. Buildings built Page 8 of 9 Revised 3/7/2011 AMJ Created 11/2010 IAQ Check List IAQ Check List Building: Lake Zurich High School Date: February 7, 2012 Building Inspection Performed by: Denys Armashov, Lyle Erstad Report Compiled by: Lyle Erstad Check List True False after 1978 are exempt from lead paint testing. N/A If lead is present, required repairs should be done immediately using lead-safe methods and, if necessary, a licensed lead contractor. Location(s) of known peeling paint in building: No lead based paint is allowed in the district. b. The following preventive measures are being taken to reduce lead exposure. i. Play areas and toys are cleaned nightly. ii. Floors are mopped nightly. iii. Dust at least weekly. c. Radon testing is recommended by IEMA every 5 years. Last testing date listed below: Date: 12/12 - 15/2011; Reading of (Highest) 1.8 pCi/L in C123. National concern: 4.0 pCi/L d. The IAQ testing equipment used for this inspection was calibrated and is in good working order. Equipment Used: Gray Wolf Last date of calibration: 1-20-2012 Page 9 of 9 Revised 3/7/2011 AMJ Created 11/2010 300 Church Street. Indoor Air Quality Testing Readings Winter 2012 Site Location Date/Time Temperature °F Relative Humidity %RH Carbon Monoxide ppm Carbon Dioxide ppm High school Outdoor Air 02-Feb-12 11:17:20 AM 36.3 45.7 0.7 376 High school A114 A 02-Feb-12 02:11:56 PM 71.8 28.2 0.3 731 1 High school A114 02-Feb-12 02:10:22 PM 72.5 28.8 0.1 832 20 High school A115 02-Feb-12 02:26:19 PM 73.7 30.4 0.3 993 14 High school A116 02-Feb-12 02:15:58 PM 72.1 28.5 0.1 797 24 High school A117 02-Feb-12 02:28:00 PM 73.6 28.4 0.5 825 26 High school A119 02-Feb-12 02:18:08 PM 73.1 32.1 0.3 1180 26 High school Admin Main 138 02-Feb-12 11:29:17 AM 68.6 32.5 0.9 706 4 High school Admin Office 149 02-Feb-12 11:30:41 AM 69.8 32.9 0.4 666 2 High school Principal office 147 02-Feb-12 11:33:17 AM 70.7 31.1 0.4 709 2 High school Principal office 148 02-Feb-12 11:31:57 AM 70.5 32.0 0.5 723 2 High school B102 02-Feb-12 01:59:42 PM 73.0 32.4 0.2 1153 25 High school B104 02-Feb-12 01:56:05 PM 72.7 28.1 0.3 833 22 High school B105 02-Feb-12 01:52:58 PM 73.2 33.8 0.4 1510 25 High school B106 02-Feb-12 01:36:50 PM 75.7 31.2 0.3 1213 24 High school B107 02-Feb-12 01:47:17 PM 74.0 31.5 0.2 1198 25 High school B108 02-Feb-12 01:39:00 PM 74.6 31.1 0.3 1497 11 High school B110 02-Feb-12 01:32:13 PM 73.6 34.5 0.3 1344 25 High school B111 02-Feb-12 01:28:59 PM 71.5 28.9 0.2 895 26 High school B112 02-Feb-12 01:27:48 PM 72.5 29.1 0.2 884 22 High school B114 02-Feb-12 01:26:20 PM 72.8 27.8 0.4 754 3 High school B115 02-Feb-12 01:24:56 PM 73.3 30.3 0.1 882 26 High school B117 02-Feb-12 01:23:51 PM 73.4 28.3 0.0 779 7 High school B118 02-Feb-12 01:20:01 PM 74.1 32.8 0.2 1072 23 High school B119 02-Feb-12 01:22:12 PM 72.7 27.9 0.4 797 10 High school B121 02-Feb-12 01:17:56 PM 74.1 31.7 0.4 1059 28 High school B124 02-Feb-12 01:15:25 PM 74.5 30.3 0.2 1070 15 High school B126 02-Feb-12 01:11:54 PM 74.5 33.6 0.3 1129 25 High school B127 02-Feb-12 01:09:55 PM 74.1 29.7 0.1 934 9 High school B130 02-Feb-12 01:08:22 PM 72.6 30.1 0.1 863 26 High school B133 02-Feb-12 01:02:30 PM 72.8 28.2 0.1 852 16 High school B138 02-Feb-12 01:04:25 PM 72.8 28.9 0.1 914 27 High school C115 02-Feb-12 12:16:49 PM 72.6 26.6 0.2 598 7 High school C117 02-Feb-12 12:14:55 PM 72.5 28.3 0.3 748 16 High school C123 02-Feb-12 12:38:17 PM 75.3 27.9 0.1 749 26 Occupants Taken by Taken With Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Window open High school Cafeteria 02-Feb-12 01:06:03 PM 73.4 31.6 0.4 1000 150 High school F103 02-Feb-12 11:54:28 AM 72.8 26.4 0.0 539 1 High school F104 02-Feb-12 11:50:12 AM 73.0 26.7 0.2 578 4 High school F106 02-Feb-12 11:48:50 AM 72.7 27.2 0.2 611 4 High school F149 02-Feb-12 11:43:54 AM 72.5 28.0 0.1 570 1 High school Gymnasium 02-Feb-12 11:42:06 AM 70.6 29.7 0.2 655 55 High school A113 02-Feb-12 02:21:25 PM 72.8 27.7 0.2 775 1 High school PA107 02-Feb-12 12:08:30 PM 71.8 27.5 0.4 668 3 High school PA114 02-Feb-12 12:06:39 PM 73.7 26.2 0.5 701 2 High school PA122 02-Feb-12 12:05:15 PM 74.8 27.4 0.5 698 12 High school PA127 02-Feb-12 12:03:29 PM 73.8 29.2 0.1 823 70 High school PA130 02-Feb-12 12:01:57 PM 71.3 28.5 0.3 795 1 High school PA131 02-Feb-12 11:59:45 AM 71.0 28.4 0.2 713 29 High school PPS 101 02-Feb-12 02:32:30 PM 73.5 27.2 0.0 772 5 High school PPS 104 02-Feb-12 02:37:17 PM 74.6 27.2 0.2 779 1 High school PPS 107 02-Feb-12 02:35:13 PM 74.1 27.4 0.1 751 2 High school S102 02-Feb-12 12:19:06 PM 71.0 27.9 0.4 713 31 High school S107 02-Feb-12 12:23:50 PM 72.5 30.0 0.3 928 26 High school S111 02-Feb-12 12:22:08 PM 72.0 29.4 0.2 809 20 High school S113 02-Feb-12 12:28:19 PM 72.7 29.4 0.3 756 22 High school S114 02-Feb-12 12:33:37 PM 73.5 28.9 0.0 790 11 High school S116 02-Feb-12 12:36:39 PM 73.9 27.0 0.2 655 3 High school S117 02-Feb-12 12:30:35 PM 72.5 28.4 0.3 651 29 High school S126 02-Feb-12 12:44:55 PM 73.0 26.9 0.1 754 27 High school S127 02-Feb-12 12:52:53 PM 74.1 27.3 0.2 807 20 High school S131 02-Feb-12 12:40:22 PM 73.9 27.1 0.4 807 16 High school S137 02-Feb-12 12:48:59 PM 74.1 27.2 0.2 826 19 High school Tonell Gym 02-Feb-12 11:46:41 AM 72.7 28.9 0.1 593 17 Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Occupants Taken by Taken With Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Yes Co2 Formula 350+700=1050 Site Location Date/Time Temperature °F Relative Humidity %RH Carbon Monoxide ppm Carbon Dioxide ppm High school Outside Air 03-Feb-12 10:38:31 AM 34.8 44.7 0.0 386 High school A107 03-Feb-12 12:28:54 PM 74.0 25.0 0.3 659 1 High school A101 03-Feb-12 12:14:55 PM 74.0 25.4 0.1 749 2 High school A103 03-Feb-12 12:24:41 PM 74.2 24.5 0.4 740 1 High school A106 03-Feb-12 12:30:43 PM 75.0 24.4 0.1 749 1 Window open High school A104 03-Feb-12 02:01:08 PM 72.7 26.7 0.3 868 26 High school A134 03-Feb-12 02:30:15 PM 73.5 25.7 0.1 782 23 High school B131 03-Feb-12 12:03:58 PM 73.5 26.5 0.2 995 20 High school B136 03-Feb-12 12:01:29 PM 73.8 26.0 0.1 810 1 High school B101 03-Feb-12 01:45:09 PM 73.0 28.8 0.1 1091 29 High school B103 03-Feb-12 01:47:31 PM 72.0 26.0 0.2 848 17 High school B109 03-Feb-12 11:46:47 AM 71.2 28.7 0.0 950 29 High school B113 03-Feb-12 01:49:52 PM 70.6 27.2 0.2 947 19 High school B120 03-Feb-12 11:49:21 AM 72.4 24.7 0.0 629 3 High school B123 03-Feb-12 11:52:27 AM 72.1 27.2 0.3 791 7 High school B125 03-Feb-12 11:54:19 AM 72.7 27.8 0.2 904 6 High school B128 03-Feb-12 01:07:13 PM 72.5 27.3 0.0 890 15 High school B129 03-Feb-12 11:58:54 AM 72.6 28.1 0.3 796 22 High school B132 03-Feb-12 01:05:13 PM 72.5 31.5 0.1 643 9 High school C127 03-Feb-12 01:29:26 PM 73.5 23.7 0.0 508 1 High school C129 03-Feb-12 01:31:40 PM 71.7 23.8 0.3 510 9 High school C106 03-Feb-12 01:37:11 PM 73.3 26.2 0.3 810 16 High school C108 03-Feb-12 11:00:29 AM 69.8 27.5 0.1 570 6 High school C109 03-Feb-12 10:58:53 AM 70.3 29.2 0.1 562 28 High school C111 03-Feb-12 11:04:04 AM 69.8 29.1 0.1 698 23 High school C112 03-Feb-12 11:05:54 AM 70.2 32.8 0.0 793 25 High school C113 03-Feb-12 01:39:14 PM 73.3 27.7 0.2 966 24 High school C116 03-Feb-12 01:41:28 PM 73.1 25.9 0.3 858 26 High school C124 03-Feb-12 01:13:46 PM 73.9 28.4 0.2 700 25 High school C125 03-Feb-12 01:12:23 PM 73.6 25.4 0.4 808 20 High school C126 03-Feb-12 01:09:54 PM 73.3 28.5 0.0 672 5 High school D230 03-Feb-12 11:21:25 AM 71.5 25.7 0.2 788 1 High school D216 03-Feb-12 11:20:02 AM 71.6 26.6 0.1 816 20 High school D217 03-Feb-12 11:18:04 AM 71.6 28.3 0.0 836 22 High school D218 03-Feb-12 12:56:20 PM 73.5 26.5 0.0 885 2 High school D219 03-Feb-12 12:57:35 PM 73.5 25.7 0.1 871 8 High school D220 03-Feb-12 11:16:19 AM 70.9 27.2 0.1 868 27 High school D221 03-Feb-12 12:54:42 PM 72.6 25.3 0.6 834 26 High school D222 03-Feb-12 12:52:32 PM 74.8 27.6 0.2 1034 8 High school D223 03-Feb-12 12:50:04 PM 74.6 26.8 0.2 1096 23 High school D224 03-Feb-12 02:13:10 PM 74.5 27.3 0.2 927 20 High school D225 03-Feb-12 11:13:58 AM 71.0 26.6 0.2 786 26 High school D226 03-Feb-12 11:26:45 AM 71.3 25.5 0.0 624 1 Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf High school D227 03-Feb-12 11:25:15 AM 71.2 25.6 0.2 654 4 High school D229 03-Feb-12 11:23:56 AM 71.5 25.8 0.1 640 3 High school E210 03-Feb-12 11:40:15 AM 73.3 26.0 0.1 705 3 High school E200 03-Feb-12 11:35:04 AM 73.3 25.0 0.3 712 4 High school E201 03-Feb-12 11:33:49 AM 72.9 27.6 0.2 836 20 High school E202 03-Feb-12 11:31:38 AM 72.5 26.9 0.2 766 4 High school E203 03-Feb-12 02:21:46 PM 74.8 27.3 0.2 874 23 High school E204 03-Feb-12 02:19:22 PM 74.1 25.3 0.1 839 4 High school E205 03-Feb-12 01:00:14 PM 73.8 26.0 0.0 797 24 High school E206 03-Feb-12 11:29:36 AM 71.9 27.2 0.1 796 10 High school E207 03-Feb-12 02:17:36 PM 73.6 25.3 0.0 795 22 High school E208 03-Feb-12 02:15:48 PM 73.8 26.0 0.2 839 25 High school E209 03-Feb-12 11:42:51 AM 73.1 24.9 0.2 684 1 High school E211 03-Feb-12 11:38:20 AM 73.1 24.3 0.2 662 2 High school E214 03-Feb-12 11:36:43 AM 72.7 25.1 0.3 657 2 High school E215 03-Feb-12 02:24:07 PM 74.8 24.5 0.1 814 3 High school Gym Field House 03-Feb-12 12:35:18 PM 72.3 23.1 0.1 497 33 High school HS133 03-Feb-12 11:02:45 AM 70.3 27.9 0.0 626 3 High school Library A100 03-Feb-12 12:12:17 PM 72.9 26.3 0.1 710 40 High school PPS 124 03-Feb-12 12:39:26 PM 72.0 25.9 0.0 646 3 High school PPS 126 03-Feb-12 12:45:24 PM 73.6 25.9 0.3 793 1 High school PPS 127 03-Feb-12 12:43:44 PM 73.9 27.1 0.3 933 6 High school PPS102 03-Feb-12 01:59:25 PM 73.0 25.9 0.0 821 11 High school Principal 145 03-Feb-12 10:57:16 AM 69.3 27.8 0.2 510 1 High school S101 03-Feb-12 01:22:13 PM 73.4 26.1 0.1 810 18 High school S104 03-Feb-12 01:17:51 PM 73.2 23.3 0.1 587 15 High school S105 03-Feb-12 01:19:37 PM 73.4 25.2 0.0 629 25 High school S106 03-Feb-12 01:16:03 PM 74.1 25.1 0.2 708 7 High school S122 03-Feb-12 01:54:03 PM 74.5 29.8 0.0 1002 31 High school S133 03-Feb-12 12:06:40 PM 73.4 26.1 0.2 901 Date/Time Temperature °F Relative Humidity %RH Carbon Monoxide ppm Carbon Dioxide ppm 17 Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Occupants Taken by Taken With Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Yes Co2 Formula 350+700=1050 Site Location High School Outdoor Air 2/6/2012 10:30:30 AM 26.6 65.1 0.0 382 High School A133 06-Feb-12 11:35:36 AM 72.7 24.5 0.2 1004 26 High School B101 06-Feb-12 10:45:00 AM 69.5 27.4 0.1 748 17 Window open High School B102 06-Feb-12 12:19:02 PM 70.6 24.2 0.1 726 24 High School B105 06-Feb-12 10:48:15 AM 68.8 28.6 0.1 1036 23 High School B106 2/6/2012 10:49:29 AM 70.2 27.0 0.1 831 24 High School B107 06-Feb-12 10:51:51 AM 69.6 26.3 0.1 575 19 High School B108 06-Feb-12 10:53:03 AM 69.3 28.6 0.1 913 20 High School B110 06-Feb-12 10:55:44 AM 69.4 28.4 0.0 870 24 High School B118 06-Feb-12 10:57:42 AM 69.3 28.1 0.2 970 23 High School B121 06-Feb-12 10:59:01 AM 69.6 28.9 0.3 1040 24 High School B124 06-Feb-12 11:02:15 AM 70.0 26.4 0.2 799 8 High School B126 06-Feb-12 11:00:59 AM 69.9 29.0 0.4 1017 29 High School C106A 06-Feb-12 11:11:22 AM 70.9 23.8 0.1 585 11 High School C100 06-Feb-12 11:19:30 AM 72.0 24.4 0.1 604 13 High School C101 06-Feb-12 12:24:39 PM 69.2 24.8 0.1 730 19 High School C104 06-Feb-12 11:13:23 AM 69.9 24.0 0.2 634 1 High School C118 06-Feb-12 11:15:41 AM 71.2 23.9 0.0 584 1 High School D223 06-Feb-12 10:39:22 AM 69.0 30.9 0.2 885 26 High School A119 06-Feb-12 12:21:40 PM 70.9 25.3 0.5 903 22 High School S119 06-Feb-12 11:06:45 AM 70.3 26.5 0.1 845 22 Co2 Formula 350+700=1050 Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Denys Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf Gray Wolf