Document Revision July 27, 2006 2447 H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Cooper Industries Crouse-Hinds Division Crouse-Hinds Airport Lighting 1200 Kennedy Road Windsor, CT 06095 For Parts or Technical Service Call (860) 683-4300 Copyright © 2006 Cooper Technologies Company Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 1 Configuration Record The following information is specific to the equipment describes as shipped from the factory and should be retained. It should be provided when contacting the factory about this equipment for any reason. Constant Current Regulator, FAA Type Manufacturer’s Part Number Serial Number Date of Manufacture Factory Installed Options Description Option/Part Number ii Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 2 Revisions Revision Number A B Issue/Reissue Letter Number A204-304 A205-121 C A205-182 D A205-303 E A206-107A F A206-176 G H A206-243 A206-275 Description Initial Issue Revised to add missing information and clarify installation and trouble shooting Sh 19 & 45, added 10047-2937 SSR thermal pad; Sh 4, Figure 1, added 60 Hz only to 30 kW sizes Fig 6, 7 & 8, S-1 P/N was 30775 & revised pictorial Added Fig 9A; Fig 6, 30775 was 30771 & revised pictorial in all locations; added copyright to cover page; 8.1.5.1 5. was 4. & 4. was 5. & revised 5., was install main circuit card to cabinet door per doc. 2512; re-numbered pages as req’d; Fig 8, deleted K2 P/N 10047-2787 (4-10 kW); Fig 7, added lock out brkt P/N’s; spare parts list, item 4, deleted P/N 10047-2787 (4-10 kW); 6.2.3.2, added “Notice” & “Warning” Information Added 2006 to copyright on cover page; 6.2.3.2, revised NOTICE & WARNING wording; Figure 1, revised option V description; 7.1.5.3, F2 was 1A Slo-Blo; Figure 11 & 11D, 34031 F2 was 1A SloBlo; pg 49, item 9, F2 was 1A Slo-Blo 6.2.3.1 spec 150/5345-10F was -10E Figure 1, Kilowatt rating “31” was 30 iii Checked KF 03-29-05 Approved JMM PG 7/7/05 PG 8/25/05 PG 3/27/06 PG 6/23/06 PG 7/11/06 7/27/06 PG PG Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 3 Limited Product Warranty THE FOLLOWING WARRANTY IS EXCLUSIVE AN IN LIEU OF ALL OTHER WARRANTIES, WHETHER EXPRESS, IMPLIED OR STATUTORY, INCLUDING, BUT NOT BY WAY OF LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Crouse-Hinds Airport Lighting Products (the “Company”) warrants each original Buyer of Products Manufactured by the Company that such Products are, at the time of delivery to the Buyer free of material and workmanship defects, provided that no warranty is made with respect to: (a) any Product which has been repaired or altered in such a way, in Company’s judgement, as to affect the Product adversely; (b) any Product which has in Company’s judgment, been subject to negligence, accident or improper storage ; (c) any Product which has not been operated and maintained in accordance with normal practice and in conformity with recommendations and published specifications of company; and, (d) any Products, component parts or accessories manufactured by others but supplied by Company (any claims should be submitted directly to the manufacturer thereof). Crouse-Hinds Airport Lighting Products’ obligation under this warranty is limited to use reasonable efforts to repair or, at its option, replace, during normal business hours at any authorized service facility of Company, any Products which in its judgement proved not to be as warranted within the applicable warranty period. All cost of transportation of Products claimed not to be as warranted and of repaired or replacement Products to or from such service facility shall be borne by Purchaser. Company may require the return of any Product claimed not to be as warranted to one of its facilities as designed by Company, transportation prepaid by Purchaser, to establish a claim under this warranty. The cost of labor for installing a repaired or replacement product shall be borne by Purchaser. Replacement parts provided warranty period of the Products upon which they are installed to the same extent as if such parts were original components thereof. Warranty services provided under the Agreement do not assure uninterrupted operations of Products; Company does not assume any liability for damages caused by any delays involving warranty service. The warranty period for the Products is 24 months from date of shipment or 12 months from date of first use whichever occurs first. iv Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 4 Safety Notices This equipment is normally used or connected to circuits that may employ voltages which are dangerous and may be fatal if accidentally contacted by operating or maintenance personnel. Extreme caution should be exercised when working with this equipment. While practical safety precautions have been incorporated in this equipment, the following rules must be strictly observed: 4.1 KEEP AWAY FROM LIVE CIRCUITS Operating and maintenance personnel must at all times observe all safety regulations. DO NOT PERFORM MAINTENANCE ON INTERNAL COMPONENTS FOR RELAMP WITH POWER ON. 4.2 STORED ENGERGY Ensure capacitors are discharged before working on equipment 4.3 RESUSCITATION Maintenance personnel should familiarize themselves with the technique for resuscitation found in widely published manuals of first aid instruction. See FAA Advisory Circular AC 150/5340-26 for additional information. v Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 4.4 SAFETY SYMBOLS DANGER: DANGER The hazard or unsafe practice will result in severe injury or death. WARNING: WARNING The hazard or unsafe practice could result in severe injury or death. CAUTION: CAUTION The hazard or unsafe practice could result in minor injury or death. NOTICE: NOTICE Possibly dangerous situation, goods might be damaged. IMPORTANT: IMPORTANT Helpful information. vi Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 5 Table of Contents Title Page ......................................................................................................................................... i 1.0 Configuration Record................................................................................................................ ii 2.0 Revisions.................................................................................................................................. iii 3.0 Limited Product Warranty ....................................................................................................... iv 4.0 Safety Notices ............................................................................................................................v 5.0 Table of Contents.................................................................................................................... vii 6.0 General Information...................................................................................................................1 6.1 Introduction.........................................................................................................................1 6.2 Equipment Description.......................................................................................................1 6.3 Installation Requirements...................................................................................................4 7.0 Technical Description ................................................................................................................6 7.1 Theory of Operation ...........................................................................................................6 8.0 Installation and Operation..........................................................................................................9 8.1 Installation ..........................................................................................................................9 8.2 Operation ..........................................................................................................................24 9.0 Maintenance.............................................................................................................................26 9.1 Periodic Maintenance .......................................................................................................26 9.2 Corrective Maintenance ...................................................................................................26 9.3 Problem Solving Guide ....................................................................................................27 10.0 Spare Parts List ......................................................................................................................48 10.1 Recommended Spare Parts.............................................................................................48 vii Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figures Figure 1 – Catalog Number Breakdown ..........................................................................................5 Figure 2 - CCR Cabinet ................................................................................................................14 Figure 3 – CCR Upper Track Extension........................................................................................15 Figure 4 – CCR Forklift Installation Front View...........................................................................16 Figure 5 – CCR Forklift Installation Top View.............................................................................17 Figure 6 – CCR Front View...........................................................................................................18 Figure 7 – CCR Top View .............................................................................................................19 Figure 8 – CCR Side View ............................................................................................................20 Figure 9 – CCR Interior Door........................................................................................................21 Figure 9A – CCR Door Exterior....................................................................................................22 Figure 10 – Remote Control Connections by Customer................................................................23 Figure 11 – CCR Wiring Diagram.................................................................................................29 Figure 11a – CCR Wiring Diagram (Partial Expanded)................................................................30 Figure 11b – CCR Wiring Diagram (Partial Expanded)................................................................31 Figure 11c – CCR Wiring Diagram (Partial Expanded)................................................................32 Figure 11d – CCR Wiring Diagram (Partial Expanded)................................................................33 Figure 12 – P/N 34031 Circuit Board – S1 DIP Switch Configuration.........................................34 Figure 13 – 34031 Circuit Board Detail ........................................................................................47 viii Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 6 General Information 6.1 Introduction 6.1.1 Purpose This instruction manual provides information for installing and maintaining FAA Type L-828 Constant Current Regulators manufactured by Crouse-Hinds Airport Lighting Products, Windsor, Connecticut 06095, U.S.A. 6.1.2 Applicability Only Switchgear style regulators bearing Crouse-Hinds catalog number series 82XSGS are covered by this manual. Refer to Figure 1 for complete part number information. Instructions for standard options are provided as supplements to this manual. 6.2 Equipment Description 6.2.1 Features The Constant Current Regulator is a power supply designed for precision operation of airfield lighting. The output current is regulated within +/-1% at any load and for line voltages from +10% to –5% of nominal. The three or five discrete brightness steps conform to FAA standards. The regulator may be controlled both locally and from a remote location. Protective circuits are provided to sense an overcurrent or an open circuit in the series lighting loop and shutdown the regulator. The front panel display alerts maintenance personnel to the nature of the shutdown. The protective circuitry can be reset by setting the regulator control switch to off for 1 second. Provided no fault condition remains, setting the control switch to the desired brightness step will restore operation. The regulator is “hot swappable” when used in a Crouse-Hinds Switchgear System Cabinet. The output of the regulator may be connected directly to a FAA approved load switching device. 6.2.2 Options This regulator can be factory supplied with various options. See Figure 1 for a list of options. 1 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 6.2.3 Specification 6.2.3.1 FAA Classification Specification: Constant Current Regulator manufactured and qualified to FAA Advisory Circular 150/5345-10F Type: L-828 Regulator Class: 1 – 6.6 amperes output current 2 – 20 amperes output current Style: 1 – 3 Brightness Steps: 4.8, 5.5, 6.6 amperes 2 – 5 Brightness Steps: 2.8, 3.4, 4.1, 5.2, 6.6 amperes; 8.5, 10.3, 12.4, 15.8, 20.0 amperes Ratings: Sizes – 4kW, 7.5kW, 10kW, 15kW, 20kW, & 30kW Voltages – 380VAC 50Hz, & 480VAC, 60Hz 2 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 6.2.3.2 Electrical Characteristics Primary Power: Refer to Table 1 for ampacity information based on regulator size and line voltage. Remote Control Power: (a) Internal Supply – 120VAC, Standard (Other voltages optional) (b) External Supply – 120VAC, Standard (Other voltages optional) NOTICE: Condition Limits NOTICE Total CCR load shall not exceed the rated load on the nameplate, at installation and subsequent load changes. WARNING: WARNING Running the CCR for long periods of time while overloaded may cause damage to the regulator.. 3 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 6.2.3.3 Physical Characteristics Dimensions: Refer to Outline Drawings, Figures 2 thru 5 Weight 4 kW – 425 lbs. 7.5kW – 570 lbs. 10kW – 670 lbs. 15kW – 875 lbs. 20kW – 1,190 lbs. 30kW – 1,640 lbs. Mechanical: The regulator Power Module can only be installed in a Crouse-Hinds Switchgear System Cabinet. The Power Module plugs into the mating CrouseHinds connector in the cabinet to obtain input power and also make ground connection. An S1 Cutout safety switch is located on the main transformer in the front of the regulator to make load connections. The electronic control board is located on the interior of the door. The remote control terminal block also plugs directly into the control board. The CCR is designed to allow easy access to other customer serviceable parts. The main transformer is an aircooled ferroresonant type. Environmental: Temperature: 6.3 -40 degrees C to +55 degrees C (-40 degrees F to +131 degrees F) Relative Humidity: 10 percent to 95 percent Altitude: Zero to 6,600 feet (2000 m) Installation Requirements The Power Module is shipped from the factory complete and ready to install. The agency responsible for installation must supply all necessary connectors, wire and conduit. The regulator is for indoor use in a Crouse-Hinds Switchgear system power supply cabinet only. CAUTION: CAUTION Exterior metal surfaces may exceed 120ºF (49ºC) when regulator is operated at full power for more than 10 hours. 4 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS EXAMPLE: 82860SGS-480-15-5 is a 15KW L-828 Regulator with 480V, 60 Hz input and 6.6A output. It has five brightness steps. Ordering Information 8 2 S G S - - - - FAA Type: 8 = L-828 Regulator Type SGS = Switchgear System Input Voltage: 380 = 380V, 50Hz 480 = 480V, 60Hz Kilowatt Rating: 04 = 4kW, 6.6A 07 = 7.5kW, 6.6A 10 = 10kW, 6.6A 15 = 15kW, 6.6A 16 = 15kW, 20A 20 = 20kW, 6.6A 21 = 20kW, 20A 30 = 30kW, 6.6A (60 Hz only) 31 = 30kW, 20A (60 Hz only) Output Brightness Steps: * 1 = 1 Step (5.5A) 3 = 3 Step (4.8, 5.5 &6.6A) 5 = 5 Step (2.8, 3.4, 4.1, 5.2, & 6.6A) * = 6.6A Output Units Only Options: ** C = Computer ready interface D = Digitrac ™ computerized control and monitoring system (includes option C) M = Megatrac ™ integral earth leakage detector and door interface V = 24, 48 & 60 VDC control voltage Standard remote control voltage is 120 VAC, 50/60 Hz ** Potential & Current transformer included, circuit board with relay contacts for loss of input power and local /remote control Figure 1 Catalog Number Breakdown 5 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 7 Technical Description 7.1 Theory of Operation (Basic Regulator) The information presented here applies to a standard model Constant Current Regulator (CCR). Regulators supplied with options may have minor operating differences, but the basic operation is the same for all units. Many functions in the CCR are controlled by a custom programmed electronic circuit. This device performs brightness step and digital display control, open circuit and over-current sensing, and handles system fault conditions. Several optional features also use the programmed circuit to reduce the amount of additional circuitry required. Each of the standard functions is discussed in detail in the following paragraphs. Optional functions are discussed in Supplemental sections of this manual. 7.1.1 Current Regulation A power transformer in conjunction with a Solid State Relay (SSR) is used for current regulation. This design provides precise control regardless of the load size or line voltage. For very low loads or low brightness settings, the on-time of the SSR will be large. At increased loads or higher brightness settings, the on-time will be less. The SSR is controlled using closed-loop electronic feedback control. Load current is sensed by a current transformer which generates an analog signal. The signal is processed by an electronic circuit and compared to a predetermined reference. The result is a pulse width modulated control signal. This control signal is applied to the coil of the SSR. 7.1.2 Brightness Control Each brightness step has a specific digital reference value store in electronic memory. When the desired step is selected by the rotary switch, the proper memory value is converted to an analog signal. This signal is the reference used for comparison as discussed in paragraph 7.1.1. All remote brightness connections are electrically isolated from the control electronics by optocouplers for transient protection. 6 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 7.1.3 Remote Control Operation The regulator can operate remotely using external switches connected to the remote control terminal block TB1. The exact wiring of these switches depends upon whether control power is obtained from the regulator internal supply or from an external source. The regulator turns on to brightness B1 (or B10 or ON) when control power is applied to terminal CC and B1 (B10). To get a higher brightness, control power is applied to terminal B2, B3, B4 or B5. (For three-step regulators, apply control power to B30 or B100, for one-step regulators, apply control power to on). Only the terminal for the desired step and CC require control power. If two or more steps are energized together, the regulator will operate at the highest brightness step selected. 7.1.4 Digital Display A multi-purpose Digital Display provides system operation data. Under normal conditions, the display shows the output current being supplied by the CCR. Under power-up and the system fault conditions, it displays specific CCR status data. 7.1.5 Protective System 7.1.5.1 Overcurrent Protection Overcurrent protection is triggered by comparison of the value of the feedback signal to predetermined limits. In the event of a minor overcurrent (between 5% and 25% above rated output), the control system responds within 5 seconds. If a major overcurrent (greater than 25% above rated output), occurs, the control system responds immediately. The response consists of de-energizing the load by opening the main contactor and providing status data to the digital display. To reset and re-energize the CCR, the rotary switch or remote brightness control switch must be set to OFF for at least one second. 7.1.5.2 Open –Circuited Load Protection This protection is triggered by comparison of the value of the feedback signal to a minimum current level. If the current remains below 2 amps for about 2 seconds, the control system performs the same shutdown sequence as for overcurrent protection. 7 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 7.1.5.3 Fuses Fuse Designator F1 F2 F3 F4 F201 F202 Location 34031 Circuit Board 34031 Circuit Board 34031 Circuit Board 34031 Circuit Board 34054 Interface Board 34054 Interface Board Purpose Remote Control CC Fuse Main DC Power Supply Fuse Reference Voltage Fuse Remote Control Neutral Fuse 120 VAC Control Fuse 120 VAC Option Fuse Size 1/8A Slo-Blo 2A Slo-Blo 1/8A Slo-Blo 1/8A Slo-Blo 1A Slo-Blo 1A Slo-Blo 7.1.5.4 Transient Protection Protection against transients from lighting or other sources is provided. Lighting arrestor LA1 protects the regulator power lines. Arrestors LA2 and LA3 protect the regulator load lines. Varistors are provided on the control system assembly to protect it from transients on the power and control lines. The lighting protection provided exceeds the requirements of the applicable Advisory Circular. Lighting is a naturally occurring phenomenon that varies in intensity and frequency based upon geographic location. Therefore, each installation should be evaluated to determine the need for additional lighting protection. 7.1.6 System Status Information The CCR Digital Display is used during power-up and fault conditions to provide data regarding system status. 7.1.6.1 Power-Up When power is applied to the CCR and when resetting from a latched fault mode, the control electronics performs a series of internal checks. If these are completed without incident, the control program number will be displayed for one second. The display will then begin to indicate CCR output current. If any check is not successfully completed, the system will “lock-up” and not allow the regulator to come on in any step. Cycle power to recover. 8 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 7.1.6.2 Fault Status Message If the CCR control circuits detect an abnormal system shutdown, a message will automatically scroll across the display. When two or more fault conditions exist, the most recent occurrence is displayed. Messages are cleared when the system is reset or conditions return to normal. Refer to the Operations Section 8.2 for information on specific messages. 8 Installation and Operation WARNING: WARNING Installation, service, maintenance or operation should be performed by qualified personnel only. 8.1 Installation The Constant Current Regulator is supplied ready for operation with all ordered options installed. When properly connected, no electrical adjustment other than noted in this section should be necessary before use. 8.1.1 Location The regulator is designed for indoor locations meeting the environment specified in Section 6.2.3.3. The area should be clean and dry, protected from rain, snow, dust, etc., and have adequate ventilation. The equipment should be accessible to qualified personnel only. Cabinets should be installed and bolted on a flat and level floor. Refer to cabinet manual for further mounting details. 8.1.2 Installation Drawings Typical details and dimensions are provided in Figures 2 thru 10. 9 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.1.3 Power Requirements Table 1 lists the line current requirements for the different CCR power ratings. Table 1 Power Requirements CCR Rating 4kW 7.5kW 10kW 15kW 20kW 30kW 8.1.4 Rated Input Current (RMS Amperes) 380V 480V 12A 9A 22A 17A 29A 23A 43A 34A 58A 46A N/A 69A Cable and Conduit Do not locate line and load cables near sensitive control, radar, or communication lines. For suggested cable entrance locations, see Figure 5. 8.1.5 Installation Check List Read these instructions before attempting installation. 1. Improper installation can damage this regulator and may void the warranty! If the equipment fails to perform properly at any step of this procedure, consult the troubleshooting guide in Section 9. Call Crouse-Hinds Airport Lighting Products (860) 683-4300 if further information is required during installation. 2. Instructions for each equipment option included should also be read before proceeding with installation 3. SUGGESTION: completed. To stay organized, make a check mark next to each step as it is 10 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.1.5.1 Mechanical Installation 1. Unpack the Constant Current Regulator, and check for any shipping damage. 2. For handling, a 2” forklift clearance is provided underneath the unit on the side of the trolley. These should be used for lifting the CCR. NOTE: There is a flat metal plate the fork must clear on the side nearest to the floor. 3. Refer to Figures 2 thru 7 for mechanical installation details. Adequate clearance should be left around the regulator for accessing and cooling. Maintain 1-foot clearance between cabinet and rear wall. 4. Adjust CCR power module circuit breaker position so breaker switch actuator and lockout tabs protrude through the cabinet door. Use a 3/8 inch socket to adjust door plate and a 5/16 inch wrench to adjust the four circuit breaker bracket screws DANGER: DANGER 5. POWER IS LIVE TO CCR POWER CIRCUIT BREAKER LINE SIDE WHEN MAIN SYSTEM CIRCUIT BREAKER IS ON AND CCR POWER IS ENGAGED INTO BUS STABS. THE POWER IS PRESENT IN THE PROCEEDING CONDITIONS EVEN WHEN THE CCR POWER MODULE CIRCUIT BREAKER IS IN THE OFF POSITION. Install the main circuit card to the cabinet door. Refer to document 2512 included with the circuit board for further details. 11 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.1.5.2 Load Wiring and Check out CAUTION: CAUTION Do not connect counterpoise system to this terminal. 1. Before connecting remote control lines, check regulator operation using the rotary switch on the front panel. Follow steps A-C below. Notice: The regulator is equipped with a safety interlock switch so that when the door is opened, the regulator will de-energize. Be sure that the interlock switch is in its normal operating position before operating. A. Apply main power to the regulator B. Operate the regulator at all brightness steps and check the load current levels are correct. See regulator nameplate for load current levels. IMPORTANT: IMPORTANT Only a true RMS instrument can accurately measure the regulator output externally. Other instruments will provide improper readings. C. Shut off main power to the regulator. 2. Connect the series lighting circuit to the output of S-1 Safety Switch. Note: There is connected to S-1 output (load) size provided with L-823 connectors (one male and one female) attached. Use caution when handling load cable. Electrical hazards may be present on cable due to field conditions. 12 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.1.5.3 Control Wiring and Checkout 1. Connect remote control lines to terminal block TB1 located on the 34031 Control Board using the appropriate wiring diagram. Refer to figure 9, 10, and 11. See Figure 10 “Connections for use of external control Power.” Be sure to read the notes when connecting a regulator to an external source of control power. Regulators are shipped for configured “Internal” control power. CAUTION: CAUTION Incorrect wiring can cause malfunction or damage to the control system and possibly void the equipment warranty. Recheck these connections before operating. 2. Apply the yellow “Caution – This Equipment is Supplied By More Than One Power Source” label supplied with this manual to the cabinet door above its associated CCR Power Module circuit breaker if you connect to an external remote control source. 3. Make final operation check using local and remote modes. Steps A-C below. A. Apply main power to the regulator B. Operate the regulator in the local mode at all brightness steps and check for the correct current levels. C. Operate the regulator in the Remote mode at all brightness steps and check for correct current levels. 8.1.5.4 Final Installation Steps 1. Remove input and control power. 2. Make any option related connections discussed in the option supplements. 3. Check that all cables and wiring are dressed within the cabinet. Reinstall all covers. 13 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS DEVICE FUNCTION ENTER SETUP CONTRAST REMOTE OFF 1 2 LOCAL CONTROL SWITCH 3 5 4 DEVICE FUNCTION ENTER SETUP CONTRAST REMOTE OFF 1 2 LOCAL CONTROL SWITCH 3 5 4 Figure 2 14 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 3 15 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 4 16 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 5 17 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 6 18 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 7 19 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 8 20 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 9 21 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 9A 22 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS EXTERNAL NOTE: Figure 10 23 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.2 Operation Figure 2 shows the standard controls and indicators on the front control panel. 8.2.1 Local Control Rotary Switch The local control rotary switch in conjunction with the digital display acts as an interactive control terminal for commanding the regulator into local brightness steps or to place it into remote control mode. 8.2.2 Digital Display During normal operation, the digital display functions as a True RMS ammeter, displaying the regulator load current. During power-up, under system fault conditions the display performs other functions. When these other functions are finished using the display, it automatically returns to reading load current. When power is initially applied to the regulator, the computer performs checks for valid operation. If these checks are completed successfully, the display will read “P-X.X.”, where X.X is the software program version number, for a period of 1 second. The normal display activity will begin. If the regulator should shut down due to system fault, a message will immediately begin to scroll across the display to explain the reason for the shut down. See Section 9 for further information. 8.2.3 System Fault Display If a regulator shutdown occurs, you can find out what happened by reading the display: “HIGH LOAD CURRENT” – Overcurrent protection trip. “LOOP” – Open Load protection trip. 24 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 8.2.4 Circuit Breaker The circuit breaker on the regulator turns on/off the main input voltage to the regulator. WARNING: WARNING 8.2.5 Power is still present to the circuit breaker line side even when breaker is in the off position Bus Engaged Indicator Light When the CCR power module bus stabs are engaged into their mating halves on the cabinet bus, the indicator light will illuminate. Note, only turning off the main input power circuit breaker or de-engaging its associated CCR power module from its cabinet bus stab half, will remove 120V power from is associated 480/120V step-down transformer. The CCR power module circuit breaker and door interlock switch are not connected to the indicator light voltage source. 25 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 9 Maintenance WARNING: WARNING Installation, service, maintenance or operation should be performed by qualified personnel only. 9.1 Periodic Maintenance The Constant Current Regulator should be inspected periodically as shown below: Interval Procedure 1. Remove main power from the regulator. 2. Open the front door 3. Check all wiring connection for loose connections and tighten as necessary. 4. Check for broker or damaged wires and parts. 6 months 5. Remove dust build – up. 6. Inspect housing for rust or chipped paint. Clean and touch up with paint as required. 7. Close door. 8. Restore primary power to the regulator. Operate the regulator at all brightness steps, first by local control, then by remote control. Check for proper load currents. 9.2 Corrective Maintenance Corrective maintenance is required when the regulator does not work properly. This usually requires the replacement of parts or subassemblies. The use of easily removable subassemblies make repairs a simple task. The removal and replacement method should be obvious to qualified personnel. Refer to cabinet manual for bus maintenance. 26 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS WARNING: WARNING Voltages above 1000 volts are present when the regulator is operating. Do not repair or service without first removing power from the regulator. The use of lock-out devices is recommended. The control assembly contains parts that can be replaced in the field by a service person. If properly trained personnel are not available, replace the entire control assembly. Improper removal and handling can cause damage to the equipment. Particular areas of concern are: A. Remove power from the regulator before disconnecting the connector plugs from the control board. B. Note connections of terminal block connectors when replacing them back onto the control board. CAUTION: CAUTION The circuit cards located on the door are static sensitive. Do not remove or handle them without a static control wrist strap. 9.3 Problem Solving Guide This guide will assist qualified airport maintenance personnel in locating and correcting equipment failures. Problems associated with option functions are addressed in the specific option Supplement. If further assistance is required, contact the Customer Service Department at CrouseHinds Airport Lighting Products, Windsor, Connecticut. (Reference Figure 11 Wiring Diagram) 27 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 9.3.1 Fault Isolation The first step in fault isolation is the preliminary evaluation. Start by checking for disconnected wires, switches in the wrong position, blown or missing fuses, etc. Determine if other equipment on the same circuit is operating properly. Be sure that the equipment is being used properly by checking the operation instructions. Finally, if the digital display is working, use the displayed message to localize the problem. If these checks do not pinpoint the problem, try operating the regulator with a short across the load terminals. OPERATING INTO A SHORT WILL NOT HARM THE REGULATOR. This is the best way to find out if the problem is with the regulator or the load circuit. Once these checks have been made, refer to the checklist for further instructions. 28 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 11 – CCR Wiring Diagram See following pages for expanded views 29 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 11a 30 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 11b 31 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 11c 32 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 11d 33 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 12 34 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 9.3.1.2 DISPLAY MESSAGES AND WHAT THEY MEAN DISPLAY MESSAGE WHAT IT MEANS ‘P-X.X’ (where X.X is a number like 1.1) This is the indication that all power up checks are OK. The number is the program version. This should appear for 1 second. ‘High Load Current’ The regulator has tripped off-line due to an over current condition. See the section of protection problems to fix. ‘LOOP’ The regulator has tripped off-line due to an open circuit condition. Try operating the regulator into a short circuit. If it doesn’t trip again, check the field wiring for an open. If no open is found, or the unit trips even with a short circuit see the section on protection problems. Display shows some other readable Message. See the option supplement to find out what the message means. Display shows a bunch of funny things or See the section on display problems. garbage. 35 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS QUICK PROBLEM SOLVING CHECKLIST SYMPTOM 1. 2. System will not turn on. 3. Control display OFF. 4. System will not turn Control display is ON. on. WHAT TO DO Check power source turned on. Check for 120 VAC across X1 and X2 on transformer T2. It is probably bad. Check F2. If good, see the section on power supply problems. Check door interlock switch. 1. If display reads ‘0.00’ see the section on local control problem. 2. See the section on digital problems. System will not turn off 1. See section on local control problems. 2. See section on remote control problems. System turn on for 1 to 5 seconds, then trips out. 1. If display reads ‘LOOP’ or “High load current” see section on protection problems. 2. See section on digital problems. System works fine in Local but 1. See section on remote control problems. does not work in remote. 1. Check for overload. Check for overload by shorting the output terminals either with a shorting wire that will handle the CCR output current or by pulling the S1 handle if installed. If the regulator outputs appropriate step current in Wrong current levels in any or all steps, then the airfield circuit is probably overloading the all steps. CCR. 2. If problem is only in remote see section of remote control problems. 3. Otherwise, see section on regulation problems. Regulator works but display is 1. See section on display problems. out or showing ‘funny’ data. 36 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 9.3.2 Detail Problem Solving Guide On the next few pages are detailed problem solving guides. These guides make use of the digital display and the indicators on the control box circuit card to speed repair. 9.3.2.1 Opening the CCR CAUTION: CAUTION Turn off main power to the regulator before starting. To open the regulator, turn the door latch to the left. Override the interlock switch by pulling the interlock located in the top right corner of the unit. Turn on main power to the regulator to begin trouble-shooting. DANGER: DANGER BE CAREFUL! THE CIRCUITS INSIDE AND AROUND THE CABINET INTERIOR ARE ENERGIZED AND CONTAINED DANGEROUS CURRENT LEVELS. 9.3.2.2 Circuit Card Indicators Before doing any problem solving, take a few minutes to become familiar with the circuit card indicators. They are provided as an aid in deciding what part or subassembly to change. Now go to the detail checklist for the problem being addressed. 37 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS The following is a list of the indicators and their function: Designator DS1 Name +5V Description Indicates +5V is available. DS2 +12V Indicates +12V is available. DS3 -12V Indicates –12V is available. DS4 Unreg Indicates unregulated power is available for 5V and +/-12V regulators DS5 Contactor Indicates contactor is energized DS6 Remote Indicates rotary switch is in remote position. DS7 Run Indicates the CPU is running when on constantly. There is a CPU problem if it is off or flashing. DS8 Halt Indicates the CPU is running when off constantly. There is a CPU problem if it is off or flashing. DS9 Sync Indicates the control is receiving a 60Hz signal from the power transformer. DS10 Feedback Indicates the control is receiving a feedback signal from the output current transformer. The following LEDs indicate the associated relay is energized. DS11 Relay1 Indicates the board is in remote mode. DS12 Relay2 Indicates the CCR has input power. DS13 Relay3 Indicates the CCR is outputting current. DS14 Relay4 Indicates the CCR is outputting current in step 1. DS15 Relay5 Indicates the CCR is outputting current in step 2. DS16 Relay6 Indicates the CCR is outputting current in step 3. DS17 Relay7 Indicates the CCR is outputting current in step 4. DS18 Relay8 Indicates the CCR is outputting current in step 5. 38 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS POWER SUPPLY PROBLEM CHECKLIST SYMPTON All board indicators are OFF 1. 2. 3. One power supply indicator is OFF or it is very dim. 4. 1. WHAT TO DO Check fuse F2 to see if it has failed. If so, replace. If fuses are okay, replace the 34031 board. If the F2 fails again, replace the 34031 board. If the indicators light, but the regulator still does not work got to the next symptom. Check door interlock switch. Replace the 34031 Board For further help contact Crouse-Hinds Airport Lighting Products. CAUTION: CAUTION Turn off main and control power before removing or installing circuit cards. 39 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS PROTECTION PROBLEM CHECKLIST SYMPTOMS Display reads ‘LOOP; WHAT TO DO 1. Operate the regulator into shorted load. If problem clears, open airfield load is suspected. 2. Observe feedback indicator on the control board. If OFF, check current transformer T3 for an open winding. If T3 is OK, replace 34031 board. 3. While de-energized, check to see if K2 (Solid State Relay) SSR is shorted. If SSR is shorted replace relay. 4. Ensure K1 contactor coil is getting power. Display reads ‘HIGH LOAD CURRENT’ 1. If regulator operates on lower steps but currents are high, replace 34031 board. 2. If regulator trips right away, regardless of step, replace 34031 board. 3. K2 SSR may be open. Check coil connections to K2 SSR. Replace K2 SSR if necessary. For further help contact Crouse-Hinds Airport Lighting Products. 40 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS CAUTION: CAUTION Turn off main and control power before removing or installing circuit cards. REGULATION PROBLEM CHECKLIST SYMPTOM All currents low. WHAT TO DO 1. Check fuse F3 to see if control winding fuse has blown. If okay, replace 34031 board. 2. Check to see if K2 SSR is shorted. 3. Check connections to C1 capacitor bank. Measure capacitance to verify while CAP1 and CAP2 leads of power transformer are disconnected: 4kw, 60Hz = 150uF 7.5kw, 60Hz = 300uF 10kw, 60Hz = 400uF 15kw, 60Hz = 500uF 20kw, 60Hz = 700uF 30kw, 60Hz = 950uF WARNING: WARNING C1 capacitors contain stored energy and should be handled accordingly. High steps OK, but low steps are high. One-step high or low. Low steps OK, but high steps are low. 1. Replace 34031 board 1. If in local and remote control replace 34031 board. See section on Remote Control problems. 1. Run regulator in a short. If OK, regulator is over-loaded. 2. Check connections to C1 capacitor bank. Verify capacitance of C1 capacitor bank. 41 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS WARNING: WARNING C1 capacitors contain stored energy and should be handled accordingly. REGULATION PROBLEM CHECKLIST CONTINUED SYMPTOM Current fluctuates over a wide range. WHAT TO DO 1. Operate the regulator into shorted load. If problem clears, excessive lamps out on load is suspected. 2. Observe +12V indicator. If it blinks, then be sure area temperature is below 130 degrees F. If it is OK, replace the 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 42 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS CAUTION: CAUTION Turn off main and control power before removing or installing circuit card. LOCAL CONTROL PROBLEM CHECKLIST SYMPTOMS System will not turn on. 1. 2. System will not turn off. 1. 2. WHAT TO DO Observe Contactor indicator. It should go on and off when switching from off to a step. If it doesn’t then replace 34031 board. Check K1 coil for open. If open replace K1. If OK replace 34031 board. If system will not turn off when the interlock switch is opened, K1 may be welded closed. Observe Contactor indicator. If on all the time, replace 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 43 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS CAUTION: CAUTION Turn off main and control power before removing or installing circuit card. REMOTE CONTROL PROBLEM CHECKLIST SYMPTOM System will not turn on. WHAT TO DO 1. Check in local control. If not OK, see section on local control problems. 2. Check remote supply and wiring. If OK, replace 34031 board. 3. Check door interlock switch System will not turn off. 1. Check for control lines longer than 10,000 feet in length. Current fluctuates up or down. 1. Check for control lines longer than 10,000 feet in length. 2. Test in Local For further help contact Crouse-Hinds Airport Lighting Products 44 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS CAUTION: CAUTION Turn off main and control power before removing or installing circuit card. DIGITAL PROBLEM CHECKLIST SYMPTOM System will not turn on. WHAT TO DO 1. Observe Run and Halt indicators. If they are blinking, replace control board. If the Run indicator is on all the time, see the section on local control problems. For further help contact Crouse-Hinds Airport Lighting Products. 45 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS CAUTION: CAUTION Turn off main and control power before removing or installing circuit card. DISPLAY PROBLEM CHECKLIST SYMPTOM Regulator runs but no display. Regulator runs but Display shows wrong current. Regulator works but display is out or showing “funny” data WHAT TO DO 1. Check for a loose cable from the display to the control board If OK replace32752. Display Card. 1. Check S1 DIP switch settings on the control board. 2. Replace 34031 board. 1. If display reads ‘P-.X.X.’ and does not change, see the section on digital problems. 2. Replace 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 46 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Figure 13 47 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS 10 Spare Parts List 10.1 Recommended Spare Parts Parts that are option related (when installed) are discussed in the respective drawing for that option at the end of this manual. RECOMMENDED SPARE PARTS Item Number 1 2 Reference Designation LA1 T2 3 K1 3 K1 3 K1 4 K2 SSR 4A 5 6 Capacitor Bank 7 8 T3 8 T3 8 T3 Description Input Lightning Arrestor 36V/120V Control Transformer Contactor, 75A Resistive (4-10kW Units) Contactor, 94A Resistive (15kW Units) Contactor, 120A Resistive (20kW Units) Solid State Relay. SSR thermal transfer pad for SSR P/N 10047-2789 Control Board Capacitor, 50uF, 600V Display Board Current Transformer, 6.6A (4-10kW) Current Transformer, 6.6A (15-30kW) Current Transformer, 20A 48 Crouse-Hinds Part Number 10047-885 32279 Manufacturer Part Number GE 9L15ECB001 10047-1249 32084 32085 10047-2789 (4-30kW) 10047-2937 34031-1 32990 32752 31329 31374 31394 Ronken Industries 91D23506H32 Document 2447 Rev. H Instruction Manual Constant Current Regulator Switchgear System Series 82XSGS Item Number 9 Reference Designation LA2, LA3 F1, F3, F4 F201, F202 F2 10 11 Description Output Lightning Arrestor, 3kV Fuse, 1/8 A Slo-Blo 5 x 20 mm Fuse, 1A Slo-Blo 5 x 20 mm Fuse, 2A Slo-Blo 5 x 20 mm Display PC Board/Switch Assembly (knob not included) Ribbon Cable (Display Board to Control Board) 49 Crouse-Hinds Part Number 10053-703 32752 10047-2912 Manufacturer Part Number Cooper Power Systems UHS0303-0A0D0A1A Bussman GMD125mA Bussman GMD1A Bussman GMD2A