Installation Instructions NeoSwitch Passive Infrared (PIR) 347V Single Relay Occupancy Sensing Wall Switch (Ground Required) P/N 9850-000335-01 General Information • Readallinstructionsonbothsidesofthis sheetfirst EcoMeter Operation • InstallinaccordancewithALLlocalcodes • Forindooruseonly Load 1 EcoMeter LED OFF ON ON OFF Specifications Technology:PassiveInfrared(PIR) Electrical Ratings: 347VAC: • Incandescent/Tungsten–Max.load:4.3amps, 1500W,50/60Hz • Fluorescent/Ballast–Max.load:4.3amps, 1500W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test(10min Auto),Selectable5,15,30minutes Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Model Model Model Model Model Light Level Sensing:0to200foot-candles Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%Non-condensing Housing:Durable,injectionmoldedhousing. PolycarbonateresincomplieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.35"Hx1.732"W(110.49mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection;Green LEDactsasEcoMeterornightlightlocator. Action EcoMeter Apersonentersthespaceand theloadisactivated Benefit OFF Theareaisvacatedandthe lightsturnOFFautomatically 100% Increasedawarenessofenergysavings; Actsasanightlightlocator ApersonturnsthelightsOFF manuallyuponexitinganarea 100% Increasedawarenessofenergysavingsand remindsindividualstotakecontroloftheir lightingforadditionalsavings;Actsasanight lightlocator Thedaylightfeatureprevents thelightsfromautomatically turningONwhenaperson entersanarea 100% Increasedawarenessofenergysavingsand letsindividualknowthatthedaylighting featureisworking Coverage 36 , , 20 Minor Motion, IR TheONW-P-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontrol andconventionalWallSwitchall-in-one,usedforenergysavingsandconvenience. ONW-P-1001-347-W ONW-P-1001-347-V ONW-P-1001-347-LA ONW-P-1001-347-G ONW-P-1001-347-B Installation TheONW-P-1001-347canbeinstalledinanystandardsingle gangbox.Itmaybeinstalledinthesamemannerasanordinary WallSwitch. • WiretheONW-P-1001-347asdescribedinthe wiringsection. • MounttheONW-P-1001-347inthejunctionbox. Wiring TheONW-P-1001-347isdesignedforofficesupto300squarefeet. Major Motion, IR Description # # # # # , 8 PIR Technology Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone. TheONW-P-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch. ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitformanualONoperation. InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the Maximum coverage area may lightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.Ineithermode,thelightsstayON vary somewhat according to room aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafter shape and the presence of obstacles. apresetTimeDelayinterval. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential energysavingsthatareavailableintheparticularapplication. TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding Location individualstotakecontroloftheirlightingtomaximizeenergysavings. TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight. WheninstallingtheONW-P-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.The coverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclearLinesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetect of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-P-1001-347directlyintothehallway motion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minuteTimeDelay. whereitmaydetectpassers-by. CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements. 3.MountunittoWallBox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.InstallWallSwitchplate. Wiring Diagram 1: 347 VAC single level single circuit wiring diagram BLACK 347 VAC GREEN BLUE LOAD GROUND NEUTRAL Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Wiring Diagram 2: 347 VAC single level switch dual level wiring using a toggle switch wiring diagram BLUE BLACK 347 VAC GREEN LOAD 1 LOAD 2 GROUND NEUTRAL Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram TRAVELER WIRES BLUE BLUE GREEN GROUND THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. DIP Switch Settings DIP Switch Legend Not Used PIR Sensitivity Walk-Through Mode EcoMeter Override Relay 1 DIP Switch 1 2 Auto* Auto Full Disable Enable Disable 5 Minutes Manual 50% Enable Disable Enable 15 Minutes 30 Minutes *Self-Adjusts to 10 min. user mode 3 4 6 5 PIR Lens Daylight Sensor Level Adjustment Troubleshooting Issue DIP Switches ON/OFF Button 7 8 Default = 1 2 3 4 5 6 7 PIR Sensitivity 1.Standindifferentareasoftheroomandwaveyourhands. 2.IftheRedLEDdoesnotturnON,checkforanyobstructions. 3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4.IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up. 8 Daylight Adjustments ThedaylightingfeaturepreventsthelightsfromturningONwhentheroom isadequatelyilluminatedbynaturallight.Ifthereisenoughlightintheroom regardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough lightintheroom,thesensorwillallowthelightstoturnONwhenoccupied.The sensorwillnotallowthedaylightingfeaturetoturntheloadOFFuntilthespaceis vacantorthelightlevelrisesabovethesetpointandtheTimeDelayexpires.While inManualActivationMode,ifsomeoneattemptstoturntheloadONandthereis sufficientdaylightavailablethedaylightingfeaturewillholdthelightsOFF. 1.Setthelightlevelwhentheambientlightisatthelevelwherenoartificial lightisneeded.Ifthisfeatureisnotneeded,leavethelightlevelat maximum.(fullyCW) 2.Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode, toggleDIPSwitch8outofitscurrentposition,wait3secondsandthenback intoitsoriginalposition. 3.SettheLightleveltominimum.(fullyCCW) 4.LetthesensortimeoutsolightsareOFF.EnterthespaceandlightsshouldremainOFF. 5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall increments.Pause5secondsbetweeneachadjustment) 6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting. Possible Causes Suggestions SensorisinManualONmode PressPushbutton.IfAutoMode isdesiredchangeActivationModetoAuto. SensorwasturnedOFFmanually.IftheSensor Lights wasturnedOFFmanuallybeforetheTimeDelay Will Not expired,lightswillremainOFFfortheremainder Turn ON oftheTimeDelay. automatically Lights Will Not Turn ON manually CheckEcoMeterLED,ifLEDisONthisis anindicationthatthelightswereturnedOFFmanually. PressthePushbuttontoturnthelightsbackON. DaylightFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring. DaylightFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring. If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Field-of-view outside the space 1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up. 2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace. NEUTRAL Activation Red (PIR) Detection LEDs Installer Adjustments BLACK GREEN LOAD 1 GROUND Time Delay Override TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1.MoveDIPSwitch8up. 2.ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF. Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. 347 VAC BLACK 1.WalkaroundtheroomandmonitorLEDs. 2.Standindifferentpartsoftheroomandwaveyour hands.LEDshouldonlyturnONforonesecondwith eachmotion.(IfLEDdoesnotturnON,gotoInstaller AdjustmentsSection) 3.Standstillthreetofourfeetawayfromsensorforfive seconds.LEDshouldnotturnON.(IfLEDturnson,go toInstallerAdjustmentssection) 4.Walkoutsidetheroomandwait15secondsforthe lightstoturnOFF.(IflightsdonotturnoffgotoInstaller AdjustmentsSection) 5.Re-entertheroomtoactivatesensor.(Iflightsdonot turnONgotoTroubleshootingSection) 6.Atthispointyoucanexittheroomandletthesensor Time-outandisOFFwithpoweronforfiveminutes,the unitwillgotoa10minuteTimeDelayuser modeseting. Override MakesuresensorisnotinOverrideMode(DIPSwitch8up). Self-Adjust IfsensorisinSelf-AdjustMode,itmaybepossibleforthe unittohaveincreasedtheTimeDelaytoa30minutedelay. IfthelightsdonotturnOFFafter30minutesfollownextstep. 30MinuteDelay MaximumTimeDelayis30Minutes.CheckDIPSwitches toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe setTimeDelay,checknextstep. PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up. Lights Will Not Turn OFF automatically Lights Will Not Turn OFF automatically CallTechnicalServices If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Checkout and Adjustment Time Delay Adjustments PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10 minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithno normaloffinbetween,byalternatelymakingslightadjustmentsto eitherTimeDelay(by2minuteincrements)orsensitivity,sothere shouldbenoneedformanualadjustment.Ifmanualadjustmentis desired,refertoTimeDelaysettingsinDIPSwitchlegend. Self-Adjust ResetsensorTimeDelaytofactorysettingsbymovingDIP Sensorisshippedinself-adjustmode.ThisappliestoTimeDelay,USandPIRsensitivity.Inpreparationforthe 1 2 3 4 5 6 7 8 DIP Switches Switches1and2down.(IfDIPSwitches1and2arealready InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the 1&2 unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching down,toggleDIPSwitch1outofitscurrentposition,wait3 seconds,andthenbacktoitsoriginalposition) theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom. AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof airflowontheoperationoftheONW-P-1001-347.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup andstabilize. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com