Installation Instructions NeoSwitch Passive Infrared (PIR) 347V

advertisement
Installation Instructions
NeoSwitch Passive Infrared (PIR) 347V
Single Relay Occupancy Sensing Wall Switch
(Ground Required)
P/N 9850-000335-01
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
EcoMeter Operation
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Load 1
EcoMeter LED
OFF
ON
ON
OFF
Specifications
Technology:PassiveInfrared(PIR)
Electrical Ratings:
347VAC:
• Incandescent/Tungsten–Max.load:4.3amps,
1500W,50/60Hz
• Fluorescent/Ballast–Max.load:4.3amps,
1500W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Model
Model
Model
Model
Model
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.35"Hx1.732"W(110.49mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDactsasEcoMeterornightlightlocator.
Action
EcoMeter
Apersonentersthespaceand
theloadisactivated
Benefit
OFF
Theareaisvacatedandthe
lightsturnOFFautomatically
100%
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ApersonturnsthelightsOFF
manuallyuponexitinganarea
100%
Increasedawarenessofenergysavingsand
remindsindividualstotakecontroloftheir
lightingforadditionalsavings;Actsasanight
lightlocator
Thedaylightfeatureprevents
thelightsfromautomatically
turningONwhenaperson
entersanarea
100%
Increasedawarenessofenergysavingsand
letsindividualknowthatthedaylighting
featureisworking
Coverage
36
,
,
20
Minor Motion, IR
TheONW-P-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontrol
andconventionalWallSwitchall-in-one,usedforenergysavingsandconvenience.
ONW-P-1001-347-W
ONW-P-1001-347-V
ONW-P-1001-347-LA
ONW-P-1001-347-G
ONW-P-1001-347-B
Installation
TheONW-P-1001-347canbeinstalledinanystandardsingle
gangbox.Itmaybeinstalledinthesamemannerasanordinary
WallSwitch.
• WiretheONW-P-1001-347asdescribedinthe
wiringsection.
• MounttheONW-P-1001-347inthejunctionbox.
Wiring
TheONW-P-1001-347isdesignedforofficesupto300squarefeet.
Major Motion, IR
Description
#
#
#
#
#
,
8
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
TheONW-P-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitformanualONoperation.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
Maximum coverage area may
lightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.Ineithermode,thelightsstayON
vary somewhat according to room
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafter
shape and the presence of obstacles.
apresetTimeDelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential
energysavingsthatareavailableintheparticularapplication.
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding
Location
individualstotakecontroloftheirlightingtomaximizeenergysavings.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
WheninstallingtheONW-P-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.The
coverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclearLinesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetect of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-P-1001-347directlyintothehallway
motion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minuteTimeDelay.
whereitmaydetectpassers-by.
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.MountunittoWallBox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.InstallWallSwitchplate.
Wiring Diagram 1: 347 VAC single level single circuit wiring diagram
BLACK
347 VAC
GREEN
BLUE
LOAD
GROUND
NEUTRAL
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Wiring Diagram 2: 347 VAC single level switch dual level wiring using a toggle switch wiring diagram
BLUE
BLACK
347 VAC
GREEN
LOAD 1
LOAD 2
GROUND
NEUTRAL
Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram
TRAVELER
WIRES
BLUE
BLUE
GREEN
GROUND
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
DIP Switch Legend
Not Used
PIR Sensitivity Walk-Through Mode
EcoMeter
Override
Relay 1
DIP Switch
1
2
Auto*
Auto
Full
Disable
Enable
Disable
5 Minutes
Manual
50%
Enable
Disable
Enable
15 Minutes
30 Minutes
*Self-Adjusts to
10 min. user mode
3
4
6
5
PIR Lens
Daylight
Sensor Level
Adjustment
Troubleshooting
Issue
DIP Switches
ON/OFF Button
7
8
Default =
1
2
3
4
5
6
7
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
8
Daylight Adjustments
ThedaylightingfeaturepreventsthelightsfromturningONwhentheroom
isadequatelyilluminatedbynaturallight.Ifthereisenoughlightintheroom
regardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough
lightintheroom,thesensorwillallowthelightstoturnONwhenoccupied.The
sensorwillnotallowthedaylightingfeaturetoturntheloadOFFuntilthespaceis
vacantorthelightlevelrisesabovethesetpointandtheTimeDelayexpires.While
inManualActivationMode,ifsomeoneattemptstoturntheloadONandthereis
sufficientdaylightavailablethedaylightingfeaturewillholdthelightsOFF.
1.Setthelightlevelwhentheambientlightisatthelevelwherenoartificial
lightisneeded.Ifthisfeatureisnotneeded,leavethelightlevelat
maximum.(fullyCW)
2.Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,
toggleDIPSwitch8outofitscurrentposition,wait3secondsandthenback
intoitsoriginalposition.
3.SettheLightleveltominimum.(fullyCCW)
4.LetthesensortimeoutsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.Pause5secondsbetweeneachadjustment)
6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Possible Causes
Suggestions
SensorisinManualONmode
PressPushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.IftheSensor
Lights
wasturnedOFFmanuallybeforetheTimeDelay
Will Not
expired,lightswillremainOFFfortheremainder
Turn ON
oftheTimeDelay.
automatically
Lights
Will Not
Turn ON
manually
CheckEcoMeterLED,ifLEDisONthisis
anindicationthatthelightswereturnedOFFmanually.
PressthePushbuttontoturnthelightsbackON.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
NEUTRAL
Activation
Red (PIR)
Detection LEDs
Installer Adjustments
BLACK
GREEN
LOAD 1
GROUND
Time Delay
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.
2.ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
347 VAC
BLACK
1.WalkaroundtheroomandmonitorLEDs.
2.Standindifferentpartsoftheroomandwaveyour
hands.LEDshouldonlyturnONforonesecondwith
eachmotion.(IfLEDdoesnotturnON,gotoInstaller
AdjustmentsSection)
3.Standstillthreetofourfeetawayfromsensorforfive
seconds.LEDshouldnotturnON.(IfLEDturnson,go
toInstallerAdjustmentssection)
4.Walkoutsidetheroomandwait15secondsforthe
lightstoturnOFF.(IflightsdonotturnoffgotoInstaller
AdjustmentsSection)
5.Re-entertheroomtoactivatesensor.(Iflightsdonot
turnONgotoTroubleshootingSection)
6.Atthispointyoucanexittheroomandletthesensor
Time-outandisOFFwithpoweronforfiveminutes,the
unitwillgotoa10minuteTimeDelayuser
modeseting.
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedtheTimeDelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
MaximumTimeDelayis30Minutes.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe
setTimeDelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
automatically
Lights
Will Not
Turn OFF
automatically
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithno
normaloffinbetween,byalternatelymakingslightadjustmentsto
eitherTimeDelay(by2minuteincrements)orsensitivity,sothere
shouldbenoneedformanualadjustment.Ifmanualadjustmentis
desired,refertoTimeDelaysettingsinDIPSwitchlegend.
Self-Adjust
ResetsensorTimeDelaytofactorysettingsbymovingDIP
Sensorisshippedinself-adjustmode.ThisappliestoTimeDelay,USandPIRsensitivity.Inpreparationforthe
1 2 3 4 5 6 7 8
DIP Switches
Switches1and2down.(IfDIPSwitches1and2arealready
InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
1&2
unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching down,toggleDIPSwitch1outofitscurrentposition,wait3
seconds,andthenbacktoitsoriginalposition)
theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom.
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheONW-P-1001-347.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Printed in Malaysia
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com