Installation Instructions Digital Wall Switch Timer 120/277 VAC General Information

advertisement
Installation Instructions
Digital Wall Switch Timer
Model # TSW-MV-W
120/277 VAC
P/N 9850-000414-00
General Information
Features
• Readallinstructionsonbothsidesofthis
sheetfirst
• Planallcomponentlocationscarefully
• Installinaccordancewithalllocalcodes
• Forusewith120VACor277VAConly
• Notforusewheretemperaturesfallbelow60°For
exceed90°F
• Forindooruseonly
Specifications
Operating Environment:
• Temperature:60°F–80°F(15°C–26°C)
• RelativeHumidity:Lessthan90%non-condensing
• Forindooruseonly
Size:
• MountingPlateDimensions:
4.15"Hx1.94"W(105.41mmx49.28mm)
• ProductHousingDimensions:
2.73"Hx1.8"Wx1.8"D
(69.34mmx45.72mmx45.72mm)
Electrical Ratings:
120VAC:
• Tungsten–Max.load:
10amps,960W,+/-10%60Hz
• Ballast–Max.load:
10amps,1200W,+/-10%60Hz
• MotorLoad:¼HP@120VAC
277VAC:
• Ballast–Max.load:
10amps,1200W,+/-10%60Hz
No Minimum Load Requirement
Contact Ratings:
TYPE OF LOAD
120 VAC
277 VAC
Resistive
15A
15A
Ballast
10A
10A
LEDDriver
1200W
1200W
Tungsten
960W
-
Motor
1/4HP
-
PilotDuty
360VA
-
• LCDdisplaythatstandsoutstronglyinlightedareasandisbacklitforvisibilityindarkareas
• Tamperresistanttime-oninterval,whichcanbepreset.Inaddition,amanualscroll-upmodethatcanoverridethe
settingtemporarily–thisfeaturecanbedisabled,therebyprovidingafixedintervaltimer
• Flickeroflightsand/orbeepwarning,whichbegins2minutesbeforetime-out(eitherorbothcanbedisabled)
• Zeropowerswitchingtoprolongthelifeofrelaycontactsbyswitchinghighinrushequipmentatorcloseto
zeropower
• Incandescentlighting,ormotorloads,compatiblewithelectronicballasts
• Decoratortypefacewithmatchingwallplateincluded
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
Wiring Diagram 1: Single Pole Wiring
Installation
CAUTION: Before wiring and servicing, power to this time switch and the equipment in controls must be turned
OFF at the main panel.
WARNING: Unit must be properly grounded to operate correctly.
1.Connectthewiresasshowninthesinglepolewiringdiagram.
2.Captheunusedgroundwire.
3.Mountthetimerinsidetheelectricalboxusingthe2mountingscrewsprovided.
4.Installtheenclosedcoverplate.
5.TurnthepowerONattheelectricalpanel.
6.Whenpoweringupforthefirsttime,allow1minutefortheunittoshowOFFonthescreen.AnLCD“OFF”message
willbedisplayedasadefaultandtheloadwillbeswitchedOFF.
Wiring Diagram 1: Three-Way Wiring
Description
Thesolidstateintervaltimerisdesignedtocontrollightingandmotorloads.Momentarilypressingthestart/stop
buttonlocatedonthefrontoftheunitwillturntheloadONandstartthecount-downtime(setbytheuserutilizingthe
DIPSwitches)attheendofwhichtheloadwillturnOFF.IfthereisaneedtoturntheloadOFFbeforethecount-down
timehasexpired,presstheSTART/STOPbuttonmomentarily.TheunitcanbeprogrammedviaDIPswitchsettingsto
flickertheload(lights),and/orbeepasawarningindicatingthattheloadisabouttoturnOFF.Ascrolloptioncanbe
settotemporarilychangethepresetcount-downtimebypressingandholdingdownthestart/stopbuttonformore
than3seconds.
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Settings
• Thetamperresistanttime-onintervalcanbepreset.Inaddition,amanualscroll-upmodecanoverridethe
settingtemporarily–thisfeaturecanbedisabled,therebyprovidingafixedintervaltimer.
• Aflickerofthelightsand/orabeepwarningbegins2minutesbeforetime-out(eitherorbothcanbedisabled).
Operation
Troubleshooting
1.ToturnloadON,presstheSTART/STOPbuttonmomentarily.
•TheLCDwilldisplaythecountdowntimeintervalselected.Thetimeintervalwillstartcountingdown.
TheTSW-MVisfactorypresettomeetnewerenergycodeoverridemandates.Noadjustmentisrequired.This
settingwillprovideatwohourmaximumoperatingtimebeforeshut-off.Thescrollfeatureisactivetoallowtheuser
tochangetheoperatingtimewiththemaximumtimesettingattwohours.
Closethetimerdoorandtheunitisready.OnepressofthebottomcoverturnstheloadON.TheloadwillstayON
untilacount-downtothepresetOFFtime.PressingthebottomcoveragainwillturnloadOFF.
SET FOR:
1.4HR:SetONforpreset4hourmaximum
countdownwhen2HRissettoOFF.(Also
usedincustomtimeprogramming.)
2.2HR:SetONforpreset2hourmaximum
countdownwhen4HRissettoOFF.(Also
usedincustomtimeprogramming.)
3.LIMIT:Usedwithprogrammingsequence.
SwitchfromONtoOFFtolimitscrollto
matchcustomtime.
4.SCROLL:SetONallowingthetimertoscroll
toashorterruntime.SetOFFtodisable.
SwitchfromONtoOFFtosetacustomtime.(Alsousedinprogrammingsequence.)
Thetimescrollsinsteps:
•5minutestepsfrom5minutesto1hour
•10minutestepsfrom1to4hours
•30minutestepsfrom4to12hours
•1hourstepsfrom12to24hours
5.BEEPER:SetONactivatingthefeatureforabeepwarningevery15secondsstarting2minutesbeforeOFF.
6.BLINK:SetONactivatingafeatureforloadflash2minutesbeforeOFF.
1.Totesttheunit,settheDIPSwitchtotheminimaltime-outinterval(5minutes).
2.Iftheunitdoesnotfunction:
a.Check thegroundwire.Makesuretheboxhasgoodgroundandisattachedproperly.
b.Checkallotherwiringtomakesureconnectionissecure.
c.Checkifpoweristurnedbackonatthemaincircuitbreakerpanel.
d.Iftheunitstilldoesnotfunction,consultthefactory.
3.IftheloadwillnotturnOFFautomatically:
a.CheckiftheloadgoesON/OFFwhenpressingSTART/STOPbutton.Ifnot,checktheredwireforgood connection.IfloaddoesgoON/OFF,consultthefactory.