Installation Instructions Digital Wall Switch Timer Model # TSW-MV-W 120/277 VAC P/N 9850-000414-00 General Information Features • Readallinstructionsonbothsidesofthis sheetfirst • Planallcomponentlocationscarefully • Installinaccordancewithalllocalcodes • Forusewith120VACor277VAConly • Notforusewheretemperaturesfallbelow60°For exceed90°F • Forindooruseonly Specifications Operating Environment: • Temperature:60°F–80°F(15°C–26°C) • RelativeHumidity:Lessthan90%non-condensing • Forindooruseonly Size: • MountingPlateDimensions: 4.15"Hx1.94"W(105.41mmx49.28mm) • ProductHousingDimensions: 2.73"Hx1.8"Wx1.8"D (69.34mmx45.72mmx45.72mm) Electrical Ratings: 120VAC: • Tungsten–Max.load: 10amps,960W,+/-10%60Hz • Ballast–Max.load: 10amps,1200W,+/-10%60Hz • MotorLoad:¼HP@120VAC 277VAC: • Ballast–Max.load: 10amps,1200W,+/-10%60Hz No Minimum Load Requirement Contact Ratings: TYPE OF LOAD 120 VAC 277 VAC Resistive 15A 15A Ballast 10A 10A LEDDriver 1200W 1200W Tungsten 960W - Motor 1/4HP - PilotDuty 360VA - • LCDdisplaythatstandsoutstronglyinlightedareasandisbacklitforvisibilityindarkareas • Tamperresistanttime-oninterval,whichcanbepreset.Inaddition,amanualscroll-upmodethatcanoverridethe settingtemporarily–thisfeaturecanbedisabled,therebyprovidingafixedintervaltimer • Flickeroflightsand/orbeepwarning,whichbegins2minutesbeforetime-out(eitherorbothcanbedisabled) • Zeropowerswitchingtoprolongthelifeofrelaycontactsbyswitchinghighinrushequipmentatorcloseto zeropower • Incandescentlighting,ormotorloads,compatiblewithelectronicballasts • Decoratortypefacewithmatchingwallplateincluded Wiring CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. Wiring Diagram 1: Single Pole Wiring Installation CAUTION: Before wiring and servicing, power to this time switch and the equipment in controls must be turned OFF at the main panel. WARNING: Unit must be properly grounded to operate correctly. 1.Connectthewiresasshowninthesinglepolewiringdiagram. 2.Captheunusedgroundwire. 3.Mountthetimerinsidetheelectricalboxusingthe2mountingscrewsprovided. 4.Installtheenclosedcoverplate. 5.TurnthepowerONattheelectricalpanel. 6.Whenpoweringupforthefirsttime,allow1minutefortheunittoshowOFFonthescreen.AnLCD“OFF”message willbedisplayedasadefaultandtheloadwillbeswitchedOFF. Wiring Diagram 1: Three-Way Wiring Description Thesolidstateintervaltimerisdesignedtocontrollightingandmotorloads.Momentarilypressingthestart/stop buttonlocatedonthefrontoftheunitwillturntheloadONandstartthecount-downtime(setbytheuserutilizingthe DIPSwitches)attheendofwhichtheloadwillturnOFF.IfthereisaneedtoturntheloadOFFbeforethecount-down timehasexpired,presstheSTART/STOPbuttonmomentarily.TheunitcanbeprogrammedviaDIPswitchsettingsto flickertheload(lights),and/orbeepasawarningindicatingthattheloadisabouttoturnOFF.Ascrolloptioncanbe settotemporarilychangethepresetcount-downtimebypressingandholdingdownthestart/stopbuttonformore than3seconds. Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Settings • Thetamperresistanttime-onintervalcanbepreset.Inaddition,amanualscroll-upmodecanoverridethe settingtemporarily–thisfeaturecanbedisabled,therebyprovidingafixedintervaltimer. • Aflickerofthelightsand/orabeepwarningbegins2minutesbeforetime-out(eitherorbothcanbedisabled). Operation Troubleshooting 1.ToturnloadON,presstheSTART/STOPbuttonmomentarily. •TheLCDwilldisplaythecountdowntimeintervalselected.Thetimeintervalwillstartcountingdown. TheTSW-MVisfactorypresettomeetnewerenergycodeoverridemandates.Noadjustmentisrequired.This settingwillprovideatwohourmaximumoperatingtimebeforeshut-off.Thescrollfeatureisactivetoallowtheuser tochangetheoperatingtimewiththemaximumtimesettingattwohours. Closethetimerdoorandtheunitisready.OnepressofthebottomcoverturnstheloadON.TheloadwillstayON untilacount-downtothepresetOFFtime.PressingthebottomcoveragainwillturnloadOFF. SET FOR: 1.4HR:SetONforpreset4hourmaximum countdownwhen2HRissettoOFF.(Also usedincustomtimeprogramming.) 2.2HR:SetONforpreset2hourmaximum countdownwhen4HRissettoOFF.(Also usedincustomtimeprogramming.) 3.LIMIT:Usedwithprogrammingsequence. SwitchfromONtoOFFtolimitscrollto matchcustomtime. 4.SCROLL:SetONallowingthetimertoscroll toashorterruntime.SetOFFtodisable. SwitchfromONtoOFFtosetacustomtime.(Alsousedinprogrammingsequence.) Thetimescrollsinsteps: •5minutestepsfrom5minutesto1hour •10minutestepsfrom1to4hours •30minutestepsfrom4to12hours •1hourstepsfrom12to24hours 5.BEEPER:SetONactivatingthefeatureforabeepwarningevery15secondsstarting2minutesbeforeOFF. 6.BLINK:SetONactivatingafeatureforloadflash2minutesbeforeOFF. 1.Totesttheunit,settheDIPSwitchtotheminimaltime-outinterval(5minutes). 2.Iftheunitdoesnotfunction: a.Check thegroundwire.Makesuretheboxhasgoodgroundandisattachedproperly. b.Checkallotherwiringtomakesureconnectionissecure. c.Checkifpoweristurnedbackonatthemaincircuitbreakerpanel. d.Iftheunitstilldoesnotfunction,consultthefactory. 3.IftheloadwillnotturnOFFautomatically: a.CheckiftheloadgoesON/OFFwhenpressingSTART/STOPbutton.Ifnot,checktheredwireforgood connection.IfloaddoesgoON/OFF,consultthefactory. Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com