Installation Instructions NeoSwitch Passive Infrared (PIR) Dual Relay Vacancy Sensing Wall Switch

advertisement
Installation Instructions
NeoSwitch Passive Infrared (PIR)
Dual Relay Vacancy Sensing Wall Switch
(Ground Required)
P/N 9850-000287-02
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
EcoMeter Operation
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Specifications
Technology:PassiveInfrared(PIR)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–Max.load:6.7amps,
800W,50/60Hz
• Fluorescent/Ballast–Max.load:10amps,1200W,
50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–Max.load:9.8amps,
2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Model # VNW-P-1001-DMV-W
Model # VNW-P-1001-DMV-V
Model # VNW-P-1001-DMV-G
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDactsasEcoMeterornightlightlocator.
Action
EcoMeter
Benefit
50%
Increasedawarenessofenergysavings
Load 1
Load 2
EcoMeter LED
Apersonentersthespaceandoneof
theloadsisactivated
OFF
OFF
100%
BothloadsareON
OFF
ON
OFF
50%
ON
50%
Theareaisvacatedandthelightsturn
OFFautomatically
100%
OFF
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ON
ON
OFF
ApersonturnsthelightsOFF
manuallyuponexitinganarea
100%
Increasedawarenessofenergysavings
andremindsindividualstotakecontrol
oftheirlightingforadditionalsavings;
Actsasanightlightlocator
Ifthedaylightingfunctionisactivated
foroneofthetwoloadsandthereis
sufficientdaylightinthespace,theunit
willholdthatloadOFF
50%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
Ifthedaylightingfunctionisactivated
forbothloadsandthereissufficient
daylightinthespace,theunitwillhold
thatloadsOFF
100%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
Coverage
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
Wiring Diagram 1: 120/277 VAC dual level single circuit wiring diagram
TheVNW-P-1001-DMVisdesignedforofficesupto300squarefeet.
36
Wiring
,
,
20
120/277 VAC
Minor Motion, IR
Description
TheVNW-P-1001-DMVVacancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontrol
andconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
BLACK
BLUE
RED
RED
Major Motion, IR
GREEN
,
8
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
TheVNW-P-1001-DMVallowsthecontroloftwoseparateloadswithoneoccupancysensorswitch.
ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,the
Maximum coverage area may
lightsstayONaslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFF
vary somewhat according to room
automaticallyafterapresetTimeDelayinterval.
shape and the presence of obstacles.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
Location
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding
WheninstallingtheVNW-P-1001-DMVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
individualstotakecontroloftheirlightingtomaximizeenergysavings.
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearline-ofTheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNW-P-1001-DMVdirectlyintothehallway
BathroomMode–Whenselected,bathroommodekeepsthesecondrelayONforanadditional8minutes,after
whereitmaydetectpassers-by.
thefirstrelayhasbeenturnedoff.Combinethiswithchangingthepushbuttontothelight/fangraphicandyounow
havetheuniversallyrecognizedandeasytousebathroomsolution.
RelaySwapOption–Acommonprobleminelectricwiringiswiringthewrongswitchtothewrongload.Thiscan
Installation
makecontrolofloadsconfusingtoanenduser.TheRelaySwapoptionsolvestheproblembyallowingtheswitch
buttonsonthefaceoftheunittobeswapped,aftertheunitiswiredandinstalled.
TheVNW-P-1001-DMVcanbeinstalledinanystandardsinglegangbox.It
maybeinstalledinthesamemannerasanordinarywallswitch.
• WiretheVNW-P-1001-DMVasdescribedinthewiringsection.
• MounttheVNW-P-1001-DMVinthejunctionbox.
LOAD 1
LOAD 2
GROUND
NEUTRAL
Wiring Diagram 2: 120/277 VAC dual level dual circuit wiring diagram
CIRCUIT 1
120/277 VAC
BLACK
BLUE
CIRCUIT 2
120/277 VAC
RED
RED
GREEN
LOAD 2
LOAD 1
CIRCUIT 1
GROUND
NEUTRAL (CIRCUIT 2)
NEUTRAL (CIRCUIT 1)
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Wiring Diagram 3: 120/277 VAC dual level single circuit three-way wiring diagram
4.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6.Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisinactiveforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
TRAVELER
WIRES
120/277 VAC
BLACK
BLUE
RED
RED
BLUE
RED
GREEN
Installer Adjustments
GREEN
GROUND
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
GROUND
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
DIP Switch Legend
Time Delay
Not Used
PIR Sensitivity
Not Used
EcoMeter
Override
Bathroom
Relay Swap
Daylighting
Relay 1
Relay 2
DIP Switch
1
2
Auto*
Full
Enable
Disable
Disable
Normal
Disable
Disable
5 Minutes
50%
Disable
Enable
Enable
Swap
Enable
Enable
15 Minutes
30 Minutes
3
4
5
6
7
8
9
10
11
12
*Self-Adjusts to
10 min. user
mode
Default =
1
2
3
4
5
6
7
8
9
10 11 12
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheVNW-P-1001-DMV.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelighting
circuit,waitapproximatelytwominutesfortheswitch
topowerupandstabilize.
Self-Adjust
Red (PIR)
Detection LED
SensorisshippedinSelf-AdjustMode.Thisapplies
totimedelayandPIRsensitivity.Inpreparationforthe
Daylight
InstallerTest,thetimedelayissetto15seconds,after
Sensor Level
thesensorisinstalled,poweredONandhasstabilized,
Adjustment
theunitwilltime-out15secondsafterthelastmotion
EcoMeter
detected.Coverageandsensitivitycanbeconfirmedby
watchingtheRed(PIR)indicatorLEDonthefrontofthe
sensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.
2.Standindifferentpartsoftheroomandwave
yourhands.LEDshouldonlyturnONforone
secondwitheachmotion.(IfLEDdoesnotturn
ON,gotoInstallerAdjustments–Sensitivity
ON/OFF Buttons
1&2
AdjustmentSection)
3.Standstillthreetofourfeetawayfromsensorfor
fiveseconds.LEDshouldnotturnON.(IfLEDturnsON,gotoInstallerAdjustments–Sensitivity
Adjustmentssection)
PIR Lens
DIP Switches
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.
Ifthereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough
lightintheroom,thesensorwillallowthelightstoturnON.TheDaylightingfeatureallowstheselectionofwhichrelayto
controlviadaylighting(dualloadmodelsonly).ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntil
thespaceisvacantifthelightlevelrisesabovethesetpointandtheTimeDelayexpires.Ifsomeoneattemptstoturnthe
loadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOFF.
1.Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnot
needed,leavethelightlevelatmaximum(fullyCW).
2.SetDIPSwitches11(Relay1)and/or12(Relay2)for
daylightcontrol.
3.Withtheload(s)ON,putthesensorintoTestMode.To
placeintoTestMode,toggleDIPSwitch12outofits
currentposition,wait3secondsandthenbackintoits
1 2 3 4 5 6 7 8 9 10 11 12
11 and 12
originalposition.
4.Setthelightleveltominimum(fullyCCW).
5.Letthesensortime-outsolightsareOFF.Enterthe
spaceandlightsshouldremainOFF.
6.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.(Pause5secondsbetweeneachadjustment)
7.LightswillnotturnONuponmanualactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemay
needalongertimedelaythanthedefaultsettingof10minutes.
Aslongastheself-adjustingfeatureisenabled,theswitch
willrespondtoeachpairoffalse-offswithnonormalOFFin
between,byalternatelymakingslightadjustmentstoeithertime
1 2 3 4 5 6 7 8 9 10
delay(by2minuteincrements)orsensitivity,sothereshouldbe 1 and 2
noneedformanualadjustment.Ifmanualadjustmentisdesired,
refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIP
Switches1and2down.(IfDIPSwitches1and2arealready
down,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Issue
Lights
Will Not
Turn ON
manually
RED
LOAD 1
LOAD 2
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
BLACK
Troubleshooting
Possible Causes
Suggestions
DaylightFeatureEnabled
IfalllightsarerequiredadjustDIPSwitches
11and12and/ordaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
MakesuresensorisnotinOverrideMode
(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedtheTimeDelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
MaximumTimeDelayis30Minutes.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe
setTimeDelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
11 12
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.
2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Printed in Malaysia