Installation Instructions NeoSwitch Passive Infrared (PIR) Single Relay Vacancy Sensing Wall Switch with Night Light (Neutral Required) P/N 9850-000353-01 General Information • Readallinstructionsonbothsidesofthis sheetfirst Coverage • InstallinaccordancewithALLlocalcodes • Forindooruseonly Wiring TheVNLW-P-1001-MV-Nisdesignedforofficesupto300squarefeet. 36 , , 20 Specifications Technology:PassiveInfrared(PIR) Electrical Ratings: 120VAC: • Incandescent/Tungsten–Max.load:6.7amps, 800W,50/60Hz • Fluorescent/Ballast–Max.load:10amps,1200W, 50/60Hz MotorLoad:¼HP@125VAC 277VAC: • Fluorescent/Ballast–Max.load:9.8amps, 2700W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test,1,5,15, 20,30minutes,1hour,2hours Model # VNLW-P-1001-MV-N-W Model # VNLW-P-1001-MV-N-V Model # VNLW-P-1001-MV-N-LA Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%Non-condensing Housing:Durable,injectionmoldedhousing. PolycarbonateresincomplieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.195"Hx1.732"W(106.553mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection; AmberLEDnightlight. Minor Motion, IR Major Motion, IR , 8 CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements. 3.MountunittoWallBox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.InstallWallSwitchplate. Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram Description Location ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightisalightingcontrolandWall Switchall-in-onethatisusedforenergysavingsandconvenience. WheninstallingtheVNLW-P-1001-MV-Ninanewjunctionbox,choosetheswitchlocationcarefullytoprovide optimumcoverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclear Line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNLW-P-1001-MV-Ndirectlyintothe hallwaywhereitmaydetectpassers-by. PIR Technology ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightusesPassiveInfrared(PIR) sensortechnologiestomonitoraroomforoccupancy. TheVNLW-P-1001-MV-Nallowsthecontrolofoneloadwithonevacancysensorswitch. ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.ThelightsstayONaslong asthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapreset Installation TimeDelayinterval. TheVNLW-P-1001-MV-Ncanbeinstalledinanystandardsingle A30secondgraceperiodisaddedafterthelightsshutOFFtogivetheoccupanttimetomoveagainincasethe gangbox.Itmaybeinstalledinthesamemannerasanordinary lightsshutOFF.Thispreventstheoccupantfromhavingtowalk-uptopressthePushbuttontoreactivatethesensor. WallSwitch. ThenightlightactivateswhensensorturnslightsOFF.Thisfeaturecanbedisabled,seeDIPSwitchSettings. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand • WiretheVNLW-P-1001-MV-Nasdescribedinthewiringsection. TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential • MounttheVNLW-P-1001-MV-Ninthejunctionbox. energysavingsthatareavailableintheparticularapplication. BLUE BLACK 120/277 VAC Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. GREEN LOAD WHITE GROUND NEUTRAL Wiring Diagram 2: 120/277 VAC single level single circuit three-way wiring diagram TRAVELER WIRES 120/277 VAC BLACK GREEN GROUND BLUE BLUE WHITE LOAD 1 WHITE BLACK GREEN GROUND NEUTRAL THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com DIP Switch Settings Time Delay Adjustments PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10 minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithnonormal OFFinbetweenbyalternatelymakingslightadjustmentstoeitherTimeDelay(by2minuteincrements)orsensitivity,so thereshouldbenoneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIP Switchlegend. ResetsensorTimeDelaytofactorysettingsbymovingDIPSwitches1,2,and3down.(IfDIPSwitches1,2,and3are alreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition) DIP Switch Legend Time Delay Not Used DIP Switch 1 2 3 PIR Sensitivity 4 Not Used 5 Night Light 6 Override 7 8 Auto* Full Enable Disable 1 Minute 50% Disable Enable 5 Minutes 15 Minutes 20 Minutes 30 Minutes 1 Hour 2 Hours *Self-Adjusts to 10 min. user mode 2 3 4 5 6 7 Issue Possible Causes Suggestions SensorisinManualONmode PressPushbutton.IfAutoMode isdesiredchangeActivationModetoAuto. Lights SensorwasturnedOFFmanually.IftheSensor Will Not wasturnedOFFmanuallybeforetheTimeDelay Turn ON automatically expired,lightswillremainOFFfortheremainder oftheTimeDelay. Default = 1 Troubleshooting 8 1 2 4 3 5 6 7 8 CheckEcoMeterLED,ifLEDisONthisis anindicationthatthelightswereturnedOFFmanually. PressthePushbuttontoturnthelightsbackON. Powerinterruption Checkincomingvoltageand/orwiring. Powerinterruption Checkincomingvoltageand/orwiring. 1, 2, and 3 Lights Will Not Turn ON manually Checkout and Adjustment AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof airflowontheoperationoftheVNLW-P-1001-MV-N.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup andstabilize. Self-Adjust Sensorisshippedinself-adjustmode.ThisappliestoTimeDelayandPIRsensitivity.Inpreparationforthe InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilizedthe unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom. 1.WalkaroundtheroomandmonitorLED. 2.Standindifferentpartsoftheroomandwaveyourhands.LEDshouldonlyturnONforonesecondwitheach motion.(IfLEDdoesnotturnON,gotoInstallerAdjustments–SensitivityAdjustmentSection) 3.Standstillthreetofourfeetawayfromthesensorforfiveseconds.LEDshouldnotturnON.(IfLEDturnsON, gotoInstallerAdjustments–SensitivityAdjustmentSection) 4.Walkoutsidetheroomandwait30secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection) 6.AtthispointyoucanexittheroomandletthesensorTime-out.WhenthesensorTimes-outandisinactivefor fiveminutes,theunitwillgotoa10minuteTimeDelayusermodesetting. Night Light UnitisshippedwithNightLightfeaturedenabled.WhensensorturnsthelightsOFF,NightLightisactivated.Todisablethis featuremoveDIPSwitch7up. If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 7 and 8 1 2 3 4 5 6 7 8 Override MakesuresensorisnotinOverrideMode. CheckDIPSwitch8tomakesureitisdown. SelfAdjust IfsensorisinSelf-AdjustMode.Itmaybe possiblefortheunittohaveincreasedtheTimeDelayto a30minutedelay.Ifthelightsdonot turnOFFafter30minutesfollownextstep. 2hourDelay MaximumTimeDelayis2hours.CheckDIPSwitches toverifyDIPSwitchsettings.IflightsdonotturnOFF atthesetTimeDelay,checknextstep. PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up. Lights Will Not Turn OFF automatically Override TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1. MoveDIPSwitch8up. 2.ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF. Lights Will Not Turn OFF manually Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. CallTechnicalServices If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Installer Adjustments PIR Sensitivity 1. PressthePushbuttontoactivatesensor. 2. Standindifferentareasoftheroomandwaveyour hands. 3. IftheRedLEDdoesnotturnON,checkforany obstructions. 4. Standstillthreetofourfeetawayfromsensorforfive seconds.LEDshouldnotturnON. 5. IfRedLEDturnsONwithoutmotionorisconstantly ONadjustPIRsensitivityto50%bymovingDIP Switch5up. Field-of-view outside the space 1. AdjustPIRsensitivityto50%bymovingDIPSwitch 5up. 2. Usenon-reflectivetapestripstocovertheportionsof thesensorlensthatviewoutsidethespace. Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Lens glows amber when night light is activated PIR Lens Red (PIR) LED DIP Switches ON/OFF Button Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com