Installation Instructions NeoSwitch Passive Infrared (PIR) Single Relay (Neutral Required)

advertisement
Installation Instructions
NeoSwitch Passive Infrared (PIR) Single Relay
Vacancy Sensing Wall Switch with Night Light
(Neutral Required)
P/N 9850-000353-01
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
Coverage
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Wiring
TheVNLW-P-1001-MV-Nisdesignedforofficesupto300squarefeet.
36
,
,
20
Specifications
Technology:PassiveInfrared(PIR)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–Max.load:6.7amps,
800W,50/60Hz
• Fluorescent/Ballast–Max.load:10amps,1200W,
50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–Max.load:9.8amps,
2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test,1,5,15,
20,30minutes,1hour,2hours
Model # VNLW-P-1001-MV-N-W
Model # VNLW-P-1001-MV-N-V
Model # VNLW-P-1001-MV-N-LA
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
AmberLEDnightlight.
Minor Motion, IR
Major Motion, IR
,
8
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.MountunittoWallBox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.InstallWallSwitchplate.
Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram
Description
Location
ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightisalightingcontrolandWall
Switchall-in-onethatisusedforenergysavingsandconvenience.
WheninstallingtheVNLW-P-1001-MV-Ninanewjunctionbox,choosetheswitchlocationcarefullytoprovide
optimumcoverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclear
Line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNLW-P-1001-MV-Ndirectlyintothe
hallwaywhereitmaydetectpassers-by.
PIR Technology
ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightusesPassiveInfrared(PIR)
sensortechnologiestomonitoraroomforoccupancy.
TheVNLW-P-1001-MV-Nallowsthecontrolofoneloadwithonevacancysensorswitch.
ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.ThelightsstayONaslong
asthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapreset Installation
TimeDelayinterval.
TheVNLW-P-1001-MV-Ncanbeinstalledinanystandardsingle
A30secondgraceperiodisaddedafterthelightsshutOFFtogivetheoccupanttimetomoveagainincasethe
gangbox.Itmaybeinstalledinthesamemannerasanordinary
lightsshutOFF.Thispreventstheoccupantfromhavingtowalk-uptopressthePushbuttontoreactivatethesensor.
WallSwitch.
ThenightlightactivateswhensensorturnslightsOFF.Thisfeaturecanbedisabled,seeDIPSwitchSettings.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
• WiretheVNLW-P-1001-MV-Nasdescribedinthewiringsection.
TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential
• MounttheVNLW-P-1001-MV-Ninthejunctionbox.
energysavingsthatareavailableintheparticularapplication.
BLUE
BLACK
120/277 VAC
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
GREEN
LOAD
WHITE
GROUND
NEUTRAL
Wiring Diagram 2: 120/277 VAC single level single circuit three-way wiring diagram
TRAVELER
WIRES
120/277 VAC
BLACK
GREEN
GROUND
BLUE
BLUE
WHITE
LOAD 1
WHITE
BLACK
GREEN
GROUND
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED
ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per
relay. Both circuits must be fed from the same phase.
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithnonormal
OFFinbetweenbyalternatelymakingslightadjustmentstoeitherTimeDelay(by2minuteincrements)orsensitivity,so
thereshouldbenoneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIP
Switchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIPSwitches1,2,and3down.(IfDIPSwitches1,2,and3are
alreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
DIP Switch Legend
Time Delay
Not Used
DIP Switch
1
2
3
PIR Sensitivity
4
Not Used
5
Night Light
6
Override
7
8
Auto*
Full
Enable
Disable
1 Minute
50%
Disable
Enable
5 Minutes
15 Minutes
20 Minutes
30 Minutes
1 Hour
2 Hours
*Self-Adjusts to
10 min. user mode
2
3
4
5
6
7
Issue
Possible Causes
Suggestions
SensorisinManualONmode
PressPushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
Lights
SensorwasturnedOFFmanually.IftheSensor
Will Not
wasturnedOFFmanuallybeforetheTimeDelay
Turn ON
automatically expired,lightswillremainOFFfortheremainder
oftheTimeDelay.
Default =
1
Troubleshooting
8
1 2
4
3
5
6
7
8
CheckEcoMeterLED,ifLEDisONthisis
anindicationthatthelightswereturnedOFFmanually.
PressthePushbuttontoturnthelightsbackON.
Powerinterruption
Checkincomingvoltageand/orwiring.
Powerinterruption
Checkincomingvoltageand/orwiring.
1, 2, and 3
Lights
Will Not
Turn ON
manually
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheVNLW-P-1001-MV-N.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.ThisappliestoTimeDelayandPIRsensitivity.Inpreparationforthe
InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilizedthe
unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching
theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLED.
2.Standindifferentpartsoftheroomandwaveyourhands.LEDshouldonlyturnONforonesecondwitheach
motion.(IfLEDdoesnotturnON,gotoInstallerAdjustments–SensitivityAdjustmentSection)
3.Standstillthreetofourfeetawayfromthesensorforfiveseconds.LEDshouldnotturnON.(IfLEDturnsON,
gotoInstallerAdjustments–SensitivityAdjustmentSection)
4.Walkoutsidetheroomandwait30secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6.AtthispointyoucanexittheroomandletthesensorTime-out.WhenthesensorTimes-outandisinactivefor
fiveminutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Night Light
UnitisshippedwithNightLightfeaturedenabled.WhensensorturnsthelightsOFF,NightLightisactivated.Todisablethis
featuremoveDIPSwitch7up.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
7 and 8
1
2
3
4
5
6
7
8
Override
MakesuresensorisnotinOverrideMode.
CheckDIPSwitch8tomakesureitisdown.
SelfAdjust
IfsensorisinSelf-AdjustMode.Itmaybe
possiblefortheunittohaveincreasedtheTimeDelayto
a30minutedelay.Ifthelightsdonot
turnOFFafter30minutesfollownextstep.
2hourDelay
MaximumTimeDelayis2hours.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFF
atthesetTimeDelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
automatically
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPSwitch8up.
2.ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Lights
Will Not
Turn OFF
manually
Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Installer Adjustments
PIR Sensitivity
1. PressthePushbuttontoactivatesensor.
2. Standindifferentareasoftheroomandwaveyour
hands.
3. IftheRedLEDdoesnotturnON,checkforany
obstructions.
4. Standstillthreetofourfeetawayfromsensorforfive
seconds.LEDshouldnotturnON.
5. IfRedLEDturnsONwithoutmotionorisconstantly
ONadjustPIRsensitivityto50%bymovingDIP
Switch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch
5up.
2. Usenon-reflectivetapestripstocovertheportionsof
thesensorlensthatviewoutsidethespace.
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.