Installation Instructions NeoSwitch Passive Infrared (PIR) Single Relay Vacancy Sensing Wall Switch (Ground Required) P/N 9850-000284-02 General Information • Readallinstructionsonbothsidesofthis sheetfirst EcoMeter Operation • InstallinaccordancewithALLlocalcodes • Forindooruseonly Load 1 EcoMeter LED OFF ON ON OFF Specifications Technology:PassiveInfrared(PIR) Electrical Ratings 120VAC: • Incandescent/Tungsten– Max.load:6.7amps,800W,50/60Hz • Fluorescent/Ballast– Max.load:10amps,1200W,50/60Hz MotorLoad:¼HP@125VAC 277VAC: • Fluorescent/Ballast– Max.load:9.8amps,2700W,50/60Hz Ballast Compatibility:Compatiblewithmagneticand electronicballasts No Minimum Load Requirement Time Delays:Self-Adjusting,15seconds/test(10min Auto),Selectable5,15,30minutes Model # VNW-P-1001-MV-W Model # VNW-P-1001-MV-V Model # VNW-P-1001-MV-G Coverage:Majormotion–1000sq.ft. Minormotion–300sq.ft. Light Level Sensing:0to200foot-candles Operating Environment: • Temperature:32°F–104°F(0°C–40°C) • RelativeHumidity:20%to90%non-condensing Housing:Durable,injectionmoldedhousing. PolycarbonateresincomplieswithUL94VO. Size: • MountingPlate/StrapDimensions: 4.195"Hx1.732"W(106.553mmx44mm) • ProductHousingDimensions:2.618"Hx1.752" Wx1.9"D(66.5mmx44.5mmx48.26mm) LED Indicators:RedLEDindicatesPIRdetection; GreenLEDactsasEcoMeterornightlightlocator. Action EcoMeter Apersonentersthespace andtheloadisactivated Benefit OFF Theareaisvacatedandthe lightsturnOFFautomatically 100% Increasedawarenessofenergysavings; Actsasanightlightlocator ApersonturnsthelightsOFF manuallyuponexitinganarea 100% Increasedawarenessofenergysavings andremindsindividualstotakecontrol oftheirlightingforadditionalsavings; Actsasanightlightlocator TheDaylightingfeature preventsthelightsfrom automaticallyturningON whenapersonentersanarea 100% Increasedawarenessofenergy savingsandletsindividualknowthat theDaylightingfeatureisworking Coverage TheVNW-P-1001-MVVacancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontroland conventionalwallswitchall-in-one,usedforenergysavingsandconvenience. PIR Technology Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone. TheVNW-P-1001-MVallowsthecontrolofoneloadwithoneoccupancysensorswitch. ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,the lightsstayONaslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFF automaticallyafterapresettimedelayinterval. Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand timedelayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotential energysavingsthatareavailableintheparticularapplication. TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding individualstotakecontroloftheirlightingtomaximizeenergysavings. TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight. TheVNW-P-1001-MVcanbeinstalledinanystandardsinglegangbox.Itmaybe installedinthesamemannerasanordinarywallswitch. • WiretheVNW-P-1001-MVasdescribedinthewiringsection • MounttheVNW-P-1001-MVinthejunctionbox Wiring TheVNW-P-1001-MVisdesignedforofficesupto300squarefeet. 36 , , 20 Minor Motion, IR Major Motion, IR Description Installation , 8 CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. 1.MakesurepoweristurnedOFFatthebranchcircuitbreaker. 2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements. 3.Mountunittowallbox. 4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize. 5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection) 6.Installwallswitchplate. Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. 120/277 VAC BLACK BLUE Location GREEN WheninstallingtheVNW-P-1001-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNW-P-1001-MVdirectlyintothehallway whereitmaydetectpassers-by. LOAD GROUND NEUTRAL Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Wiring Diagram 2: 120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram BLUE BLACK 120/277 VAC GREEN LOAD 1 LOAD 2 GROUND NEUTRAL Wiring Diagram 3: 120/277 VAC single level single circuit three-way wiring diagram TRAVELER WIRES 120/277 VAC Self-Adjust SensorisshippedinSelf-AdjustMode.Thisappliestotime delayandPIRsensitivity.InpreparationfortheInstallerTest, thetimedelayissetto15seconds,afterthesensorisinstalled, Red (PIR) Detection LEDs poweredONandhasstabilized,theunitwilltime-out15 PIR Lens secondsafterthelastmotiondetected.Coverageandsensitivity Daylight canbeconfirmedbywatchingtheRed(PIR)indicatorLEDon Sensor Level Adjustment thefrontofthesensor,whilemovingaroundtheroom. 1.WalkaroundtheroomandmonitorLEDs. DIP Switches 2.Standindifferentpartsoftheroomandwaveyourhands. LEDshouldonlyturnONforonesecondwitheachmotion. (IfLEDdoesnotturnON,gotoInstallerAdjustments– SensitivityAdjustmentSection) 3.Standstillthreetofourfeetawayfromsensorforfive ON/OFF Button seconds.LEDshouldnotturnON.(IfLEDturnsON,goto InstallerAdjustments–SensitivityAdjustmentssection) 4.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller AdjustmentsSection) 5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection) 6.Atthispointyoucanreattachthepushbuttonandexittheroom.Whenthesensortimes-outandisOFFforfive minutes,theunitwillgotoa10minutetimedelayusermodesetting. Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition. BLUE BLACK BLUE GREEN LOAD 1 GROUND GROUND NEUTRAL THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase. DIP Switch Settings DIP Switch Legend Time Delay PIR Sensitivity Not Used EcoMeter Not Used Override DIP Switch 1 2 Auto* 5 Minutes Full Enable Disable 50% Disable Enable 15 Minutes 30 Minutes *Self-Adjusts to 10 min. user mode 3 4 5 6 7 8 Default = 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 Override Theoverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure. 1.MoveDIPSwitch8up. 2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF. Troubleshooting Issue Possible Causes Suggestions DaylightingFeatureEnabled IfalllightsarerequiredtoturnON adjustdaylightpotentiometer. Powerinterruption Checkincomingvoltageand/orwiring. BLACK Installer Adjustments GREEN Time Delay Adjustments Peoplewhoremainverystillforlongperiodsoftimemay needalongertimedelaythanthedefaultsettingof10minutes. Aslongastheself-adjustingfeatureisenabled,theswitch willrespondtoeachpairoffalse-OFFswithnonormalOFFin DIP Switches between,byalternatelymakingslightadjustmentstoeithertime 1&2 delay(by2minuteincrements)orsensitivity,sothereshouldbe noneedformanualadjustment.Ifmanualadjustmentisdesired, refertoTimeDelaysettingsinDIPSwitchlegend. ResetsensortimedelaytofactorysettingsbymovingDIP Switches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition, wait3seconds,andthenbacktoitsoriginalposition) 8 Checkout and Adjustment AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectof airflowontheoperationoftheONW-P-1001-MV.Useonlyinsulatedtoolstomakeadjustments. Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-up andstabilize. PIR Sensitivity 1.Standindifferentareasoftheroomandwaveyourhands. 2.IftheRedLEDdoesnotturnON,checkforanyobstructions. 3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON. 4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up. Lights Will Not Turn ON manually If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879 Field-of-view outside the space 1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up. 2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace. Daylight Adjustments TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight. Ifthereisenoughlightintheroom,regardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough lightintheroom,thesensorwillallowthelightstoturnON.ThesensorwillnotallowtheDaylightingfeaturetoturn theloadOFFuntilthespaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.Ifsomeone attemptstoturntheloadONandthereissufficientdaylightavailablethe DaylightingfeaturewillholdthelightsOFF. 1.Setthelightlevelwhentheambientlightisatthelevelwherenoartificial lightisneeded.Ifthisfeatureisnotneeded,leavethelightlevelat maximum(fullyCW). 2.Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTest Mode,toggleDIPSwitch8outofitscurrentposition,wait3secondsand thenbackintoitsoriginalposition. 3.Setthelightleveltominimum(fullyCCW). 4.Letthesensortime-outsolightsareOFF.Enterthespaceandlights shouldremainOFF. 5.Makesurenottoblockthesensorfromthedaylightsourceandadjust thelightlevelpotentiometerCWinsmallincrements.(Pause5seconds betweeneachadjustment) 6.LightswillnotturnONuponmanualactivation,whentheambientlight levelexceedsthedaylightthresholdsetting. Lights Will Not Turn OFF automatically Override MakesuresensorisnotinOverrideMode(DIPSwitch8up). Self-Adjust IfsensorisinSelf-AdjustMode,itmay bepossiblefortheunittohaveincreasedthe timedelaytoa30minutedelay.Ifthelightsdo notturnOFFafter30minutesfollownextstep. 30MinuteDelay Maximumtimedelayis30Minutes.CheckDIP SwitchestoverifyDIPSwitchsettings.Iflightsdo notturnOFFatthesettimedelay,checknextstep. PIRactivatedbyheatsource otherthanoccupant MoveDIPSwitch5up. Lights Will Not Turn OFF manually CallTechnicalServices If lights will still not turn OFF, call Technical Services at 1-800-553-3879 Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. Printed in Malaysia Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com