Installation Instructions NeoSwitch Passive Infrared (PIR) Single Relay Vacancy Sensing Wall Switch

advertisement
Installation Instructions
NeoSwitch Passive Infrared (PIR)
Single Relay Vacancy Sensing Wall Switch
(Ground Required)
P/N 9850-000284-02
General Information
• Readallinstructionsonbothsidesofthis
sheetfirst
EcoMeter Operation
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Load 1
EcoMeter LED
OFF
ON
ON
OFF
Specifications
Technology:PassiveInfrared(PIR)
Electrical Ratings
120VAC:
• Incandescent/Tungsten–
Max.load:6.7amps,800W,50/60Hz
• Fluorescent/Ballast–
Max.load:10amps,1200W,50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–
Max.load:9.8amps,2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Model # VNW-P-1001-MV-W
Model # VNW-P-1001-MV-V
Model # VNW-P-1001-MV-G
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
GreenLEDactsasEcoMeterornightlightlocator.
Action
EcoMeter
Apersonentersthespace
andtheloadisactivated
Benefit
OFF
Theareaisvacatedandthe
lightsturnOFFautomatically
100%
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ApersonturnsthelightsOFF
manuallyuponexitinganarea
100%
Increasedawarenessofenergysavings
andremindsindividualstotakecontrol
oftheirlightingforadditionalsavings;
Actsasanightlightlocator
TheDaylightingfeature
preventsthelightsfrom
automaticallyturningON
whenapersonentersanarea
100%
Increasedawarenessofenergy
savingsandletsindividualknowthat
theDaylightingfeatureisworking
Coverage
TheVNW-P-1001-MVVacancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontroland
conventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
TheVNW-P-1001-MVallowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,the
lightsstayONaslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFF
automaticallyafterapresettimedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
timedelayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotential
energysavingsthatareavailableintheparticularapplication.
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandreminding
individualstotakecontroloftheirlightingtomaximizeenergysavings.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
TheVNW-P-1001-MVcanbeinstalledinanystandardsinglegangbox.Itmaybe
installedinthesamemannerasanordinarywallswitch.
• WiretheVNW-P-1001-MVasdescribedinthewiringsection
• MounttheVNW-P-1001-MVinthejunctionbox
Wiring
TheVNW-P-1001-MVisdesignedforofficesupto300squarefeet.
36
,
,
20
Minor Motion, IR
Major Motion, IR
Description
Installation
,
8
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1.MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
120/277 VAC
BLACK
BLUE
Location
GREEN
WheninstallingtheVNW-P-1001-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNW-P-1001-MVdirectlyintothehallway
whereitmaydetectpassers-by.
LOAD
GROUND
NEUTRAL
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Wiring Diagram 2: 120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram
BLUE
BLACK
120/277 VAC
GREEN
LOAD 1
LOAD 2
GROUND
NEUTRAL
Wiring Diagram 3: 120/277 VAC single level single circuit three-way wiring diagram
TRAVELER
WIRES
120/277 VAC
Self-Adjust
SensorisshippedinSelf-AdjustMode.Thisappliestotime
delayandPIRsensitivity.InpreparationfortheInstallerTest,
thetimedelayissetto15seconds,afterthesensorisinstalled,
Red (PIR)
Detection LEDs
poweredONandhasstabilized,theunitwilltime-out15
PIR Lens
secondsafterthelastmotiondetected.Coverageandsensitivity
Daylight
canbeconfirmedbywatchingtheRed(PIR)indicatorLEDon
Sensor Level
Adjustment
thefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.
DIP Switches
2.Standindifferentpartsoftheroomandwaveyourhands.
LEDshouldonlyturnONforonesecondwitheachmotion.
(IfLEDdoesnotturnON,gotoInstallerAdjustments–
SensitivityAdjustmentSection)
3.Standstillthreetofourfeetawayfromsensorforfive
ON/OFF Button
seconds.LEDshouldnotturnON.(IfLEDturnsON,goto
InstallerAdjustments–SensitivityAdjustmentssection)
4.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5.Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6.Atthispointyoucanreattachthepushbuttonandexittheroom.Whenthesensortimes-outandisOFFforfive
minutes,theunitwillgotoa10minutetimedelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
BLUE
BLACK
BLUE
GREEN
LOAD 1
GROUND
GROUND
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
DIP Switch Legend
Time Delay
PIR Sensitivity
Not Used
EcoMeter
Not Used
Override
DIP Switch
1
2
Auto*
5 Minutes
Full
Enable
Disable
50%
Disable
Enable
15 Minutes
30 Minutes
*Self-Adjusts to
10 min. user mode
3
4
5
6
7
8
Default =
1
2
3
4
5
6
7
1
2
3
4
5
6
7
8
Override
Theoverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.
2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Troubleshooting
Issue
Possible Causes
Suggestions
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring.
BLACK
Installer Adjustments
GREEN
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemay
needalongertimedelaythanthedefaultsettingof10minutes.
Aslongastheself-adjustingfeatureisenabled,theswitch
willrespondtoeachpairoffalse-OFFswithnonormalOFFin
DIP Switches
between,byalternatelymakingslightadjustmentstoeithertime
1&2
delay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,
refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIP
Switches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,
wait3seconds,andthenbacktoitsoriginalposition)
8
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheONW-P-1001-MV.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-up
andstabilize.
PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Lights
Will Not
Turn ON
manually
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.
Ifthereisenoughlightintheroom,regardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough
lightintheroom,thesensorwillallowthelightstoturnON.ThesensorwillnotallowtheDaylightingfeaturetoturn
theloadOFFuntilthespaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.Ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailablethe
DaylightingfeaturewillholdthelightsOFF.
1.Setthelightlevelwhentheambientlightisatthelevelwherenoartificial
lightisneeded.Ifthisfeatureisnotneeded,leavethelightlevelat
maximum(fullyCW).
2.Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTest
Mode,toggleDIPSwitch8outofitscurrentposition,wait3secondsand
thenbackintoitsoriginalposition.
3.Setthelightleveltominimum(fullyCCW).
4.Letthesensortime-outsolightsareOFF.Enterthespaceandlights
shouldremainOFF.
5.Makesurenottoblockthesensorfromthedaylightsourceandadjust
thelightlevelpotentiometerCWinsmallincrements.(Pause5seconds
betweeneachadjustment)
6.LightswillnotturnONuponmanualactivation,whentheambientlight
levelexceedsthedaylightthresholdsetting.
Lights
Will Not
Turn OFF
automatically
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmay
bepossiblefortheunittohaveincreasedthe
timedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep.
PIRactivatedbyheatsource
otherthanoccupant
MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879