The Fail-Safe VR 2000 12" Square combines strength-gaining architecture
with energy-saving technology. Architecturally angled facets with radius
corners actually increase the ability of the lens to deflect blows and
absorb impact. Extra-thick, injection-molded polycarbonate lens
incorporates optical design that obscures the lamp image and spreads
light evenly. UL/cUL listed for wet locations. The durable, versatile 12"
Square GC/GW is perfect for use in corridors, dormitories, public rest
rooms, rapid transit stations, loading docks and minimum security
institutions.
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
Fa s te n e r s
Four T20 stainless steel TORX®
screws with center reject pin.
Screw heads are recessed into lens
to maximize tamper-resistance.
Fasteners are captive in the lens
and sealed by means of a neoprene
O-ring.
Lens
S o cke t
One-piece, injection-molded UVstabilized polycarbonate, min.
0.130" thick. All light control prisms
and blondels are on the inside
surface of the lens, reducing dirt
build-up and making cleaning
easier.
Porcelain medium base socket with
nickel-plated brass screw shell.
Shock absorbing socket bracket
protects lamp from impact. For
Metal Halide, protected socket is
standard, for use with "O" openrated, protected Metal Halide
lamps only.
Housing
R e f l e c to r
Die-cast aluminum with reinforcing
ribs on exposed sidewalls.
Thickened areas occur at lens
junction and at mounting/fastening
holes. Four 1/4" dia. fasteners are
required for maximum vandal
resistance. Four 1/2" NPT conduit
entries in sides and one in back of
housing. Black polyester powder
coat is standard.
16 ga. CRS with white high
reflectance polyester powder coat
finish.
Ballast
Copper wound NPF or HPF ballast
are available. Consult Ordering
Information.
H E = H o ri zo n t a l E ye l i d
Labels
UL/cUL listed, standard wet
location.
G a s ke t
One-piece, die-cut closed cell
silicone mounting gaskets seal
entire lens and housing.
P P = Pe ri m e te r Pa i n t
12" Sq.
[305mm]
S t a n d a rd - N o Pa i n t
GC/GW
SIDE DIMENSIONS
Deep
12" Square
VR2000
High Pressure Sodium
Incandescent
Pulse Start Metal Halide
Vandal Resistant
SURFACE
Polycarbonate
Clear Prismatic or White
5"
[127mm]
E N E R G Y D ATA
4 3/16"
[106mm]
For Energy Management related
technical data to support the
performance of this fixture series,
refer to the ordering information for
input wattage.
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADC041424
2010-11-24 12:31:56
G C / G W - HID 12" Square
O R D E R I N G I N F O R M AT I O N
SAMPLE NUMBER: MPGC-50N-277V-OR
Paint
Configuration
Product
Family
Lamp
Type
Wattage
HP=High Pressure
Sodium 1
PP=Perimeter Paint
HE=Horizontal Eyelid
MP=Pulse Start
Metal Halide 1, 3
Paint is optional.
Black is standard.
50=50W
70=70W
100=100W 5
150=150W 2, 5
175=175W 2, 5
N=Normal
Power Factor
H=High
Power Factor
12” Square
GC=Clear Prismatic
Polycarbonate Lens
GW=White Polycarbonate
Lens
Voltage
Ballast
120V
208V
240V
277V
347V
480V
MT=Multi-Tap
(120, 208,
240, 277V)
Options
Socket
OR=Open-rated
socket for pulse
start metal halide
lamps 4
___=Not applicable
(HPS or not
compatible with
OR socket)
Color
F1=Single Fused
F2=Double Fused
LL=Lamp Included
Q=Quartz restrike
(Lamp by others)
QS=Quartz Socket Only
(Lamp by others)
Blank=Black (Standard)
WHT=White
DBZ=Bronze
AP=Gray
Accessories
(Order separately)
PB-120V=Photocell Kit
PB-277V=Photocell Kit
VRSD =T20 Center-pin
tamperproof
TORX®-head bit
NOTES:
1 All units have deep casting.
2 Not available with white lens.
3 Open-rated socket and lamp
must be used.
4 Not applicable for HPS lamps.
Required for MP.
5 Wall mount only. 70W maximum
for celing mount applications.
O R D E R I N G M AT R I X
LAMP TYPE / WATTAGE
MP
BALLAST
..
.
...
..
70=70W
All
100=100W
150=150W
Units
175=175W
HPS (High Pressure Sodium)
Have
50=50W
70=70W
Casting
100=100W
.
H
N
35=35W
Deep
...
..
...
..
N
(Pulse Start Metal Halide)
50=50W
150=150W
H
...
..
...
..
120
120
VOLTAGE
..
..
.
..
...
277
277
= Not available
= Available
..
..
..
.
MT
*
MT
-
*
...
..
..
...
F1
F1
*
..
..
.
...
..
OPTIONS
F2
F2
..
...
..
..
.
LL
LL
...
.
..
.
Q
Q
...
..
..
..
.
QS
QS
= Only available in HPF Ballast
P H OTO M E T R I C S
C a n d l e p o w e r D i s t ri b u t i o n
5
Footcandle T able
Select mounting height and read across for footcandle values
of each isofootcandle line.
Mounting
Height
Footcandle Values for
GC-2
Isofootcandle Lines
A
B
C
D
E
F
6'
22.50 11.25
4.50
2.25
1.13
0.45
9'
10.00
5.00
2.00
1.00
0.50
0.20
12'
5.63
2.81
1.13
0.56
0.28
0.11
4
3
2
1
A B C D E
0
F
1
2
3
4
5
5
4
3
2
1
0
1
2
3
4
5
Test No. 766618
HPGC-150N-120V
Lamp=150W HPS
Lumens=16000