COOPER LIGHTING - METALUX

advertisement
COOPER LIGHTING - METALUX
®
DESCRIPTION
The F-Bay I5 series is an outstanding solution for high mounting height
industrial or retail applications. The F-Bay I5 optic has been optimized to
provide maximum performance from T5 lamps. Optional uplight
component is provided to enable excellent ceiling uniformity. The I5’s
high lumen package allows the benefits of fluorescent to be applied at high
mounting heights that were traditionally exclusive to H.I.D. The primary
benefits include exceptional color rendering, high system efficacy, 95%
lumen maintenance, long lamp life, instant on/instant re-strike, economical
dimming, and uniform brightness control. Primary applications include “big
box” retail, shopping malls, light industrial, school gymnasiums, etc.
Type
Catalog #
Project
Date
Comments
Prepared by
SPECIFICATION FEATURES
Construction
Downlight/Uplight Optics
Mounting
Specification grade full body
housing, end plates and socket
tracks are die formed cold rolled
steel in 4' or 8' lengths. The
housing features an integral ballast
channel that adds strength and
provides numerous KO’s for easy
installation.
Optical modules are fully enclosed
inside housing to protect against
damage. Die formed reflectors are
faceted with two optical
distributions – medium and wide.
Medium beam optical modules
utilize 95% specular aluminum
finish. Open downlight design
optimizes performance with uplight
slots available as an option for
nominal 8% uplight component. An
optional attractive thin blade white
baffle adds longitudinal shielding. A
clear or frosted white acrylic lens is
also available. Optional heavy duty
wireguard can be used with or
without the lens or baffle. Latched
retention of shielding optics
(safety leader restraints) allows for
easy access.
The I5 series is suited for
surface, suspension
mounting with optional
wire hook and chain set,
stem or cable mounting.
Top connector box
mounting is also available.
Narrow 11" housing
allows mounting within
12" horizontally from the
nearest edge of the
sprinkler deflector.
Electrical
Class “P” ballasts are positively
secured by mounting bolts. Rotorlock Bi-Pin lampholders. An
optional top ballast access plate
enables service from above without
disturbing the internal optics.
Optional modular power
receptacle meets UL2459 and NEC
410.73 and is UL/cUL rated for
make and break under load from
outside the luminaire to speed
maintenance. UL/cUL listed.
Suitable for damp locations.
F-BAY I5 Series
Options
Integral Occupancy
Sensor available and
provides from 600 sq. ft.
(MS) up to 1250 sq. ft.
(MSO) of coverage at a
maximum mounting
height of 40'.
4' OR 8'
ULTRA 47
2, 3 OR 4 LAMPS
T5 Linear Fluorescent
High Bay Lighting System
Finish
Electrostatically applied baked
white enamel finish is preceded
by a multistage cleaning cycle,
iron phosphate coating with rust
inhibitor.
4-15/16"
[126mm]
11" [280mm]
ENERGY DATA
LAMP CONFIGURATIONS
MOUNTING DATA
11/16" [18mm] K.O. (2)
for Cable or Pendant Mounting
Top Connector Box
Mounting
Access Plate
Input Watts:
2 LAMP
3 LAMP
4-15/16"
[126mm]
4-15/16"
[126mm]
4-5/8"
[118mm]
11"
[280mm]
EHT Ballast
347T5 = (165)
447T5 = (205)
X=2-3/4"
[70mm]
11" [280mm]
X
X
11" [280mm]
4 LAMP
4-15/16"
[126mm]
46" [1168mm]
X=2-11/32"
[60mm]
11/16" [18mm] K.O.
for Cable or Pendant Mounting
Top Connector Box
Mounting
Yearly Cost of 1000 lumens,
3000 hrs at .08 KWH = $2.89
X
X
X
11" [280mm]
11/16" [18mm] K.O.
for Cable or Pendant Mounting
* Reference the lamp/ballast data in the
Technical Section for specific lamp/ballast
requirements
** Consult Pre Sales Technical Support.
Access Plate
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING TO
LOCAL, STATE OR FEDERAL LAWS
11"
[280mm]
Safe and convenient means of
disconnecting power.
46" [1168mm]
92" [2337mm]
COOPER LIGHTING
Luminaire Efficacy Rating
LER =83
Catalog Number: I5-447T5-UPL
2-3/4" [70mm]
ADF110944
I5
PHOTOMETRICS
Candela
I5-347T5-UNV
(1) Electronic Ballast
(3) F54T5-47W lamps Angle Along II
0
7706
4285 lumens
5
7636
10
7524
Spacing criterion:
15
7348
(II) 1.2 x mounting
20
7106
height, (⊥) 0.7 x
25
6803
mounting height
30
6439
35
6029
Efficiency 95.4%
40
5549
Test Report:
45
5011
I5-347T5-UNV50
4436
55
3811
EBT1.IES
60
3142
LER=83
65
2458
70
1788
Yearly Cost of 1000
75
1128
lumens, 3000 hrs at
80
546
.08 KWH = $2.89
85
120
90
Across ⊥
7706
7736
6793
5637
4235
2965
2421
2144
1912
1744
1618
1455
1221
1067
1029
801
201
4
0
45°
7706
7746
7300
6475
5564
4467
3341
2483
2088
1807
1564
1369
1206
985
771
663
429
6
2
2
C o e f fi c i e n t s o f U t i l i z a t i o n
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
114
101
89
80
72
65
59
54
50
47
43
114 114
97 94
83 79
73 67
64 58
57 51
51 46
47 41
43 38
39 34
36 32
111
102
94
87
80
74
69
65
61
57
54
111
99
88
78
70
64
58
54
50
46
43
111
95
82
72
63
57
51
46
42
39
36
111
92
78
66
58
51
46
41
37
34
32
20%
50%
50 30 10
30%
50 30 10
10%
50 30 10
0%
0
106
95
84
75
68
62
57
52
48
45
42
101
91
81
73
66
60
55
51
47
44
41
97
88
78
71
64
58
54
50
46
43
40
95
82
71
61
54
48
43
39
35
32
30
106
92
80
70
62
55
50
46
42
39
36
106
90
76
65
57
51
45
41
37
34
32
101
89
77
68
61
54
49
45
41
38
35
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
4705
6802
10248
12259
12259
%Lamp
36.6
52.9
79.7
95.4
95.4
90
Across ⊥
7137
6899
6324
5830
5690
5539
5084
4214
3464
2769
2250
1916
1740
1640
1498
947
420
5
11
45°
7137
6972
6567
6065
5626
5356
5186
4888
4324
3518
2835
2182
1685
1351
1165
1001
520
47
19
7
C o e f fi c i e n t s o f U t i l i z a t i o n
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
114
105
96
89
82
76
71
66
62
59
55
I5-447T5-UNV-UPL C a n d e l a
(1) Electronic Ballast
(4) F54T5-47W lamps Angle Along II
0
7137
4285 lumens
5
7068
10
6962
Spacing criterion:
15
6792
(II) 1.2 x mounting
20
6570
height, (⊥) 1.1 x
25
6284
mounting height
30
5945
35
5555
Efficiency 98.9%
40
5112
Test Report:
45
4619
I5-447T5-UNV50
4082
55
3504
EBT1-UPL.IES
60
2893
LER=83
65
2263
1629
Yearly Cost of 1000 70
1033
lumens, 3000 hrs at 75
80
516
.08 KWH = $2.89
85
141
%Fixture
38.4
55.5
83.6
100.0
100.0
Average
0-Deg
cd/sm
21700
20346
17810
13346
4216
101
87
74
64
56
50
45
41
37
34
31
97
86
75
66
59
53
49
44
41
38
35
97
84
72
63
56
49
44
40
37
34
31
Average
45-Deg
cd/sm
7825
7309
7137
7844
211
Average
90-Deg
cd/sm
7552
7768
7731
9477
141
rc
rw
RCR
0
1
2
3
4
5
6
7
8
9
10
Effective floor cavity reflectance
80%
70%
70 50 30 10
70 50 30 10
116
107
97
89
82
76
70
65
61
57
53
116
102
90
79
71
64
58
52
48
44
41
116 116
98 95
84 78
72 66
63 56
55 49
49 43
44 38
40 34
36 31
33 28
112
103
94
86
79
73
68
63
59
55
52
112
99
87
77
69
62
56
51
47
43
40
112
96
82
70
61
54
48
43
39
36
33
112
93
77
65
56
48
43
38
34
31
28
20%
50%
50 30 10
30%
50 30 10
50
106
94
83
73
66
59
54
49
45
42
39
99
89
78
70
63
56
51
47
43
40
37
94
84
74
66
60
54
49
45
42
39
36
106
91
78
68
59
52
47
42
38
35
32
106
88
74
63
54
47
42
37
33
30
28
99
86
74
65
57
51
45
41
37
34
31
Zonal Lumen Summary
Luminance Data
Zone
0-30
0-40
0-60
0-90
0-180
Angle
in Deg
45
55
65
75
85
Lumens
4990
7952
12913
15640
16947
%Lamp
29.1
46.4
75.3
91.3
98.9
%Fixture
29.4
46.9
76.2
92.3
100.0
Average
0-Deg
cd/sm
20003
18707
16397
12222
4954
99
84
71
61
53
46
41
36
33
30
27
10%
30 10
94
82
71
62
55
49
44
40
36
33
31
94
80
68
59
51
45
40
36
32
29
27
Average
45-Deg
cd/sm
15235
11649
9789
11843
1651
0%
0
91
78
66
56
49
43
38
34
30
27
25
Average
90-Deg
cd/sm
11991
10229
11883
11204
176
Modular F-Bay Power Supply Option
Cooper Lighting’s F-Bay Modular Power Supply option is available for use with all F-Bay products. The modular power supply
allows external fixture access for safe and easy servicing. There is no need to remove lamps or reflectors to disconnect fixture
power with F-Bay Modular Power Supply. Access to the individual fixture’s power supply allows servicing without turning off
all the fixtures, disrupting occupants. F-Bay Modular Power Supply is a time saver in installation – simply plug & power.
Code Compliance
• UL/cUL Certified for Make/Break
under load (UL2549)
• Meets NEC requirements for
ballast disconnect (NEC 410.73G)
1
• Allows for addition of Occupancy
Sensor without hard connections
2
1. Modular Power Supply Receptacle supplied
mounted into fixture Access Plate
2. Modular Power Cord & Plugs in 120, 277,
347, & 480V configurations for easy plug &
power into existing supply
No internal fixture
access required for
installation or
disconnecting power
Modular Motion Sensor Option
supplied with Mounting Box and
Modular Power Supply Receptacle
• Receptacles complete with
insulating/dust cap
Visit our web site at www.cooperlighting.com
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
5/12
ADF110944
I5
ORDERING INFORMATION
SAMPLE NUMBER: 8TI5-354T5-TBW-UNV-EBT2-UPL-U
Voltage (3)
UNV=Universal
120/277 Voltage
120V=120 Volt
277V=277 Volt
Length
Blank=4' Length
8T=8' Length
Series
I5=T5 Industrial
Options
I5 Lamps Installed (4)
L5841=T5 Lamp, 85CRI 4100K
L5850=T5 Lamp, 85CRI 5000K
Mounting Arrangement
Blank=Stand Alone
R=Continuous Row Mount
Ballast Type
T5 Systems
EBT =T5HO Linear Electronic Start High
Ambient. Total Harmonic
Distortion < 10% (5)
No. of Ballast
1, 2 or 3
Options
NUA=No Uplight Apertures In Housing (8)
UPL=Uplight Apertures
PI/CPI=Plug-In (1, 2 or 3)
TILW=Tandem Inline Wiring
MWS=Modular Wiring System
MS=360° or 180° Motion Sensor installed,
120 through 277 (6)
MP=Modular Power Receptacle (Used for
all Cord or Cord and Plug options) (1)
No. of Lamps
2=2 Lamps
3=3 Lamps
4=4 Lamps
Accessories (order separately)
I5/I8-SPM=Single Monopoint Hanger w/Hub
RH-1=Retrofit Hanger
FH-1=Fixture Hook
FL-1=Fixture Loop
SHK=Hook w/ Safety Screw
AYC-CHAIN/SET/U=(2) Hooks, 36" Chain Sets w/S-Hooks (7)
TOGGLE- =Single Toggle, #2 Cable (Specify 10' or 30' Requires two per fixture)
LOOP- =Loop Hanger, #2 Cable (Specify 10' or 30')
MC6=6' Modular Power Cord
MPC6=6' Modular Power Cord & Plug (Specify Voltage)
MMS=360° or 180° Aisle Motion Sensor with Modular
Power Receptacle (120-277V) (1)
MDS6=6' Modular Power Cord with MWS
27DS18/2G06MP Connector (9)
Lamp Type
47T5=47W T5 HO (4') Lamps (48")
Distribution Optic
Blank=Medium (Specular Aluminum)
G=Wide (High Reflectance White)
Shielding Options
Blank=Open
TBW=Thin White Baffle
FL=Frosted Acrylic Lens
& Frame (2)
CL=Clear Acrylic Lens &
Door Frame
ASY= Asymmetric
Directional Louver (2)
WG=Heavy Duty
Wireguard
Packaging
U=Unit Pack
PAL=Palletized
Out of Carton
PALC=Palletized
In Carton
NOTES: (1) Requires use of MC or MPC cord accessories, specify voltage for plugs. (2) Use with wide distribution optic
only. (3) Voltage must be specified when ordered with plugs, motion sensor or emergency ballasts. (4) Must specify
lamps when ordering. (5) EHT ballast systems suitable for operation in ambient environments not to exceed 149°F
(65°C) in open uplight configurations and less lens option. (6) When ordering MS option, specify UNV (for 120 or 277V).
(7) Not for use in gymnasiums or similar facilities. (8) Not compatible with UPL option. (9) For MWS with MP, choose MP
in fixture logic and then choose MWS accessory such as MDS6.
Door Frames (for Field Installation)
I5-FRM/LENS=Frosted Acrylic Lens & Frame
I5-FRM/CL PK=Clear Acrylic Lens & Frame
WG/I5-4FT-B=Heavy Duty Wireguard
90800PPK=Thin White Blade Baffle
90801PPK=Asymmetrical Directional Louver
SHIPPING INFORMATION
Catalog No.
Wt.
I5-254T5-TBW-UPL
8TI5-254T5-TBW-UPL
15 lbs.
30 lbs.
PI OPTION ORDERING INFORMATION
Catalog
Number
Suffix
PI 1 BLK
PI 2 BLU
PI 2 BLK
Number of
Circuits
1
2
2
Circuit
Wired To
Ballast
Black
Blue
Black
PI 3 RED
PI 3 BLU
PI 3 BLK
3
3
3
Red
Blue
Black
Catalog Numbering System
The PI System is available in sections up to 8' in length for continuous row wiring by simply plugging the sections
together. Each PI section is factory wired to the ballast leads. Color coding of wires is as follows:
PI-1 = One Circuit - 2 Wires: one black, one white
PI-2 = Two Circuits - 3 Wires: one black, one blue, one white
PI-3 = Three Circuits - 4 wires: one black, one blue, one red, one white
When ordering the PI2/PI3 System it is necessary to specify the number of fixtures required for each circuit. Each circuit in
fixture must be ordered as a separate line item, with a different hot wire color specified. All wiring to external feeds, using
cord or cord & plug, are responsibility of installing licensed contractor. Cord and cord & plug sets must be ordered
separately if PI option is chosen.
PI1 - Single Circuit Plug-In
PI2 - Two Circuit Plug-In
PI3 - Three Circuit Plug-In
SAMPLE NUMBER: PI1BLK-WG
SAMPLE NUMBER: PI2BLK-WG
SAMPLE NUMBER: PI3BLK-WG
PI1= Single
Circuit
BLK=Black Hot
NG= No Ground (ground
provided by fixture body)
WG= With Ground
(separate ground wire
in harness)
For complete product data, reference the Fluorescent
Specification binder. Specifications & dimensions subject
to change without notice. Consult your Cooper Lighting
Representative for availability and ordering information.
PI2= Two
Circuit
BLK=Black Hot
BLU=Blue Hot
Leave Blank=Single
Neutral
/WHT=White Neutral
/GRY=Gray Neutral
Leave Blank=Single
Neutral
2NEU=Two Neutrals
NG= No Ground (ground
provided by fixture body)
WG= With Ground (separate
ground wire in harness)
PI3= Three
Circuit
Leave Blank=Single Neutral
2NEU=Two Neutrals
BLK=Black Hot
BLU=Blue Hot
RED=Red Hot
NG= No Ground (ground
provided by fixture body)
WG= With Ground (separate
ground wire in harness)
Leave Blank=Single
Neutral
/WHT=White Neutral
/GRY=Gray Neutral
Visit our web site at www.cooperlighting.com
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801
5/12
ADF110944
Download