COOPER LIGHTING - SURE-LITES Catalog # Type ®

advertisement
COOPER LIGHTING - SURE-LITES ®
DESCRIPTION
The Sure-Lites Lifeway II Micro Series fast transfer inverter is a
lightweight, compact unit that takes the place of larger cabinets when
space is at a premium. The modular design allows the Micro Series
inverter to be configured to meet varying KW requirements from 500W to
2000W. The Micro can be configured at the factory to meet the specified
job load requirements, or it can be field-configured at the job-site when
an upgrade or downgrade in load capacity is needed.
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
E l e c t ri c a l
H o u s i n g C o n s t ru c t i o n
Application
- Choice of 120V or 277 VAC,
60Hz Other voltages available.
Consult Cooper Lighting
Representative.
- Available from 500 to 2000 Watts
- Single phase
- Field upgradeable from 500W
to 2000W
- Self Testing and Self Diagnostic
with Event, Test and Alarm Logs
(includes 5 minute monthly test
and 90 minute annual test)
- User programmable with
password protection for
alarms and diagnostics
- 98% efficient in standby mode no fan needed for cooling
- Battery, Input and Output
Protection Circuit Breakers
- Maintenance-Free Sealed
Lead Calcium Batteries
- Formed 16 gauge steel housing
is finished in a durable powder
coat finish
- Small footprint, lightweight size
allows for wall and floor
mounting
- Front circuit breaker and fuse
access panel for easy routine
maintenance
- Electrical knockouts for easy
contractor connection and
installation
- Modular design for ease of
installation when space is
at a premium.
- HID, Fluorescent and
Incandescent Lighting
Wa rra n t y
- Limited Manufacturer's One
(1) Year Warranty
On All Electronics*
- Limited Manufacturer's Two
(2) Year Warranty
On All Electronics
with Start-Up Service*
- Limited Manufacturer's Battery
Warranty: One (1) Year Full Value
Warranty/ 9 Years Pro Rata*
MICRO
INVERTER
SERIES
Code Compliance
- UL 924 Listed
- Meets NFPA 101 Requirements
- City of Chicago Approved
5 0 0 VA - 2 , 0 0 0 VA
26”
[660mm]
10”
[254mm]
HID
F L U O R E S C E NT
I N C A N D E S C E NT
I N V ER T E R M O D U L E
C H I C AG O C O D E
EMERGENCY LIGHTING
26”
[660mm]
B AT T E R Y M O D U L E
O N - L I N E P OW E R
I N V E RT E R SYST E M S
10”
[254mm]
10”
[254mm]
Single Phase - UPS
Emergency Lighting
Sy s t e m s
ORDERING INFORMATION
Series
CMFT=Micro Inverter
VA Rating
005=500
Voltage Input
Voltage Output
120
120
010=1000
015=1500
277
277
020=2000
Notes: *
See Optional Features on back.
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADX052051 pc
2010-08-09 10:16:18
MICRO INVERTER SERIES
S P E C I F I C AT I O N DATA
Input:
Voltage
Input Frequency
Synchronizing Slew Rate
Protection
120 or 277 VAC, Two wire plus ground, +10/-15%
60 Hz, +/-3 Hz
1Hz per second
Input Circuit Breaker
Output:
Voltage
Current Crest Factor
Voltage THD
Output Frequency
Inverter Overload
Voltage Regulation
Protection
120 or 277 VAC, Three Wire
2.8 = peak/rms
<3% THD for Linear Load
60 Hz +/- 0.05 Hz Crystal Controlled
115 % for 5 minutes
+/- 3% for +/- 25% load step change
(1) Output Circuit Breaker
Battery:
Type
Protection
String Voltage
Sealed Lead Calcium VRLA
Battery Circuit Breaker
48 VDC for all models
Environmental:
Altitude
Operating Temperature
Storage Temperature
Relative Humidity
<10,000 feet without derating
20 to 30 degrees C
-20 to 70 degrees C (Electronics Only)
<95% (non-condensing)
Physical:
Electronics Enclosure
Battery Enclosure
Dimensions = 10" x 10" x 26"
Weight = 77 lbs (35 kg)
Dimensions = 10" x 10" x 26"
Weight = 22 lbs (10 kg) per module w/o batteries; 107 lbs per module with batteries
General Features:
Microprocessor controlled, 2 x 20 character display with touch pad controls, front panel interface
Standard Metering – Voltage In, Voltage Out, Current Out, Battery Voltage, Battery Current, Temp, Date, Inverter Hours, System Days, VA, Inverter Watts
Standard Alarms – Output, Inverter, Charger, Low Battery, Near Low Battery, High Temp, Load Reduction, Overload, Overload Shutdown,
Low Voltage, High Voltage, Circuit Breaker Trip
Standard Logs – Alarm Log (Total 75), Event Log (Total 75), Test Log (Total 50)
Programmable setpoints are password controlled with user and service levels
Optional Features:
Circuit Breaker Trip Alarm, Normally Off Output, RS-232, Summary Alarm Dry Contact, Extended Runtime, Up to (2) additional output circuit breakers
L I F E WAY I I M I C R O S E R I E S SYST E M PA RT N U M B E R / R AT I N G / M E C H A N I C A L S P E C I F I C AT I O N S
Part Number
CMFT005
CMFT010
CMFT015
CMFT020
Wattage Rating
50 0
1000
1500
2000
VA Rating
50 0
1000
1500
2000
Input
Voltage
120 or 277
120 or 277
120 or 277
120 or 277
Output
Voltage
120 or 277
120 or 277
120 or 277
120 or 277
Battery Weight
(lbs.)
107
214
321
427
System Weight
(lbs.)
206
335
464
592
Cabinet
H" x W" x D"
10x26x10
10x26x10
10x26x10
10x26x10
Specifications and dimensions subject to change without notice.
Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
Cabinet Qty
2
3
4
5
ADX052051 pc
2010-08-09 10:16:18
2010-08-09 11:08:56
Download