Technical Data BMS Pro – BMS Interface Catalog# Prepared by Project Date Comments Type Overview The BMS Pro is an external, high performance, Building Automation multi-protocol gateway, providing access and control Greengate and iLumin network lighting control panels. The device provides protocol translation to lighting control panels and the BAS/BMS services using BACnet®, Modbus or LON. BMS Pro is designed to be used in facilities that require fast and easily connections to the lighting control system from the BAS/BMS. The BMS Pro device is pre-configured with Greengate and iLumin communications protocol and allows the user to field select BAS system protocols including BACnet/IP, BACnet MS/TP, Modbus or LON. Features Web browser based integration programming Device is field selectable for specific BAS protocol Integrates Greengate or iLumin lighting control systems and Building Automation Systems (BAS) Supports BACnet, Modbus and LonWorks® protocols Automatically generates all required control points and documentation for integration with the selected protocol Communication LEDs for system diagnostics Five-year limited warranty BMS Pro – BMS Interface December 2015 Specifications Supported Serial (RS-485) Protocols Supported Ethernet Protocols Supported Electrical Connections Power Requirements Operating environment Dimensions Approvals Warranty Description and Operation The BMS Pro provides up to 10,000 points of control and can communicate to multiple panel types on the lighting control network. Each BMS Pro can be programmed to communicate to either a Greengate or iLumin network and a single Ethernet access point (either the EIM or EG2-NA). BACnet MS/TP Modbus RTU BACnet IP Modbus TCP/IP (1) 6 pin Phoenix Connector (1) RS-485 +/- Ground port Power +/- Frame Ground port (1) Ethernet -10/100 Ethernet port (1) FTT-10 LonWorks port (LonWorks Version) 9-30 VDC or 12-24VAC Current draw @ 12V = 240 mA Indoor use only -40°C to 75°C (-40°F to 167°F) Relative humidity (non-condensing): 5% to 90% 4.52 x 3.25 x 1.60 inches (LxWxH) / (11.49 x 8.25 x 4.06 cm) BACnet Testing Labs (BTL) B-ASC LonMark 3.4 Certified TUV approved to UL 916 standard and CSA C22-2 For Greengate lighting control networks the BMS Pro will automatically find all network lighting control panels and prepopulate the BACnet, Modbus, or LON points of control for each panel. For iLumin lighting control networks uploading the iLumin Virtual Area file will load the Areas, Scenes and Channels programmed into the system. These are automatically mapped to BACnet, Modbus or LON points of control. The BMS Pro uses a 9-30VDC power input and can be powered from auxiliary power generated from most lighting control panels. If auxiliary power is not available a separate power supply should be provided. Catalog # FPC-N341130 (supports BACnet, Modbus BAS/BMS protocols) Five-year limited Dimensions Total Point Capacity Network Series Greengate 10,000 iLumin 3.25" FPC-N351131 (Supports LON BAS/ BMS protocol) 4.52" Ethernet connection to building LAN 1.6" (Depth) 2 Power Connection www.eaton.com/lightingsystems Greengate 4,096 iLumin Panel Supported Room Controller ControlKeeper 2 ControlKeeper 4 ControlKeeper 4A ControlKeeper T ControlKeeper M/ MB SCUN SCUN-FT SCRP SCRPB Room Controller ControlKeeper 2 ControlKeeper 4 ControlKeeper 4A ControlKeeper T ControlKeeper M/ MB SCUN SCUN-FT SCRP SCRPB Point Count Per Panel 115 161 161 181 213 225 Based on imported Virtual Area file 115 161 161 181 213 225 Based on imported Virtual Area file BMS Pro – BMS Interface December 2015 Wiring Diagram Building LAN (provided by others) BAS/BMS Communicating BACnet/IP or LON Dimmer 2 Blue - EM Line In 0-10V Dimming Outputs + + + Dimmer 3 Dimmer 1 Dimmer 3 + - Dimmer 2 + - QuickConnect Cables Integration Controls High End Not Used 3 4 Reset Occ Vac (default) 20% Energy Options Occupancy 2 1 Default 10% 0-10V Gain Adjustment 40% Status Low End 30% Dimmer 2 Dimmer 1 - Dimmer 2 + - Adjustable Skylights Switchpack Black Green Receptacle BMS/Out Dimmer 1 - + Sensors Sensors Slider Station 5 Wallstations + + + A/V Mode + Demand Response Alert Mode Time Clock 6 QuickConnect Cables White Red 4 3 2 1 Occupancy Not Used 3 2 4 Occ Vac (default) Reset 1 20% Energy Options Energy Options DIP Switch Demand Response Default 10% 30% Status 40% 0-10V Dimming Outputs + + + Dimmer 3 Dimmer 2 Dimmer 1 + Adjustable Skylights Adjustable Skylights Integration Controls Blue - Load In Yellow - Load 1 Out 0-10V Gain Adjustment 40% Status Low End 30% 1 Energy Options DIP Switch Demand Response 0-10V Gain Adjustment 4 Energy Options Not Used 3 Occ Vac (default) High End Occupancy 2 Reset 20% Black - Line In White/Black - 120V N White/Orange - 277V N Black - Line In 1 1 Default 10% CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. Red - Load 2 Out Purple - Load 3 Out 2 Energy Options DIP Switch Demand Response 2 Integration Controls Integration Controls 4 3 4 3 High End Time Clock Time Clock Low End Alert Mode 6 5 Alert Mode 0-10V Dimming Blue - Load In Sensors Sensors Wallstations + Demand Response 6 5 Wallstations + Yellow - Load 1 Out Receptacle BMS/Out Slider Station + + + A/V Mode Sensors Sensors Dimmer 3 White/Black - 120V N White/Orange - 277V N Green QuickConnect Cables Adjustable Skylights Black Receptacle BMS/Out Slider Station + + + + A/V Mode Dimmer 3 CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. Adjustable Skylights Switchpack White Red Demand Response Integration Controls Yellow - Load 1 Out White/Black - 120V N White/Orange - 277V N Blue - Load In Red - Load 2 Out Purple - Load 3 Out The Ethernet Interface Module (EIM) may be connected to any lighting control panel in the system with an RS-232 port with the cable provided (Part #: 52-018703-00) Black - Line In SG PWR+PWR- FG CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation. 24VDC Power (by others) A- Blue - EM Loads Out +PWR -PWR FRAME GND B+ Blue - EM Line In ETHERNET RS 485 RS GND485RS 485+ Green 0-10V Dimming Outputs + + + - Blue - EM Line In Blue - EM Loads Out B0 B1 B2 B3 S0 S1 S2 S3 Black Adjustable Skylights ControlKeeper TouchScreen Switchpack White Red Integration Controls 120V Power Receptacle Required A0 A1 A2 A3 A4 A5 A6 A7 Blue - EM Loads Out BMS Pro ProtoNode Red - Load 2 Out Purple - Load 3 Out EIM Dimmer 1 Dimmer 3 - + 0-10V Dimming - Dimmer 2 + - Dimmer 1 + - 0-10V Dimming www.eaton.com/lightingsystems 3 BMS Pro – BMS Interface December 2015 Ordering All BMS Pros require a dedicated Ethernet Interface Module or EG2NA to access the Greengate or iLumin lighting control network. Ensure these devices are included in the project bill of material Catalog # Description FPC-N34-1030 FPC-N35-1031 BMS Pro, BACnet, Modbus Gateway BMS Pro, LonWorks Gateway Required Accessories Catalog # Description EIM Ethernet Interface Module (Required for all Greengate installations) Ethernet Gateway (Required for all iLumin installations) EG2-NA Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton Lighting systems – Controls products 203 Cooper Circle Peachtree City, GA 30269 www.eaton.com/lightingsystems © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD503062EN December 14, 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.